Chilled Beam Systems and the 2016 WSEC

Similar documents
HVAC Systems: Overview

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

Active & Passive Beams

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone.

Element D Services Heating, Ventilating, and Air Conditioning

Active Chilled Beam System Design & Layout

Glossary of Heating, Ventilation and Air Conditioning Terms

Challenges and Failures in Green Building Design Using Under-Floor Air Distribution. Ken Urbanek, PE, HBDP, LEED AP Director of Engineering

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

Preliminary Final Proposal

Ventilation Standard For Health Care Facilities

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

Mechanical Systems Proposal revised

HVAC Simplified Approach Option

Enclosed Football Stadium Design History and Lessons Learned

Innovent LASER Packaged Fresh Air Conditioning Units

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Lesson 36 Selection Of Air Conditioning Systems

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

HVAC Basic Science - System Capacity

Topics for Today. Order of Magnitude Mechanical Estimating. Order of Magnitude Estimate Goal. Project Delivery Methods. Questions for Client

1.2 Refrigerant Equipment. General

6 MECHANICAL HVAC SYSTEMS

Radiant Panels and Chilled Sails.

How To Design A Building In New Delhi

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE ? SLIDE 1

ENHANCED LABORATORY HVAC SYSTEM

HVAC SYSTEMS ACOUSTICAL, COST & ENERGY STUDY

Glossary of HVAC Terms

Flexibility, Efficiency In San Antonio Arena

High Altitude HVAC. Silvertip Integrated Engineering Consultants

HVAC Characteristics. Test Space HVAC Characteristics

Basics of HVAC Cleaning

VAV Laboratory Room Airflow The Lowdown on Turndown

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Pool Dehumidification Basics

EnergyPro Building Energy Analysis. Assisted Living Building

Basic Selection & Proper Application of Overhead Air Distribution Devices

By Tom Brooke PE, CEM

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Condensing Boiler Efficiency

HVAC Checklist - Long Form

COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN

HVAC Calculations and Duct Sizing

SAM HOUSTON STATE UNIVERSITY

Building Energy Systems. - HVAC: Heating, Distribution -

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

AABC Specifications for Testing and Balancing HVAC Systems

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

Dedicated Outdoor Air Systems (D.O.A.S.)

Sustainable Strategies for Rehabilitation Projects: 9th Street Office Building Adaptive Reuse Case Study

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

Element D Services Heating, Ventilating, and Air Conditioning

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Comparing Energy Savings of Different VAV Systems

Design Options for HVAC Distribution Systems

HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

Subtropical Cities September Design for Energy Efficiency in Commercial Buildings in Queensland

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

MECHANICAL SYSTEMS DESIGN. Team

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

Fans and Air Handling Units. Will Rea and Paul Pilutti February 16 th, 2011

Energy Efficient HVAC-system and Building Design

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water

Acoustical Design Guidelines for HVAC Systems in Schools

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Energy Efficiency in Industrial HVAC Systems

RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA.

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

plenum slot diffusers

for Plans Examiners and Building Inspectors

Fan Applications & System Guide

Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment

WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Answers to Your Questions from the Webinar

Bring the fresh in. Dedicated Outside Air Systems

University of Maryland s Gossett Field House College Park, MD

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

Defining Quality. Building Comfort. Precision. Air Conditioning

Residential HVAC Load Sizing Training October 14, David Kaiser Green Code Plan Reviewer

SECTION MORTUARY REFRIGERATORS

Mechanical Insulation. Hospitals and Schools

Transcription:

Chilled Beam Systems and the 2016 WSEC Ken Loudermilk, P.E. Senior Chief Engineer

2016-2017 WSEC Changes Code Language Changes Ventilation (C403.2.6) Ventilation airflow not to exceed ASHRAE 62.1 minimum by more than 50% Exception where ERV (C403.5.1) is provided (required when over 5,000 CFM) DOAS for ventilation air (C403.6) Dedicated AHU and ductwork for ventilation air without operation of heating/cooling fans Practically eliminates conventional VAV systems by requiring separation of ventilation air Cooling/dehumidification supplemented at zone level Exception for high efficiency VAV systems (C403.7) Economizers (C403.3) Air economizers shall be provided on all new systems Exceptions Systems complying with section C403.6 (DOAS) Water cooled refrigeration equipment utilizing cooling towers VRF and (?) fan coil systems

