Notes. 2 Zones Master & Slave Fire Alarm Control Panel User & Installation Manual IMPORTANT

Similar documents
BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

FIREDEX Conventional Fire Panels

A.1. a Division of Pittway Corporation. Documento: M MGAS-ENG. Edizione: 01/1997 Rev.:

CB200W Water Leak Detection Panel Application Guide

RP1r. Extinguishing Control Panel. User Manual (Software version 3.x) 3 zone control panel to protect 1 extinguishing risk

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

Repeaters and Mimics Data Sheet

Fire Alarm Control Panel. Family. Operating Manual

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

Surveyor Excel-K. Fire Alarm Control Equipment. Installation, Commissioning and Operating Manual

3. MOUNTING THE FIRE ALARM PANEL PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL

conventional system operation

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February FA-300 SERIES Fire Alarm Control Panel

GST301. (Single Protection Zone) Operation Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual

Disabled Toilet Alarm. Contractor Pack. Installation & Operating Instructions

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions V1 Rev A 11/12)

TS510 & TS500. Installation & User Guide. Compatible Equipment

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

ACTIVE 5 ENGINEERING MANUAL

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS

CFP 2/4/8 ZONE ECONOMY FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU Rev 1

PROXIMITY CARD READERS C-10, C-20, C60, C70

VEGA Analogue Addressable Control Panels

Digital Keypad Use s Manual

Conventional Fire Detection and Extinguishant Control System Specification

SFC-200 SERIES LCD FIRE ALARM PANEL

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

9452/9453 Installation and User Guide

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

500r+ Installation and User Guide

Installation and Operation Manual

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU Rev 1

AlarmSense 2-wire detection and alarm system. Product Guide

User s Information Guide R1A

21. Power supply Maintenance... 22

D287/D288/D292/D293A/D293E

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2

INSTALLATION MANUAL PC2525. Version 1.1

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

Troubleshooting and Diagnostics

Premier M Plus & Infinity 8

ZETA ALARM SYSTEMS PREMIER AL MANUAL

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

Syncro. Multi Loop Analogue Addressable Fire Control Panel. Product Manual Man-1055 Issue 26 May 2016

Modular I/O System Analog and Digital Interface Modules

Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

Using your LED Plus keypad

Syncro. Multi Loop Analogue Addressable Fire Control Panel. Product Manual. Man-1055 Issue 21 September 2010

Control/Communicator Installation Manual

TABLE OF CONTENTS FEATURES

Solar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

Shunt lock function 3066

LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual

HMI display Installation Guide

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

TX GSM SMS Auto-dial Alarm System. Installation and User Manual

TMS TANK MANAGEMENT SYSTEM

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

Fire Detection Product Range

User s Manual Before using the inverter, you need to read and save the safety instructions.

User Manual. ATX12V / EPS12V Power Supply TG-I460R (460W+460W) TG-I550R (550W+550W) Switching Power Supply User Manual

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU Rev 1

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Secure Keypads for access control

User Manual. Before installation and use, please read the user manual carefully.

FIRE ALARM PANEL & SYSTEM OPERATION ID50 SYSTEM. The Fire Alarm System can be activated in the following ways :~

Owner s Manual AWM910 JENSEN AWM910 COMPACT DISC PLAYER RADIO CD COMPACT MUSIC SYSTEM MUTE AUX BAND AUX IN PUSH PUSH PWR VOL ALARM T/F AUD SPK A SPK B

Manual for Fire Suppression & Methane Detection System

D200+ Auto-Dialler Installation/Operators Manual

WD-AMX Water Detection Controllers

9448 Installation and User Guide

NC-12 Modbus Application

Model 201 Wiegand Touchpad Reader Installation Guide

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

User Manual for CH-PFC76810

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

GSM HOME SECURITY SYSTEM

Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

LED - Indicator Panels

Fire Alarm Control Panel. Operating Manual

USER GUIDE. Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator. DM Engineering. Version 1.

INSTALLATION MANUAL CONTENTS

SILENT KNIGHT MODEL 5207

Global System Technology(UK) PLC The Intelligent Solution

(68.52) X. June 2000 Supercedes February xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we business differently

!Operation:!1. Connect an external power source to J1 (+ and - IN terminals). The

SKR - industry relay

Product Guide. Low voltage grounding system. Answers for industry.

