Temperature Regulators

Similar documents
Self-operated Temperature Regulators Temperature Regulator Type 1u

Self-operated Temperature Regulators Type 1 to Type 9. PN 16 to 40 Class 125 to 300 DN 15 to 250 NPS ½ to 10 G ½ to 1 Up to 350 C Up to 660 F

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

Terminology and Symbols in Control Engineering

Thermostatic valve Type AVTA

Type 3353 Angle Seat Valve

Series 240 Type and Type Pneumatic Control Valves Type 3244 Three-way Valve

V47 Series Temperature Actuated Modulating Water Valves

MAKING MODERN LIVING POSSIBLE. Thermostatic valve AVTA. Technical brochure

Chapter 18 Temperature, Heat, and the First Law of Thermodynamics. Problems: 8, 11, 13, 17, 21, 27, 29, 37, 39, 41, 47, 51, 57

REGULATORS 175/153 Series

1. The Kinetic Theory of Matter states that all matter is composed of atoms and molecules that are in a constant state of constant random motion

Why and How we Use Capacity Control

Type and Type Pneumatic Control Valves Type 3510 Micro-flow Valve

2-Port Self-acting Temperature Control Valve Selection for Heating and Cooling Applications

Laddomat Charging unit

Dew Point Tester. Instruction Manual. CVS Regular Chiller Model A-2. CVS Regular Chiller Model A-2

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

COUNTERBALANCE VALVES

Characteristics of Evaporators

UNDERSTANDING CENTRAL HEATING SYSTEMS

DOUBLE SEAT BRONZE BODY HIGH CAPACITY

How To Calculate The Performance Of A Refrigerator And Heat Pump

Example. Fluid Power. Circuits

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

Name: Class: Date: 10. Some substances, when exposed to visible light, absorb more energy as heat than other substances absorb.

Chapter 10 Temperature and Heat

FUNDAMENTALS OF ENGINEERING THERMODYNAMICS

Free piston Stirling engine for rural development

Data sheet Radiator Thermostats type RA 2000 Valve bodies type RA-FN and RA-G

Module 5: Combustion Technology. Lecture 34: Calculation of calorific value of fuels

Lecture 24 - Surface tension, viscous flow, thermodynamics

Practice Test. 4) The planet Earth loses heat mainly by A) conduction. B) convection. C) radiation. D) all of these Answer: C

Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Mechanical shaft seal types and sealing systems

To measure the solubility of a salt in water over a range of temperatures and to construct a graph representing the salt solubility.

Unit 24: Applications of Pneumatics and Hydraulics

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

GS-General Service Control Valves

LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS

Refrigeration Basics 101. By: Eric Nelson

Commercial Semi-Instantaneous Water Heaters

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

CO MPa (abs) 20 C

Heat. Investigating the function of the expansion valve of the heat pump. LD Physics Leaflets P Thermodynamic cycle Heat pump

Steam System Best Practices Condensate System Piping

Control ball valves for severe services. Author: Michele Ferrante, PARCOL S.p.A., Italy

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

Description of functions

Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson

UNIT 2 REFRIGERATION CYCLE

Cooling system components, removing and installing

CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2

The Unique Accelabar Flow Meter

5.2. Vaporizers - Types and Usage

New Trends in the Field of Automobile Air Conditioning

AN INSTRUMENT FOR GRAVIMETRIC CALIBRATION OF FLOW DEVICES WITH CORROSIVE GASES. J. O. Hylton C. J. Remenyik Oak Ridge National Laboratory *

Thermostatic actuator RAVV - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16)

BB-18 Black Body High Vacuum System Technical Description

جامعة البلقاء التطبيقية

The Second Law of Thermodynamics

Thermostatic Actuators

The Versatile Differential Pressure Transmitter. By David Gunn Honeywell Process Solutions

T U R B I N E G A S M E T E R

Name Class Date. F N A cm 2 A cm 2 Unknown: Step 2: Write the equations for Pascal s principle and pressure, force, and area.

