Interpreting the results of circuit breaker analysis?

Similar documents
Technical guide circuit breaker diagnosis

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold C

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

Candidate Number. General Certificate of Education Advanced Level Examination June 2014

April 1. Physics 272. Spring Prof. Philip von Doetinchem

ADMO. Maintenance management solution for protection systems

Windshield Wiper Motors

SYNCHRONOUS MACHINES

BOWIE PUMPS OPERATION - MAINTENANCE

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

A.V.R. R250. Installation and maintenance R250 0V E+ E- VOLT STAB FREQ. & L.A.M. CONFIG. 50Hz. 47.5Hz. 57Hz LAM 1 13% 2 25% OFF LAM OFF 9

TOYOTA STARTING SYSTEMS. General

WINDING RESISTANCE TESTING

Residual Current Circuit Breaker

Force on Moving Charges in a Magnetic Field

UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS

Pump Maintenance - Repair

AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE

Stop Alert Flasher with G-Force sensor

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

Dielectric Withstand Testing in a Production Environment

On-line PD Monitoring Makes Good Business Sense

A simple method to determine control valve performance and its impacts on control loop performance

Current Loop Tuning Procedure. Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) General Procedure AN-015

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Motor Fundamentals. DC Motor

Representing Vector Fields Using Field Line Diagrams

Troubleshooting with ABS Service Data Kit

Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.

Understanding Power Impedance Supply for Optimum Decoupling

SECTION VARIABLE FREQUENCY DRIVES

Figure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc.

DC MOTOR ANALYSIS & TROUBLESHOOTING

A Practical Guide to Dielectric Testing

Current and voltage measuring relays

Magnetic Fields and Their Effects

PS-6.2 Explain the factors that determine potential and kinetic energy and the transformation of one to the other.

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

8 Speed control of Induction Machines

DISTRIBUTION TRANSFORMER OVERLOAD PROTECTION TRIPPING CIRCUIT

Basics of Electricity

TROUBLESHOOTING PRELIMINARY

Electronically Controlled Air Suspension (ECAS) for Trucks

Ducoterra Radiant Heating Panel Installation Manual

Joslyn Clark Controls, Inc.

Line Reactors and AC Drives

Motors and Generators

Automated Circuit Breaker Monitoring

Graphing Motion. Every Picture Tells A Story

III. Applications of Force and Motion Concepts. Concept Review. Conflicting Contentions. 1. Airplane Drop 2. Moving Ball Toss 3. Galileo s Argument

Unified requirements for systems with voltages above 1 kv up to 15 kv

New standardized approach to arc flash protection

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

DEGREE: Bachelor's Degree in Industrial Electronics and Automation COURSE: 1º TERM: 2º WEEKLY PLANNING

The Application and Benefits of Multi-phase Auto-reclosing

(3) Explosion proof. Designed to prevent ignition of any explosive gases or dust and dirt which may surround the motor.

Solid-State Relays (SSRs) vs Electromechanical Relays (EMRs)

Input and Output Capacitor Selection

Determining the Cause of AFCI Tripping Branch/Feeder and Combination Arc Fault Circuit Interrupters Class 760

Load Cell Troubleshooting

DIRECT CURRENT GENERATORS

Adjustment functions for both span and shift have been incorporated

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

Chapter 7 Hydraulic System Troubleshooting

MOTION DIAGRAMS. Revised 9/ LC, tlo

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao. x x. x x. Figure 10: Cross sectional view

DTC P1271/78 FUEL PRESSURE REGULATOR CIRCUIT MALFUNCTION (OPEN/SHORT) DTC P1272/78 FUEL PRESSURE REGULATOR SYSTEM MALFUNCTION

Erik Backström, High Voltage breakers, After Sales & Service High voltage SF 6 live tank circuit breakers After Sales & Service Training course

Engineering Series Ratings: Is It Practical?

Troubleshooting accelerometer installations

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

Homework # Physics 2 for Students of Mechanical Engineering

Welcome to Linear Controls Quarterly Training

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance

Electrical Circuit Theory

Circuit Breakers. NRC Series. NRC Series

Service and Maintenance. SEW-EURODRIVE Driving the world

Loudspeaker Parameters. D. G. Meyer School of Electrical & Computer Engineering

Saint Paul Public Schools Secondary Course Syllabus. Course Title: Automotive Technology 3 Course Length: Quarter/Semester/Trimester

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Section 9.5 Electric Motors

INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS

Describe the procedure used to check for spark. Discuss what to inspect and look for during a visual inspection of the ignition system.

