Chapter 9 Atrium Ventilation Strategies

Similar documents
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

Residential HVAC Load Sizing Training October 14, David Kaiser Green Code Plan Reviewer

Adapting to Change: New Thinking on Comfort Natural ventilation in UK schools: design options for passive cooling Steven Firth* and Malcolm Cook

Adaptive strategies for office spaces in the UK climate

3-D Modeller Rendered Visualisations

Mechanical and Natural Ventilation

Air Conditioning, Comfort and Energy in India s Commercial Building Sector

ELIMINATING AIR CONDITIONERS IN NEW SOUTHERN CALIFORNIA HOUSING

ENERGY EFFICIENT AFFORDABLE HOUSING; Validating HEED s Predictions of Indoor Comfort

Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation The Building Regulations 2010

Case Study Family Room Renovation 3br family home, Melbourne

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Energy efficient home design

Software Development for Cooling Load Estimation by CLTD Method

Energy Efficiency HOSPITALITY.

Key energy-efficient features of your new home

about your house How to Get the Ventilation That You Need in Your House Figure 1 Infiltration and exfiltration of air in a house

All the best brands all under one roof

Whole House Dehumidification for Occupant Comfort and Energy Savings

DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple

THERMAL LOSSES Thermal Losses Calculations

Technical Series

CONDENSATION IN REFRIDGERATED BUILDINGS

Selecting Energy Efficient New Windows in Florida

FLORIDA SOLAR ENERGY CENTER

Element D Services Heating, Ventilating, and Air Conditioning

Residential HVAC System Sizing

Using Time-of-Day Scheduling To Save Energy

Air Conditioning Contractors of America

Energy Saving Tips. Adjust set point temperature up a few degrees... Window contact. Occupancy sensor. A Programmable Thermostat

CIBSE Loads User Guide

Measured Cooling Load, Energy, and Peak Demand Savings from High-Performance Glass in a California Production House

Heating and Ventilation

Energy Efficiency. Bars & RestauRants.

EFFECT OF TUNNEL VENTILATION AND EVAPORATIVE COOLING ON THE BARN ENVIRONMENT AND COW COMFORT IN MIDWEST DAIRY FACILITIES

Priority School Building Programme

Opening the Bonnet. Prof Darren Woolf WYSINWYG 1

Energy savings in the residential area are essential in

Case Studies: Infrared Heating in Industrial Applications

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

Red River College MECB 101 School of Construction and Engineering Technologies Manitoba Energy Code for Buildings 101 (MECB 101)

CHAPTER 11: PASSIVE SOLAR HOMES

Attached is a link to student educational curriculum on plug load that provides additional information and an example of how to estimate plug load:

Building skin and energy efficiency in a hot climate with particular reference to Dubai, UAE

Klosterenga, Oslo, Norway, page - 1

Energy Savings in High-Rise Buildings Using High-Reflective Coatings

Molds and mildew are fungi that grow

Analysis of Energy Consumption, Rating Score, and House Size

Advice to consumer Reference 50.1 May Condensation. Some causes, some advice.

Housing Fact Sheets. Moisture Condensation at the Windows

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, , ]

IES <Virtual Environment> Tutorial. Apache Sim (Version 6.0)

IEA SHC Task 47 Renovation of Non-Residential Buildings towards Sustainable Standards

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

A global list. The Fortification Depot A CO 2 -reduction project

Cool Spaces. earth-wise guide to. green strategies: light strategies: Keep Austin Cool

The District Energy Manager and Classroom Heating

FACTORS AFFECTING ENERGY CONSUMPTION OF BUILDINGS

Energy Saving Fact Sheet Air Conditioning

Passive & Active Design

THE COMFORT HOUSES. - The Experienced and Measured Indoor Environment

Creating Efficient HVAC Systems

AIRCONDITIONING Cooling Loads Calculations

Selecting Energy Efficient Replacement Windows in Nevada

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:

Answers to Your Questions from the Webinar

SIMULATION OF RADIANT COOLING PERFORMANCE WITH

How To Get A Passive House

Selecting Energy Efficient New Windows in Georgia

CO2 Emissions. Indirect CO 2. Emissions Electricity and Heat Production 25 % Direct Emissions AFOLU 24 % Energy 1,4% Buildings 6,4 % Industry 11 %

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Dealing with Thermal Issues in Data Center Universal Aisle Containment

WALLS Three common wall types are described below, with their insulation solutions.

