Introduction to Transformer Rated Meters

Similar documents
Chapter 24. Three-Phase Voltage Generation

Definition AC Power Distribution

INFORMATION FOR METER SERVICE PROVIDERS (MSP) FOR ARIZONA CERTIFICATION

Measurement of Power in single and 3-Phase Circuits. by : N.K.Bhati

Services. Three Phase Service

THREE PHASE CIRCUITS

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

How To Wire A Three Phase, Single Phase, Wye Transformer

TRANSFORMER LOSS COMPENSATION FOR METERMEN PRESENTED BY: MICHAEL K. BEARDEN

11. MEASUREMENT OF POWER CONSUMPTION OF THE NONBALANCED THREE-PHASE LOAD

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

TESLA Recorder Power Metering Setup Configuration for 3 and 2 Element Watt/VAR Metering

WINDING RESISTANCE TESTING

Lecture Notes ELE A6

ALPHA Meter Installation Information

CURRENT TRANSFORMERS INSTALLATION GUIDE

Three-phase AC circuits

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

Odyssey of the Mind Technology Fair. Simple Electronics

Three phase circuits

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

Unit 33 Three-Phase Motors

Polyphase kwh Electricity Meter

Step Voltage Regulators

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Multiple Meter Installation Amperes Per Position -Single Phase, Self-contained

Cable Tray Selection-

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

INSTALLATION GUIDE LOW VOLTAGE TRANSFORMER

JEFFERSON ELECTRIC, INC. Buck-Boost Transformer Application Manual

Ampere's Law. Introduction. times the current enclosed in that loop: Ampere's Law states that the line integral of B and dl over a closed path is 0

Product Guide. Low voltage grounding system. Answers for industry.

Current Transformers

I = V/r P = VI. I = P/V = 100 W / 6 V = amps. What would happen if you use a 12-volt battery and a 12-volt light bulb to get 100 watts of power?

Section B: Electricity

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

How To Understand And Understand The Electrical Power System

Lab 3 - DC Circuits and Ohm s Law

Series and Parallel Resistive Circuits

Buck - Boost Transformers

ANALOG AND DIGITAL METERS ANALOG VS. DIGITAL METERS VOLTMETERS ANALOG AND DIGITAL

Experiment NO.3 Series and parallel connection

Three-Phase Electric Power Distribution for Computer Data Centers

3-Phase AC Calculations Revisited

Understanding the Alternator

Vaporization of Liquid Nitrogen

Transformer Calculations

Series and Parallel Circuits

DISTRIBUTION SYSTEMS INDEX NOV 06 SECTION 2. Detroit Ann Arbor Mt. Clemens Port Huron

INDUCTION REGULATOR. Objective:

Transformer circuit calculations

(3 )Three Phase Alternating Voltage and Current

UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE. Department of Electrical and Computer Engineering

Power Transducer User s Guide

VOLTAGE REGULATOR AND PARALLEL OPERATION

The Fundamentals of Three-Phase Power Measurements. Application Note

Instrument Transformer Wiring Troubleshooting Guide Three Phase Meters Revision 0, Initial Issue, April 26, 1993

Measuring Processor Power

Coupled Inductors. Introducing Coupled Inductors

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

Tristan s Guide to: Solving Series Circuits. Version: 1.0 Written in Written By: Tristan Miller Tristan@CatherineNorth.com

USE OF A SINGLE ELEMENT WATTMETER OR WATT TRANSDUCER ON A BALANCED THREE-PHASE THREE-WIRE LOAD WILL NOT WORK. HERE'S WHY.

Various Applications of Electric Metering & How They Relate to Revenue Protection. Presented by: Guy Cattaruzza United Illuminating

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Harmonics in your electrical system

Digital and Analog I/O

Fronius inverters named on the "Go Solar California Eligible Inverter listing

Customer Metering and Services Guide

Kirchhoff's Current Law (KCL)

Fundamentals of Electrical Power Measurement

SmartBlock Power and Energy Monitor With Rogowski Coil (di/dt) Support HE579ACM302

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture phase System 4

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

W03 Analysis of DC Circuits. Yrd. Doç. Dr. Aytaç Gören

Polarity. Electrical Quals

IRRIGATION PUMPING Table of Contents - Section 900

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp

Low Voltage Transformer Through-Fault Protection: A System Approach

Electrical Fundamentals Module 3: Parallel Circuits

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

Table of Contents. TransformerIQ FAQs 1

Instrument Transformers. Technical Information and Application Guide

Digital I/O: OUTPUT: Basic, Count, Count+, Smart+

First Year (Electrical & Electronics Engineering)

High voltage power supply (1 to 20 KV)

ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS

2) Based on the information in the table which choice BEST shows the answer to 1 906?

Alternating current three-phase circuits

The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law.

Lab E1: Introduction to Circuits

The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system.