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

6. Synchronous machine dynamics

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

CPL SYSTEMS / GROENEVELD AUTOMATIC GREASING SYSTEM COMPLETE SYSTEM CHECK PNEUMATIC PUMP

AC Generators. Basic Generator

Understanding Ignition Waveforms

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.

Best Practices for Creating Your Smart Grid Network Model. By John Dirkman, P.E.

To help avoid personal injury due to poor braking. DO NOT Tap into the vehicle's brake system to operate a trailer brake system.

The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law.

Testing and Condition Monitoring of Electromechanical Solenoids

Transcription:

Interpreting the results of circuit breaker analysis? Important tests during circuit breaker analysis and the interpretation of the measured results - coil current, dynamic contact resistance and motion analysis 1 Introduction Circuit breakers are like insurances for every energy distribution network. They are there in case something bad happens. And if it happens, they have to do their duty and prevent any further damage. Therefore circuit breakers need to be inspected regularly to assure that they are operating as specified. Cutting-edge circuit breaker-analyzing devices provide methods which help identify malfunctions or worn parts of a circuit breaker. In order to achieve a condition assessment in a time-efficient manner an analysis must be done, preferably without disassembling the circuit breaker. 2 Different measurements and their interpretation For a reliable condition assessment of a circuit breaker it is of vital importance to have a correct interpretation of the results obtained during an analysis. As the interpretation of a timing analysis is pretty straight forward it will not be discussed any further in this article. However, to draw the right conclusions from - coil current analysis, - dynamic contact resistance measurements, and - motion analysis, more background knowledge about what is going on inside a circuit breaker is required. These three methods are widely used worldwide for a successful condition assessment of circuit breakers. However, our daily work reveals that there are usually a lot of open questions when it comes to the interpretation of the measured results. The coil current analysis of the trip coil gives you a deeper understanding on what is going on during the closing or opening sequence of the main contacts. By taking a closer look at the coil current a lot of useful information can be revealed. For instance: - the electrical properties of the coils, such as the time constant, - the force, i.e. current which is proportional to that force, and must be applied in order to trigger the loaded spring, - the correct timing sequence of the auxiliary contacts 52a and 52b. Measuring the dynamic contact resistance combined with a motion analysis is an approach that is commonly used for determining the length and the condition of the arcing contact without disassembling the main contacts of the circuit breaker. That contact underlies a natural abrasion, because each time a circuit breaker is tripped during load, an arc is created which vaporizes parts of the arcing contact. Due to this process-related abrasion the contact must be inspected regularly in order to avoid any malfunctions. When the contact length goes below a reference value given by the manufacturer, the correct functionality of the circuit breaker cannot be guaranteed any longer and the breaker must undergo maintenance. A motion analysis can detect weak mechanical components of a circuit breaker. This, for example, can be worn out damping units, problems with storing the energy (a worn spring or leaking pressure system) for tripping or closing, and contacts which have already reached the end of their life cycle. By detecting these problems at an early stage, counteractions can be applied to guarantee a safe circuit breaker operation and ensure reliable distribution of electrical energy throughout the grid.

3 Interpretation of coil current analysis During a coil current analysis the current flow in the trip or close coil during the closing or opening sequence of the main contacts is measured and displayed in a diagram over time. Resulting curve deviations from the electrical coil properties that are expected (time constant), the necessary driving force (proportional current), and the correct timing sequence of the auxiliary contacts are indicators for electrical or mechanical problems within the trip and close mechanism of the circuit breaker. An interpretation of the different curve sections is given in the following diagram. Figure 1: Typical curve of coil current flow Curve section 1 to 2 After the coil has been energized the current starts to flow. The speed of the current rise depends on the coil impedance. That impedance depends on the position of the armature, which is still static between point 1 and 2 of the curve (see Figure 2). After point 2 the armature starts to move out of the coil. Figure 2: Coil at Point 1 Any current flow deviation in this section indicates a problem with the electrical coil properties and the voltage supply. Here it is important to make sure that the coil even trips at an undervoltage condition. The time constant (L/R) of the coil can be calculated by measuring the time between point 1 and point 2 and the peak current at point 2. If the time constant of the coil deviates from the reference value it indicates that a coil is damaged (e.g. short-circuited windings). Curve section 2 to 3 The moving armature induces a back e.m.f. which causes a reduction of the coil current. A slow movement of the armature is an indicator that lubricant has entered the wrong area.

