KAP Series -Air Purification Unit

Similar documents
BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

Cooktop Low-Profile Ventilation Hoods

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services

ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL

Spray Booth Guideline

The Basics of Commercial Kitchen Exhaust Cleaning

Acumen Enterprises, Inc.

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

DRYER VENTING SPECIFICATIONS DRYER SAFETY

Ceiling Mount Air Handler Manual

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

Evaluate, Clean, and Tune Guidance

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13

Element D Services Heating, Ventilating, and Air Conditioning

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:

DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL

Trouble Shooting. Pump

ATS Overhead Table Shelf System INSTRUCTION MANUAL

Digi-Motor Installation Guide

SECTION MORTUARY REFRIGERATORS

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

SINGLE PHASE MOTORS. INSTALLATION AND MAINTENANCE MANUAL March 21, 2006

SECTION A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer.

CE6500 Energy Recovery Ventilator

D Youville College July 31, 2008 New Academic Building Cannon Design Project No

Commercial Kitchen Fire Safety

DBF 4XL Dryer Booster Fans

city of edmonds development information

SECTION GENERAL PROVISIONS FOR HVAC WORK

Installation Instructions

ELECTRIC DUCT HEATERS

INSTALLATION and OPERATION RANGE BALL CONVEYOR MODEL NO: BC-001AN

Why is my air conditioner dripping on my customers?

PDmB, Inc. Definitions

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

, User s Manual

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

HVAC Design Requirements

Commercial Gas Furnace Upflow

Office of the State Fire Marshal. Fire Rated Doors

2010 Residential Water Heater Replacement Check List

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

READ AND SAVE THESE INSTRUCTIONS

OHIO MEDICAL CORPORATION. Medical Gas Panel. Installation and Maintenance Manual

Name Of Occupancy Date. Yes No Describe

TWIN EAGLES ALL WEATHER ELECTRIC RADIANT HEATER

WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin / March 2013

PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual

CARING FOR YOUR WATER HEATER

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler

Oil and Coolant Circulating Heating System. Model - OCSM

KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT CHEVROLET/GMC VANS FOR

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Installation and maintenance instructions. Danfoss Vent

KITCHEN HOODS GUIDELINES

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales

Owner s Manual Phoenix 1200 Desiccant Dehumidifier

HV AC CODE CHECKLISTS

3 IN 1 BATHROOM HEATER

COMPREHENSIVE PROPERTY INSPECTIONS

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW

Chapter 7 Hydraulic System Troubleshooting

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

Ceiling Fan Installation Instructions

CEILING CASSETTE FAN COIL UNIT

User s Guide. Oreck Air Purifier with HEPA Filtration. Important! Read this manual carefully, and keep for future reference.

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

First irst Co. Products

Installation, operation and maintenance manual TX 35A

Geismar Site Reviewed: 07/05/16 Effective: 07/05/16 Supersedes: 08/04/14 Preparer: Owner: Approver: S/IH Team Leader S/IH Team Leader Manager LA Hub

ASX7-4-IOM-7 J

PRODUCT: WASHER / WASHER-DRYER COMBO MODEL: AW 120 / AW 122 / AW 125 AWD 120 / AWD 121 / AWD 129

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)

SL280UHV SERIES GAS FURNACE WARNING

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation

E-PDD Duct Smoke Detector Installation Sheet

How To Install A Perfect 16 Id Series Filter System

Air Boss ATS Series Electrostatic Precipitators Commercial & Industrial Applications READ AND SAVE THESE INSTRUCTIONS

Cooling Capacity CFM in. w.c. (125 Pa)

MODEL INSTALLATION INSTRUCTIONS

Winnipeg Fire Department Fire Prevention Branch

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

RPV - RP - RA air handling units

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Johnson Air-Rotation Systems

Mechanical Installation

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER

Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.

