assembly design. This article will focus specifically on vapor retarders. NRCA guidelines

Similar documents
Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.

Roof Insulation Building. Energy. Environment friendly e-library

How do I measure the amount of water vapor in the air?

Presented by: Jennifer Doyle, P.E., RRC, LEED AP

Temperature and Humidity

Low-slope reroofing guidelines

Natatorium Building Enclosure Deterioration Due to Moisture Migration

Renovating Your Basement

Article. Protecting the Building Envelope from Water Damage. MemBrain Smart Vapor Retarder & Air Barrier Film

HVAC Calculations and Duct Sizing

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

keep moisture in check by getting fairly hot and facilitating downward time the sun came out, Then, after installation roof no longer got very

1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability

Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction

CONDENSATION. Section Break (Next Page)

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

CONDENSATION IN REFRIDGERATED BUILDINGS

Predicting Moisture Problems in Low-Slope Roofing

Common Problems with Walls

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

TECH BULLETIN. Roofing No. Impact of Temperature on Polyiso R-value. Subject: Impact of Temperature on the R-value for Polyisocyanurate Insulation

Best Practices for Crawl Space Insulation

Underwriters Laboratories Testing Information

Field Performance of Different Interior Basement Insulation Systems

Retrofitting an Insulated Cold Roof

Foundation. Foundation

CHAPTER 7: Building Systems ROOFING SYSTEMS

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

FOAMULAR LT40, 400 and 600 insulations with minimum compressive strengths of

PIMA Technical Bulletin #115. The High R Roof: Guidelines for Energy-Efficient Roofing and Re-Roofing. What is a High R Roof?

COMMERCIAL BUILDING APPLICATIONS

Continuous Insulation Using Polyiso Wall Sheathing

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN Fax: Re-Roofing: Asphalt Shingles

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE

THE PSYCHROMETRIC CHART AND ITS USE

The Fallacies of Venting Crawl Spaces January 3, 2002 Craig DeWitt, PhD, PE

Environmental Data Center Management and Monitoring

Akton Psychrometric Chart Tutorial and Examples

CertainTeed. Protecting Your Home From Ice Dams Homeowner s Guide

Housing Fact Sheets. Moisture Condensation at the Windows

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

Attic ventilation is needed for two primary reasons:

Nondestructive Evaluation of USCG Hawkins Pt. Road Curtis Bay, MD Provided by: HurleyIR

J3.4 DESIGN TEMPERATURES FOR HEATING AND COOLING APPLICATIONS IN NORTHERN COLORADO -- AN UPDATE

Preventing Ice Dams on Roofs

Heating Load Calculation

Asphalt Shingle Application Requirements

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

Water Damage & Repair

September 3, Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION

Avoiding Air Barrier Pitfalls

THE HUMIDITY/MOISTURE HANDBOOK

FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Refrigeration Manual. Part 3 - The Refrigeration Load

Answers to Your Questions from the Webinar

Performance of 8 Passive House Envelopes in Cold Climates

Characteristics of Evaporators

Humidity the story for teachers

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.

S e l f Drying R o o f s : What! No Dripping!

SECTION MORTUARY REFRIGERATORS

EcoTouch Insulation with PureFiber Technology

CONVENTIONAL ROOFS: MEASURING IMPACTS OF INSULATION STRATEGY & MEMBRANE COLOUR IN CANADA

ROOFS, SNOW AND ICE DAMS

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Molds and mildew are fungi that grow

Getting The Most Out of Your Roof Asset. Program #099 PM

National Building Code of Canada 2010

ASHRAE Climatic Data Activities. Dru Crawley Didier Thevenard

5 Things. You Must Know. Before Buying. Radiant Barrier

Creating Efficient HVAC Systems

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

How do Scientists Forecast Thunderstorms?

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Building Owners Guide to a Duro-Last System!

Open-cell spray foam & what every contractor

R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2C Energy & IAQ (2013) Related TEK: 2-5B, 6-1C, 6-4B, 6-11A, 6-12C, 6-12D, 6-12E

SunGuard IS 20 Technical Information

Long-Term Hygrothermal Performance of Green Roofs

Tsawwassen BC Arena Before & After installation of the Low-E ceiling

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS

UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS

Introduction to Energy Performance of Brick Masonry

) and air spaces (R a

ES 106 Laboratory # 6 MOISTURE IN THE ATMOSPHERE

R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2B Energy & IAQ (2009) Related TEK: 6-1B, 6-11, 6-12C INTRODUCTION

In accordance with the Department of Labor and Industry s statute , Subd. 11,

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS

Cooling Load Calculations and Principles

Roofing Retrofits: Focus on Sustainability

Nondestructive Evaluation of. Lockheed Martin Building at Windsor BVLD, Windsor Mill, MD. Provided by: HurleyIR

Greenhouse Cooling. Why is Cooling Needed?

