Direct Mounting Allows Differential Pressure (DP) Based Flow Measurement Optimization

Similar documents
Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

SELECTING PRESSURE TRANSMITTERS TO IMPROVE CENTRIFUGAL COMPRESSOR SAFETY & EFFICIENCY

The Unique Accelabar Flow Meter

Thermal Dispersion Mass Flow

Custody Transfer Measurement. with the V-Cone Flowmeter

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems

Grant Agreement No SFERA. Solar Facilities for the European Research Area SEVENTH FRAMEWORK PROGRAMME. Capacities Specific Programme

Application of the Orifice Meter for Accurate Gas Flow Measurement page 1. Application of the Orifice Meter for Accurate Gas Flow Measurement.

Gas Custody Transfer Calibration

The Versatile Differential Pressure Transmitter. By David Gunn Honeywell Process Solutions

Theory overview of flow measurement using differential pressure devices based on ISO-5167 standard.

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

Advanced Differential Pressure Flowmeter Technology V-CONE FLOW METER TECHNICAL BRIEF

THEORETICAL UNCERTAINTY OF ORIFICE FLOW MEASUREMENT page 1 THEORETICAL UNCERTAINTY OF ORIFICE FLOW MEASUREMENT INTRODUCTION COEFFICIENT OF DISCHARGE

Chapter 10. Flow Rate. Flow Rate. Flow Measurements. The velocity of the flow is described at any

Experiment # 3: Pipe Flow

Advances in Thermal Dispersion Mass Flow Meter Accuracy

Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids

OIL & GAS PRODUCTION AUDITING

Testing Protocol for Differential Pressure Measurement Devices API MPMS Chapter 22.2

Energy and Flow Measurement for Hydronic Systems

Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson

Certified according to DIN EN ISO 9001 Technical Datasheet KVO Series Vortex Flow Meter

FLOW MEASUREMENT 2001 INTERNATIONAL CONFERENCE DERIVATION OF AN EXPANSIBILITY FACTOR FOR THE V-CONE METER

Flow System Calibration in Medical and Bio-medical Production Processes.

AN INSTRUMENT FOR GRAVIMETRIC CALIBRATION OF FLOW DEVICES WITH CORROSIVE GASES. J. O. Hylton C. J. Remenyik Oak Ridge National Laboratory *

For Multi-Parameter Meters see mvx

Accurate Air Flow Measurement in Electronics Cooling

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

APPENDIX A CONTROL VALVE TESTING PROCEDURES AND EQUATIONS FOR LIQUID FLOWS

Rosemount Orifice Plate in Wet Gas

PULSATION REDUCTION BY ACOUSTIC FILTERS FOR METERING APPLICATIONS. Robert J. McKee Ray G. Durke

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE

APPLICATION OF DENSITOMETERS TO LIQUID MEASUREMENT Class # 2010

A LAMINAR FLOW ELEMENT WITH A LINEAR PRESSURE DROP VERSUS VOLUMETRIC FLOW ASME Fluids Engineering Division Summer Meeting

HEAVY OIL FLOW MEASUREMENT CHALLENGES

Laminar and Turbulent flow. Flow Sensors. Reynolds Number. Thermal flow Sensor. Flow and Flow rate. R = Mass Flow controllers

O C M III. Open Channel Flow Monitor

Entrained Gas Diagnostic with Intelligent Differential Pressure Transmitter

Dynamic Process Modeling. Process Dynamics and Control

Submersion/Insertion Toroidal Sensor

Sanitary and CIP Toroidal Sensor

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

Flow Measurement. Reference - Flow Measurement FUNDAMENTALS. ρ = fluid density (lb/ft3 or kg/m3)

Sanitary Type Electronic Flow Switches

Energy Efficiency in Steam Systems

Oil and Gas Custody Transfer

Flow Measurement Options for Pipeline and Open Channel Flow

Reliable Pressure Measurement with Remote Diaphragm Seals in Cold Weather Applications

Fundamentals of Mass Flow Control

COUNTERBALANCE VALVES

Density Measurement. Technology: Pressure. Technical Data Sheet INTRODUCTION. S min =1.0 S max =1.2 CONSTANT LEVEL APPLICATIONS

FLUID FLOW Introduction General Description

INDIAN STANDARDS FOR NATURAL GAS PIPELINE SYSTEM

THE THERMAL FLOW METER, A GAS METER FOR ENERGY MEASUREMENT

Using meters to measure steam flow

Toroidal Conductivity Sensor

Valve Sizing. Te chnic al Bulletin. Flow Calculation Principles. Scope. Sizing Valves. Safe Product Selection.