Transcription:

KAP Series -Air Purification Unit Installation, Operation and Maintenance Manual

CONTENTS DESCRIPTION... 3 Common Installation Formats... 4 INSTALLATION... 4 Preparation... 4 Duct Work & Minimum Sizes... 5 Grease/Water Drains... 6 Roof Installation / Floor Installation... 6 Ceiling Mount Installation... 7 Air Pressure Switch... 8 Fire System... 9 OPERATION...10 Tools Required...10 Start-Up Check List...10 Start-Up Procedure...10 Troubleshooting...11 General Maintenance...12 Filter Chart...13 Gasket Chart...13 Maintenance Intervals...14 DOCUMENTATION... 15 Job & Site Information...15 Name Plate/APU Information...15 Maintenance Record... 16 Listings...17 Warranty...17 HD Service Dept...17

DESCRIPTION The listed air purification unit is suitable for the removal of smoke, grease laden vapors and odors in commercial cooking installations. Hood Depot KAP purification units are specified in CFM ratings from 5,000 to 40,000 CFM to handle all size kitchens with any cooking equipment configuration. Grease ducts must still conform to NFPA 96 and your local mechanical codes applicable to gauges, sizing and cleanout requirements. If a grease fire has occurred, the system should be dismantled and inspected by a professional engineer. Hood Depot International cannot be held responsible for grease duct systems that are not properly maintained or have been subjected to a grease fire. COMMON INSTALLATION FORMATS Interior Split Fan & Filter Interior Horizontal Suspension KAP KAP Exterior Roof Mounted Interior Floor Mounted Pg. 3

INSTALLATION Installation must be done in strict accordance with the designed airflow, exhaust fan placement, filters and construction details required by this manual. Lifting the unit in place must be accomplished by using an equipment lift (rated above the unit weight) or by hoisting using the proper hoisting straps (see below). PREPARATION 1. Installation site should be clear to safely lift unit into proper position. Be sure hoisting equipment and/or lifts are adequate to the weight load of the unit according to manufacturer s estimated weight. 2. Position unit to allow at least 34 of clearance on the access side of unit to open door, replace filters and perform maintenance. 3. Unit should be located as close to the space it serves as practical to avoid lengthy and complex duct runs. This will reduce total fire hazard exposure and amount of duct to be cleaned. 4. When the unit is ground or floor mounted, make sure it sits at least 6 (minimum) off the ground for interior location and 18 (minimum) above ground for exterior locations including roof mounted. 5. The exhaust fan must be located between the air purification unit and the discharge duct. DO NOT locate the fan between the hood and the air purification unit as this would cause the KAP to be under positive pressure. 6. It is recommended that the unit s grease drains are connected to the building grease interceptor or an approved building drain system. Pg. 4

(INSTALLATION Cont d.) DUCTWORK Performance of the air purification unit is highly affected by ductwork configuration, proper alignment and seals. The following airflow factors must be accounted for: 1. Any change in duct direction must be at least five duct diameters away from the unit inlet. The maximum velocity at the inlet of the unit must be less than 1,000 feet per minute. 2. The air purification unit requires commercial (NFPA 96) or Listed grease ductwork. Clearance ratings of any ductwork connected to the unit apply to the unit as well and must be installed in accordance with IMC, NFPA 96 and state and local codes. 3. All grease ducts before or after the KAP must be designed and installed as per NFPA 96, local mechanical/building codes, SMACNA and any/all state and local codes. GREASE/WATER DRAINS Each section of the unit contains a drain that should be connected to an approved grease interceptor or to an approved drainage point to allow water to drain away from the unit. If installed outdoors, the drains must be piped in such a way to avoid water build-up in pipes that could burst in freezing conditions. It is recommended that units located where freezing may occur have electric heat tape. Drain line must be pitched for proper drainage Pg. 5

(INSTALLATION Cont d.) ROOF INSTALLATION When roof mounting, the KAP unit should be mounted on a roof-curb or rail at least 18 above the roof surface. Secure the unit on a support frame with at least eight (8) #14 anchor bolts, welding 1 long every 12 or AHJ approved fasteners. Roof curb rail to be mounted according to federal, state and local codes. Drain lines and roof curb rails that penetrate the roof need to be properly flashed to avoid roof leaks. Be sure to allow proper clearances for service access doors (see page 4). INDOOR/FLOOR MOUNTED INSTALLATIONS When mounting the KAP unit on a floor, make sure it is mounted on support rails with a minimum of 8 from the bottom of unit to the floor. Verify with your plumber that this is sufficient clearance for the drains. Secure the unit through the unit support frame to the rail with at least eight (8) #14 sheet metal screws, anchor bolts or AHJ approved fasteners. Secure support rails to the floor in accordance with federal, state and local codes. Make sure the unit has proper clearance for the service access doors (see page 4). Make sure the bottom of the unit (not including support frame) has at least 18 clearance from combustibles as per NFPA 96 and federal, state and local codes. Pg. 6