Cooling system components, removing and installing

SAMPLE CHAPTERS UNESCO EOLSS

Heating Water by Direct Steam Injection

Keggomax CM Reflux Still

Chemistry 13: States of Matter

Differential Relations for Fluid Flow. Acceleration field of a fluid. The differential equation of mass conservation

Vogt Valves The Connection Bulletin for Forged Steel Flow Control Valves CB 15

Calculating Heat Loss by Mark Crombie, Chromalox

Grant Agreement No SFERA. Solar Facilities for the European Research Area SEVENTH FRAMEWORK PROGRAMME. Capacities Specific Programme

WASHING PROCESS OF CARGO TANKS ON TANKERS FOR TRANSPORTATION OF CRUDE OIL

FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

Cooling system components, removing and installing

Rusty Walker, Corporate Trainer Hill PHOENIX

Dimensional analysis is a method for reducing the number and complexity of experimental variables that affect a given physical phenomena.

series Materials Body: 1/2, 3/4 and 1 : dezincification resistant alloy brass EN CW617N

Chapter 2: Forms of Energy

Fluid Mechanics: Static s Kinematics Dynamics Fluid

Volkswagen Golf > VW Rabbit GTI 2006->

ENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS

PERMEABILITY TEST. To determine the coefficient of permeability of a soil using constant head method.

Facts About. Industrial gases for better injection molding. This article appeared in the trade journal Kunststoffe plast europe, issue 12/2004.

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

ENGINE COOLING SYSTEM

Gas Custody Transfer Calibration

Unit 24: Applications of Pneumatics and Hydraulics

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA MECHANICAL PRINCIPLES OUTCOME 2 ENGINEERING COMPONENTS TUTORIAL 1 STRUCTURAL MEMBERS

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves

1. At which temperature would a source radiate the least amount of electromagnetic energy? 1) 273 K 3) 32 K 2) 212 K 4) 5 K

Testing methods applicable to refrigeration components and systems

Chokes. Types Reasons Basics of Operations Application

Transcription:

Technical Information Temperature Regulators 2 Part 2 Self-operated Regulators

Technical Information Part 1: Fundamentals Part 2: Self-operated Regulators Part 3: Control Valves Part 4: Communication Part 5: Building Automation Part 6: Process Automation Should you have any further questions or suggestions, please do not hesitate to contact us: SAMSON AG Phone (+49 69) 4 00 94 67 V74 / Schulung Telefax (+49 69) 4 00 97 16 Weismüllerstraße 3 E-Mail: schulung@samson.de D-60314 Frankfurt Internet: http://www.samson.de

Part 2 L205 EN Temperature Regulators SAMSON AG 99/12 Temperature regulators........................ 5 Sensors............................... 6 Liquid expansion principle............................... 6 Sensor volume....................................... 7 Filling medium....................................... 8 Adsorption principle................................... 9 Vapor pressure principle............................... 10 How the sensor design influences the dynamic behavior........ 12 Types of bulb sensors.................................. 12 Set point adjustment.................................. 13 Excess temperature................................... 14 Mounting position.................................... 15 Dynamic behavior of sensors..................... 17 Valves and their applications..................... 20 Force-balancing..................................... 20 Mixing and diverting valves............................. 22 Globe valves in cooling service........................... 26 Appendix A1: Additional literature.................. 27 CONTENTS 3

Self-operated Regulators Temperature Regulators SAMSON AG V74/ HS 4

Part 2 L205 EN Temperature regulators The characteristic feature of self-operated temperature regulators is their compact design, including a sensor, a valve and a capillary tube. Their simple operating principle is based on fundamental mechanical, physical and thermodynamic laws. A temperature control loop with a heat exchanger is shown in Fig.1. When the water has left the heat exchanger and circulates in the domestic hot water loop, its temperature must be kept constant. In the heating loop, a heat transfer medium, e.g. hot water, circulates through the heat exchanger and transfers part of its heat to the domestic hot water loop. If we assume that the temperature of the hot water remains constant, the transferred heat quantity depends on the flow rate. The flow of hot water is adjusted by the self-operated regulator. temperature control loop The sensor measures the temperature of the variable to be controlled and converts the measured value into a travel signal which is used as output variable. The sensor output signal is transmitted via the capillary tube to the valve where the signal changes the position of the plug as required. Temperature regulators obtain their actuating power from the medium to be controlled, so they do not need supply lines or auxiliary devices. This is the most important benefit of self-operated regulators. They keep costs low, while exhibiting high operational reliability. self-operated regulator temperature sensor heating loop domestic hot water loop heat exchanger SAMSON AG 99/12 Fig. 1: Temperature control loop with heat exchanger 5