Selecting Energy Efficient New Windows in Arizona

HEATING, VENTILATION & AIR CONDITIONING

Residential Windows, 3 rd edition Corrected index 1

Hospital Application Guide. Cost-effective climate control for hospitals

CHAPTER 3 Window design for day lighting, ventilation and to

SENSITIVITY STUDY FOR ARCHITECTURAL DESIGN STRATEGIES OF OFFICE BUILDINGS IN CENTRAL CHILE: EFFECTIVENESS OF NOCTURNAL VENTILATION.

Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings

VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEPARTMENT OF CIVIL ENGINEERING

Purpose: To determine the dew and point and relative humidity in the classroom, and find the current relative humidity outside.

High Performance School Buildings Resource and Strategy Guide

The Integrated Design Process

IECC Compliance Guide for Homes in Virginia

CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM

Tech Byte 27: Small Computer Room and IT Closet Cooling

Mission 7: Saving Energy

CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?

6 Ceiling fans! Although they only use about as. 8 Redecorate. Hang lighter colored curtains

air conditioners how to choose a cooling system

THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING. R.M.J. Bokel

The replacement or modification of existing windows shall comply with the following requirements:

Before You Start an Energy Efficiency Retrofit The Building Envelope

Managing Heat Stress in Poultry

NAIOP OF SOUTHERN NEVADA SUSTAINABILE DEVELOPMENT COMMITTEE - EDUCATION SERIES

The Reunion experience

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE

Transcription:

Chapter 9 Atrium Ventilation Strategies Building Energy Efficiency Technical Guideline for Passive Design (Draft 1) CK Tang

Foreword This document is produced as part of Component 4, Building Sector Energy Efficiency Program (BSEEP) by CK Tang (ck@gbeet.com) and Nic Chin (nc.environmentology@gmail.com). The views expressed in this document, which has been produced without formal editing, are those of the authors and do not necessarily reflect the views of neither JKR nor UNDP. Comments and opinions from readers are encouraged and please email it to either ck@gbeet.com or nc.environmentology@gmail.com or comment at our Facebook page: www.facebook.com/bseepc4 CK Tang August 23, 12 Page 2 of 13

Table of Contents 9 Atrium Ventilation Strategies... 4 9.1 Introduction... 4 9.2 Key Recommendations... 4 9.3 Comfort... 5 9.4 Natural Ventilation... 5 9.5 Simulation model... 7 9.6 Air Conditioned Atrium Strategies... 8 9.7 Natural Ventilation Strategies... 10 Page 3 of 13