Basements are Changing. Basements Part of the Enclosure. Basements. Energy Efficient, Durable, Healthy. Below grade enclosure

Insulating Unvented Attics With Spray Foam

Transcription:

he fundamental purpose of a roof assembly is to keep water from entering a building through the roof. Low-slope roof assemblies, when properly designed and constructed, perform this function well. However, moist air within a building can enter a roof assembly and condense into water. The climate in which a building is located significantly will affect the type, direction of flow and degree of moisture migration and vapor drive that will occur into and out of a building. T Vapor drive from a building s interior to exterior is likely to be strongest when the exterior temperature and relative humidity are low and the interior temperature and relative humidity are high. These conditions will occur most often during winter months in cold climate regions. Warmer interior air exerts a higher vapor pressure than cooler outside air. Roof assemblies create a barrier between these areas of differing vapor pressures. If a roof assembly is not sufficiently insulated, warm, moist air will rise into the roof assembly and may cool to its dew-point temperature, causing condensation to occur. There are three primary methods used to prevent moisture from accumulating in low-slope roof assemblies: use of a vapor retarder, ventilation of interior space and self-drying roof 48 assembly design. This article will focus specifically on vapor retarders. NRCA guidelines Vapor retarders primarily are used in low-slope roof assemblies to prevent large quantities of moisture-laden air from a building s interior from moving into the roof assembly where condensation may occur. The use of a vapor retarder has been debated in the roofing industry for years. NRCA has maintained a vapor retarder should be considered by roof system designers when the following two conditions are met: the outside average January temperature is below F (4 C) and the expected interior winter relative humidity is 45 percent or greater. The outside average temperature for a specific location can be determined from historical climatic data compiled by the National Weather Service. Local climatic data also may be available from private weather services, local television or radio meteorologists, or local weather observers. If local historical climatic data are not available, the map in Figure 1 can be used to determine the general regions that have outside average January temperatures below F (4 C). The expected interior winter relative humidity of a particular building can be determined from the design relative humidity value. This value typically is determined by the designer of the building s heating, ventilating and airconditioning (HVAC) system. For existing buildings, the design interior relative humidity sometimes can be obtained from a knowledgeable building maintenance engineer or whoever maintains the building s HVAC and mechanical control systems. NRCA s guidelines for determining the need for a vapor retarder have the benefit of simplicity; they are not supported by a great deal of scientifically developed data. Further support for the inclusion of vapor retarders can be obtained from the U.S. Army Corps of Engineers Cold Regions Research and Engineering Laboratory (CRREL) or American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASRHAE) Inc. In any case, NRCA considers the roof system designer to be responsible for determining whether a vapor retarder is necessary. For a vapor retarder to perform its intended function, the temperature at a vapor retarder s level must be warmer than the dew-point temperature. Once it has been determined a vapor retarder is to be used, the design temperature at the bottom side of the vapor retarder should be calculated and the design dew-point temperature determined. To ensure the temperature

at the vapor retarder remains higher than the dew-point temperature, sufficient insulation amounts must be determined and installed above the vapor retarder to maintain the vapor retarder at a warm enough temperature. Heat loss During winter, warm interior air will cool as it passes through or across a roof assembly. The rate at which the air cools depends on the material it is passing through because every building material has distinct thermal-resistance properties. It is a roof system designer s goal to make sure the temperature at the vapor retarder membrane is warmer than dew-point temperature, which, in effect, causes dew-point temperature to occur within the insulation that is installed above the vapor retarder. One method to accomplish this is to graphically illustrate the temperature change. Graphic method The temperature gradient, or amount of heat loss, can be illustrated on a roof assembly diagram. The following example is based on a simplified procedure that shows a graphic demonstration of temperature distribution through a roof assembly. Consider the following example problem: The building in question is a textile mill located in Baltimore. The interior design dry bulb temperature is 70 F, and the interior design relative humidity is 65 percent. Your job is to calculate and illustrate the temperature gradient through a roof assembly composed of a gravel-surfaced built-up roof, 3 4-inch-thick perlite insulation, 2-inch-thick polyisocyanurate insulation, two-ply felt and asphalt membrane vapor retarder, 1 2-inch-thick gypsum board and metal deck. The first step is to determine the winter interior design dry bulb temperature. This value should come from the HVAC system designer or, if it is an existing building, a knowledgeable building maintenance engineer or whoever maintains the building s HVAC and mechanical control systems. For this Figure 1: Mean January temperature map example, as mentioned, the winter interior design dry bulb temperature is 70 F. Next, determine the winter exterior design dry bulb temperature. Design values can be found in Appendix 3 Climate/Design Data of The NRCA Roofing and Waterproofing Manual, Fifth Edition, or in Chapter Climatic Design Information of the 01 ASHRAE Handbook Fundamentals. For Baltimore, the winter exterior design dry bulb temperature is 10 F. Then, draw the roof assembly at a reasonable scale, such as 3 inches equals 1 foot. Next, lay out a temperature scale underneath the drawing. The starting temperature of the scale s left side will be the winter interior dry bulb design temperature. The scale Figure 2: Temperature gradient through a roof assembly will end on the right side with the winter exterior design dry bulb temperature value. Then, place evenly spaced vertical lines between these two lines to represent 5- and 10-degree increments. (See Figure 2.) Next, determine the roof assembly s overall R-value. Typical thermal properties of common building materials can be found in the Moisture Control section of The NRCA Roofing and Waterproofing Manual, Fifth Edition, or Chapter 25 Thermal and Water Vapor Transmission Data of the 01 ASHRAE Handbook Fundamentals. It is important to note air film exists on a roof assembly s exterior and interior sides. Air film has an R-value that contributes to a roof assembly s overall 49

