M 75 FACU FIRE ALARM SYSTEM NOTES ALL DEVICES WILL BE MOUNTED ON JUNCTION BOXES IAW THEIR DATA SHEETS, MANUFACTURERS' RECOMMENDATIONS AND STANDARD INDUSTRY RACTICES, EXCET WHERE NOTED ON THIS DRAWING ALL NOTIFICATION DEVICES SHALL BE FROM THE SAME MANUFACTURER FROM THEIR CURRENT MODEL LINE WIRING NOTES: ALL FIRE ALARM WIRING CAN BE INSTALLED IN CONDUIT IAW NFA70 ALL EXOSED CONDUIT WILL BE AINTED TO MATCH THE ADJACENT SURFACE AND WILL HAVE 1" WIDE RED BANDS AT 10' INTERVALS OR NO LESS THAN 2 IN THE LINE OF SIGHT. FLEX CONDUIT MAY NOT BE USED BELOW THE CEILINGS OR WHERE VISIBLE FROM THE FLOOR ALL FIRE ALARM CONDUIT JUNCTION BOXES THAT DON'T HAVE DEVICE SHALL BE AINTED RED OR HAVE RED AINTED COVERS ALL SIGNAL LINE CIRCUITS WILL BE CLASS B IAW NFA 72 ALL NOTIFICATION CIRCUITS WILL BE CLASS B IAW NFA 72 ALL FIRE ALARM CIRCUITS WILL BE CONTINUOUS FROM THE ANEL TO THE LAST DEVICE AND/OR THE EOL SUERVISORY DEVICE THE JUNCTION BOX OR THE DEVICE THAT CONTAINS THE EOL DEVICE SHALL BE LABELED "EOL" AN ADDRESSABLE SYSTEM MUST BE UTILIZED AND THE DEVICE ADDRESS MUST HE INDICATED ON A LABEL ON THE DEVICE OR JUNCTION BOX THE CIRCUITS MUST BREAK ONLY AT DEVICES WITH SCREW TERMINALS NO SLICE BOXES OR WIRE-NUTS MAY BE USED ALL FIRE ALARM CIRCUITS WILL BE COLOR CODED AND THE COLORS MUST NOT CHANGE WITHIN THE CIRCUIT. CONDUIT OR EMT INSTALLED UNDER THIS CONTRACT SHOULD ALSO INCLUDE ULL STRING FOR FUTURE USE. CONDUIT INSTALLED UNDER THIS CONTRACT SHALL SIZED TO NOT EXCEED THE FILL RATIOS RESCRIBED IN NFA 70. FINAL CONDUIT ROUTING IS IS BASED ON THE INSTALLERS FINAL SYSTEM DESIGN AND MUST BE INDICATED ON THE AS-BUILT DRAWINGS. DESIGN STANDARDS: IBC (2012) INTERNATIONAL BUILDING CODE IBC(2012) INTERNATIONAL FIRE CODE NFA - 72 (2010) 10-Aug- FIRE ALARM LEGEND SYMBOL DESCRITION MOUNTING HT- AFF ANN MANUAL ULL STATION 48" TO CENTER HORN / STROBE 82"OR AS NOTED 75 M SMOKE DETECTOR STROBE F/A ADDRESSABLE MONITOR MODULE CEILING LEVEL 82" OR AS NOTED 48" TO CENTER FAC ADDRESSABLE FIRE ALARM CONTROL ANEL FIRE ALARM WIRE / CABLE LEGEND 48" TO THE CENTER OF THE CONTROLS CIRCUIT SIGNAL LINE CIRCUIT WIRE TYE TWISTED AIR FL CIRCUIT STYLE CLASS "B" NAC- HORN/STROBES TWISTED AIR FL OR THHN CLASS "B" 75 110 75 FIRE ALARM & DETECTION SYSTEM OERATIONAL MATRIX SYSTEM INUTS INITIATING DEVICE INUTS MANUAL ULL STATIONS ACTIVATE FIRE ALARM CONTROL ANEL ALARM RELAY ACTIVATE FIRE ALARM CONTROL ANEL SUERVISORY RELAY ACTIVATE CONTROL ANEL INTERNAL FIRE ALARM SOUNDER ACTIVATE CONTROL ANEL INTERNAL TROUBLE ALARM ACTIVATE CONTROL ANEL TROUBLE RELAY SYSTEM OERATIONS TRANSFER ANEL OWER TO INTERNAL BATTERIES ACTIVATE CONTROL ANEL INTERNALSUERVISORY ALARM START CLEAR FIRE ALARM HORN STROBES REQUIRED SYSTEM OUTUTS INITIATION NOTIFICATION TRANSMITSUERVISORYNOTIFICATIONTOCENTRALSTATION TRANSMIT TROUBLE NOTIFICATION TO CENTRAL STATION TRANSMIT FIRE ALARM NOTIFICATION TO CENTRAL STATION