Self-operated Regulators Temperature Regulators Sensors measurement is based on three methods Sensors are used to measure the temperature of the medium to be controlled. A good sensor must fulfill two important requirements. It must respond quickly to temperature changes and provide accurate values of variables that change over time. The self-operated regulator measures variables according to the three following principles: liquid expansion adsorption vapor pressure These principles utilize the change in volume, in structure or the conversion of a matter s state of aggregation. Liquid expansion principle When measuring the expansion of a liquid, the quality of the results depends to a great extent on two factors: the sensor volume and the specific heat capacity of the filling medium. 1: sensor 2: operating element 3: cylinder h 2 h2,0 VV2,0 h 2.0 2.0 V2 h2 1 V 1 =V 2 D2 V 1.0 =V 2.0 h 1.0 h 1 < h 2 h 1.0 < h 2.0 3 V1,0 V 1.0 V1 h1 h1,0 D1 Fig. 2: Expansion of a liquid in a cylinder SAMSON AG V74/ HS 6

Part 2 L205 EN Sensor volume Solids, gases and almost all liquids expand when the temperature increases. This physical principle of expansion is utilized by thermometers. An increase in temperature causes the liquid level in a capillary to rise and the height of the liquid column indicates the measured temperature. A sensor operating on the liquid expansion principle is shown in Fig. 2. The liquid expands in the cylinder when the temperature rises. As the wall of the cylinder prevents lateral expansion, the liquid expands only in the axial direction, pushing the piston and the connected pin upward. expansion in the cylinder The increase in volume can be calculated as follows: V = V 0 γ T The expansion of the filling medium is determined by two factors - the specific coefficient of expansion γ which depends on the type of fluid used and the change in temperature T. The height of the pin protruding from the cylinder is a measure for the expansion and represents a function of the temperature (h=f(t)). To achieve a particular travel of the pin h, the shape of the operating element must be considered and adapted as required. Generally, small sensor volumes yield larger travels than large volumes (Fig. 2). In instrumentation, small sensor volumes are preferred since the measuring span is better represented when the pin travel is large. In this way, more accurate measurement results are obtained. However, a disadvantage of small-volume sensors is the low power transmission. When sizing a sensor, a compromise must be found between the change in travel and temperature as well as the increase in force. expansion as a function of temperature SAMSON AG 99/12 7

Self-operated Regulators Temperature Regulators Filling medium small heat capacity for fast-responding sensors To quickly obtain accurate measurements, the quantity of heat a sensor must absorb and release should be as low as possible. This can be achieved either by keeping the volume or the mass low, or by choosing a filling fluid with a low specific heat capacity. The quantity of heat stored in the fluid calculates as follows: W = c p m T c p is the specific heat capacity, m the mass and T the change in temperature in C. Note that the specific heat capacity is not constant, but changes with the temperature. water not suitable as filling medium Due to its high specific heat capacity, water is not suitable as filling medium. It has yet another disadvantage. With the exception of water, all liquids expand continuously with increasing temperatures and condense when the temperatures fall. Water, however, reaches its highest density at 4 C and expands at higher as well as lower temperatures. Therefore, the temperature measured in these ranges would not be clear. SAMSON temperature sensors use low-viscous, synthetic oil as filling medium. This liquid is harmless, i.e. it endangers neither health nor environment. It can be discharged with the waste water if leakage occurs (water danger class 0). Formerly used silicone oils were not accepted by the automotive industry since silicone oils cause wetting problems with water-based lacquer. Apart from liquids, resins and elastomers can also be used as filling fluid. Expansion resins are particularly favorable when a great change in volume is to be achieved within a narrow temperature range. SAMSON AG V74/ HS 8

