Testing of Potential Transformers By Les Warner (PCA Valence) and Chris Werstiuk (Valence Electrical Training Services LLC)

Similar documents
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

ANALOG AND DIGITAL METERS ANALOG VS. DIGITAL METERS VOLTMETERS ANALOG AND DIGITAL

VOLTAGE REGULATOR AND PARALLEL OPERATION

Current Transformers Ratio / Polarity / Types

TROUBLESHOOTING PRELIMINARY

Essential Electrical Concepts

A Practical Guide to Dielectric Testing

Type SA-1 Generator Differential Relay

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

First Year (Electrical & Electronics Engineering)

Properties of electrical signals

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

WINDING RESISTANCE TESTING

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS:

Fig. 1 Analogue Multimeter Fig.2 Digital Multimeter

INSTALLATION & SERVICE MANUAL. Display Panel

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

SECTION VARIABLE FREQUENCY DRIVES

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

Short Circuit Current Calculations

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

What is a multimeter?

Basic voltmeter use. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

CURRENT TRANSFORMERS INSTALLATION GUIDE

World Leader in HV Testing Technology

High Voltage Power Supplies for Analytical Instrumentation

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21,

Single-Phase AC Synchronous Generator

Lab 3 - DC Circuits and Ohm s Law

CAPACITOR BANK TESTING SWP

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

12 Volt 30 Amp Digital Solar Charge Controller

GENERAL POWER SYSTEM WIRING PRACTICES APPLIED TO TECNADYNE DC BRUSHLESS MOTORS

Manual Ranging MultiMeter

Diode Applications. by Kenneth A. Kuhn Sept. 1, This note illustrates some common applications of diodes.

Capacitor Voltage Transformer. Answers for energy.

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

TROUBLESHOOTING GUIDE

BSNL TTA Question Paper-Instruments and Measurement Specialization 2007

Model UT201/202: OPERATING MANUAL. Table of Contents

ST Style Generator. Owners/Operators Manual

Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate.

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SECTION ELECTRICAL ACCEPTANCE TESTS

Battery Chargers. Revised 8/00 Form Number FORM NO / BATTERY CHARGER SERVICE MANUAL / PARTS LIST - 45

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

User Guide. Model Insulation Tester / Megohmmeter

Line Reactors and AC Drives

UNIVERSITY OF WATERLOO ELECTRICAL & COMPUTER ENGINEERING DEPARTMENT ME269 ELECTROMECHANICAL DEVICES AND POWER PROCESSING.

Unit 6 Transformers. Lead-in. Basic principles. Task 1. Task 2. What applications of transformers do you know?

ECEN 1400, Introduction to Analog and Digital Electronics

Electrical Predictive and Preventative Maintenance

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

INDUCTION REGULATOR. Objective:

The full wave rectifier consists of two diodes and a resister as shown in Figure

Understanding Insulation Resistance Testing

City Of Ottawa High Voltage Substation Inspection, Maintenance Rev July 17 and Testing, ROPEC Page 1

SERIES-PARALLEL DC CIRCUITS

Electrical Shore Connections / Cold Ironing

Current Transformers

Wires & Connections Component Circuit Symbol Function of Component. Power Supplies Component Circuit Symbol Function of Component

A Guide to Transformer Winding Resistance Measurements

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.

Exploring the Necessity of the Hot Hipot Test

Tamura Closed Loop Hall Effect Current Sensors

E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.

Fitting/Installation Guide - UNIVERSAL

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

6 Buck Boost Transformers

Tips for connecting 24-volt power

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

AutoRanging Digital MultiMeter

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR)

Windshield Wiper Motors

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

Power Plant Electrical Distribution Systems

CT Application Guide for the 489 Generator Management Relay

Troubleshooting accelerometer installations

MIT510/2, MIT520/2 and MIT1020/2

Safety technique. Emergency stop module BO 5988 safemaster

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

Unified requirements for systems with voltages above 1 kv up to 15 kv

ELECTRICIAN TRADE REGULATION

Rutland 913 Windcharger Fault Finding Guide

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

Checking Capacitor Banks for Failed Capacitors

Service Manual Type MVTU Definite Time Delayed Relays

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

MEGGER Insulation & Low Resistance Tester

Diode Applications. As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off.

