SM 1234 ANALOG INPUT/OUTPUT MODULE Function The SM 1234 analog input/output signal modules convert analog signals from the process into digital signals for internal processing by the SIMATIC S7-1200. convert digital signals of the SIMATIC S7-1200 into signals for controlling the respective process. Technical specifications Page 904 Mar 2008 Siemens ITS
Technical specifications 6ES7 234-4HE30-0XB0 SM 1234 A I4x13 bit AQ 2x14 bit Supply voltage 24 V DC Input current Current consumption, typ. 60 ma from backplane bus 5 V DC, typ. 80 ma Power losses Power loss, typ. 2 W Analog inputs Number of analog inputs 4; Current or voltage differential inputs permissible input frequency for current input ± 35 V permissible input voltage for voltage input 35 V permissible input current for voltage input 40 ma Cycle time (all channels) max. 625 µs Page 905 Mar 2008 Siemens ITS
permissible input current for current input 40 ma Input ranges Voltage ; ±10 V, ±5 V, ±2.5 V Current ; 0 to 20 ma Thermocouple Resistance thermometer Resistance Input ranges (rated values), voltages -10 V to +10 V Input resistance (-10 V to +10 V) 9 MOhm -2.5 V to +2.5 V Input resistance (-2.5 V to +2.5 V) 9 MOhm -5 V to +5 V Input resistance (-5 V to +5 V) 9 MOhm Input ranges (rated values), currents 0 to 20 ma Input resistance (0 to 20 ma) 250 ohms Temperature compensation Parameterizable Analog outputs Number of analog outputs 2; Current or voltage Output ranges, voltage -10 to +10 V Page 906 Mar 2008 Siemens ITS
Output ranges, current 0 to 20 ma Load impedance (in rated range of output) with voltage outputs, min. 1 000 Ω with current outputs, max. 600 Ω Analog value creation Measurement principle Differential Integrations and conversion time/ resolution per channel Resolution (incl. overrange) Voltage: 14 bits; Current : 13 bits Resolution with overrange (bit including 12 bit; + sign sign), max. Integration time, parameterizable Interference voltage suppression for interference frequency f1 in Hz Smoothing of measured values Parameterizable Step: ne Step: low Step: Medium Step: High Errors/accuracies Temperature error (relative to input area) 40 db, DC to 60 V for interference frequency 50 / 60 Hz Page 907 Mar 2008 Siemens ITS 25 C ±0.1 % to 55 C ±0.2 % total measurement range
Temperature error (relative to output area) 25 C ±0.3% to 55 C ±0.6% total measurement range Basic error limit (operational limit at 25 C) Voltage, relative to input area +/- 0,1 % Current, relative to input area +/- 0,1 % Voltage, relative to output area +/- 0,3 % Current, relative to output area +/- 0,3 % Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency common mode voltage, max. 12 V Interrupts/diagnostics/status information Alarms Alarms Diagnostic alarm Diagnoses Diagnostic functions Monitoring the supply voltage to the electronics Wire break Short circuit Diagnostics indication LED for status of the inputs For status of the outputs for maintenance Page 908 Mar 2008 Siemens ITS
Galvanic isolation Galvanic isolation analog outputs between the channels and the power supply of the electronics Climatic and mechanical conditions for storage and transport Climatic conditions for storage and transport Free fall Drop height, max. (in packaging) Temperature Permissible temperature range Air pressure acc. to IEC 60068-2-13 Permissible air pressure Mechanical and climatic conditions during operation Climatic conditions in operation Temperature Permissible temperature range Air pressure acc. to IEC 60068-2-13 Page 909 Mar 2008 Siemens ITS 0.3 m; five times, in dispatch package -40 C to +70 C 1080 to 660 hpa 0 C to 55 C horizontal installation 0 C to 45 C vertical installation
Permissible air pressure Pollutant concentrations SO2 at RH < 60% without condensation Degree and class of protection IP20 Standards, approvals, certificates CE mark C-TICK FM approval Connection method required front connector Mechanics/material Type of housing (front) Plastic Dimensions Width Height Depth Weight Weight, approx. 1080 to 795 hpa S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free Page 910 Mar 2008 Siemens ITS 45 mm 100 mm 75 mm 220 g