6 Buck Boost Transformers

Size: px
Start display at page:

Download "6 Buck Boost Transformers"

Transcription

1 6 uck oost Transformers uck-oost transformers are small, single phase, dry type distribution transformers designed and shipped as insulating/isolating transformers. They have a dual voltage primary and a dual voltage secondary. These transformers can be connected for a wide range of voltage combinations. The most common use is to buck (lower) or boost (raise) the supply voltage a small amount, usually 5 to 27%. uck-boost transformers are in compliance with NEC rticle 210.9, Exception 1 when field connected as an autotransformer. The major advantages of uck-boost transformers are their low cost, compact size and light weight. They are also more efficient and cost less than equivalent isolation transformers. When connected as an autotransformer, they can handle loads up to 20 times the nameplate rating. buck-boost transformer is the ideal solution for changing line voltage by small amounts. When a buck-boost has the primary and secondary windings connected, per recommended instructions, it becomes an autotransformer. Now, only the secondary windings are transforming voltage and current. The majority of the kv load passes directly from the supply to the load. This is the reason buck-boost transformers can supply a load with a much larger kv rating than the nameplate indicates. Low voltage lighting control applications SolaHD buck-boost transformers are designed to supply power to low voltage lighting circuits, control panels or other systems requiring 12, 16, 24, 32, or 48 Volts. When connected as an insulating transformer (by following the wiring diagram located after the specification tables on the inside of the transformer case), the transformer s capacity matches the nameplate kv rating. SolaHD buck-boost transformers are also suited for low voltage landscape lighting. They are UL Listed for outdoor service and their compact size makes them the perfect solution for providing power to accent lighting applications. Electrical diagrams are shown at the end of this section. Use dimmers on the output of the transformer that are designed and rated for use with magnetic loads. We strongly recommend contacting the dimmer manufacturer for advice on your specific lighting application. Certifications and Compliances Listed - UL CS C22.2 No. 66 ccessories Surge Protective Devices ctive Tracking ilters Selection Steps 1. Line easure the supply voltage with a voltmeter. 2. equired for the Load Check the load equipment to determine the voltage requirement. 3. kv or mpere ating of the Load ind either the load kv or the load amperage requirements. This information is listed on the nameplate of the load equipment. E requency Either 50 or 60 Hz. The frequency of the transformer must match the frequency of the load. 5. Number of Phases Single or three phase line and load must match. ( transformer cannot convert single to three phase.) common application is to make a single phase connection from a three phase supply by using one phase of the three phase supply circuit. e careful not to overload that phase of the three phase supply. or buck-boost applications the supply must provide load kv not just the nameplate rating of the buck-boost. efer to the Selection Tables on the following pages. 230

2 uck oost Transformers 6 Three phase, buck-boost applications require two or three transformers. Check the equired column of the Three Phase Selection Tables for the exact quantity. using uck-oost Transformers or determining the correct size of breaker or fuse for a given range of input or output ampere ratings, refer to Section 450.4, of the National Electric Code (NEC). Where an overcurrent protection device is required, the electrical connections and selection tables will reference appropriately. Using the Selection Tables 1. Determine if you are trying to oost (raise) or uck (lower) your voltage. Select an input/output voltage combination that comes closest to matching your application from the appropriate single or three phase charts on the following pages. 2. ove across your selected input/output voltage row to the amperage or kv rating closest to, but greater than the rating required by your load. 3. eading the top of the column will give you the catalog number of the exact buck-boost transformer you need. See the Specification Tables on the next page. 4. Connect the transformers according to the diagram indicated. See the Electrical s section at the end of this section. diagrams are packed with each transformer. Overcurrent devices OC-1a and OC-1b are shown correctly installed in accordance with NEC Locating an overcurrent device in series with the shunt winding anywhere between and is not permitted. The shunt winding is the winding common to both the input and the output circuits. 231