Part 2 L205 EN CO2 CO2 T 1,p 1 T 1 > T 2 activated carbon p 1 > p 2 Fig. 3: CO 2 molecules depositing on activated carbon Adsorption principle The adsorption principle is based on a physical method. The temperature sensor contains activated carbon and carbon dioxide. When the sensor is heated by the medium to be measured, the activated carbon releases single CO 2 molecules. The pressure inside the sensor (Fig. 3) increases, representing a significant value for each temperature value. When the internal pressure is transmitted via a control line to the operating bellows, the valve position is changed with respect to the temperature. The most important benefit of the adsorption principle is its good adaptation to the respective application. The measuring span of an adsorption sensor can be set in two ways: activated carbon releases CO 2 molecules flexible application... SAMSON AG 99/12 different types of activated carbon and gases yield different pressure-temperature curves; varied filling conditions yield different operating ranges. Four overlapping set point ranges are available, covering the range from 0 to 150 C. The disadvantage of adsorption sensors is that their thrust is much smaller than that developed by vapor-pressure or liquid-expansion sensors.... but small thrust 9

Self-operated Regulators Temperature Regulators Vapor pressure principle The vapor pressure principle is based on a thermodynamic method. When a liquid is subjected to heat, it begins to boil at a certain temperature and steam is generated. The boiling temperature, however, depends on the prevailing pressure. The lower the pressure, the lower the temperature at which the liquid starts to boil. Example: In an open vessel, water boils at 100 C. The boiling temperature in a pressure cooker, however, is considerably higher because the pressure created in the airtight cooker is much higher. sensor system utilizes steam pressure curve The steam pressure curves of hydrocarbons are plotted in Fig. 4. When the temperature of the medium to be measured increases, the boiling pressure in the closed sensor system increases as well, following the rising steam curve. Depending on the measured temperature, a significant pressure is created in the sensor. The internal sensor pressure acts on a bellows in the thermostat, generating a thrust. The filling medium in sensors for self-operated regulators often is a mixture of hydrocarbon compounds (HC-compounds). propane n-butane 100 n-pentane 10 n-heptane pv [bar] 1 0.1 0,1-50 0 50 100 150 200 T [ C] Fig. 4: Steam pressure curves of hydrocarbons SAMSON AG V74/ HS 10

Part 2 L205 EN The maximum ambient temperature must be minimum 15 K lower than the set point to prevent the filling medium from vaporizing in the control line. The basic properties of the different measurement methods are compared in the following table. Sensor liquid solids vapor adsorption expansion expansion pressure thrust strong strong medium weak expansion behavior excess temp. safety linear almost linear not linear linear low low medium high mount. position any any defined any time constant medium large small small Table 1: Properties of different sensor systems SAMSON AG 99/12 11

Self-operated Regulators Temperature Regulators How the sensor design influences the dynamic behavior Types of bulb sensors Bulb sensors are in direct contact with the medium. The resulting heat exchange is characterized by the heat transfer coefficient. sensors require large heat transfer surfaces The heat transfer coefficients of liquids are remarkably higher than those of gases. Temperature changes of a liquid act therefore faster on the sensor case, the filling medium and finally the valve position. When sizing the temperature sensor, the surface provided for heat transfer must be as large as possible. While the cylindrical surface of a bulb sensor is sufficient for measuring water and other liquids, gases require a specially manufactured four-bulb sensor. In this sensor, the ratio between the sensor surface and the volume of the filling medium is larger than that of the bulb sensor. Y 1 water Y 0.6 0.2 1 air 200 water bulb sensor 400 600 800 t [s] Fig. 5: 0.6 0.2 200 air four-bulb sensor 400 600 800 t [s] Unit step response of a bulb sensor and a four-bulb sensor SAMSON AG V74/ HS 12