9 Atrium Ventilation Strategies 9.1 Introduction It is commonly considered that natural ventilation in atrium spaces is an energy efficient feature in buildings. However, if the atrium space is surrounded by air conditioned spaces, the exposure of the atrium space to outdoor air will introduce more surface area of the building to be in contact with outdoor air temperature and humidity. This type of exposure increases the risk of conduction heat and air leakages into the air conditioned space. Therefore, there is a need to provide a clear guideline on conditions where an atrium is better to be naturally ventilated, when it should not be naturally ventilated or partially naturally ventilated. Results from simulation studies testing these conditions will be presented in this Chapter. 9.2 Key Recommendations In terms of comfort at atrium ground floor level it is most comfortable for the space to be airconditioned. Even the best case of natural ventilation tested for this chapter, it was not able to provide 100% of the occupancy hours at a thermally comfortable environment. At best, a hybrid natural ventilation can maintain thermally comfortable condition for 66% of the building occupancy hours, mostly in the morning hours. In the afternoon, discomfort hours are approximately 3.4 hours per working day. A hybrid natural ventilation strategy is a system where natural ventilation is promoted whenever the outdoor air temperature is lower than the atrium air temperature and kept air tight, whenever the outdoor air temperature is higher than the atrium air temperature. This strategy may be implemented using a set of temperature controlled motorized louvers install at the ground floor of the atrium space or manually by the building security/maintenance staff that open the doors for natural ventilation at a fixed time every evening and closed it at a fixed time every morning. It terms of energy efficiency, the best case of hybrid natural ventilation strategy reduces (based on this case study model) total building energy by a significant 3.3%. Combining air conditioning system with natural ventilation strategy (natural ventilation during weekend and night time) reduces total building energy by 0.6% as opposed to the base case of air conditioned scenario with the atrium space kept air tight all the time. In summary, if an average discomfort level of ~3 hours every day is acceptable at the atrium space, it will be most energy efficient to provide hybrid natural ventilation strategy. However, if it is not acceptable to have any discomfort hours at all for the atrium space, air conditioning an air tight atrium space is the simplest solution. An energy efficiency reduction of 0.6% Finally, these studies were made with the assumption that daylight harvesting was optimized for the atrium space and very low small power is used in the atrium space. I.e. Daylight Factor is less than 6% at the atrium ground floor level and a maximum of 1 computer is used. Page 4 of 13

9.3 Comfort In the test reference building scenario, it was found that the most comfortable strategy is to provide air conditioning to the atrium floor level. This strategy will ensure that comfort conditions are provided during the entire building occupancy hours of 8am to 6pm. A test was also conducted with the top of the atrium space open to ventilation (i.e. to allow hot air to escape out of the top of building) while keeping the ground floor level air conditioned. The result of this test showed a total building energy consumption increase of 1.8%. This increase in energy consumption of the building is largely caused by a higher infiltration rate at the air conditioned ground floor level when doors are opened for people to walk in and out of the building. This condition could be solved by the installation of a revolving door system at the ground floor (however this situation was not tested due to the limited time available). In short, it was found in these simulation studies that keeping the atrium roof air tight reduces the infiltration rate at the ground floor level when doors are opened and closed for occupant assess. Therefore, it is better to keep the atrium roof air tight to reduce building total energy consumption as oppose to having a ventilated atrium roof space to exhaust hot air out. It is also possible to improve energy efficiency further by providing high U value materials at the atrium roof top level to allow heat to be easily conducted out of the building while keeping the atrium space air tight because the simulation showed that the top of the atrium space has a consistently higher temperature than outdoor air temperature. It was also simulated that it is possible to improve tested building energy consumption by 0.6% if natural ventilation strategy is employed whenever the outdoor air temperature is colder than the atrium air temperature even when the ground floor atrium space is air conditioned. However, if a lower comfort level is acceptable for the atrium space, it is possible to save more than 3% of total building energy with the application of optimized natural ventilation strategy for the atrium space. 9.4 Natural Ventilation After a few attempts to optimize natural ventilation in atrium space, it was found that the optimum scenario of natural ventilation tested for this chapter would provide 66% of building occupancy hours of 9am to 5pm, within comfort conditions, i.e. operative temperature below 29 C (refer to Chapter 1 on thermal comfort of naturally ventilated spaces). This study also showed that on the hottest day scenario, where the outdoor temperature exceeds 35 C, the atrium ground floor operative temperature was able to maintain 4 C lower than the outdoor air temperature. In addition, a total building energy reduction of 3.3% was achieved using the optimum natural ventilation tested for this chapter. The optimum natural ventilation strategy tested for this chapter is a type of hybrid ventilation system that open the atrium space to natural ventilation when indoor air temperature is higher than the outdoor air temperature and closed the atrium space natural ventilation ability when the outdoor air temperature is higher than the indoor air temperature. This requires controls over the openings at the atrium ground floor level. This hybrid ventilation strategy is as follows: 1. Ground Floor space should be air tight from the hours of 7am to 4pm and open for natural (stack) ventilation effect from 4pm to 7am daily. The opening hours of 4pm to 7am daily allowed the cooler outdoor air to cool the atrium space down during night time to early morning hours. The closing of the ground floor atrium space from 7am to 4pm, will keep the Page 5 of 13