Chilled Beam Types Passive chilled beams Active chilled beams

Passive Chilled Beams Passive beams are typically 4 to 6 FPI Passive beams are not radiant cooling devices Passive beams are not effective for heating Require separate ventilation source

Types of Passive Beams Exposed passive beam Recessed passive beam Sensible cooling only Recessed or exposed mounting

Active Chilled Beams DOAS AHU max. 1.5 x ASHRAE 62.1 min. OA rate Pre-treated Primary Air 1 Part 0.4 to 0.7 in. SP Entrained Room Air 2 to 4 Parts Supply Air to Room 3 to 5 Parts When properly selected, constant volume supply airflow rate ensures ASHRAE Standard 55-2014 compliance. Consistent air distribution performance eliminates dumping

Placement of Active Beams T 100 V H1 A V C T 100 Occupied zone per ASHRAE Standard 55-2014 H1 Distance H1, ft 7.0 6.0 5.0 4.0 3.0 Based on an effective discharge velocity of 450 FPM 2.8 2.4 2.0 1.6 1.4 V C /V H1 10 ft. T 100 = 5 T 100 = 5 For the velocity entering the occupied zone 3½ feet below the plane of discharge to be less than 50 FPM, the collision point velocities must be less than 100 FPM If T 100 = 5 feet, the outlets must be spaced at least 10 feet on center

Sensible Cooling with Active Beams 60 to 80% reduction in primary airflow 60 to 80% of space sensible heat removal by water

Heating with Active Beams 4 Pipe Heating

Types of Active Beams Ceiling integrated beams Exposed beams Displacement beams

Multiservice Chilled Beams

WHY BEAMS?

Why Chilled Beams 16 x 16 Air Duct 1 Dia. Water Pipe Water density is 800 times that of air Water heat transfer capacity is 3,500 times that of air on a mass basis!

Architectural Savings 16 48 16 36 13-0 12-0 9-0 9-0

Impact of Reduced Slab Spacing Structural steel Curtain wall Fire proofing Air barrier Insulation Exterior caulking Masonry (interior & exterior) Dry wall Steel studs Stairs Elevators $7,200 $10,500 $600 $8,787 $7,200 $1,522 $97,692 $55,249 $22,824 $2,500 $5,000 Electrical $30,000 Total cost savings $245,298 Viterbo University (LaCrosse, WI) 65,000 ft 2 building, 5 floors Reduction of 12 per floor Structural savings of $3.77 per square foot Source: Pope and Leffingwell of HGA, Inc. and Bauer of Butler- Fetting Co. ASHRAE CRC presentation

Space Savings Ductwork and component sizes Duct area reduced by 50 % or more Supply and return chases reduced by 50% Air handling units AHU footprint reduced 30 to 40% Weight reduction to structure Increase in usable floor space

Transport Energy Comparison BHP = CFM x SP BHP = GPM x HD 6,356 x FAN EFF 3,960 x PUMP EFF 555 CFM = 1 Ton Assuming fan SP = 3 in. H 2 O Assuming fan eff. = 75% 4 GPM = 1 Ton Assuming pump HD= 40 ft. H 2 O Assuming pump eff. = 75% BHP (to move 1 Ton) = 0.35 BHP (to move 1 Ton) = 0.05

Energy Savings Air handling unit operating cost BHP typically reduced by 50% Fan energy savings of 40 to 70% Chiller operating cost Higher return water temperature to chiller increases COP by 2 to 4% per degree Dedicated chiller COP increased by up to 40%

Maintenance Costs No filtration required Low face velocities, dry coil surface Maintenance savings $100 per beam-year No blowers/motors Motor life expectancy 8 to 10 years Cost of replacement $450 to $500 Low cost of ownership Significant energy savings Minimal maintenance and repair

Chilled Beam Applications

Chilled Beam Applications Where to Use Them Anywhere you can control the indoor humidity Laboratories Office buildings Educational facilities Government facilities Health care facilities Ideal Applications Limited plenum space Applications with conflict between sensible cooling and ventilation demand Where Not to Use Them Spaces where indoor humidity cannot be controlled Kitchen and bathroom areas Other areas with low sensible heat ratios Use Them with Caution Rooms with operable windows Entrance lobbies/atriums

Passive Beams with UFAD

UFAD Plenum Heat Transfer High supply air temperature UFAD perimeter airflow rates as much as twice that of overhead systems 67 F 64 F 63 F 62 F 68 F 65 F 63 F