Part 2 L205 EN measuring span for K P1 measuring span for K P2 H 100 H 100 K P2 > K P1 H 0 H 0 T A T E T A T E Fig. 1: Effect of K P on measuring span Fig. 5 compares the unit step response of a bulb sensor with that of a four-bulb sensor after they have been immersed into warm circulating water and into an air duct. The temperature difference is so big that the pin passes through its entire travel. Particularly in the air duct, the larger sensor volume proves favorable. The pin of the four-bulb sensor almost reaches its final travel after twelve minutes, while the bulb sensor takes 40 minutes, which is too slow for fast control loops. Set point adjustment Self-operated regulators usually exhibit proportional control action (P regulators). In the case of self-operated temperature regulators, the P action causes the valve travel to change proportionally with the measured temperature T. The proportional-action coefficient is K P (formerly: proportional band x P ;x P = 100%/K P ). The following equation describes the control action of temperature regulators. control action of self-operated regulators h = K P * T SAMSON AG 99/12 13

Self-operated Regulators Temperature Regulators large travel at small T universal application requires set point adjuster As described in the Control Engineering Fundamentals (see also Lit [2]), P regulators have a steady-state error. When the steady-state error is to be kept small, a large proportional-action coefficient is required (small proportional band). This means for the temperature regulator that a large travel must be achieved at a small T. The measuring span of the sensor becomes accordingly smaller (Fig. 6). However, narrow measuring spans are an obstacle to the universal application of sensors. Therefore, the temperature regulator in Fig. 7 is equipped with a set point adjuster. In the sensor, an externally adjustable piston can be moved to change the volume of the system. When the piston is pushed into the right cylinder, the pin in the operating element is lifted, providing the required volume. As a result of the changed pin position, the travel position of the valve is changed, too. Excess temperature sensor protected against excess temperature When the temperature reaches the upper limit of the set point range, the pin is fully extended. The valve is in its end position and the liquid fills the sensor completely. When the temperature rises above this value, the liquid in the sensor cannot expand further. If no equalizing volume is provided, the rising pin operating element piston Fig. 7: Set point adjustment at temperature sensor SAMSON AG V74/ HS 14

Part 2 L205 EN set point adjuster connection to operating element excess temperature spring gasket piston Fig. 8: Pressure relief fitting at sensor internal pressure will damage the sensor. To prevent this, a pressure relief fitting is installed (Fig. 8). When excess temperatures occur, the rising filling pressure acts on the piston bottom and pushes the piston out of the sensor against the force of the excess temperature spring. This increases the sensor volume. The excess temperature spring has no effect on the set point adjustment. Mounting position A prerequisite for the proper functioning of temperature control systems is the optimum location of the sensor. It should be totally immersed in the medium to be measured. Fig. 9 illustrates various mounting positions. If the sensor is mounted perpendicular to the flow direction (Fig.9 d), the sensor surface is in contact with the medium only shortly. In this case, the absorbed heat quantity can be too small to yield accurate measurement results. wrong position affects measurement results dead times must be avoided SAMSON AG 99/12 Another important requirement is that the sensor measure nearly without dead time. Dead times occur, for example, in a heating system when the sensor is not located directly at the heat source, e.g. the heat exchanger, but far 15

Self-operated Regulators Temperature Regulators away in the heating pipe. In this case, temperature changes are measured with delay. a) correct b) still possible c) less suitable d) wrong Fig. 9: Sensor locations SAMSON AG V74/ HS 16

Part 2 L205 EN Dynamic behavior of sensors The dynamic behavior of a self-operated regulator depends on the dynamic behavior of its sensor. The dynamic behavior is characterized by the time constant τ. The constant describes the time the pin needs to reach approximately 63 percent of the new operating point when forced by a step change in temperature. When looking at the sensor from the viewpoint of control engineering, the sensor can be regarded as energy store. Its dynamic behavior can be described by means of an exponential function using the time constant T 1 = τ (first-order delay). When mounting a thermowell, another energy store is added to the system. Hence, a second-order system is created. To describe sensor and thermowell both exhibit PT 1 action Y 1 0.8 Y 0.63 A B C sensors sensors: A: vapor pressure B: adsorption C: liquid expansion 0.2 Y τ A τ B 20 40 60 τ 80 100 C t[s] 1 B 0.6 A sensors with thermowell 0.2 C SAMSON AG 99/12 20 40 60 80 100 Fig. 10: Unit step responses of sensors t[s] 17