COMBIMASS. Technical Data COMBIMASS eco-bio +

A Practical Overview of Level Measurement Technologies

User s Manual Laminar Flow Elements

Measurement & Analytics. VIS Multiphase Flow Meter High gas content applications solved with no radioactive source - Measurement made easy

Variable V Area Flowmeter Rotameter The Original

Chemical Measurement Solutions

Why and How we Use Capacity Control

Chokes. Types Reasons Basics of Operations Application

In-Line Electronic Flow Switches

Electronic Flow Switches

Smart Electromagnetic Flowmeter Open channel Flowmeter Detector

Turbine Flowmeters for Gas Applications

Fluid Flow Instrumentation

What is a successful Steam Trap Management Program?

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing

Fiscal Measurement Natural Gas

Experiment 3 Pipe Friction

Sentinel LCT. Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement. GE Measurement & Control Solutions. Benefits.

ABB Flowmeters Review of industrial processing flowmeters

BASIC UNDERSTANDING OF FLOW CALCULATIONS AND ESTIMATES MAKES SIZING VALVES SIMPLER

Select the Right Relief Valve - Part 1 Saeid Rahimi

Liquid level measurement using hydrostatic pressure and buoyancy

LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS

Typical Aluminum GFM Mass Flow Meter

TERMINOLOGY USED IN INSTRUMENT ACCURACY Rick Williams Rawson & Co., Inc.

Fault codes DM1. Industrial engines DC09, DC13, DC16. Marine engines DI09, DI13, DI16 INSTALLATION MANUAL. 03:10 Issue 5.0 en-gb 1

Optimize Pipeline Hydraulics with Multiphase Flow Modeling

ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation

Chapter 10. Control Design: Intuition or Analysis?

SUMMARY of PRODUCTS. HVAC Systems Control Airflow, Space, & Building Pressurization. Accurate airflow measurement for demanding applications

The Use of Control Valve Sizing Equations with Simulation Based Process Data

Integrated Custom Systems

SMV 3000 Smart Multivariable Flow Transmitter

C. starting positive displacement pumps with the discharge valve closed.

Averaging Pitot Tubes; Fact and Fiction

FAQ s on Siemens Magmeters

191: Calibration and Standards in Flow Measurement. Richard Paton National Engineering Laboratory, Scotland, UK 1 GENERAL PRINCIPLES

TECHNIQUES FOR NATURAL GAS SAMPLING A DISCUSSION OF FIELD METHODS FOR OBTAINING SPOT SAMPLES. Randall Messman SW Regional Sales Manager

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

ngenieros Ingenieros Asociados De Control S.L.

PORTER MASS FLOW MEASUREMENT AND CONTROL SYSTEMS

Transcription:

Direct Mounting Allows Differential Pressure (DP) Based Flow Measurement Optimization Gregory Robert Strom, Marketing Product Manager Gregory Livelli, Manager of Worldwide Pressure Marketing Rosemount, Inc. 5601 N 71 st Street Boulder, CO 80301 Keywords Direct Mounting, Multivariable Compensation, Installed Accuracy ABSTRACT The accuracy of a differential pressure (DP) flow measurement point can be optimized by eliminating impulse lines, compensating for changing flow equation coefficients, and utilizing the most accurate DP measurement instrumentation available. Plugging, leak points, and head uncertainty are direct consequences of complex impulse tubing arrangements used in traditional DP flow measurement installations. Cost and accuracy issues associated with installation at grade were once considered a necessity due to the reliability of traditional DP measurement devices. A new generation of DP measurement instrumentation has robust characteristics that allow for direct mounting to the primary element and elimination of traditional limitations. Multivariable transmitters can be programmed to alleviate introduction of bias errors attributed to flow equation coefficient non-linearity. Accuracy dividends will be particularly noticeable at low flow rates, which correspond to lower Reynolds numbers. The major contributor to inaccuracy in a DP flow measurement is the uncertainty of the DP measurement. The square root relationship between the flow rate and the DP induced across a primary element results in the inaccuracy at lower flow rates. Careful selection of instrumentation focusing on of the characteristics that most effect flow measurement can enhance system accuracy. Direct mount DP flowmeter technology offers a greater degree of process control, provides competitive advantages, and generates economic benefits.