Air Conditioning Sign-Off Sheet

Objectives: Part 1: Build a simple power supply. CS99S Laboratory 1

Transcription:

Testing of Potential Transformers By Les Warner (PCA Valence) and Chris Werstiuk (Valence Electrical Training Services LLC) Potential transformers (PTs) are necessary to a power system for metering and protective relaying to convert higher system voltages to lower control voltages that are more practical from an equipment, operation, and safety perspective. There are three basic styles used to transformer system voltages to control voltages: 1. Potential Transformers (PTs) or Voltage Transformers (VTs) PTs or VTs are the most common device used. These devices use standard transformer theory with 2-3 windings (one primary with one or two secondary windings) with a magnetic connection via an iron core. The high side winding is constructed with more copper turns than the secondary(ies) and any voltage impressed on the primary winding is reflected on the secondary windings in direct proportion to the turns ratio or PT ratio. The secondary windings often have 2 taps with a nominal voltage of 115/67V, 120/69V, or 120/208V. This style of PT is the most accurate style in use. A typical PT is shown in Figure 1. Figure 1

2. Control Potential Transformers (CPTs) CPTs are standard PTs or VTs with a higher VA rating and are used to supply control power for a circuit breaker or motor starter. These transformers are not designed for accuracy and should not be used in revenue metering or primary protection systems. Special attention should be paid to following items: The equipment ratings connected to the secondary should be verified to ensure the combination of devices does not exceed the VA rating of the transformer. The primary connection is also important as a CPT connected to the load side of the circuit breaker or motor starter may prevent the device from operating until after the device has been closed. All CPTs that supply trip power should be supplemented with an external device such as a capacitive trip unit to provide at least one trip signal after a power system loss of voltage. Some typical CPTs are shown in Figure 2. A typical application is shown in Figure 3. Figure 2 Figure 3

3. Capacitive Voltage Transformers (CVTs) CVTs are often used in high voltage (115kV and higher) applications and use a series of capacitors as a voltage divider. The capacitors are connected between the system voltage and the polarity of a PT. As the PT secondary is normally grounded through an internal jumper, an external switch is often used to isolate the PT from ground during testing. The correct switch position must be determined before energizing the CVT to ensure correct operation. An internal schematic diagram of a CVT is shown in Figure 4. CVTs are less expensive and are often used in place of high voltage PTs to reduce capital costs. Figure 4

This article is a basic guideline for PT testing using the most basic of equipment and is arranged in accordance with the NETA standards for easy reference. 1.0 Visual and Mechanical Inspections I. Compare equipment nameplate data with drawings and specifications. Every PT test form should include the serial number, model number, ratios and accuracy class. The serial number is important for PT identification and comparisons between your results and the manufacturer s. The model number is important for comparison of test results to manufacturer s specifications and for ordering replacement or spare PT s or parts. The PT ratio is the most important piece of information and must be recorded from the nameplate or the design criteria. The ratio determines the PT operating characteristics. If the PT has multiple taps (different possible ratio combinations), all taps should be recorded for future reference in case a new PT ratio is required for the application. The accuracy class indicates the PT s performance characteristics. A PT s accuracy is dependent on the number of devices connected to the secondary terminals. PT load is also called the burden that is usually defined in Volt Amps and Power Factor at 120 secondary volts. Standard burden designations are shown in Table 1. Classifications for accuracy have also been designated as shown in Table 2. It is possible that one PT can be rated for different accuracies at different burdens. For example a PT can be rated 0.3W, 0.6Y and 1.2ZZ. However, if the actual burden or power factor falls outside the guidelines in Tables 1 and 2, the PT s accuracy is not guaranteed. Table 1 - Standard Burdens for Potential Transformers Burden Volt-Amps at 120V Burden Power Factor W 12.5 0.7 X 25.0 0.7 Y 75.0 0.85 Z 200.0 0.85 ZZ 400.0 0.85 Table 2 - Accuracy Classes for Potential Transformers Accuracy Class Limits of Transformer Ratio Correction Factor Limits of Power Factor Load 1.2 1.012 0.988 0.6 1.0 0.6 1.006 0.994 0.6 1.0 0.3 1.003 0.997 0.6 1.0 Based on Tables 1 and 2, this means our example PT (0.3W, 0.6Y and 1.2ZZ) will have the following operating characteristics: 0.3W indicates the PT will operate with an accuracy between 99.7-100.3% if: The operating system power factor is greater than 0.6