Self-operated Regulators Temperature Regulators such a system, the time constant T u and the build-up time T g can be used. For further details, please refer to the Technical Information L102 EN. As can be seen in Fig. 10, small time constants are typical to fast-responding sensors. thermowells prolong the response time Table 2 lists the time constants of the different SAMSON sensors. Measurements have been made in water. You can see from the table below that a thermowell used with an adsorption and a vapor pressure sensor causes long delays. So the fast response times inherent to those sensors are practically eliminated and they are almost as slow as liquid-expansion sensors. Principle type without thermowell with thermowell liquid expansion 2213 70 120 2231 70 120 2232 65 110 2233 25 2234 15 2235 10 adsorption 2430 15 30 40 80 2212 40 2430-L 8 2439 40 vapor pressure 2430-3 3 3 55 2403 40 sensor diameters d= 9.5 16 div. 9.5 16 div. Table 2: Effect of thermowell on time constant SAMSON AG V74/ HS 18

Part 2 L205 EN Standard materials for sensors and thermowells are usually copper or bronze because of their excellent conductivity. For aggressive media, stainless steel versions are used which, however, increase the time constants of the sensors by approximately ten percent. With thermowells, stainless steel does not affect the time constant. sensor material: bronze and copper Thermowells are not suited to be used with sensors for air. Due to the special sensor shape, a narrow air gap is formed between the thermowell and the sensor, which has an insulating effect. The time constant of an air sensor with thermowell would be much higher than that of a standard sensor with thermowell. NOTE: You may find technical literature where variables, such as T 0.5 (half-value period) or T 0.9 (90% value) are used to describe the dynamic behavior of sensors. These values can be calculated for first-order systems using the equation below and the time constant τ: y τ ( 1 e T ) = T 0.5 T 0.9 = 0.7 τ = 2.3 τ SAMSON AG 99/12 19

Self-operated Regulators Temperature Regulators Valves and their applications Force-balancing spring and actuating force are balanced in a state of equilibrium The signal pressure of self-operated regulators is generated by the expansion of the filling medium in the operating element. To make the interaction of the different forces understandable, a valve balanced by a bellows is described in the following example (see also Lit [3]). The upstream pressure p 1 and the downstram pressure p 2 acting on the valve plug are balanced by the bellows. As a result, the actuating force F A is opposed only by the pre-loaded spring F F (Fig. 11). Both forces are balanced in a state of equilibrium. F A1 F F1 T 1 = const. F A2 F F2 Fig. 11: Force balance after increase in temperature T 2 = T 1 + T SAMSON AG V74/ HS 20

Part 2 L205 EN The self-operated regulator is used to reduce or increase the flow rate when the temperature at the measuring point rises or falls. The temperature is regulated as follows: When the medium is heated, the filling liquid in the operating element expands and exerts the actuating force F A on the valve. The valve closes against the spring force F F, reducing the flow of the heating medium. When the flow is reduced, the temperature falls until a new equilibrium of forces and, hence, a new valve position is reached. NOTE: When sizing a system including a heat exchanger, the upstream temperature must be minimum 10 K above the set point temperature to ensure safe closing of the valve. SAMSON AG 99/12 21

Self-operated Regulators Temperature Regulators B A AB Fig. 12: Three-way mixing valve Mixing and diverting valves Heating and cooling control systems require different valve styles. Globe valves control one flow to adjust the desired temperature. Three-way valves, on the other hand, mix or divert two heat flows. B A AB Fig. 13: Three-way diverting valve SAMSON AG V74/ HS 22

Part 2 L205 EN Three-way valves have three ports (A, B, AB), while globe valves have two. When no actuating force is exerted on the valve, a return spring ensures that the double plug is firmly placed on one of the two seats. In mixing valves (Fig.12), the heating medium enters at port B via the seat/plug assembly and leaves through port AB. Port A is closed. When an actuating force acts on the medium flow through mixing valves control task: constant temperature in the consumer loop flow control mixing diverting globe valve three-way mixing valve three-way diverting valve when temperature increases valve closes A opens B closes A closes B opens SAMSON AG 99/12 Fig. 14: Example of a heating system 23