INTRODUCTION The fundamental principles that form the basis of all DP flow measurement are outlined in Bernoulli s streamline energy equation. This equation defines the relationship between kinetic and potential energy in a flow stream. It allows the inference of volumetric flow rate based on the measurement of DP across a restriction. DP based measurement has a history that reaches back to ancient times and has the largest installed base of any process flow technology. DP flow measurement continues to be the most often specified flow technology, not because of its tradition in flow measurement, but because of the value it offers. While new flow measurement technologies have emerged, which have strength in certain applications, the DP flowmeter remains a favorite for process flow applications for reasons such as: application flexibility excellent repeatability proven reliability direct process mounting easy to calibrate and troubleshoot worldwide industry standardization low installation costs meter interchangeability Recent developments in DP flow measurement bring the primary element together with the secondary element. The combination of software, electronics and primary element allows the end-user to save on installation costs and improve reliability. Enhanced differential pressure flowmeters herald the beginning of a new era in DP based measurement.

IMPULSE TUBE ELIMINATION The reliability of a flow measurement point can be directly correlated to the length of impulse tubing used. The differential pressure generated by a primary element must be effectively communicated to the sensing apparatus of a secondary element to allow accurate measurement. Following direct mounting practices can minimize errors due to plugging, process leaks, and inequalities in the hydrostatic head of impulse tubes while lowering the total installed cost of the measurement point. Plugging Plugging often occurs in steam application impulse tubing as a result of flashing. Flashing is the phenomena in which a fluid quickly changes from a liquid to a gaseous state. Precipitate, composed of suspended solids found in steam, can be deposited on the walls of an enclosure when flashing occurs. Consistent flashing can cause enough precipitate accumulation to plug the impulse tubing. A plugged impulse tube can not communicate the differential pressure generated by a primary element and will result in inaccurate measurement. The potential for flashing in a given application is influenced by the manner in which the primary element is connected to the secondary element. Flashing is common in remote mount applications with long impulse tubes. Temperature oscillations along the length of the impulse tubes cause the fluid to change state continuously; forming layers of precipitate that ultimately result in plugged tubing. Direct mounting results in a fixed transition from the gaseous state to the liquid state. This eliminates the opportunity for flashing and the plugging commonly associated with it. The geometric and thermal transfer characteristics of direct mount assemblies result in the fixed transition. Precipitate accumulation is another common cause of impulse tube blockage. Solids in a flow stream will have a tendency to accumulate at the lowest point in an impulse tube arrangement. Impulse tubing is often plumbed around and over obstacles resulting in many areas of low potential energy where solids can collect. Direct mounting eliminates elbows and traps where solids could potentially accumulate, effectively eliminating the potential for precipitate blockage. Leakage Process leaks in impulse tubing result in erroneous DP readings and can have a significant effect on flow measurement accuracy. The potential for a leak in a DP flow measurement system is directly proportional to the number of connections in the system. The integration of the electronics and differential producer through direct mounting eliminates fittings, tubing, valves, manifolds, and adapters resulting in a significant reduction in potential leak points.

Hydrostatic Head Uncertainty Variation in the hydrostatic head in impulse tubes can mask the DP generated by a primary element. These variations in hydrostatic head are the result of temperature variation and geometric inconsistencies in the impulse tubing. Impulse tubes must be installed carefully and properly insulated from the environment to prevent serious accuracy issues. These issues become acute at flow rates that generate low differential pressure signals. Direct mounting ensures consistent impulse tube geometry and reduces the potential for temperature variation due to the close proximity of high and low side impulse tubes. Lowered Total Installed Cost Integrated flowmeters offer significant savings compared to traditional installation techniques. These innovative products consist of a primary element, a secondary element, and connection accessories. They are specified with a single model code. Typically, these products are pre-assembled, pre-calibrated, and leak tested by the supplier. Cost savings from fully integrated solutions are realized in a number of areas including specification, procurement, material, and installation. Engineering time spent selecting, specifying, sizing, and creating drawings for flow instrumentation can be significantly reduced through the use of integrated solutions. Traditional measurement requires the separate specification of differential, gage, and temperature transmitters, as well as a primary element, impulse lines, mounting hardware, RTD, thermowell, electrical wiring and conduit, and a flow computer. When using integrated meters, a single model code completely defines the primary element, secondary element, and connection accessories. The procurement of measurement instruments is a significant cost that is commonly overlooked. Savings are realized during request for quote (RFQ) and purchase order (PO) generation due to the single model code. Receiving costs are also reduced due to the reduction in paperwork and model codes to check against product received. Using integrated solutions can also reduce material costs. Suppliers will typically offer a price break on the discrete components of the system to ensure single source ordering. The cost of the transmitter and primary element often accounts for only a fraction of the total cost of the flow measurement system. Depending on the primary element selected, additional cost for flanges, mounting hardware, isolation valves, and plumbing are needed to complete the system.