UFAD Perimeter Zone Treatment Passive Chilled Beam Return Air Plenum Return Grille Passive beam handles perimeter sensible load UFAD plenum airflow reduced by 50% or more! Diffusers responsible for ventilation and latent load Trench heating along perimeter wall Floor Diffuser Supply Air Plenum Hydronic Fin Tube Coil

100 Howe Building Campuses in Covington, KY and Southlake, TX UFAD with passive chilled beams Two identical buildings in Covington with VAV systems UFAD system airflow reduced 60% by use of chilled beams First year 41% HVAC energy savings in new facility 2010 ASHRAE Technology Award winner

Active Beams for Laboratories

Laboratory Characteristics General Strict ventilation requirements protect staff Laboratories with chemicals and gases must exhaust all return air Laboratory classifications Make-up air driven. generally more than 10 ACH -1 Heat driven (less than 10 ACH -1 ) Heat driven laboratories Space sensible heat gains of 60 to 70 BTUH/FT 2 Space ventilation requirements typically 6 to 8 ACH -1 All air systems require 18 to 20 ACH -1 to satisfy laboratory sensible load

Three fold reduction in lab air change rate! 67% reduction in primary airflow 28 67% of space sensible heat removal by water 40 to 60% savings in air handling unit and chiller installed capacity 25 to 50% savings in annual HVAC energy costs

Active Beams for Healthcare

Patient Care Areas Ventilation requirements Minimum of 6 total ACH -1 Minimum of 2 outdoor ACH -1 Room air recirculation not counted Filtration requirements MERV 14 at AHU MERV 6 within room

Hospital HVAC Energy Usage Hospitals use 2.5 times the average of other commercial buildings on a per ft 2 basis! Hospital HVAC Energy Usage Breakdown 52% 14% 23% Cooling Fans and Pumps Central Heating 11% ASHRAE/DOE challenge to reduce hospital HVAC and lighting energy 30% by 2020

All Air VAV Systems Primary Air Air Design 80% 20% of Cooling of Design Load 7 ACH -1 = 25 Btu/h-ft 2 6 ACH -1 = 22 Btu/h-ft 2 25 205 Btu/h-ft 2 22 Reheat 17 2 Btu/h-ft 22

ANSI/ASHRAE Std. 170-2013 Total ACH -1 reduced from 6 to 4 Still requires 2 ACH -1 of outside air Filtered (MERV 14) at the AHU Recirculation within same space counts toward the 2 non-outside air changes No room side filtration required if coils remain dry

Patient Suite HVAC Energy Use Comparison of VAV system supplying at 55 F versus DOAS beam system supplying at 65 F Air changes Outside air 2 4 5.5 20 BTU/H-FT 2 (Design) 14.5 BTU/H-FT 2 (72% of design) 10 BTU/H-FT 2 (50% of design) 20 BTU/H-FT 2 4 BTU/H-FT 2 16 BTU/H-FT 2 14.5 BTU/H-FT 2 4 BTU/H-FT 2 10.5 BTU/H-FT 2 VAV System cooling load reduction of 28% w/o reheat! 14.5 BTU/H-FT 2 4.5 19 BTU/H-FT 2 4 BTU/H-FT 2 6 6 BTU/H-FT 2 (30% of design) 4 BTU/H-FT 2 14.5 BTU/H-FT 2 2 8.5 BTU/H-FT 2 23 BTU/H-FT 2 4 BTU/H-FT 2 (20% of design) 14.5 BTU/H-FT 2 10.5 BTU/H-FT2 25 BTU/H-FT 2 Beam load reduction of 4 BTU/H-FT 2 80% w/o reheat!

Moses Cone Hospital Greensboro, NC 270,000 ft 2, 96 acute patient beds, completed 2011 Design team Architect: Perkins & Will MEP: AEI, Raleigh, NC Savings Cooling energy 66% Fan energy 27% Reheat energy 88% Presentation Seminar 50 2015 ASHRAE Winter Meeting, Chicago, IL Reference: Robert Sherman Affiliated Engineers, Raleigh, NC rhsherman@aeieng.com

Office Building Installations Constitution Center Washington, DC National Geospatial Intelligence Agency Fort Belvoir, VA

Educational Facilities Effective ventilation Improved acoustics Disease transmission Absenteeism Learning environment