Self-operated Regulators Temperature Regulators plug stem, the valve moves towards its other end position, reducing the flow through the inlet port B and opening the inlet port A. medium flow through diverting valves The flow through diverting valves (Fig. 13) is quite different. Here, the cooling medium enters at port AB. The streams are diverted according to the valve position and finally leave through the ports A and B. control task: constant temperature in the consumer loop flow control mixing diverting globe valve three-way mixing valve three-way diverting valve when temperature increases valve opens A opens B closes A closes B opens Fig. 15: Example of a cooling system SAMSON AG V74/ HS 24

Part 2 L205 EN The operating principle of the valves and their application in a heating and a cooling system are illustrated in Figs. 13 and 14. The Figs. 13 and 14 show typical installation examples where the valves can be installed either in the flow pipe or in the return pipe. In heating systems with high temperatures and low pressures, cavitation can cause problems, therefore the valve should be installed in the cooler return pipe. installing valves in heating or cooling systems When engineering the heating or cooling installation, make sure that the process medium flows in the opening direction of the plug of the mixing or diverting valve so that "vibrations" near the closing position are prevented. Otherwise the small surface, the high velocity and the low pressure would cause the plug to be seized in the seat and released again when the flow is interrupted. SAMSON AG 99/12 25

Self-operated Regulators Temperature Regulators Globe valves in cooling service reversing device changes operating direction The globe valves described above close when the temperature at the sensor rises, hence, they are suitable for heating service. In cooling installations, however, a valve is required that opens with increasing temperature. This can be achieved either by changing the seat/plug position or by installing a reversing device (Fig. 16) between the sensor and the bellows housing of a normal globe valve. In the latter case, the valve is closed by the spring force and opens when the temperature rises. plug stem connection to operating element reversing device Fig. 16: Reversing device SAMSON AG V74/ HS 26

Part 2 L205 EN Appendix A1: Additional literature [1] Terminology and Symbols in Control Engineering Technical Information L101 EN; SAMSON AG [2] Controllers and Controlled Systems Technical Information L102 EN; SAMSON AG [3] Self-operated Regulators Technical Information L202 EN; SAMSON AG SAMSON AG 99/12 APPENDIX 27

Self-operated Regulators Temperature Regulators Figures FIGURES Fig. 1: Temperature control loop with heat exchanger......... 5 Fig. 2: Expansion of a liquid in a cylinder............... 6 Fig. 3: CO 2 molecules depositing on activated carbon......... 9 Fig. 4: Steam pressure curves of hydrocarbons........... 10 Fig. 5: Unit step response of a bulb sensor and a four-bulb sensor... 12 Fig. 6: Effect of K P on measuring span................ 13 Fig. 7: Set point adjustment at temperature sensor.......... 14 Fig. 8: Pressure relief fitting at sensor................ 15 Fig. 9: Sensor locations...................... 16 Fig. 10: Unit step responses of sensors................ 17 Fig. 11: Force balance after increase in temperature.......... 20 Fig. 12: Three-way mixing valve................... 22 Fig. 13: Three-way diverting valve.................. 22 Fig. 14: Example of a heating system................. 23 Fig. 15: Example of a cooling system................. 24 Fig. 16: Reversing device...................... 26 SAMSON AG V74/ HS 28

Part 2 L205 EN SAMSON AG 99/12 NOTES 29

Self-operated Regulators Temperature Regulators NOTES SAMSON AG V74/ HS 30

SAMSON right on quality course ISO 9001 Our quality assurance system, approved by BVQi, guarantees a high quality of products and services.

SAMSON AG MESS- UND REGELTECHNIK Weismüllerstraße 3 D-60314 Frankfurt am Main Phone (+49 69) 4 00 90 Telefax (+49 69) 4 00 95 07 Internet: http://www.samson.de 1999/12 L205 EN