How To Get A Power Line Extension

Three-Phase AC Power Circuits

Transcription:

Introduction to Transformer Rated Meters Module 141 87 rd Annual Short Course and Conference Southeastern Electricity Metering Association November, 2012 Orlando, FL Larry Waters General Electric Company Atlanta, GA

Self Contained Meters Meter Types Usually class 100, 200 or 320 (max. amps) Up to 480 volts (some higher, e.g. Canada) Smaller loads Average homes and small commercial Voltages and currents connect to same terminals; load currents flow through meter The meter multiplier is 1 (typically)

Meter Types Self Contained Meters Voltages and currents connect to same terminals; load currents flow through meter N A C Line 2S Load The meter multiplier is 1 (typically); may be 10 depending on how dials are displayed

Meter Types Transformer Rated Meters -- Class 10 or 20; generally CL 20 today Load currents above 200 amps and/or voltages above 480v. (typically) Used with voltage transformers and/or current transformers Larger commercial and industrial customers; large homes Voltages and currents connect to separate terminals on meter The meter multiplier is not 1 (normally)

Transformer Rated Meters -- Meter Types Voltages and currents connect to separate terminals on meter A LINE C LINE N LINE A LOAD C LOAD N LOAD 4S The meter multiplier is not 1 (normally); it is the product of the VT and CT ratios

Transformer Rated Meters - Safety Voltage transformers should never be shorted. A LINE A LOAD C LINE C LOAD N LINE 4S N LOAD Current transformers must always be shorted when not in use; never pull a transformer rated meter unless CT circuits are shorted.

Transformer Rated Meters A LINE C LINE N LINE 4S A LOAD C LOAD N LOAD Voltage transformer transforms the voltage; typically to 120 volts from the primary voltage Current transformer transforms the current; typically to 5 amps from the primary current Polarity must be observed for CT s and VT s The ratio is expressed as X to Y (X:Y) and represents the rated primary value as compared to the secondary value.

Meter Multipliers Current transformers but no voltage transformers - Example: 400 amp primary (service) 400 amp to 5 amp (400:5) current transformer 80:1 ratio (400/5 = 80) The meter multiplier, then, is 80

Meter Multipliers Current transformers and voltage transformers - Example: Service is 12470Y/7200 volts and rated 400 amps VT s are connected phase to neutral 7200:120 or 60:1 400 amp to 5 amp (400:5) current transformers 80:1) The meter multiplier, then, is 60 x 80 or 4800

Meter Multipliers Dial Multipliers and Primary Reading Registers Meter register must show the actual primary usage values Example: Transformer Factor is 4800 Meter multiplies values by 4800 and displays result A dial multiplier may be required to prevent wrap around, e.g. x100, x1000, etc.

Blondel s Theorem Blondel says: If energy be supplied to any system of conductors through N wires, the total power in the system is given by the algebraic sum of readings of N wattmeters, so arranged that each of the N wires contains one current coil, the corresponding potential coil being connected between that wire and some common point. If this common point is on one of the N wires, the measurement may be made by the use of N-1 wattmeters. Andre E. Blondel, 1893 We would use watthour meters in place of watt meters and energy in place of power. We would also consider ground as a possible current carrying conductor when counting N.

What is a meter Form Number? A Form designation tells us: The number and arrangement of meter terminals, and The number and internal connection of meter elements (stators). The Form designation describes the meter, not the service. With modern meters, some meter Forms may be used to correctly meter more than one service configuration. More than one meter Form could be used with a particular service depending on the connection of the Instrument Transformers. The same Form designation is usually applicable to equivalent meters of all manufacturers.

* Not intended for Form 5S equivalent, 4 wire delta connections. ** Some electronic meters may be used in 4wY or 4w circuits. Basic Meter Forms Meter Form S.C./ T.R. Number of Stators Number of Current Circuits Number of External Circuit Wires 1S, 1A SC 1 1 2 2S, 2A SC 1 2 3 3S, 3A TR 1 1 2 4S, 4A TR 1 2 3 5S, 5A TR 2 2 3 (or 4) 35S, 35A TR 2 2 3* 45S, 45A TR 2 2 3 (or 4) 6S, 6A TR 2 3 4Y 36S, 36A TR 2 3 4Y 8S, 8A TR 2 3 4 9S, 9A TR 3 3 4Y (or **) 12S, 12A SC 2 2 3 14S, 14A SC 2 3 4Y 15S, 15A SC 2 3 4 16S, 16A SC 3 3 4Y (or **) SC = Self Contained; TR = Transformer Rated S = Socket Base; A = Bottom Connected

Self Contained vs Transformer Rated What is one of the key differences...... when we look at ANSI forms? N A C A LINE A LOAD Line C LINE N LINE C LOAD N LOAD 2S 4S Load Self-Contained Transformer-Rated

Applicable ANSI Meter Forms Form 3S* 1 Element, Transformer Rated 2 wire, single phase, 3 wire, single phase Form 4S* 1-1/2 Element, Transformer Rated 3 wire, single phase * ANSI Forms looking from the front of the meter

Applicable ANSI Meter Forms Form 5* Form 35* Form 45* 2 Element, 3 wire, network 2 Element, 3 wire, network 2 Element, 3 wire, network * ANSI Forms looking from the front of the meter

Polyphase Meters 4 Wire Wye Services A LINE N LINE A LOAD N LOAD B LINE N LINE B LOAD N LOAD C LINE N LINE C LOAD N LOAD 3S 3S 3S

4 wire Wye Metering K Y Z K Y Z K Y Z Form 9 Form 6 Form 36 3 Element, 4 wire, wye Transformer-rated 2½ Element, 4 wire, wye 2½ Element, 4 wire, wye

4 wire, Wye Metering N C B A K Y Z 9S Transformer-rated

4 Wire, Delta Metering C N A B A LOAD B LOAD C LOAD N LOAD K Y Z 9S

Summary Transformer rated meters are required when voltages and currents exceed the meter s direct connect capability A form designation tells us about the number or terminals, their location and the internal meter wiring In CT and VT connections, polarity must be observed for metering to be correct CT s must be shorted when not in use; VT s should not be shorted Meter multipliers are critical in transformer rated applications