The secondary connected devices do not exceed 12.5VA and operate at a power factor greater than 0.7. 0.6Y indicates the PT will operate with an accuracy between 99.4-100.6% if: The operating power factor is greater than 0.6 The connected devices do not exceed 25VA and operate at a power factor greater than 0.85. 1.2ZZ means the PT will operate with an accuracy between 99.8-101.2% if: The operating power factor is greater than 0.6 The connected devices do not exceed 25VA and operate at a power factor greater than 0.85. II. III. Inspect physical and mechanical condition. The PT should be checked for any cracks or any other obvious damage that may have occurred during shipping or installation. Verify that all grounding connections provide contact. Use an ohmmeter or contact resistance test set to measure the resistance between the PT primary grounding connection and a known ground to ensure an electrical connection exists. Visually inspect the connection to ensure it is tight and protected from obvious physical damage. Use an ohmmeter or contact resistance test set to measure the resistance between the PT secondary grounding connection and ground to ensure an electrical connection is installed. Special attention is required to ensure that the PT secondaries of any connected group are grounded at one point only and that the ground connection cannot be easily removed while the PT is in service. (E.g. Grounding point made on the line side of test switches) Ensure (if possible) that multiple grounds do not occur when synchronizing systems are enabled.

IV. Verify correct operation of transformer withdrawal mechanism and grounding operation. When the PT is withdrawn ensure that there is no longer any connection with the primary electrical system. It is a good idea to remove all as a safety precaution to prevent back-feeding dangerous voltages into the system during testing. The fuses should not be replaced until all PT and control system testing is completed and the PT energization is imminent. Use an ohmmeter or contact resistance test set to measure the resistance between the PT primary and ground when in the fully withdrawn position to ensure the PT grounding device is operational. V. Verify correct primary and secondary fuse sizes. Inspect the fuses and ensure they are the sized correctly for the particular application and meet the design requirements. Typically E rated current limiting fuses are used to protect PT s. 2.0 Electrical Tests I. Perform insulation resistance tests winding to winding and each winding to ground. To test the insulation integrity you will need a megohmmeter or hipot rated to produce the specified maximum test voltage. The test voltage should NEVER exceed 1.6 times the PT rating unless authorized by the PT manufacturer. Use the following test procedure for PT insulation tests. a. Isolate all windings from ground. b. Install a jumper across each full winding. c. Connect the megohmmeter to one terminal of the H side of the PT and the negative to one side of the X side and to ground. d. Increase the voltage slowly to the test voltage and let stand for one minute. Monitor the insulation resistance during the test to ensure that reading is not linear and does not increase exponentially as the test voltage increases. Either condition could indicate insulation failure, poor insulation, and/or improper test connections. e. Record the insulation resistance, temperature, humidity, and equipment designation. f. Use the insulation resistance compensation Table 3 to determine the equivalent insulation resistance at 20 C. g. Check NETA ATS 99 Table 10.9 to ensure the 20 C equivalent resistance is not lower than the specified value or compare results to previous test results. Ensure previous results have been converted to equivalent 20 C resistances.

h. Repeat steps a. through g. exchanging primary and secondary connections to include all the following tests for 2 and 3 winding PTs. Use Figure 5 diagrams to help you visualize the connections. o 2 winding H X&G X H&G o 3 Winding H X&G (Guard Y) H Y&G (Guard X) X H&G (Guard Y) Y H&G (Guard X) X Y&G (Guard H) Figure 5