The labor cost associated with the installation of an integrated meter can be significantly lower than that of a traditional installation. The transmitter, manifold, and primary element are received as and assembly. Impulse tubing, root valves, mounting brackets, and interconnections are all eliminated. Units are preconfigured for the application, an especially important fact in light of emerging multivariable technologies. Figure 1 summarizes anticipated total installed cost savings. The integrated orifice assembly consists of a single model code that defines the pressure transmitter, isolation manifold, and primary element. The traditional orifice assembly meter consists of a pressure transmitter, orifice plate, flange union, three-valve manifold, mounting bracket, and impulse tubing. Procurement and engineering costs are based on discussions with engineering contractors. Materials and labor costs are based on Richardson s Process Plant Construction Estimating Standards, 1997 and Rosemount Inc. Price Lists. Figure 1-1 1/2" Total Installed Cost Comparison 5000 Dollars 4000 3000 2000 1000 Labor Materials Procurement Engineering 0 Integrated Orifice Assembly Meter Traditional Orifice Assembly Meter

MULTIVARIABLE COMPENSATION A new generation of multivariable flow transmitters allows simultaneous measurement of differential pressure, static pressure, and temperature. Traditionally, DP flow has been calculated in a flow computer or DCS using a simplified mass flow equation. This practice does not produce the most accurate flow measurement possible due to the fact that it compensates for changes in fluid density only. State of the art examples of the new multivariable transmitters perform complex real time calculations to compensate for coefficient variation in the flow equation. The following flow equation is commonly used to perform fully compensated mass flow calculations: Q mass = NC d 2 EY1d DP( ρ) Where: N = units conversion factor, C d = discharge coefficient, E = velocity of approach factor, Y 1 = gas expansion factor, d 2 = bore of differential producer, DP = differential pressure, ρ = density The only constant value in this equation is the units conversion factor. The other terms are functions of the process variables. A simplified flow equation cannot compensate for changes in these terms, resulting in unrecorded errors in the calculated flow rate. Compensating for changes in discharge coefficient, velocity of approach factor, gas expansion factor, differential producer bore, and density can minimize flow measurement uncertainty. The discharge coefficient is the ratio of theoretical flow rate to actual flow rate. Many primary elements have discharge coefficients that vary depending on the velocity profile of the flow stream. The velocity profile of a flow stream is related to a unitless value called a Reynolds number. The Reynolds number can be calculated real time with a multivariable transmitter allowing dynamic discharge coefficient compensation. Discharge coefficients tend to change most dramatically at the low Reynolds numbers most often found in liquid applications. As a result, despite the incompressible nature of liquids, multivariable technology allows significant accuracy improvement over traditional methods. As the area available to a fluid travelling through a pipe changes the velocity of the fluid must change. A primary element is essentially a tightly toleranced restriction associated with a large collection of empirical data that relates the differential pressure generated across it to fluid velocity. Process temperature can effect the restriction presented to the flow stream by the primary element. The velocity of approach factor compensates for geometric variation due to temperature effects.