atrium space cooler for longer hours because it prevent the hot outdoor air from heating the atrium space during daytime. In addition, the leaked cooling from the offices is retained by the closed atrium space. 2. The atrium roof space is recommended to remain permanently open for natural ventilation. When the ground floor space are kept air tight (i.e. during daytime), it is difficult for outdoor air to infiltrate into the atrium space. However, when the ground floor space are open for ventilation during night hours, it will promote natural ventilation (due to stack ventilation effect), where the hot air rise up to exit the atrium space at the roof level and colder outdoor air will enter the atrium space from the ground floor openings below. 3. Further improvement can be obtained from having an automatic system that open the ground floor and roof to natural ventilation whenever the measured indoor air temperature is higher than the outdoor air temperature. However, the advantage achieved from such automatic system is not significant enough to insist on such recommendations. It was also found in these studies that natural ventilation using permanently fixed openings are not as effective as those strategies that allowed the openings at the ground floor level to be opened and closed according to the measured temperature or timed. The following permanently fixed strategies will cause the atrium space to have more than 50% of the occupied hours above comfort conditions: 1. Permanently Closed Ground Floor Level and Closed Roof (38% comfort hours). 2. Permanently Closed Ground Floor Level and Open Roof (40% comfort hours). 3. Permanently Open Ground Floor Level and Open Roof (48% comfort hours). Summary of simulation results are presented in Table 9.4.1 below: Cases Base: Air Conditioned Ground Floor. Atrium Permanently Closed at Bottom and Top Case 1: Natural Ventilation. Atrium Permanently Open at Bottom and Top Case 2: Natural Ventilation. Permanently Closed at Bottom and Top Case 3: Natural Ventilation. Permanently Closed at Bottom and Open at Top. Case 4: Natural Ventilation. Temperature Controlled Ventilation at Bottom and Top. Case 5: Natural Ventilation. Time Controlled Ventilation at Bottom and Top. Case 6: Natural Ventilation. Time Controlled Ventilation at Bottom and Permanently Open Top. Case 7: Natural Ventilation. Temperature Controlled Ventilation at Bottom and Permanently Open Top. Total Building Energy Saved (%) Comfort Hours/Year at Atrium Floor Level, (8am to 6pm, Mon Fri) Comfort Hours/Year (%) 0.0% 2,600 100% 1.0% 1,235 48% 2.3% 977 38% 2.3% 1,040 40% 3.3% 1,713 66% 3.0% 1,666 64% 3.0% 1,669 64% 3.3% 1,713 66% Page 6 of 13

Case 8: Air Conditioned Ground Floor. Atrium Permanently Open at the Top. 0.9% 2,600 100% Case 9: Air Conditioned Ground Floor. Atrium Temperature Controlled at the 0.4% 2,600 100% Top Case 10: Air Conditioned Ground Floor. Atrium Temperature Controlled at both Top and Bottom. 0.6% 2,600 100% Table 9.4.1: Summary results of 11 simulated cases tested for Chapter 9. 9.5 Simulation model An eight (8) floor office building was modeled for this study with the atrium located in the center of the building, surrounded by air conditioned office space from 1 st floor level to 8 th floor level. The entire ground floor is modeled as part of the atrium space and will be air conditioned or naturally ventilated depending on the case studies. The rest of the atrium spaces were not air conditioned for all cases. In addition, the simulation model for Chapter 9 has taken these factors into considerations: 1. Internal walls facing the atrium space has a window to wall ratio of 70%. These internal walls separate the air conditioned offices from the atrium space. The internal glazing was assigned as single glazing clear glass. In addition, 1% of the internal glazing area was assumed to be permanently open to model air leakages between the office and the atrium space. This assumption will be valid for most building where the internal windows are all kept closed to the atrium space. The 1% opening assumption made in this study will represent the leakages due to the cracks between the window frame and the wall. 2. Atrium roof top is modeled to be higher than the highest office floor level. The higher roof height of atrium spaces is typically designed for aesthetical reason but in this case it is also to create a space for storage of heat by the air for it to be conducted or ventilated out of the building. 3. % of the atrium roof was modeled as a skylight to allow natural daylight into the atrium space. Page 7 of 13