Class 2 transformer (TBT) Low Tension Conform to EN A LED turns ON when the current exceeds 1 A at the 14V output connector

MSL1000 Monitored Serial Link Interface Manual V1.01

Transcription:

2 Zones Master & Slave ire larm Control Panel User & Installation Manual Notes ZONE1 ZONE2 SOUND ZONE1 ZONE2 SOUND EVCUTE SILENCE TEST/RESET EVCUTE SILENCE TEST/RESET Master Panel Slave Panel IMPORTNT This manual should be left with the panel after installation. We reserve the right to change product specifications without prior notice.

INSTRUCTION MNUL 3 Introduction The information provided in this manual covers the Master and Slave fire alarm control panel. The panel range is designed to meet the requirements of EN54 Parts 2 & 4. This product should be installed, commissioned and maintained by suitably qualified service personnel with reference to IEE regulations and any statutory requirements. General Description The panel 2 zones ranges of fire alarm control panels are microprocessor controlled and are available with 2 sense zones (detector zones). The panels have 1 alarm sound output zones (bell zones), a 24V supply energised on fire, one set of volt free changeover contacts which operate on fault, and two sets of volt free changeover contacts which operate on fire. Installation Procedure Before proceeding with the installation, please read the section Panel Operation. Installation of the panel should be carried out by qualified personnel. 4 IRE LRM PNEL Using the metal box as a template, mark the position of the fixing holes on the wall. Drill and plug the wall, then screw the panel to the wall. Ensure the panel is free from knockout discs, swarf and other debris. The back of panel box is as below, there are three wiring holes on the back, and another three holes on the top of box for cable wiring. nd there are six diameter 6mm holes on the back of box for screws to fix the box on the wall. 140mm 57mm 28.5mm 28.5mm Diameter 6mm 12mm 29.5mm 105mm 82mm 59mm Diameter 20mm

INSTRUCTION MNUL 5 Do not remove any end of line resistors from the panel until after the following test is performed. With all end of line resistors fitted inside the panel, connect the panel DC24V input to an external DC22 to 26V power supply. Switch the external DC24V supply on. The internal buzzer will sound. With the panel DC power supplies connected, the panel should be silent and in its normal operating mode, the power running lamp (above the Test/Reset button) would flash (about 10 seconds without communication, about 5 seconds with communication), alarms & buzzer silent. If a fault is indicated, refer to the fault finding section before proceeding. Switch off the mains supply. Remove the 5k6 end of line resistor from sense zone 1. Terminate sense zone 1 circuit wiring in the panel observing correct polarity and fit the end of line resistor at the very end of the circuit. Check that all the detectors and call points are correctly wired. With sense zone 1 connected and all other end of line resistors fitted inside the panel, connect the DC power supplies. If the panel indicates a fault, refer to the fault finding section before proceeding. Do not megger cables connected to either the panel or any field devices. If no faults are indicated then 6 IRE LRM PNEL power down the panel and follow the same procedure with the additional sense zones and then the alarm zones. dding the zones one at a time makes fault finding and commissioning much simpler. Make sure that no bare wires come into contact with the panel circuit boards during installation. Detector Head Removal The Panel supports head removal. The basic principle of head removal is to ensure that all call points will function even if a detector head has been removed. Head removal requires either zener clamp bases or schottky diode bases with the appropriate end of line device to be fitted. When a detector head is removed, the panel will show a fault, but the sense zone circuit will remain intact.

INSTRUCTION MNUL 7 8 IRE LRM PNEL Control panel fascia In addition to the mandatory controls and indications required by the EN54-2/4 standards, Reset, Test, and Silence larm/ault buttons are provided to allow easy operation to the control pane. Master Panel Slave Panel Zone1 larm LED Zone2 larm LED Sound larm LED Sound ault LED Zone1 ault LED Zone2 ault LED Silence LED Zone1 larm LED Zone2 larm LED Zone1 ault LED Zone2 ault LED Sound larm LED Sound ault LED Digital LED Silence LED Evacuate LED Evacuate Button RUN LED Test/Reset Button Silence Button RUN LED Evacuate LED Slave panel has no 4 digital LED. Evacuate Button Test/Reset Button Silence Button Master panel has 4 digital LED.