Displacement Ventilation 60 to 65 F 40 to 70 fpm

Displacement Chilled Beams Room side mixing simplifies AHU design especially in humid climates Separate coils allow for consistent ventilation effectiveness in both cooling and heating Vertical coil allows provision of gravity drain condensate tray Meets ANSI S12.60 requirements (background noise level 35 dba)

Chilled Beam System Design

Air and Water Temperatures Conventional system Discharge (supply) air, cooling 53-55 F Discharge (supply) air, heating 90-95 F Chilled water supply (to AHU) 40-45 F Hot water supply 140-180 F Chilled beam system Primary air (cooling) Discharge (supply) air, cooling Discharge (supply) air, heating Chilled water supply Hot water supply 53-65 F 61-70 F 80-85 F 55-62 F 100-140 F

Primary Airflow Rate 60 to 80% reduction in space latent cooling 60 to 80% reduction in primary airflow 60 to 80% of space sensible heat removal by water Beam s primary airflow rate is the greatest of the following: Primary airflow rate required for space ventilation Primary airflow rate required for the necessary space latent heat removal Primary airflow rate required to drive the space sensible cooling Direct contribution by cool primary air introduced into the space Plenum pressurization to adequately drive the beam induction process Ideal scenario occurs when all three functions require same primary airflow rate!

Primary Airflow Rates Primary airflow rate, CFM/ft 2 2.0 1.8 1.6 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0 Design primary airflow rates in office buildings Chart based on: - One person per 100 ft 2 - Interior zones sensible cooling 11 Btu/h- ft 2, latent 2 Btu/h- ft 2 - Perimeter zones sensible cooling 30 Btu/h- ft 2, latent 5 Btu/h- ft 2 0.20 0.20 0.20 0.20 0.10 0.10 0.10 0.10 ACB system VAV system ACB system VAV system Interior office areas 0.50 0.50 0.55 0.50 Perimeter office areas 1.4

Water Side Design Chilled water source Piping and zoning Condensation

Closed Loop Beam Supply Supply temperature Chiller 43 to 45 F Pump 57 to 61 F Beam distribution loop supply Modulating valve Plate heat exchanger Air handling unit Beam distribution loop return

Open Loop Beam Supply Chiller Pump Storage vessel Modulating valve 43 to 45 F 57 to 61 F Pump Supply temperature Beam distribution loop supply Pump Air handling unit Beam distribution loop return

Dedicated Chilled Water Source

Water Distribution Strategies Zoning similar to all air system! 2 pipe water distribution system Commonly used where beams are not required to provide heat Not recommended when simultaneous cooling and heating is required

Water Distribution Strategies 4 pipe water distribution system Commonly used where beams are also used for heating

Condensation Formation Chilled water supply temperature = 58 F Room dew point = 60.6 F Room dew point = 64.8 F Room dew point = 62.6 F Room dew point = 66.2 F

VRF Systems Refrigerant issues High pressure piping (500 psi) Leakage potential Replacement and reclaim every two years Likely refrigerant change outs over building life Application issues Not suitable for high rise buildings Not suitable for open office plans Little or no room air distribution data Operation and maintenance Filter changes every 3 to 4 months Condensate removal Economic issues Proprietary system, limited bidders High component cost and repair costs Questionable energy performance

Chilled Beam Alternative Refrigerant issues Water is the primary cooling media Any refrigerant issue is contained in the mechanical room Application issues Suitable for any building type and size where chilled water can be justified Can be used with geothermal heat sinks Documented air distribution performance Operation and maintenance No condensation within the space No filters required Vacuum coil every five years Economic issues Many suppliers, comparable performance No moving parts on beam, simple control system Proven energy performance

Chilled Beams and the 2016 WSEC Chilled beam systems compliance Ventilation (C403.2.6) ACB with DOAS complies with maximum ventilation air restriction ERV (C403.5.1) not required for DOAS units serving less than 30,000 ft 2 DOAS for ventilation air (C403.6) Cooling/heating supplemented at zone level 60 to 80% of space sensible heat removal is water borne, increases number of hours where OA can be delivered without mechanical cooling or heating Significant reduction in space reheat energy Economizers (C403.3) Prescriptive in language Exceptions Systems complying with section C403.6 (DOAS) Water cooled refrigeration equipment utilizing cooling towers VRF and (?) fan coil systems Air side economizer not required due to DOAS exception If water side is required, what about any other systems utilizing a chiller