INSTALLATION (Cont d.) INDOOR/CEILING MOUNTED INSTALLATIONS When hanging the KAP from the ceiling/roof structure above, make sure it is mounted with structural steel or uni-strut supports from underneath the unit. Verify the size and number of supports required as well as ceiling integrity with your building s structural engineer. Make sure that the supports do not interfere with the service access doors or with filter removal by providing proper clearance (see page 4). Make sure the unit has 18 clearance from combustibles as per NFPA 96 and federal, state and local codes. Pg. 7

(INSTALLATION Cont d.) AIR PRESSURE SWITCH Air pressure switch is factory preset to.15 w.c. above the internal static pressure of the unit (with clean filters). The pressure switch is located in downstream filter module. Route wiring from hood control panel to the unit using 1/2 conduit through quick-seal (lower right of filter module). Use existing conduit in the module to route wires from module exterior to pressure switch (see wiring label above switch). Tighten all conduit fittings. When filters become clogged, the switch will close kitchen illumination lighting to signal the cleaning or replacement of filters. Air Pressure Switch (Within downstream air flow) Air Line Routing Air Pressure Switch Location Pg. 8

(INSTALLATION Cont d.) FIRE SYSTEM Air Purification Units require a fire suppression system to be installed with the unit. The HD KAP Series unit can be factory fitted with Kidde, Ansul or Buckeye fire equipment products. The system uses fusible links to activate the fire system. The KAP fire system must be interlocked with a hood fire suppression system so that it may be activated by the hood system even in the absence of fire in the KAP and is activated by the KAP even in the absence of fire in the hood. If the fire suppression system is accidently activated, the disposable filters and prefilter must be replaced. Immediately discard all filters and wash (with soap and water) any part of the unit that was in contact with the fire suppressant. If a fire occurs in the ductwork leading to the APU, the following maintenance must be done: 1. The unit must be cleaned of all suppression agent and grease. 2. All filters must be replaced including the pre-filter. 3. Replace any damaged gasketing. 4. Fire-damaged components of the KAP, if any, must be replaced by by factory service personnel. Installation, repair or refitting of the fire system must be done ONLY by a licensed fire system installer according to exact manufacturer guidelines. FIRE SYSTEM UTILITY CABINET A utility cabinet is recommended for indoor or outdoor installations to house the fire system. An optional heated temperature controller is available upon request. Pg. 9

Air Purification Unit with fire system utility cabinet installed OPERATION Before starting up the KAP, check all fasteners for tightness and be sure to check the module connection seal and door seals. With power to the fan shut off, check the airflow direction of the filters to match the label on the filters. START-UP TOOLS REQUIRED: 1. Standard Hand Tools 2. Static Pressure Meter START-UP PROCEDURE: 1. Check duct connections to inlet and outlet of unit for proper welds. 2. Check that entire duct system is intact and that all clean-out doors are properly installed. 3. Install all filters in correct direction 4. Start fan and check for rotation, voltage and proper operation. 5. Inspect entering & exiting ductwork connections and grease duct for leaks or pinholes (grease rated duct must be continuously welded to the transition, if factory provided). 6. Inspect all fire suppression piping and components. Pg. 10

(OPERATION Continued) TROUBLE SHOOTING SYMPTOM POSSIBLE CAUSE REMEDY Not enough airflow Excessive airflow Excess vibration / noise Fan rotating in wrong direction Restricted outlet condition Static pressure in duct too high Blower speed too low Dirty filters Belt slipping Missing filters Fan speed too high Motor incorrectly wired Overload in starter set too low Duct static pressure too low Damaged / unbalanced wheel Misaligned pulleys Fan operating outside of stable fan curve Bearing lubrication needed Fan speed too high Worn or greased belts Correct according to rotation label Provide straight clear duct at outlet Repair or reconfigure ductwork to reduce losses Increase fan RPM (do not overload) Clean / replace Adjust belt tension Install all filters & doors Reduce fan RPM Conform to motor wiring diagram on fan motor Set overload to FLA. value Reduce fan RPM Replace wheel Align pulleys Adjust to performance curve Lubricate or replace bearings Reduce fan speed RPM Inspect and replace as needed Check KAP filter light on (if installed with this option) Check KAP light will not turn on (if installed with this option) Dirty / clogged filters Incorrect switch setting Internal static pressure higher than estimated Light is burned out Switch is set incorrectly Internal static pressure is lower than estimated Clean / replace filters Set to.15 w.c. above internal pressure Increase switch setting by.1 w.c. Check light and related wiring with jumper wire / circuit tester; repair as needed Set switch to.15 w.c. above internal pressure (with clean unit) Decrease switch setting by.1 w.c. Smoke or odor from KAP Exhaust fan installed at wrong end of KAP unit Relocate fan to the discharge end of KAP unit Pg. 11