R-value. Also, there are different Rvalues for interior and exterior air films during winter and summer. Figure 3 lists the R-values for the example building. The next step is to calculate the amount of heat loss occurring at each material using the fundamental heatloss formula temperature drop = Ti - [(R/RT) x st] where: Ti = design inside (interior side) temperature, degrees Fahrenheit st = (winter interior design dry bulb temperature) - (exterior design dry bulb temperature) st = 70 degrees - 10 degrees = degrees R = cumulative R-values of materials starting from the interior RT = R-value of the total assembly Definitions Design dry bulb temperature, exterior: This is the winter design outside dry bulb temperature. The unit of measurement is expressed as degrees Fahrenheit. Design dry bulb temperature, interior: This is the design dry bulb temperature of the inside of the building during winter conditions. The unit of measurement is expressed as degrees Fahrenheit. Dew-point temperature: This is the temperature at which air becomes saturated with water vapor or the temperature at which air has a relative humidity of 100 percent. The unit of measurement is expressed as degrees Fahrenheit. Dry bulb temperature: This is the temperature of air as measured by an ordinary thermometer. The unit of measurement is expressed as degrees Fahrenheit. R-value: This represents thermal resistance value as it applies to a specific thickness of a material or construction. Thermal resistance is the mean temperature difference between two defined surfaces of material or construction that induces heat flow through a unit area under steady conditions. In English units, it is expressed as degrees F ft2 h/btu. Relative humidity: This is the ratio of the pressure of water vapor present in a given volume of air to the pressure of fully saturated water vapor at the same temperature. It is expressed as a percentage. continues on page 52 Circle Reader Service #84

continued from page R-value Material See Figure 4 for calculations for the example building. Then, plot the temperature gradient values for each material on the roof assembly drawing. Note the temperature determined in the previous step is located on the top surface of the material layer. Draw a line from the interior temperature to the next value and continue connecting the plotted temperature values until the line reaches the exterior design temperature as shown in Figure 2. Next, determine the dew-point temperature. Dew-point temperature can be determined by using a simplified version of the ASHRAE psychrometric chart, which is shown in Figure 5. As previously mentioned, the interior design conditions are 70 F for design dry bulb temperature (design inside temperature) and 65 percent relative humidity (design relative humidity). Along the top of the table, locate the Exterior air film (winter) 0.17 Gravel-surfaced built-up roof 0.33 4-inch-thick perlite insulation 2.08 2-inch-thick polyisocyanurate 14.30 3 Two-ply felt and asphalt membrane 0.12 2-inch-thick gypsum board 0.56 Metal deck 0.00 Interior air film (winter) 0.61 1 Total R-value 18.17 Figure 3: Sample R-values for percent and 70 percent relative humidity as follows: interpolated dew-point value = DP1 + RH - RH1 (DP2 - DP1) RH2 - RH1 where: DP1 = degrees (dew-point temperature for percent relative humidity) DP2 = degrees (dew-point temperature for 70 percent relative humidity) RH = 65 percent RH1 = percent design dry bulb (interior) temperature column, which, in this case, is 70 F. Next, locate the relative humidity row along the left side of the table. The dew-point temperature is at the intersection of the design dry bulb temperature column and relative humidity row. In this case, 65 percent isn t specifically listed as a relative humidity, so you must use linear interpolation between the dew-point values given RH2 = 70 percent Therefore: + 65- (-) 57.5 degrees 70- Finally, locate the dew-point temperature value on the temperature gradient line. If the dew-point temperature falls within the insulation that is placed above the vapor retarder, continues on page 54 The Selection You Need... Service you can trust. Specializing in select product lines and categories, ABC Supply offers the professional contractor competitive pricing, superior service and the highest quality building materials available. You can depend on ABC Supply for the products you need to be delivered when you need them. Contact ABC Supply today for your building supply needs. Roofing Siding Windows Tools Gutter Accessories And More Visit our website at www.abcsupply.com to find our nearest location or to learn more about ABC Supply Co. Circle Reader Service #2 52