3 6 uck oost Transformers Specification Tables Group x 240 Volt Primary, 12/24 Volt Secondary KV aximum Secondary mperage 12 V 24 V Height in (mm) Width in (mm) Non-Encapsulated - 50/60 Hz, Single Phase Depth in (mm) pprox. Ship Weight lbs (kg) 0.05 HS (152.4) 4.00 (101.6) 3.00 (76.2) 2.0 (0.91) HS (152.4) 4.00 (101.6) 3.00 (76.2) 4.0 (1.82) HS (190.5) 4.00 (101.6) 4.00 (101.6) 5.0 (2.27) HS (190.5) 4.00 (101.6) 4.00 (101.6) 8.0 (3.64) 2 1 Encapsulated - 60 Hz, Single Phase 0.5 HS (254.0) 6.00 (152.4) 5.00 (127.0) 22.0 (10.00) HS (254.0) 6.00 (152.4) 5.00 (127.0) 27.0 (12.27) HS (254.0) 6.00 (152.4) 5.00 (127.0) 28.0 (12.73) HS (304.8) (254.0) 7.00 (177.8) 38.0 (17.27) HS (304.8) (254.0) 7.00 (177.8) 45.0 (20.45) HS (304.8) (254.0) 7.00 (177.8) 55.0 (25.00) HS (431.8) (355.6) 9.00 (228.6) (45.45) HS (431.8) (355.6) 9.00 (228.6) (61.36) 4 1 Design Style Elec Conn Group x 240 Volt Primary, 16/32 Volt Secondary KV aximum Secondary mperage 16 V 32 V Height in (mm) Width in (mm) Non-Encapsulated - 50/60 Hz, Single Phase Depth in (mm) pprox. Ship Weight lbs (kg) 0.15 HS (203.2) 4.00 (101.6) 4.00 (101.6) 6.0 (2.73) HS (203.2) 4.00 (101.6) 4.00 (101.6) 8.0 (3.64) 2 2 Encapsulated - 60 Hz, Single Phase 0.5 HS (254.0) 6.00 (152.4) 5.00 (127.0) 22.0 (10.00) HS (254.0) 6.00 (152.4) 5.00 (127.0) 27.0 (12.27) HS (254.0) 6.00 (152.4) 5.00 (127.0) 28.0 (12.73) HS (304.8) (254.0) 7.00 (177.8) 38.0 (17.27) HS (304.8) (254.0) 7.00 (177.8) 45.0 (20.45) HS (304.8) (254.0) 7.00 (177.8) 55.0 (25.00) HS (431.8) (355.6) 9.00 (228.6) (45.45) HS (431.8) (355.6) 9.00 (228.6) (61.36) 4 2 Design Style Elec Conn Note: Weights and dimensions may change and should not be used for construction purposes. 232

4 uck oost Transformers 6 Specification Tables continued Group x 480 Volt Primary, 24/48 Volt Secondary KV Catalog Number aximum Secondary mperage 24 V 48 V Height in (mm) Width in (mm) Non-Encapsulated - 50/60 Hz, Single Phase Depth in (mm) pprox. Ship Weight lbs (kg) 0.15 HS (203.2) 4.00 (101.6) 3.00 (76.2) 5.0 (2.27) HS (203.2) 4.00 (101.6) 3.00 (76.2) 8.0 (3.64) 2 3 Encapsulated - 60 Hz, Single Phase 0.5 HS (203.2) 6.00 (152.4) 5.00 (127.0) 22.0 (10.00) HS (254.0) 6.00 (152.4) 5.00 (127.0) 27.0 (12.27) HS (254.0) 6.00 (152.4) 5.00 (127.0) 28.0 (12.73) HS (304.8) (254.0) 7.00 (177.8) 38.0 (17.27) HS (304.8) (254.0) 7.00 (177.8) 45.0 (20.45) HS (304.8) (254.0) 7.00 (177.8) 55.0 (25.00) HS (431.8) (355.6) 9.00 (228.6) (45.45) HS (431.8) (355.6) 9.00 (228.6) (61.36) 4 3 Note: Weights and dimensions may change and should not be used for construction purposes. Design Style Elec Conn Electrical s for Low pplications = Earth Ground Volt Primary, 12/24 Volt Secondary Taps: None Volt Primary, 16/32 Volt Secondary Taps: None Volt Primary, 24/48 Volt Secondary Taps: None Primary Interconnect Connect Lines To 240 to & 120 Secondary to to Interconnect & Connect Lines To 24 to & to to to to HS19 and S19 Series -- & Primary Interconnect Connect Lines To 240 to & 120 Secondary to to Interconnect & Connect Lines To 32 to & to to to to HS20 and S20 Series -- & Primary Interconnect Connect Lines To 480 to & 240 Secondary to to Interconnect & Connect Lines To 48 to & to to to to HS22 and S22 Series -- & 233

5 6 uck oost Transformers Design Styles Custom Design Styles Style 2 - Non-Encapsulated Style 5 - Encapsulated vailable for all encapsulated kv sizes (or Type 4, 12 and 4) Style 3 - Encapsulated Style 4 - Encapsulated 234