Figure: Cross Section View of Atrium Simulation Model. 9.6 Air Conditioned Atrium Strategies Base Case: Air Conditioned, Permanently Closed Atrium Space. 38 Dry resultant temperature: Offices 0 (base_closedacbtm_door.aps) In typical building scenario, the closed atrium space will remain closed day and night. Note that the temperature in the atrium space is significantly warmer than outdoor air temperature during night hours and weekends. Page 8 of 13

Case 8: Air Conditioned Ground Floor. Atrium Permanently Open at the Top. 38 Dry resultant temperature: Offices 0 (c8_ac_opentop.aps) The Idea: Since cold and dry air conditioned air is heavier than hot and humid air, this strategy will attempt to allow hot and humid air to rise in the atrium space and allows it to escape at the top of the building space. The Reality: Having the top of the atrium space opened to ventilation increases the infiltration rate significantly at the ground floor level when doors are opened and closed for occupant access. This increase in infiltration rate increases both the sensible and latent load for the air conditioning system at the ground floor level. The total building energy consumption was increased by 0.9% in this test case scenario compared to the Base Case scenario. The atrium ground floor doors were modeled to be open 10% of the building air conditioning hours. Case 9: Air Conditioned Ground Floor. Temperature Controlled Openings at the Top. 38 Dry resultant temperature: Offices 0 (c9_ac_autotop.aps) The Idea: Instead of keeping the top of the atrium roof permanently open to natural ventilation, an attempt is made to have the roof ventilation open to exhaust hot air out of the atrium space whenever the measured indoor air temperature at the roof space is warmer than the outdoor air temperature. Otherwise the atrium space is kept air tight. The Reality: The simulation result was similar to Case 8 where the top of the atrium space was kept permanently open. Total building energy consumption increased by 0.4% in this test case scenario Page 9 of 13

compared to the Base Case scenario where the atrium space was kept air tight. Again, it was found that having the top of the atrium space opened to ventilation increases the infiltration rate significantly at the ground floor level when doors are opened and closed for occupant access. This increase in infiltration rate increases both the sensible and latent load for the air conditioning system at the ground floor level. The atrium ground floor doors were modeled to be open 10% of the building air conditioning hours. Case 10: Air Conditioned Ground Floor. Temperature Controlled Openings at the Top and Bottom. Dry resultant temperature: Offices 0 (c11_ac_nvnite.aps) The Idea: It was observed that the ground floor atrium space air temp is significantly higher than the outdoor air temperature whenever the air conditioning system is switched off. In this case study, once the air conditioning system is switched off The Reality: The simulation result was similar to Case 8 where the top of the atrium space was kept permanently open. Total building energy consumption increased by 0.4% in this test case scenario compared to the Base Case scenario where the atrium space was kept air tight. Again, it was found that having the top of the atrium space opened to ventilation increases the infiltration rate significantly at the ground floor level when doors are opened and closed for occupant access. This increase in infiltration rate increases both the sensible and latent load for the air conditioning system at the ground floor level. The atrium ground floor doors were modeled to be open 10% of the building air conditioning hours. 9.7 Natural Ventilation Strategies Case 1: Permanently Open Top and Bottom. Mon Tue Wed Thu Date: Mon 06/Mar to Wed 08/Mar Dry resultant temperature: Offices 0 (c1_opentopbtm.aps) Page 10 of 13