(OPERATION Continued) ABOUT MAINTENANCE Poor maintenance (failure to clean or replace filters) accounts for most KAP problems. To assure proper operation of the KAP, keep the system clean and follow the manufacturer guidelines below. Be sure to record any service on the unit in the documentation section of this manual. WARNING: Do not attempt service or maintenance on the KAP unless the electrical supply has been completely disconnected from the fan GENERAL MAINTENANCE 1. KAP doors and approaches to unit should be kept clean and obstruction free. 2. Filters must be installed according to airflow direction indicated by arrow labels. Pre-filters must be installed so that drains are at the bottom edge of filter. 3. All fasteners must be checked for tightness each time maintenance is performed. 4. Ductwork and KAP should be cleaned according to local code requirements. 5. Make sure KAP drains are clear and that they drain properly. PROPER FILTER POSITIONS FIRST STAGE FILTERS SECOND STAGE FILTERS Pg. 12

GASKETS One type of gaskets is used on the KAP Series Air Purification Unit: Orange gasket is used for exterior weather-proofing (rated at 450º F with PSA Backing) of the doors and any access panels. Gasket Application Size Temp. Rating Part Number Orange High Temp. Closed Cell On door seal 3/16 x1 450ºF #SNS-ROLL Pg. 13

MAINTENANCE INTERVALS Two weeks after start-up: 1. Inspect unit for grease or air leaks and repair if needed. 2. Check fasteners and hardware for tightness. 3. Monitor filter loading to determine replacement frequency. 4. Clean pre-filters and check remaining filters. 5. Adjust air pressure switch to assure proper of indicator light. Every Month: 1. Inspect unit for grease or air leaks and repair if needed. 2. Clean 1st stage steel pre-filters. 3. Clean or replace 2nd stage filters as necessary. 4. Monitor filter loading to determine replacement frequency. 5. Clean pre-filters and check remaining filters. 6. Adjust air pressure switch to assure proper of indicator light. Yearly: 1. Inspect all seals for wear and replace if needed. 2. Clean 1st stage steel pre-filters and replace if necessary 3. Replace all 2nd stage filters. 4. Inspect ductwork junction with unit and repair if necessary. NOTE on Duct Cleaning: 1. Place tarp / dropcloth under unit for over-spray during cleaning. 2. Place tarp over blower insulation and motor to prevent damage during cleanup. 3. Remove tarps from unit after cleaning. Pg. 14

DOCUMENTATION START-UP & MAINTENANCE DOCUMENTATION The following documentation is necessary to maintain warranty and inform service personnel for any future service call. Note: Start-up Measurements and documentation should be recorded only after system has been tested and air-balanced by factory rep Job Name Purchase Date Address City State Zip Phone Number Fax Number Contact Purchase Date Job & Site Information Service Company Address City State Zip Phone Number Contact Start-Up Date Air Purification Unit Information* Name Plate & Unit Information Model Number Serial Number Pressure Switch Set Point Estimated Unit Weight *Refer to start-up procedure in this manual to complete this section Pg. 15

(DOCUMENTATION Continued) MAINTENANCE RECORD The following documentation is necessary to maintain warranty and inform service personnel for any future service call. Note: Service by unauthorized personnel may void warranty Date Service Description Initials Pg. 16

(DOCUMENTATION Continued) LISTINGS The HD KAP Series Air Purifier Unit is certified by the following listing authorities: WARRANTY One Year Limited Warranty Hood Depot warrants this Kitchen Air Purifier against defects of material and workmanship for a period of one year from date of installation contingent upon proper maintenance as described in the KAP Series Air Purification Unit Installation, Operation and Maintenance Manual. Hood Depot will not be held responsible for... [More copy to come as per existing (?) warranty... etc. More copy to come as per existing (?) warranty... More copy to come as per existing (?) warranty] Issue Date: Expires: Authorized by: FACTORY SERVICE Hood Depot s highly qualified service department personnel are ready to answer any question and quickly resolve any problem with your KAP unit. Call 24/7 at: 1-800 322-8730 Your One-Stop Source for Kitchen Ventilation Pg. 17