Temperature at top face of material (degrees Fahrenheit) Material Interior air film 70-[(0.61/18.17) x ] 68.0 Metal deck 70-[(0.61+ 0.0/18.17) x ] 68.0 2-inch-thick gypsum board 70-[(0.61+0.0+0.56/18.17) x ] 66.1 Two-ply felt and asphalt membrane vapor retarder 70-[(0.61+0.0+0.56+0.12/18.17) x ] 65.7 2-inch-thick polyisocyanurate insulation 70-[(0.61+0.0+0.56+0.12+14.3/18.17) x ] 18.5 4-inch-thick perlite insulation 70-[(0.61+0.0+0.56+0.12+14.3+2.08/18.17) x ] 11.7 Gravel-surfaced built-up roof 70-[(0.61+0.0+0.56+0.12+14.3+2.08+0.33/18.17) x ] 10.6 Exterior air film 70-[(0.61+0.0+0.56+0.12+14.3+2.08+0.33+0.17/18.17) x ] 10.0 1 3 A word of caution Figure 4: Calculations for the sample building continued from page 52 condensation should not occur on the bottom side of the vapor retarder. If it mp14 ad2.qxd 1/14/05 3:39 PM select a new amount of insulation and perform the graphic analysis again to determine whether the dew-point temperature falls within the insulation. Additionally, if the dew-point temperature falls within the upper portion (around the upper one-third) of the insulation, the insulation amount may be able to be reduced as long as the dew point stays within the insulation and the insulation amount meets building code requirements. It is necessary to perform the graphic analysis to determine whether the reduced insulation amount continues to keep the dew point within the insulation. falls below the insulation, additional insulation is required. If additional insulation is required, Page 1 The graphic method presented in this article is a simplified procedure using theoretical constant values. Actual relative humidity and dew-point temperature values constantly change in typical building environments as the ambient temperature and/or water Have you ever been on the job and discovered you didn t have the right fastener for the application? Having a box of the MP14 multi-purpose fasteners on hand is your assurance that you will have the right fastener for the job! MP14... The one fastener solution Works in metal, concrete, or wood including ACQ treated lumber! Designed to work in metal, concrete, or wood including ACQ! Each box includes a nutsetter, carbide tip drill bit, and a technical sheet! Specialty Fasteners and Services for Commercial Construction TRIANGLE FASTENER (800) 486-1832 www.trianglefastener.com Circle Reader Service #228 54 Always have a box on hand! Circle Reader Service #6

Dew-Point Temperature ( F) Relative Humidity Design Dry Bulb (Interior) Temperature ( F) 32 F 35 F F 45 F F F F 65 F 70 F 75 F 80 F 85 F 90 F 95 F 100 F 100% 32 35 45 65 70 75 80 85 90 95 100 90% 30 33 37 42 47 52 57 62 67 72 77 82 87 92 97 80% 30 34 39 44 49 54 58 64 68 73 78 83 88 93 70% 31 36 45 64 69 74 79 84 88 % 28 32 36 41 46 51 65 69 74 79 83 % 16 28 33 36 41 46 64 69 73 78 % 12 15 18 23 31 35 45 49 53 58 62 67 71 30% 8 10 14 16 21 25 29 33 37 42 46 54 59 62 % 6 7 8 9 13 16 28 31 35 43 48 52 10% 4 4 5 5 6 8 9 10 13 17 30 34 Adapted from ASHRAE Psychrometric Chart, 1993 ASHRAE Fundamentals Handbook. Figure 5: A table version of ASHRAE s psychrometric chart vapor pressure in the air change. An HVAC system designer typically determines design values to size equipment and for building envelope thermal insulation and water vapor control. These design values most often are Circle Reader Service #180 based on anticipated maximum extreme conditions. Because the graphic method is just one way to determine whether a vapor retarder will perform its intended function, roof system designers should further substantiate their analyses by using other methods. Additional methods can be found in The NRCA Roofing and Waterproofing Manual, Fifth Edition. n Joan P. Crowe is an NRCA manager of technical services. Circle Reader Service #226