Point 3 Figure 3: Coil at Point 3 Here the armature hits the trigger which up to this point kept the charged spring from moving (see Figure 3). The armature must have sufficient power to overcome the mechanical resistance of the trip mechanism. Any deviations here are usually an indicator of oil or grease within the coil area which causes a damping effect on the movement. With the help of the coil current diagram in that section a poorly aligned armature-trigger configuration or obstacles blocking the trip mechanism can also be identified. Curve section 3 to 4 Figure 4: Coil between 3 and 4 The armature releases the charged spring and keeps moving until it reaches its end position (see Figure 4). The current level decreases until the armature comes to a stop. A deviation from the lowest current value indicates that the armature did not reach its designated end position due to a mechanical issue. Curve section 4 to 5 Figure 5: Coil between 4 and 5 Now that the armature has come to a stop, back e.m.f is no longer generated to reduce the current flow (see Figure 5). Therefore the current level increases again. However, this time the current value reaches a higher level, because the coil inductance has changed due to the displacement of the armature. A deviation from the expected time constant indicates once again that there is electrical damage in the coil windings. Point 5 At this time the current has overcome the coil inductance and stays constant until the auxiliary contact opens and interrupts the current flow. An early or delayed interruption indicates that the timing between the main and auxiliary contacts (52a and 52b) needs to be adjusted.

Point 6 Between the release of the charged spring at point 3 and point 6 the main contact and (with a short delay) the auxiliary contacts change their state and open. Curve section 6 to 7 The changing state of the auxiliary contact interrupts the voltage supply to the coil and therefore the armature starts to move back into the coil until it reaches its starting position again. A slower current decrease or even short current increase may show that the movement of the armature has been decelerated. A strong deviation from the reference value indicates mechanical friction or a damaged recovery diode. 4 Interpretation of DRM results Motivation for the dynamic contact resistance measurement A dynamic contact resistance measurement is a commonly used method, because it determines the contact length without having to disassemble the circuit breaker. When the arcing contact becomes shorter than the minimum requirement specified by the circuit breaker manufacturer, a safe operation can no longer be guaranteed and the interrupter unit needs to be maintained properly. In order to apply that method it is important to know the components of an SF6 circuit breaker interrupter unit and how the current is interrupted during an open operation. Figure 6 through 10 show the different phases of an opening sequence. Figure 6: Current flow via main contacts Figure 7: Current flow via arcing contact Figure 8: Arcing Figure 9: Increasing arcing until it gets extinguished Figure 10: Save position prevents any re-strike Detailed description of an opening sequence When the interrupter unit is closed, the current flows via the main and arcing contact of a circuit breaker (see Figure 6). As soon as the opening process starts, the main contacts are separated first and now the current flows only via the arcing contacts (see Figure 7). After a few milliseconds the arcing contacts also move apart but the current continues flowing, because the voltage across the contacts initiates an arc

(see Figure 8). As the sinus-shaped current crosses the zero point the dielectric strength between the contacts is sufficient enough to resist a re-initiation and the ionised gases are removed. At this point the arc is extinguished. The contacts continue to separate, increasing the dielectric strength threshold as the voltage across the contacts increases, preventing any restrike (see Figure 10). During each opening process the resulting arc destroys parts of the arcing contact material. The amount of wear depends on the current level. With higher currents more contact material is burned away. During the arcing stage the current is only limited by the supply circuit impedance. Determination of contact length The dynamic contact resistance method measures the contact resistance continuously during the opening operation of the circuit breaker s interrupter unit. This is done with the breaker being isolated from the HV supply and performing a four wire resistance measurement test during the opening operation. The dynamic contact resistance measurement goes through the phases shown in Figure 6 through 10. They show an increase in resistance as the contacts open. As soon as the main contact is open, a steep decrease can be seen. Now the arcing contact is the only connection. The resistance level shows strong deviations. They are caused by the noise produced during the arcing process. When the arcing contact movement comes to an end, the resistance increases again until it exceeds the measurable limit and becomes infinite (i.e. contact is open). The arcing contact length is determined by measuring the time between Figure 7 and 8 (i.e. time of current flow via arcing contact until interruption). This time is used for calculating the actual contact travel (see Figure 11). A closing operation is usually not used for dynamic contact resistance measurements, because the mechanical forces applied to the contact fingers would result in an extremely noisy resistance measurement. Figure 11: DRM curve interpretation