The Idea: To allow natural stack ventilation to cool the atrium space the entire day. The Reality: The operating hours of office building coincides with the hottest temperature of the day. Allowing such natural ventilation strategy allowed hot outdoor air temperature to heat up the ground floor space during daytime. However, during night time, the colder outdoor air temperature do helps to cool the space down. Case 2: Permanently Closed Top and Bottom. 38 Dry resultant temperature: Offices 0 (c2_closedtopbtm.aps) The Idea: Let s try to capture all the cooling that is conducted and infiltrated from the offices into the atrium space. The Reality: Keeping the atrium sealed air tight turn this space into a green house, especially during the weekends, without the air conditioning system running in the offices, the atrium space become hotter than outdoor air temperature. During weekdays, with the air conditioning running in the offices, the conduction and infiltration leakages into the atrium space reduces its daily peak operative temperature but not enough to keep it at comfortable level. Case 3: Permanently Closed Bottom and Open Top. 38 Dry resultant temperature: Offices 0 (c3_closebtm_opentop.aps) The Idea: This case study attempts to capture all the cooling that is conducted and infiltrated from the offices into the atrium space, while allowing the hot air to escape via the top of the atrium roof. The Reality: Although it worked as planned, the amount of hot air escaping from the top of the atrium space is not significant enough to reduce the operative temperature of the ground floor level much. Page 11 of 13

Case 4: Temperature Controlled Ventilation at Bottom and Top. Dry resultant temperature: Offices 0 (c4_autobtmtop.aps) The Idea: Open the ground floor and rooftop for natural ventilation whenever, the air temperature of the indoor atrium space is higher than the outdoor air temperature. Close the natural ventilation whenever, the outdoor air temperature is higher than the indoor atrium space air temperature. This will allows colder outdoor air to cool the atrium space down when the time is right and when the outdoor air is hot, keep the atrium space air tight to prevent it from heating up the space. The Reality: Due to the captured cooling that was conducted and infiltrated from the offices to the atrium space, the peak operative temperature of the ground floor atrium space is approximately 4 C lower than the peak outdoor air temperature. In short, this strategy worked as planned and provides the best combination of comfort and energy reduction scenario. Unfortunately, we are still unable to achieve comfort condition at all time for the atrium space. In this best case scenario it was simulated that the operative temperature will be higher than 29 C (80% of the thermal adaptive comfort limit) for 887 hours a year, or an average of 3.4 hours per working day. Case 5: Time Controlled Ventilation at Bottom and Top. Dry resultant temperature: Offices 0 (c5_timebtmtop.aps) The Idea: Since the air temperature in Malaysia is fairly consistent daily, what would be the impact of using a time controller instead of differential temperature controller? In this case study, the Page 12 of 13

atrium openings are kept open from the hours of 7am to 4pm and closed from the hours of 4pm to 7am. The Reality: It increases the discomfort hours by 2% as compared to Case 4. It can be concluded herewith that the time controller is almost as effective as using differential temperature controller. Case 6: Time Controlled Ventilation at the Bottom and Permanently Open at the Top. Dry resultant temperature: Offices 0 (c6_timebtm_opentop.aps) The Idea: Instead of having controls at both top and bottom of the atrium space for natural ventilation, this simulation case study will test the option of leaving the top of the atrium space without any controls to allow hot air to escape out. In the meantime, the bottom of the atrium space may be manually or automatically controlled to keep hot outdoor air out of the building during daytime and allowing natural ventilation during night time when the outdoor air is colder than the atrium air temperatures. The Reality: It increases the discomfort hours by 2% as compared to Case 4 and matched the result for Case 5. It can be concluded herewith that it is not required to place any controls on the top floor of atrium space when the atrium is naturally ventilated. Controls is only required at the ground floor level to increase comfort level in the building. End of Chapter 9 Page 13 of 13