OFF-SITE NOTIFICATION ANCILLARY FUNCTIONS NOTES SMOKE DETECTOR SUERVISORY INUTS ANEL RESET TO CLEAR SYSTEM TROUBLE INUTS FIRE ALARM OEN CIRCUIT F/A CIRCUIT GROUND FAULT FIRE ALARM LAN F/A GENERAL ANEL FAULT AC OWER FAILURE SCALE: 1 8 "=1'-0" GENERAL NOTES: 120VAC FROM DEDICATED BREAKER WITH LOCK REFER TO THE FIRE ROTECTION SECIFICATIONS FOR ADDITIONAL INFORMATION REGARDING THE FIRE IT IS THE RESONSIBILITY OF THE FIRE ALARM CONTRACTOR TO INSTALL ALL EQUIMENT AS SHOWN ON ROTECTION SYSTEM. DRAWINGS AND SECIFICATION ARE COMLIMENTARY; WORK CALLED FOR IN EITHER DRAWINGS AND SECIFICATIONS AND THE REFERENCED CODES. THE DRAWINGS OR THE SECIFICATIONS SHALL BE TREATED AS IF CALLED FOR BY BOTH. TVSS FIRE ALARM CONTROL UNIT 2 TELEHONE LINES FAC M SRINKLER MONITOR AT RISER RISER DIAGRAM IS DIAGRAMMATIC. SEE FLOOR LANS FOR EXACT NUMBER OF DEVICES THE FIRE ROTECTION SYSTEM WILL BE MONITORED BY A CENTRAL STATION FIRE ALARM SYSTEM. IT IS THE RESONSIBILITY OF THE FIRE ALARM CONTRACTOR TO INSTALL ALL EQUIMENT AS SHOWN ON DRAWINGS AND SECIFICATIONS AND THE REFERENCED CODES. THE FIRE ALARM CONTRACTOR WILL BE RESONSIBLE FOR THE COORDINATED DESIGN, COORDINATION OF INSTALLATION OF THE FIRE ALARM SYSTEM TO INSURE A COMLETE OERATING SYSTEM IN ALL RESECTS. THE FIRE ROTECTION SYSTEM WILL BE MONITORED BY A CENTRAL STATION FIRE ALARM SYSTEM. ALL FIRE ALARM ANELS, A/V DEVICES AND WIRING TO THE THE ALARM SYSTEM SHALL BE BY THE FIRE ALARM CONTRACTOR. THE FIRE ALARM CONTRACTOR WILL BE RESONSIBLE FOR THE COORDINATED DESIGN, COORDINATION OF INSTALLATION OF THE FIRE ALARM SYSTEM TO INSURE A COMLETE OERATING SYSTEM IN ALL RESECTS. IT IS NOT THE INTENT OF THESE LANS AND SECIFICATIONS TO ROVIDE A COMLETE DETAILED ALL FIRE ALARM ANELS, A/V DEVICES AND WIRING TO THE THE ALARM SYSTEM SHALL BE BY THE FIRE DESCRITION OF THE AARATUS, MATERIALS, EQUIMENT, ETC. WHICH IS REQUIRED TO MAKE A COMLETE ALARM CONTRACTOR. AND FUNCTIONAL INSTALLATION OF THE SECIFIC FIRE ROTECTION SYSTEM. IT IS THE RESONSIBILITY OF THE FIRE ALARM CONTRACTOR TO ROVIDE ALL REQUIRED MATERIAL, EQUIMENT AND COORDINATION AND IT IS NOT THE INTENT OF THESE LANS AND SECIFICATIONS TO ROVIDE A COMLETE DETAILED ERFORM ALL WORK REQUIRED TO INSTALL A COMLETE AND AROVED INSTALLATION. DESCRITION OF THE AARATUS, MATERIALS, EQUIMENT, ETC. WHICH IS REQUIRED TO MAKE A COMLETE AND FUNCTIONAL INSTALLATION OF THE SECIFIC FIRE ROTECTION SYSTEM. IT IS THE RESONSIBILITY OF AT THE COMLETION OF THE SYSTEM TESTING, THE FIRE ALARM CONTRACTOR SHALL COMLETE OR HAVE THE FIRE ALARM CONTRACTOR TO ROVIDE ALL REQUIRED MATERIAL, EQUIMENT AND COORDINATION AND COMLETED THE CERTIFICATE OF COMLETION IAW NFA72. ERFORM ALL WORK REQUIRED TO INSTALL A COMLETE AND AROVED INSTALLATION. AT THE COMLETION OF THE SYSTEM TESTING, THE FIRE ALARM CONTRACTOR SHALL COMLETE OR HAVE COMLETED THE CERTIFICATE OF COMLETION IAW NFA72. FIRE ALARM SYSTEM RISER