INSTRUCTION MNUL 9 Panel Operation Normal Status. If the panel is in its normal condition, the RUN led (above the TEST/RESET button) would flash once every 10 seconds (without communication) or 5 seconds (with communication).. Performing a lamp test. If the panel is in its normal condition, pressing the Test/Reset button will cause the panel to perform a lamp test. In the normal condition, press and hold down Test/Reset button about 10 seconds, the panel would be reset. Resetting the panel after a fire or fault is detected. To reset the panel after a fire or fault event, press the Silence button first and then press the Reset button. Resetting the all the panels. If any of the panel functions have been activated, pressing Silence button first and then press the Reset button will return the panel to its normal condition. When the master panel s Reset button pressed, master panel and all the slave panels would be reset. 10 IRE LRM PNEL Silencing the internal buzzer. If a fault or a alarm is detected by the panel, the internal buzzer will sound. To silence the buzzer press the Silence button. Silencing the Sound larms. If a fire is detected, the panel will automatically activate the sound circuits. To silence the sound alarms, press and hold down the Silence button about 5 seconds. ctive sound alarm manually. nytime, press the Evacuate button, the sound output would be activated. ctive ire1 & ire2 Relay output manually nytime, press and hold down the Evacuate button first, and then press and hold down the Silence button, and then press Test/Reset button, then release the Test/Reset button, then release Silence button, at last release the Evacuate button, the Evacuate LED would flash, and then ire1 relay and Sound output would be activated, after 30 seconds delay, the ire 2 relay would be activated. The Evacuate LED would be light steady. Pause the ire2 Relay output delay time

INSTRUCTION MNUL 11 Whenever automatically or manually active the 30 seconds count down delay time,, press Evacuate button, the count down delay time would be paused, the Evacuate LED and Silence LED would flash together, when press Evacuate button again, the Silence LED would not flash, the count down delay time would go on continuously. ault inding RUN LED blinks intermittently This is perfectly normal and indicates that the processor is running an internal memory check. ault LED and sense zone fault LED flashing, buzzer sounding. aults monitored are: Open circuit on the sense zone wiring. Detector head removal. Check all detectors and call points on the sense zone indicated. Check wiring is as in example diagrams and ensure the end of line monitor is a 5k6 resistor or an active end of line device. 12 IRE LRM PNEL Short circuit on the sound output wiring. The end of line diode not connected or not connected correctly. Head removal not working. Check compatible base is being used and is wired correctly. Other faults. Switch off the power supply and restart the power on. ault Output The fault output, marked ULT on the PCB, is a set of volt free changeover contacts. When the panel is in fault, common (C) is shorted to normally open (NO). In normal operation with no faults, common (C) is shorted to normally closed (NO). Sound fault LED flashing, buzzer sounding. aults monitored are: Open circuit on the sound output wiring.

INSTRUCTION MNUL 13 Panel Inside 14 IRE LRM PNEL Panel Specifications Master Slave System Voltage (V DC) DC22-26V DC22-26V Normal Quiescent Current (normal status) <50m <50 m larm Current (not include the others) <150 m <150 m Detector Voltage (V DC) 24 24 Number of Sense Zones 1-2 1-2 Maximum Number of Detectors per Zone 30 30 iring Resistance (Ohms) 510 ± 200 510 ± 200 Sense Zone End of Line (Ohms) 4K7-10K 4K7-10K larm Voltage (V DC) 24 24 Number of larm Zones 1 1 Maximum larm Current per Zone (m) 300 300 Maximum Number of Sounders per Zone 16 16 Sound Output End of Line Diode 1N4007 1N4007 Max. Sound Supply Current in ire () 1/24V 1/24V ire, ault Relay contacts Load () 2/24V 2/24V Panel Weight [Without Battery] (kg) 520g 500g Panel Dimensions (mm) 108 x 143 x40 108 x 143 x40

INSTRUCTION MNUL 15 Terminal Wiring Diagram 16 IRE LRM PNEL Sense Zone Wiring Diagrams Sounders Diode 1N4007 5K6 Zone Detectors 5K6 ind the detector bases you will be using and check to see which end of line device is required - either a 5k6 resistor or an active end of line unit. The 5k6 resistor should be used if a zone is comprised entirely of call points. Polarised Sounder uxiliary Signalling Relays IRE2 IRE1 ULT S S S S RS485 Communicaiton DC24 V POWER INPUT Sense zone with a 5k6 end of line resistor. Zone+ +in +out +in +out -in -out -in -out Zone- 5k6 EOL SOUND + IRE2 C NO IRE1 C NO ULT ZONE2 ZONE1 RS485 24VDC NO C + + B + The color bars on a 5k6 resistor are red blue green gold The panel is supplied with 5k6 end of line resistors as standard. Manual call point can be connected into Zone wiring, when the manual call pint switch closed, the sense zone wire would be short, the panel would alarm when the sense zone circuit is short.