6 uck oost Transformers 6 Selection Tables: Single Phase Table 1: Using Group 1 (120 x 240 V Primary, 12/24 V Secondary) Transformers eq d D C D1 218 ** D C1 132 ** ** D2 252 ** C2 264 ** D2 pplication HS1950 HS19100 HS19150 HS19250 HS19500 HS19750 HS191 OOSTING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size UCKING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size * or alternate electrical connection diagrams, refer to the section immediately following the selection tables. ** Shaded items are 60 Hz only (ll other ratings shown are 50/60 Hz). 235

7 6 uck oost Transformers Selection Tables: Single Phase Table 1: Using Group 1 (120 x 240 V Primary, 12/24 V Secondary) Transformers eq d D C D1 218 ** D C1 132 ** ** D2 252 ** C2 264 ** D2 pplication HS191.5 HS192 HS193 HS195 HS197.5 OOSTING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size UCKING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size * or alternate electrical connection diagrams, refer to the section immediately following the selection tables. ** Shaded items are 60 Hz only (ll other ratings shown are 50/60 Hz). 236

8 uck oost Transformers 6 Selection Tables: Single Phase Table 2: Using Group 2 (120 x 240 V Primary, 16/32 V Secondary) Transformers eq d D C D C1 240 ** D1 136 ** ** D2 256 ** C2 272 ** D2 pplication HS20150 HS20250 HS20500 HS20750 HS201 OOSTING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size UCKING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size * or alternate electrical connection diagrams, refer to the section immediately following the selection tables. ** Shaded items are 60 Hz only (ll other ratings shown are 50/60 Hz). 237

9 6 uck oost Transformers Selection Tables: Single Phase Table 2: Using Group 2 (120 x 240 V Primary, 16/32 V Secondary) Transformers eq d D C D C1 240 ** D1 136 ** ** D2 256 ** C2 272 ** D2 pplication HS201.5 HS202 HS203 HS205 HS207.5 OOSTING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size UCKING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size * or alternate electrical connection diagrams, refer to the section immediately following the selection tables. ** Shaded items are 60 Hz only (ll other ratings shown are 50/60 Hz). 238

10 uck oost Transformers 6 Selection Tables: Single Phase Table 3: Using Group 3 (240 x 480 V Primary, 24/48 V Secondary) Transformers eq d ** D C D D1 458 ** C1 277 ** C2 418 ** D2 504 ** C2 528 ** D2 pplication HS22150 HS22250 HS22500 HS22750 HS221 OOSTING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size UCKING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size * or alternate electrical connection diagrams, refer to the section immediately following the selection tables. ** Shaded items are 60 Hz only (ll other ratings shown are 50/60 Hz). 239

11 6 uck oost Transformers Selection Tables: Single Phase Table 3: Using Group 3 (240 x 480 V Primary, 24/48 V Secondary) Transformers eq d ** D C D D1 458 ** C1 277 ** C2 418 * D2 504 ** C2 528 ** D2 pplication HS221.5 HS222 HS223 HS225 HS227.5 OOSTING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size UCKING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size * or alternate electrical connection diagrams, refer to the section immediately following the selection tables. ** Shaded items are 60 Hz only (ll other ratings shown are 50/60 Hz). 240

12 uck oost Transformers 6 Selection Tables: Three Phase Table 4: Using Group 1 (120 x 240 V Primary, 12/24 V Secondary) Transformers eq d E J1 228 ** E L E ** E2 264 ** pplication HS1950 HS19100 HS19150 HS19250 HS19500 HS19750 HS191 OOSTING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size UCKING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size * or alternate electrical connection diagrams, refer to the section immediately following the selection tables. ** Shaded items are 60 Hz only (ll other ratings shown are 50/60 Hz). 241

13 6 uck oost Transformers Selection Tables: Three Phase Table 4: Using Group 1 (120 x 240 V Primary, 12/24 V Secondary) Transformers eq'd pplication HS191.5 HS192 HS193 HS195 HS E J1 228 ** E L E ** E2 264 ** OOSTING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size UCKING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size * or alternate electrical connection diagrams, refer to the section immediately following the selection tables. ** Shaded items are 60 Hz only (ll other ratings shown are 50/60 Hz). 242

14 uck oost Transformers 6 Selection Tables: Three Phase Table 5: Using Group 2 (120 x 240 V Primary, 16/32 V Secondary) Transformers eq'd pplication HS20150 HS20250 HS20500 HS20750 HS E J E L E ** E2 272 ** OOSTING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size UCKING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size * or alternate electrical connection diagrams, refer to the section immediately following the selection tables. ** Shaded items are 60 Hz only (ll other ratings shown are 50/60 Hz). 243

15 6 uck oost Transformers Selection Tables: Three Phase Table 5: Using Group 2 (120 x 240 V Primary, 16/32 V Secondary) Transformers eq'd pplication HS201.5 HS202 HS203 HS205 HS E J E L E ** E2 272 ** OOSTING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size UCKING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size * or alternate electrical connection diagrams, refer to the section immediately following the selection tables. ** Shaded items are 60 Hz only (ll other ratings shown are 50/60 Hz). 244

16 uck oost Transformers 6 Selection Tables: Three Phase Table 6: Using Group 3 (240 x 480 V Primary, 24/48 V Secondary) Transformers eq'd G G E K K E G K K2 504 ** E2 528 ** pplication HS22150 HS22250 HS22500 HS22750 HS221 OOSTING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size UCKING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size * or alternate electrical connection diagrams, refer to the section immediately following the selection tables. ** Shaded items are 60 Hz only (ll other ratings shown are 50/60 Hz). 245

17 6 uck oost Transformers Selection Tables: Three Phase Table 6: Using Group 3 (240 x 480 V Primary, 24/48 V Secondary) Transformers eq'd G G E K K E G K K2 504 ** E2 528 ** pplication HS221.5 HS222 HS223 HS225 HS227.5 OOSTING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size UCKING kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size kv Load mps use Size * or alternate electrical connection diagrams, refer to the section immediately following the selection tables. ** Shaded items are 60 Hz only (ll other ratings shown are 50/60 Hz). 246

18 uck oost Transformers 6 lternate Electrical s for uck-oost pplications Diagram 1 oosting Diagram 1 oosting Diagram C1 oosting Diagram 2 ucking Diagram 2 ucking Diagram C2 ucking The O symbol shown on these connection diagrams indicates where fuses or breakers should be field installed for line to neutral applications. or line to line applications, fuses or breakers should be installed on both lines. pplication Note: On all auto-wye connections, the source neutral must be present and connected to the transformer bank. If source neutral is not present, do not use an auto-wye connection. 247

19 6 uck oost Transformers lternate Electrical s for uck-oost pplications OPEN DELT OPEN DELT Diagram D1 oosting Diagram E1 oosting Diagram 1 oosting OPEN DELT OPEN DELT Diagram D2 ucking Diagram E2 ucking Diagram 2 ucking 248

20 uck oost Transformers 6 lternate Electrical s for uck-oost pplications OPEN DELT OPEN DELT UTO-WYE CONNECTION C Diagram G1 oosting Diagram oosting Diagram J1 oosting OPEN DELT OPEN DELT UTO-WYE CONNECTION C Diagram G2 ucking Diagram ucking Diagram J2 ucking 249

21 6 uck oost Transformers lternate Electrical s for uck-oost pplications UTO-WYE CONNECTION C UTO-WYE CONNECTION C UTO-WYE CONNECTION C Diagram K1 oosting Diagram L1 oosting Diagram 1 oosting UTO-WYE CONNECTION C UTO-WYE CONNECTION C UTO-WYE CONNECTION C Diagram K2 ucking Diagram L2 ucking Diagram 2 ucking 250

22 uck oost Transformers 6 pplication Note pplication Limitations with uck-oost Transformers 1. uck-oost transformer cannot be used to develop a three phase, four wire wye circuit from a three phase, three wire delta circuit. delta to wye connection does not supply enough current carrying capability to provide for unbalanced currents flowing in the neutral wire of the four wire circuit. The neutral created is not stable and under load will not deliver desired line to neutral voltages. This connection would also be in violation of the National Electric Code, rticle uck-oost transformers cannot be used in a closed delta connection. closed delta requires more kv capacity than a wye or an open delta connection, plus phase shifting comes into play on the output side. 3. uck-oost transformers should not be used to correct for voltage drop on a long circuit run where the load fluctuates. drop varies with the load and buck-boost transformers are connected for a specific voltage change. If a buck-boost transformer was used to correct voltage drop during peak loading conditions, high voltages may result under light load conditions. This could be equally detrimental to the load and possibly pose safety hazards. 4. uck-oost transformers cannot be used to create a 240/120 Volt, single phase service from a 208Y/120 Volt three phase supply. Two problems that would occur:. Two neutrals would exist on the same circuit. Since neutrals must be grounded according to the National Electric Code, a short circuit would be created.. Unbalanced line to output neutral voltages would be created; one line would read 120 Volts, the other 130+ Volts. What is a uck-oost transformer and why is it used? Isolation transformers have separate primary and secondary windings, electrically insulated and isolated from one another. With a relatively high voltage primary (typically 120, 240 or 480 Volts) and a relatively low voltage secondary (typically 12, 16, 24, 32 or 48 Volts), buck-boost transformers are designed to be field connected as autotransformers. These are transformers with one continuous winding, a portion of which is jointly shared between the input and the output. No electrical isolation is present in an autotransformer. uck-oost transformers have two major uses: 1. When field connected as an autotransformer, they can be used to uck (lower) or oost (raise) available line voltage in the range of 5 to 27% and at a kv rating many times that listed on the transformer nameplate. 2. When left as an isolation transformer, they can be used to supply power to low voltage circuits at the nameplate rating listed. The importance of altering available line voltage. Electrical equipment is designed to operate at maximum efficiency at a specific standard supply voltage. Your voltage may not be at the standard supply voltage level. Causes can be proximity to a large utility transformer, losses in the line voltage due to loads on that circuit, or a difference between the standard supply voltage available and the standard supply voltage needed to run the equipment. Normally the problem is having low voltage available. Low voltage on a circuit, even as little as 5% lower can cause a decrease in incandescent light output, and a decrease in resistive heat output. With motors low voltage can cause a decrease in motor torque, an increase in motor amperage requirements, an increase in motor temperature and decrease in motor life expectancy. 251

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80 Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

Buck - Boost Transformers

Buck - Boost Transformers Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single

More information

JEFFERSON ELECTRIC, INC. Buck-Boost Transformer Application Manual

JEFFERSON ELECTRIC, INC. Buck-Boost Transformer Application Manual JEFFERSON ELECTRIC, INC. Buck-Boost Transformer Application Manual Revised on February 15, 2012 Table of Contents I. Introduction... 2 II. Choosing the Proper Transformer... 2 III. Rapid Selector Charts...

More information

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

3) What is the difference between Insulating, Isolating, and Shielded Winding transformers? Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer

More information

5 Non-Ventilated Automation Transformers

5 Non-Ventilated Automation Transformers 5 Non-Ventilated Automation Transformers Automation Transformers - Non-Ventilated 50 VA to 45 SolaHD encapsulated transformers are rated for Hazardous Locations as well as harsh industrial environments.

More information

5 Non-Ventilated Automation Transformers

5 Non-Ventilated Automation Transformers 5 Non-Ventilated Automation Transformers Automation Transformers - Non-Ventilated 50 VA to 45 SolaHD encapsulated transformers are rated for Hazardous Locations as well as harsh industrial environments.

More information

Distribution Dry Type Transformers

Distribution Dry Type Transformers Distribution Dry Type s Sentron Power Centers Bolt-in Breaker Option The same economical space saving package, NEMA 3R rated enclosure, and UL listed transformer of the original Sentron Power Center but

More information

ACME ELECTRIC CORPORATION PDPD-01

ACME ELECTRIC CORPORATION PDPD-01 4815 West Fifth Street Lumberton, NC 28358 (910) 738-1121 Inside NC (800) 334-5214 Outside NC (910) 739-0024 Fax www.acmepowerdist.com ACME ELECTRIC CORPORATION PDPD-01 ATD-101-1001 Revised-02/ 06 Printed

More information

Rotary Phase Converters

Rotary Phase Converters FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON

More information

Three Phase Transformers

Three Phase Transformers Three Phase Transformers ontents Three Phase - General Purpose... 26 Three Phase - General Purpose Scott ed... 30 Three Phase - dditional ombinations vailable... 31 Three Phase - ion Diagrams... 32 Series

More information

Distribution Dry Type Transformers

Distribution Dry Type Transformers 8 TRASFORMERS Distribution Dry Type Transformers Table (Contact Sales office for List Price) (commonly used) 1a. 115 C Rise F 1b. 80 C Rise B 4. Wall Brackets1 W 6. Low noise XdB below std. LX Type bg

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information

CompactLogix Power Supplies Specifications

CompactLogix Power Supplies Specifications Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,

More information

Single Phase Three Phase Single Phase Export Model Transformers Single Phase Buck and Boost Transformers Stainless Steel Enclosed Transformers

Single Phase Three Phase Single Phase Export Model Transformers Single Phase Buck and Boost Transformers Stainless Steel Enclosed Transformers Transformers Selection Guide Description Page Three Phase Single Phase Aluminum, Copper, 150 Degree Rise Aluminum, Copper, 115 Degree Rise Aluminum, Copper, 80 Degree Rise Epoxy Encapsulated Aluminum,

More information

Motor Protection Voltage Unbalance and Single-Phasing

Motor Protection Voltage Unbalance and Single-Phasing Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the

More information

How To Protect A Motor From Overcurrent

How To Protect A Motor From Overcurrent Phase ailure elays Type PS and PD Class 8430 Catalog 04 CONTENTS Description.....................................................Page Product Description and Definitions......................................

More information

REGULINE 600VA / 1000VA REGULATOR USER MANUAL

REGULINE 600VA / 1000VA REGULATOR USER MANUAL REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate

More information

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING There are several ways to wire multiple batteries to achieve the correct battery voltage or capacity for a particular DC

More information

Low Voltage Transformers Sealed, General Purpose, Dry Type

Low Voltage Transformers Sealed, General Purpose, Dry Type Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

INDUCTION REGULATOR. Objective:

INDUCTION REGULATOR. Objective: INDUCTION REGULATOR Objective: Using a wound rotor induction motor an Induction Regulator, study the effect of rotor position on the output voltage of the regulator. Also study its behaviour under load

More information

600 Volt Class Transformers

600 Volt Class Transformers Transformers ISO 9001:2008 REGISTERED 11 11 Table of Contents - Transformers Page Full Load Current Tables... 12 General Information, Standards, Testing... 13 Selection and Application Considerations...

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Three-phase AC circuits

Three-phase AC circuits Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Guidelines on the Short Circuit Current Rating for Industrial Control Panels usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A

More information

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff

More information

Surgelogic Surge Protective Device (SPD)

Surgelogic Surge Protective Device (SPD) Surgelogic Surge Protective Device () EB, EM, and HW Series atalog 1310T0202R05/09 2009 lass 1310 OTETS Description............................................. Page Product Description...........................................2

More information

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE WHITE PAPER WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE EXPLANATION AND ASSISTANCE FOR APPLYING SOLID STATE SOFT STARTERS IN TRADITIONAL REDUCED VOLTAGE APPLICATIONS Introduction..............................................................2

More information

Transformer Questions & Answers

Transformer Questions & Answers Transformer Questions & Answers. What is a transformer and how does it work? A transformer is an electrical apparatus designed to convert alternating current from one voltage to another. It can be designed

More information

The Different Types of AC Power Connectors in North America

The Different Types of AC Power Connectors in North America The Different Types of AC Power Connectors in North America White Paper #20 Executive Summary A confusing array of AC power plugs and receptacles exist to deliver power to various electronic loads. This

More information

TRANSFORMERS. Unit 14 OBJECTIVES

TRANSFORMERS. Unit 14 OBJECTIVES Unit 14 TRANSFORMERS OBJECTIVES After studying this unit, the student will be able to state the purpose of a transformer. explain the principle of mutual induction. determine the output voltage of a transformer

More information

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D 7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values

More information

8146/5 Series Breaker Panelboards

8146/5 Series Breaker Panelboards 8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division

More information

12VDC MAGNETIC LED DIMMABLE POWER SUPPLIES SPEC SHEET DIGEST

12VDC MAGNETIC LED DIMMABLE POWER SUPPLIES SPEC SHEET DIGEST 12VDC MAGNETIC ED DIMMABE POER SUPPIES SPEC SEET DIGEST TM-30-DIM TM-50-DIM T-60-DIM TM100-DIM TM200-DIM TM300-DIM iring Diagram for TM-50-DIM and TM-100-DIM ED 12VDC MAGNETIC DIMMABE 30 POER SUPPY Smallest

More information

WINDING RESISTANCE TESTING

WINDING RESISTANCE TESTING WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

Power Supplies 3. SDN-P DIN Rail Series

Power Supplies 3. SDN-P DIN Rail Series SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.

More information

Variable Transformers Product Design & Engineering Data

Variable Transformers Product Design & Engineering Data Variable Transformers Product Design & Engineering Data Product Design & Engineering Data Type 1010B Cutaway General Information STACO ENERGY PRODUCTS CO. is a leading manufacturer of variable transformers,

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

Manual motor starter MS116

Manual motor starter MS116 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6 Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of

More information

Continuous Power... Continuous Protection

Continuous Power... Continuous Protection Series 165 We Keep Your Power On Continuous Power... Continuous Protection An Automatic Transfer Switch helps prevent... Your business or home from losing power during bad weather or utility power equipment

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

CHAPTER 2 EXAMPLES AND TABLES

CHAPTER 2 EXAMPLES AND TABLES CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of

More information

12V Dimmable Driver EL-TMDRVR

12V Dimmable Driver EL-TMDRVR Elemental LED, LLC website: elementalled.com 11 9 5 P a r k A v e., S u i t e 2 11 Emeryville, CA 94608 toll free 877.564.5051 fax 510.740.4457 12V Dimmable Driver EL-TMDRVR ETL Listed #4001928 CSA Listed

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

Mini Power-Zone Unit Substation

Mini Power-Zone Unit Substation Catalog 7440CT0901 2009 Class 7440 CONTENTS Description............................................. Page Product Description...........................................2 General Information...........................................3

More information

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

Surgelogic Surge Protection Device EMA, EBA, and HWA Series

Surgelogic Surge Protection Device EMA, EBA, and HWA Series Surgelogic Surge Protection Device EM, EB, and HW Series atalog 1310T0202R5/07 2007 lass 1310 OTETS Description..............................................Page Product Descriptions..........................................

More information

32VFD Variable Frequency Drives for Centrifugal Chillers

32VFD Variable Frequency Drives for Centrifugal Chillers 32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to

More information

Product Guide AC Voltage Control Devices. Guide Guide. Popular Variable Transformers and AC Power Supplies. www.stacoenergy.com

Product Guide AC Voltage Control Devices. Guide Guide. Popular Variable Transformers and AC Power Supplies. www.stacoenergy.com Popular Variable Transformers and AC Power Supplies Product Guide AC Voltage Control Devices Guide Guide Your Tailored Power Solutions Provider TM Staco Energy Products Co. has been a leading manufacturer

More information

Electrical system concerns

Electrical system concerns ISE, Inc. 10100 Royalton Rd. Cleveland, OH 44133 USA Tel: (440) 237-3200 Fax: (440) 237-1744 http://instserv.com VOLTAGE REGULATORS & POWER CONDITIONERS The AVR voltage regulator and PLC power conditioner

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

How To Test A Power Distribution Unit

How To Test A Power Distribution Unit PDUAC3U SERIES AC POWER DISTRIBUTIO UITS www.unipowerco.com Manual o. PDUAC3U-1 pduac3u-man-rev1-1015.indd 2015 UIPOWER LLC All Rights Reserved ORTH AMERICA 3900 Coral Ridge Drive, Coral Springs, Florida

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Transformer Calculations

Transformer Calculations Transformer Calculations Transformers Transformers are one of the most basic yet practical devices used today. No matter where you are there is always a transformer nearby. They are used throughout alternating-current

More information

GRX-PWM Pulse Width Modulation Interface

GRX-PWM Pulse Width Modulation Interface Pulse Width Modulation Interface pwm1 05.30.06 COOPERSBURG, PA 18036 U.S.A. Coopersburg, G 8 BR PA 18036 U.S.A. 144317 GRXTVI 19 P10 CB 0791275 Ratings Load T ype Switched Lowvoltage Load Type Switched

More information

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060 4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,

More information

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer 101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module

More information

ST Style Generator. Owners/Operators Manual

ST Style Generator. Owners/Operators Manual ST Style Generator Owners/Operators Manual LLC 216 Airport Rd NE Milledgeville, GA 31061 478-453-9358-Office 478-457-5524- Tom Cell 478-251-2914- Chris Cell Table of Contents Page 2. Table of Contents

More information

Single-Phase AC Synchronous Generator

Single-Phase AC Synchronous Generator ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description

More information

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional

More information

VOLTAGE REGULATOR AND PARALLEL OPERATION

VOLTAGE REGULATOR AND PARALLEL OPERATION VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by

More information

Low Voltage Transformer Through-Fault Protection: A System Approach

Low Voltage Transformer Through-Fault Protection: A System Approach Data Bulletin 7400DB1001 Nashville, TN USA Low Voltage Transformer Through-Fault Protection: A System Approach Introduction Low Voltage Transformer Protection Criteria NEC Article 450 Transformers and

More information

Industrial Control Transformers

Industrial Control Transformers Industrial Control Transformers Sizing...158 Selection Chart...159 SBE 55 C ise, Copper, Encapsulated, 50 VA - 1000 VA... 161 5 SBE Accessories... 165 SBE 55 C ise, Copper Open Style, 1500 VA - 5000 VA...