When a compressible fluid flows past a primary element the velocity change is accompanied by a change in density. The gas expansion factor is applied to compensate for this change. The expansion factor also compensates for small changes in the internal energy of the fluid due to the temperature difference between the upstream and downstream ports of a primary element. Process temperature variation causes thermal expansion and contraction in both the pipe and primary element. The change in geometry of the system has an impact on the blockage the primary element presents to the flow stream. Dynamic calculation of blockage eliminates any error that could be introduced by the changing geometry. The main source of flow error in most gas or steam application is error due to changes in fluid density, caused by fluid pressure and/or temperature variation. This assumes, of course, that the application requires mass flow. The need for mass rather than volumetric - flow can be inferred when a flowrate is expressed in mass (lb/hr) or standard volumetric units, such as standard cubic feet per minute (scfm). In very rare cases, the user is actually concerned with volumetric flowrate, represented in volumetric units such as actual cubic feet per minute (acfm). Multivariable technology improves measurement accuracy in liquids and gases by dynamically compensating for changes in flow equation coefficients. Performing compensation in the transmitter instead of the DCS saves valuable system resources and reduces the programming expertise required to configure a flow measurement point. IMPORTANCE OF QUALITY INSTRUMENTATION Accurate DP measurement is a prerequisite to accurate flow measurement. Many factors have an adverse impact on the installed accuracy of a measurement point including ambient temperature variation, high static pressures, and the frequency of calibration. All transmitters are not created equally in their resistance to error introduction from these factors. Reference accuracy, though important, is not the absolute measure of an instrument s ability to make a measurement. Even with a well-installed and well-maintained transmitter, real-world accuracy can be significantly worse than laboratory accuracy. The reason for this is that real-world transmitters are not installed and operated under laboratory conditions. Real-world effects may include: Ambient Temperature Variation In the vast majority of flow measurements, the transmitter can operate at a different ambient temperature than the temperature at which it was calibrated. In

some outdoor applications, ambient temperatures can vary more than 50 F from calibration temperature. These variations can have a significant effect on the accuracy of a measurement. This phenomenon is easily simulated on the bench. Simply blow warm air over a transmitter, and watch the change in output. High Static Line Pressures High static line pressure can significantly affect a differential pressure transmitter used to infer a flowrate. This can also be simulated on the bench. Apply a small differential pressure across a transmitter. When several hundred pounds of additional static pressure are added to both sides of the transmitter simulating operating conditions the output will shift. Drift/Stability The output of any analog component will vary over time. Smart transmitters are more stable than older, analog transmitters or transducers. Within regulatory or contractual restrictions, a more stable transmitter will allow the user to obtain equivalent accuracy and repeatability when calibrated less frequently. An inferior device will need to be calibrated more frequently to maintain acceptable performance. Reputable suppliers publish specifications that allow users to calculate and predict the impact of real-world effects on installed flow accuracy and repeatability. The flow errors at 100% flow due to typical installed conditions are shown in Figure 2 for three different transmitters. Reference accuracy contributes a trivial component of total installed error. Two transmitters with identical reference accuracies can provide dramatically different installed performance. If a supplier does not publish specifications for real-world effects, this does not mean that their products are immune to these effects usually, the reverse is true. Figure 2 - Percent of Flow Error % Error 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 0.075% A 0.075% B 0.2% (Analog) Reference Accuracy Drift (12 months) Line Pressure (300 psig) Ambient Temp Effect (+/- 25 of) Reference Accuracy

Figures 3 & 4 show the impact of these errors at low flowrates. Note that these errors apply to accuracy and repeatability, and are usually fixed over the DP range. Also, DP α flow 2 since DP declines twice as fast as flow, small errors at 100% - and small differences in transmitter accuracy - are magnified at lower flowrates Figure 3 Flow Error from DP Transmitter Flowrate (scfm) DP 0.075% A 0.075% B 0.2% Analog 1000 100 0.09% 0.21% 0.65% 750 50 0.16% 0.38% 1.16% 500 25 0.37% 0.85% 2.60% 250 6.25 1.48% 3.40% 10.40% Seemingly trivial improvements in transmitter accuracy yield significantly better flow accuracy and repeatability at normal flows the effect can be dramatic at lower flows. 6% Figure 4 - Flow Error from DP Transmitter Flow Error (%) 4% 2% 0.075% B 0.2% Analog 0.075% A 0% 20% 40% 60% 80% 100% Flowrate (%) Summary Accurate flow measurements allow efficient process operation and are critical to the profitability of your business. Direct mounting practices, multivariable compensation, and quality instrumentation can all have a direct impact on your bottom line.

Bibliography Flow Measurement Engineering Handbook, R. W. Miller, 1989 Handbook of Instrumentation and Controls, Howard P. Kallen, 1961 Enhanced Integral Orifice Assemblies Provide High Accurate Small Line Measurement, Gregory Livelli, 2000 Improving Flow Measurement by Real-Time Flow Calculation in Transmitters Having Multiple Process Variables, David E. Wiklund and Loren M. Englestad, 1995 Measurement Best Practices for Better Powerplant Safety, Availability, and Efficiency, Mark Menezes, Tony Norris, and Scott Mawhinney, 2000 Integrated Flowmeters Have Revolutionized Differential Pressure Based Measurement, Gregory Livelli, 1999 Richardson s Process Plant Construction Estimating Standards, 1997