INSTRUCTION MNUL 17 Sound Ouptut Wiring Diagram The sound output are wired as in the diagram below. end of line diode must be fitted at the end of the circuit. Motorised fire bells may be used, but solenoid bells MUST NOT be connected to the panel. Sound+ Sound- +in/out -in/out +in/out -in/out Diode 1N4007 18 IRE LRM PNEL uxiliary Signaling Relays and Sound Outputs There are three auxiliary signal relay output and two sound output inside the panel. ire1 Relay Output If any zones fire alarms, the ire1 relay would be activated and output relay contacts(c, NO). Meanwhile, the Sound output would be activated. ire2 Relay Output If zone 1 and zone 2 fire alarms together, the Evacuate LED flash, after 30 seconds delay, the LED would light continuously, Meanwhile the ire2 relay would be activated and output relay contacts(c, NO). ault Relay Output If any fault occurs in the panel, the ault Relay would be activated and output relay signal outputs(c, NO).

INSTRUCTION MNUL 19 ire larm Network One Master Panel could connect 1 to 31 slave panels. When the slave panel has alarm or fault event, the slave panel would send even to master panel, and then master would show the event of slaves one by one. RS 485 Communication terminal wiring Mater panel connect all the slave panel with RS485 communication port, Each panel RS485 port have two terminals and B, all the terminal should be connected in one wire, and also terminal B should be connected in another wire. lso the DC24V power of panels should be connected together. 20 IRE LRM PNEL Panel address setting Slave panel address must be from 1 to 31 continuously. nd master address should be set as the total number of slave panels. or example, if you connect 18 slaves to the master panel, the master panel address should be set to 18. nd the slave panel address should be set from one to 18. The address setting dip switch SW1 is on the PCB board. There are 5 small dip switch on the SW1 switch, from right to left each dip switch correspond to binary number of panel address. DC24+ DC24- RS485- RS485-B DC24+ DC24- RS485- RS485-B DC24+ DC24- RS485- RS485-B Master Panel No.1 Slave Panel No.2 Slave Panel No.31 Slave Panel SW1 SW1 SW1 SW1 ON is 1 and O is 0 for each bit.

INSTRUCTION MNUL 21 The following table would show all address status from 1 to 31. 1 2 3 4 22 IRE LRM PNEL RS485 EOL resistor setting or the RS485 communication network, two End of Line (EOL) resistors should be used at both end of RS485 wires. The resistor is on the PCB board already, you just use jump J1 to select. 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 0 or the master panel and the last one panel, the jump J1 should be set as below: or the other slave panel, the jump J1 should be set as below:

INSTRUCTION MNUL 23 How Master Panel show the Event of Slave Panel When then fire alarm system working, all the fire or fault event of slave panel would send to master panel. The Master panel would show fire and fault event one bye one. When there are no fire alarm events, the master would show the fault event. If there are fire event, the master would not show the fault event. Communication ault Event In the normal condition, the Master would communicate with Slave panels one by one, if one of slave panel is not respond the master panel commands. The master would show C.XX, XX is the number of slave panel, for example, if No.7 slave panel has some communication problem, the Master panel would show C.07 as below. C is short abbreviation for Communication ault. 24 IRE LRM PNEL ire alarm Event When master or slave panel alarm, the master panel would show all fire alarm events one by one. The master panel would show P.XX, XX is the address of panel, address 00 is for master panel, address 01 to 31 is for slave panel. When the digital LED show the P.XX, the corresponding zone1 or zone2 fire alarm LED would light. or example, if zone2 of slave panel 16 alarms, zone 1 of slave panel 28 alarms, the master would show information as below in cycle: ny slave panel s alarm event would active the master panel s sound output ZONE1 ZONE2 SOUND ZONE1 ZONE2 SOUND EVCUTE SILENCE TEST/RESET EVCUTE SILENCE TEST/RESET Zone2 of No.16 slave Zone1 of No.28 slave

INSTRUCTION MNUL 25 ault Event When master or slave panel has fault, the master panel would show all fault events one by one. The master panel would show P.XX, XX is the address of panel, address 00 is for master panel, address 01 to 31 is for slave panel. When the digital LED show the PXX, the corresponding zone1 or zone2 fault LED would light. or example, if zone1 of slave panel 5 has fault, zone 2 of master has fault, the master would show information as below in cycle: 26 IRE LRM PNEL Panel System Log ll events should be properly recorded in this log book. n event should include fire alarms (whether real or false), faults, tests, temporary disconnections and the dates of installing or servicing engineer s visits with a brief note of work carried out and outstanding. Name and address... of installation...... ZONE1 ZONE2 SOUND ZONE1 ZONE2 SOUND Person responsible... Date... for log book... Date...... Date...... Date... System installed by... and is maintained under contract by... Tel... EVCUTE SILENCE TEST/RESET EVCUTE SILENCE TEST/RESET. Zone1 of No. 5 slave Zone2 of Master

INSTRUCTION MNUL 27 Notes: