Motor Control Motor Overload Protection

Similar documents
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

101 BASICS SERIES LEARNING MODULE 19: STARTERS AND CONTACTORS. Cutler-Hammer

Motor Protection Voltage Unbalance and Single-Phasing

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Sentron Series Circuit Breakers

EET272 Worksheet Week 8

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

Electrical Symbols and Line Diagrams

MOTOR PROTECTION AGAINST SINGLE-PHASING

AC motor control circuits

Programming A PLC. Standard Instructions

Comparison of NEMA and IEC schematic diagrams

Low Voltage Fuses For Motor Protection

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Circuit Breakers. NRC Series. NRC Series

E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.

Motor Control V12-T13-2 V12-T13-72 V12-T13-76 V12-T13-87

Visit us on the web:

WE-350 Series ¼ Turn Electric Actuator

Agilent Technologies. Troubleshooting Three-Phase AC Motors with U1210 Series Handheld Clamp Meters. Application Note

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold C

CONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page Phase Simplex Page 8-13

How To Protect A Motor From Overcurrent

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

INSTALLATION & SERVICE MANUAL. Display Panel

, User s Manual

Electrical Resistance Resistance (R)

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

Three-phase AC circuits

Type SA-1 Generator Differential Relay

Cam switches. Page. Overview 4-2. ON-OFF switches, main switches, maintenance switches 4-3. Changeover switches, reversing switches 4-5

Diesel Engine Driven Generators Page 1 of 6

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Reversing starter circuit for single phase induction motors Updated 1 st September 2008

3BASIC RELAY INSTRUCTIONS

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Heavy Duty Control. Catalog Numbering System. General 8/47. Siemens Industry, Inc. Industrial Controls Catalog. 48 Overload Size

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

Rotary Phase Converters

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.

Installation, Operation and Maintenance Manual

SECTION VARIABLE FREQUENCY DRIVES

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER

Electronic overload relay EF19 and EF45

Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Electronic overload relay EF65, EF96 and EF146

BG or BGE Brake Rectifier

Industrial Automation Commonly-Used Terms

Parts list and Notes for making a 10 hp 240V single phase to 240V 3-phase converter.

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations

INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Why and How we Use Capacity Control

FLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

E2 Series Electric Furnaces

Circuit Breakers. Next Generation of Protection Capabilities

Electrical Grounding. Appendix C

ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual

WHITE PAPER MOTOR PROTECTION. The Importance of Effective Motor and Motor Circuit Protection

ACS-30-EU-EMDR-10-MOD

D-Line Contactors, Overload Relays and Accessories

Three-Phase Electric Power Distribution for Computer Data Centers

CONDUCTOR SHORT-CIRCUIT PROTECTION

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Ω POWEROHM RESISTORS, INC. Braking Resistors for Variable Frequency Drives APPLICATION SELECTING A STANDARD DESIGN CUSTOM RATINGS

Oil and Coolant Circulating Heating System. Model - OCSM

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Electric Motor Brake Horsepower Calculations

Magnetic Starter - 30A, 120/240V Coils

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

Operational Overview and Controls Guide

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

TC-9102 Series Surface Mount Temperature Controllers

APPLICATION NOTES. Bimetal Disc Thermostat. Operating Principle

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

Figure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc.

THERMAL MANAGEMENT SOLUTIONS

Overload Relay Heater Tables

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Grounding of AC generators and switching the neutral in emergency and standby power systems

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

*.ppt 11/2/ :48 PM 1

Product Guide. Low voltage grounding system. Answers for industry.

Italvibras USA. Operator s Manual

Commercial/Industrial Electricity

Transcription:

0 otor Control Purpose of The National Electric Code (NEC) defines as that which is intended to protect motors, motor-control apparatus, and motor branch-circuit conductors against excessive heating due to motor overloads and failure of the motor to start. is also commonly referred to as Running Protection. Note: is not intended to protect against motor branch-circuit short-circuit and ground faults. In a combination starter, this type of protection is provided by fuses, a circuit breaker, or a otor Circuit Protector (CP). This protection is commonly referred to as Short Circuit Protection and is shown circled in red in the schematic below. Fractional horsepower single-phase motor overload protection may be by: the Branch Circuit Protection, a Separate Overload Device, an Integral Thermal Protector, or Impedance Protected, or a combination of these methods, depending on whether or not the motor is permanently installed, is continuous-duty, and is manually or automatically started. Refer to the NEC Articles 430.32-430.34 for details and exceptions. Overload protection for single and three-phase AC motors in the small (above 1 horsepower) and medium horsepower range is typically provided by one of two methods: Thermal Overload Relays, or Solid-state Overload Relays. Overload protection for large three-phase motors is sometimes provided by Thermal Overload Relays which are connected to Current Transformers (CT s). However, most new installations utilized microprocessor-based motor protective relays which can be programmed to provide both overload and short-circuit protection. These protective relays often also accept inputs from Resistance Temperature Devices (RTD s) imbedded in the motor windings (usually two per phase) and the relays are capable of displaying the winding and motor bearing temperatures, and provide both alarm and trip capability. Typical Schematic Diagram Three-Phase Across-the-Line Starter with Thermal Overload Protection See Sheet 5 for an operational description of this circuit. L1 CP NEC Articles 430.31-430.44 L2 L3 FU1 FU2 X1 X2 120 VAC Control Circuit OTOR To Control Integral Thermal Protector/s (if used) are inside motor and sense motor winding temperature. See NEC Article 430.32 otor Branch-Circuit Short- Circuit and Ground Fault Protection. NEC Articles 430.51-430.58 FU3 START STOP 1 2 3 a High temperature on overload heater due to excessive current opens control circuit contact, drops-out the contactor, and stops the motor. otor Control Circuit NEC Articles 430.71-430.74 Schematic Diagram Notes The three-phase power circuit is shown in bold black. The single-phase 120 volt control circuit is shown with light-weight black lines. The bold black dashed lines indicate a mechanical connection and show that all three poles of the CP operate simultaneously as do the three poles of the ain () Contactor. Sheet 1

1 Thermal Overload Blocks Overload heaters work on principle that motor load (and therefore motor temperature) is directly related to the current drawn by the motor. Current flowing from the motor contactor to the motor passes through the motor overload heaters (one per phase) which are mounted in the control overload block. If the motor current exceeds the desired value, the heat produced by the motor overload heater will cause a control circuit contact in the overload block to open, drop out the contactor coil, and stop the motor. anufacturers provide Heater Selection Charts from which the correct heater is chosen based on the motor nameplate Full Load Amps (FLA). Overload Heater Schematic Symbol Overload Heater - Shown in installed position. Overload Reset Push Button Overload Contact Connection Terminal Eutectic Alloy Barrel (Heater Removed) Pointed Heater Position Tab Eutectic Alloy Type Center phase heater shown removed. On this style of overload block the heater can be mounted in one of four possible positions for fine adjustment of the trip value. Each position places the heater in a slightly different proximity to the melting alloy barrel. The heater has a pointed position indicator tab which shows the selected mounting orientation. Calibration Adjustment Varies trip setting from 85% - 115% of heater table value. Wire spring position sets unit for manual or automatic reset. Reset Push Button Overload Contact Terminals One side of contact is factory wired to coil terminal (red wire). Bimetallic Type Shown Plugged into Bottom of Contactor Factory installed coil jumper from overload contact (red wire). Overload Heaters One per phase otor T-Lead Connections at bottom of each heater. Ratchet Wheel Overload Heaters Assortment of various types. Two units on left are eutectic alloy type, other three are for bimetallic overload blocks. Heater on left incorporates ratchet wheel and alloy barrel into heater element. Sheet 2

2 Thermal Relay Operation Operating Principle POWER FRO CONTACTOR elting Alloy Type Overload Heater Element Ratchet Wheel Pawl The term eutectic means easily melted. The eutectic alloy in the heater element is a material that goes from a solid to liquid state without going through an intermediate putty stage. When the motor current exceeds the rated value, the temperature will rise to a point where the alloy melts; the ratchet wheel is then free to rotate, and the contact pawl moves upward under spring pressure allowing the control circuit contacts to open. CONTR POWER FRO CNTL TRANSFORER X2 After the heater element cools, the ratchet wheel will again be held stationary and the overload contacts can be reset. Normally -Closed (NC) Overload Contacts Contact Opening Spring Severe fault currents can damage the heater element and they should be replaced after such an occurrence. However, normal overloads, usually, will not affect the heater element or alter its accuracy. Bimetallic Type Overload Power from Contactor Bimetallic Strip Bends downward. Overload Heater otor T Lead Connection Insulated Spacer. Pushes contact open. Toggle-Type Spring Contact Normally closed, snaps open (up) when pushed down by insulated spacer. Stationary Contact NC Overload Contact In motor control circuit. otor Starting (S) Switch Designed to protect small single-phase motors. ounts in standard switch box. On-Off Toggle Switch Switch Box ounting Ears Plug-in Heater Sheet 3

3 Typical Heater Selection Chart How to Use the Overload Selection Chart Shown below is an overload chart for Cutler Hammer, Citation Line Starters. Assume you have an Enclosed Type C300, NEA Size 2 Starter, and that the motor nameplate Full-Load-Amps (FLA) is 11.0 amps. For this example you will use TABLE ST-3. Look down the TABLE ST-3 column until you find the heater range that includes the FLA for your motor and then look across to the Heater Coil Catalog Number column to select the correct heater. Sheet 4

C1 Schematic Diagram Three-Phase Across-the-Line Starter Schematic Diagram L1 CP L2 OTOR L3 FU1 FU2 X1 X2 120 VAC Control Circuit START STOP 1 2 3 a FU3 otor Control Circuit Description In the schematic above, the three-phase power circuit is shown in bold lines and the single-phase control circuit is shown by a lighter weight line. This circuit employs a standard START/STOP push button station and is know as a Three Wire Control Scheme because it requires three wires (shown numbered above) from the push button station to the other control components. For safety, this circuit uses a standard single-phase control transformer to provide low voltage (120 VAC) control and the X2 bushing is normally grounded. CAUTION: Some systems do not have a grounded X2! (This is sometimes done for continuity of service reasons - so that a control system ground will not shut the system down.) The transformer primary is connected downstream of the otor Circuit Protector (CP) so that when the motor control is turned off, the control circuit will also be de-energized - another important safety feature. After the fuse, the first control component is the STOP button. The normally closed Overload Contact is placed on the X2 side of the ain Contactor Coil. Additional STOP push buttons are always wired in series, and additional START push buttons are always wired in parallel. Circuit operation is as follows: Close CP to apply power to the circuit. Depress momentary START push button. This causes the ain Contactor Coil to be energized. ain Contactor Coil closes contacts (3) to start motor and also closes the a auxiliary contact. Auxiliary Contact a seals around the momentary START push button which can now be released. The motor continues to run until the normally closed STOP push button is momentarily depressed. In the event of an overload, the overload heaters will open the normally closed contact and drop-out the ain Contactor and stop the motor. After an overload trip, the overload heaters must cool to permit resetting of the overload contact. Sheet 5