TABLE 3 Insulation Resistance Conversion Factors for Conversion of Test Temperature to 20ºC Temperature ºC ºF Multiplier Apparatus Containing Immersed Insulations Oil Apparatus Containing Insulations 0 32 0.25 0.40 5 41 0.36 0.45 10 50 0.50 0.50 15 59 0.75 0.75 20 68 1.00 1.00 25 77 1.40 1.30 30 86 1.98 1.60 35 95 2.80 2.05 40 104 3.95 2.50 45 113 5.60 3.25 50 122 7.85 4.00 55 131 11.20 5.20 60 140 15.85 6.40 65 149 22.40 8.70 70 158 31.75 10.00 75 167 44.70 13.00 80 176 63.50 16.00 Solid

II. Perform a polarity test on each transformer to verify the polarity marks or H1-X1 relationship as applicable. We describe the two polarity test methods available using the most basic equipment. a. To test polarity using DC voltage, a lantern battery and a voltmeter with an analog scale is required. Use the following steps for DC polarity testing as shown in Figure 6: i. Connect the positive of the voltmeter to the marked terminal of the high voltage side of the PT and the negative lead to the non-marked. ii. Calculated the expected voltage using the battery voltage and the PT ratio. (Battery voltage * PT ratio) if the expected voltage exceeds the battery rating; switch the battery to the primary side of the PT and voltmeter to the secondary side. Re-calculate the expected voltage and set the voltmeter scale accordingly. (Battery Voltage / PT ratio) iii. Connect the negative terminal of the battery to the non-polarity of the PT winding under test. Momentarily touch or connect the battery positive terminal to the polarity terminal of the PT winding under test. iv. Closely watch the needle or analog scale of the voltmeter. It should jump in the positive direction. This happens in a fraction of a second and the meter must be monitored very closely. If the voltmeter kicks in the positive direction the polarity marks are correct and if it kicks in the negative direction then the polarity marks are incorrect. v. Figure 6 b. To test polarity using ac voltage; a variac and voltmeter are required. Use the following steps to test for PT polarity using the AC method as shown in Figure 7.

i. Connect a variac across the primary winding of the PT. ii. Connect a voltmeter (VM1) across the primary PT winding and variac. iii. Connect a voltmeter (VM2) from the polarity mark of the H side to the nonpolarity mark of the X side. iv. Connect the non-polarity mark of the H side winding to the polarity mark of the X side winding. v. Increase the voltage to a known value. Calculate the expected value. ([VM1/PT ratio]+[vm1]) if VM2 displays the expected result, the PT polarity markings are correct. If VM2 is less than the expected result, the test connection or the PT polarity markings are incorrect. (Note: VM1 and VM2 can be 1 voltmeter switching between positions if the test voltage remains stable.) vi. Figure 7 III. Perform a turn s ratio test on all tap positions if possible. Testing the ratio of a PT is a simple test and only requires a variac and a voltmeter. Use the following procedure for PT ratio Testing: a. Connect the variac across the primary winding.

b. Increase the voltage to the test voltage. (Typically an easy multiple of the PT ratio e.g. 35:1V PT ratio = 35V) Calculate the expected secondary voltage. (Test voltage / PT Ratio) c. Measure the secondary voltage and compare to the expected result. d. After the ratio tests have been completed, ensure that the connection is left as specified. Note: Never energize the secondary winding and measure the primary winding as dangerous voltages could be created. Figure 8 All of the above-mentioned tests use the same principles as the fancy test equipment available today and should they ever fail (Because that NEVER happens) you can get your trusty voltmeter and variac and keep on testing. Credits: Figure 1: http://www.geindustrial.com/cwc/products?pnlid=5&id=kvvolt Figure 2: http://www.geindustrial.com/cwc/products?pnlid=5&id=sp-pwr Westinghouse Technical Data Sheet 45-910; Instrument Transformers Technical Data, Accuracy standards Index ; December 1945 Northern Alberta Institute of Technology; Electrical Engineering Technology Program; Principle of Operation of Potential Transformers.