5 Interpretation of motion analysis A motion sensor attached to the mechanical linkage of a circuit breaker reveals a lot of useful information. Therefore it is highly recommended to use this method for tracing the motion of the current interrupting mechanism. In order to classify the condition of the damping units and mechanical issues of the circuit breaker s operating mechanism, the important performance parameters to take note of are the overtravel (amplitude, duration), total travel, and timing behaviour of the contacts. Each motion analysis compares the reference data specified by the circuit breaker manufacturer with the measured values. The following shows the measurement curves of the three performance parameters mentioned above and their interpretation. Overtravel curve Figure 12: Overtravel curve The overtravel curve displays the motion of the main contacts over time. An excessive oscillation at the end of the curve indicates a defective damping system. The purpose of the damping system is to be able to avoid any damage to the mechanical components by slowing down the motion of the contacts after they have reached a safe position. Quite often dash pot-based systems are used which have the same functional principle as the suspension systems found in cars. As seen here in the motion trace, the damping effect of these components is velocity dependent and they are designed to slow down the moving contacts before they reach the end position.

Total travel curve Figure 13: Total travel curve The total travel curve shows the difference between the start and end position of the main contacts over time. If the total travel varies from one measurement to the next this might be an indication of the fact that there was not enough energy stored (a worn spring or leaking pressure system) or the energy consumed by the motion itself has increased because of higher friction forces (corrosion at circuit breaker or mechanical parts). Timing behaviour curve Figure 14: Timing behavior curve The timing behaviour curve displays the motion of the contacts over time. When the motion starts earlier than it has in previous measurements this might indicate that the contacts are worn. When the motion in previous measurements starts at the same time but finishes earlier this indicates a change in energy balance. This means that during the last measurement more energy was stored (higher pressure in pressure system) or the contact movement itself has consumed less energy than it has during the previous measurement (contact which is too short). Anyway, it is important to state that the contacts must be within their minimum and maximum opening time as specified by the manufacturer. Otherwise the breaker must undergo maintenance.

Contacts must not open too quickly, because they would not be able to deal with a transient short-circuit current. On the other hand, they must not open too slowly in order to avoid a restrike of an arc that has already been extinguished. 6 Summary: In a conclusion it can be said that with a proper interpretation of the results obtained by the coil current analysis, dynamic contact resistance measurements and motion analysis an overall assessment of the circuit breaker s most important electrical and mechanical properties can be given. This gives the user additional information about the results already obtained through standard methods such as static contact resistance and general timing measurements. With this information it is much easier to decide whether the circuit breaker must undergo any maintenance or if it is still fit for operation. Andreas Nenning has a degree in automation engineering and mechatronics obtained by the university of applied science in Dornbirn, Austria. Since September 2013 he has been product manager of OMICRON s new circuit breaker test set CIBANO 500. He started his professional career with an apprenticeship at the municipal utilities of Feldkirch, Austria. Later he graduated as Master of Science at the university of applied science in Dornbirn, Austria. After that he spent several years abroad working as application engineer and project leader before finally returning to Austria working as product manager in the field of decentralized renewable energy. Andreas is member of the Cigré Working Group A2.32 (Non-intrusive methods for condition assessment of circuit breakers).

OMICRON is an international company serving the electrical power industry with innovative testing and diagnostic solutions. The application of OMICRON products allows users to assess the condition of the primary and secondary equipment on their systems with complete confidence. Services offered in the area of consulting, commissioning, testing, diagnosis and training make the product range complete. Customers in more than 140 countries rely on the company s ability to supply leadingedge technology of excellent quality. Service centers on all continents provide a broad base of knowledge and extraordinary customer support. All of this together with our strong network of sales partners is what has made our company a market leader in the electrical power industry. For more information, additional literature, and detailed contact information of our worldwide offices please visit our website. www.omicron.at www.omicronusa.com OMICRON