More information

6/14/02 Chapter 2: Basic Electrical Power Fundamentals 1/6

6/14/02 Chapter 2: Basic Electrical Power Fundamentals 1/6 Basic Electrical Power Fundamentals LOAD REFERENCE Kilowatts Kilovolt amps Power Factor PF Motors KW KVA USE NEC 430-148 KW < KVA.6-.95 and 430-150 to find current for given HP Indancescant Lighting USE

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

Services. Three Phase Service

Services. Three Phase Service Services Primary Service vs Secondary Service Overhead vs Underground Common Service Types Three Phase Wye Closed Open Delta Corner Grounded Center Tapped Open Single Phase Three Phase Service Wye Delta

More information

Short-circuit current rating (SCCR) of. industrial control panels. NEC Article 409 and UL 508A

Short-circuit current rating (SCCR) of. industrial control panels. NEC Article 409 and UL 508A Short-circuit current rating (SCCR) of industrial control panels NEC Article 409 and UL 508A Short-circuit current rating (SCCR) of industrial control panels 1 Introduction 2 Overview of NEC Article 409

More information

PHASED OUT. Digital dimmable ballasts for fluorescent lamps ECO series. PCA TCL ECO, 18 80 W Compact and T5c fluorescent lamps

PHASED OUT. Digital dimmable ballasts for fluorescent lamps ECO series. PCA TCL ECO, 18 80 W Compact and T5c fluorescent lamps Product description Noise-free precise control via DSI signal or switchdim CELMA energy class A1 1) Interfaces DSI switchdim Integrated SMART-Interface Functions Optimum filament heating in any dimmer

More information

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Instructions CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Catalog Number 2100-SD1 Description The Bulletin 2100 smoke detector unit is a 0.5 space factor unit for use in Bulletin

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

Three-Phase Electric Power Distribution for Computer Data Centers

Three-Phase Electric Power Distribution for Computer Data Centers Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of

More information

Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility

Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility Catalog 2800CT1001R02/13 2013 Class 2800 CONTENTS Description............................................ Page 2 Indoor Charging

More information

Actuator-Sensor-Interface

Actuator-Sensor-Interface Selection and ordering data Design Order No. Price Pack 3RX9 307-0AA00 3RX9 307-1AA00 4FD5 213-0AA10-1A 3RX9 305-1AA00 3RX9 306-1AA00 Single output IP 65 current 2.4 A Rated input voltage DC 24 V current

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

Definition AC Power Distribution

Definition AC Power Distribution COMMON AC POWER DISTRIBUTION CONFIGURATIONS The input voltage needed to power electronic equipment is provided by the manufacture in the product specifications. Matching this requirement to the facility

More information

Industrial Control Power Transformers

Industrial Control Power Transformers Class MT Features Epoxy-encapsulated (50 5000); Completely seals the transformer coils against moisture, dust, dirt and industrial contaminants for maximum protection in hostile and industrial environments

More information

Rule 5.500 Fast Track Analysis for National Life Insurance Co.

Rule 5.500 Fast Track Analysis for National Life Insurance Co. Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION

More information

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

Figure. 1 - Split Phase 240/120V circuit (180 phase shift) This technical note describes the option of connecting the 60Hz XW Inverter/Charger to a three-phase source by using a transformer to convert the AC source to split-phase 240/120V. INTRODUCTION: Split-phase

More information

Type SA-1 Generator Differential Relay

Type SA-1 Generator Differential Relay ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes

More information

UNIVERSITY OF WATERLOO ELECTRICAL & COMPUTER ENGINEERING DEPARTMENT ME269 ELECTROMECHANICAL DEVICES AND POWER PROCESSING.

UNIVERSITY OF WATERLOO ELECTRICAL & COMPUTER ENGINEERING DEPARTMENT ME269 ELECTROMECHANICAL DEVICES AND POWER PROCESSING. UNIVERSITY OF WATERLOO ELECTRICAL & COMPUTER ENGINEERING DEPARTMENT ME269 ELECTROMECHANICAL DEVICES AND POWER PROCESSING. Group # First Name Last Name UserID @uwaterloo.ca Experiment #3: DIRECT CURRENT

More information

ADM1TE 5/30A DIN rail single phase two wire energy meter

ADM1TE 5/30A DIN rail single phase two wire energy meter ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.

More information

How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc.

How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc. 1 How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc. The territory of high-performance motor control has

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

Tips for connecting 24-volt power

Tips for connecting 24-volt power Digital Designer s Guide Application NoteAN0604D Revision B Tips for connecting 24-volt power This application note covers choosing a transformer and connecting 24 volt AC power to a KMC Controls DDC controller.

More information

KEYBOARD EXTENDED RANGE. Sixty Owner, s Manual P/N 049254

KEYBOARD EXTENDED RANGE. Sixty Owner, s Manual P/N 049254 THE SOUND THAT CREATES LEGENDS KEYBOARD EXTENDED RANGE Sixty Owner, s Manual P/N 049254 INTRODUCTION Your new Fender KXR 60 Keyboard Amplifier is the result of Fender s ongoing dialog with many of today

More information