Design Practices in Harmonic Analysis Studies Applied to Industrial Electrical Power Systems

Similar documents
Introduction. Harmonics and IEEE 519 Page 1 of 19

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

Product Data Bulletin

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Typical Data Requirements Data Required for Power System Evaluation

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications

Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a

How To Understand The Electrical Power Supply Of A Power Supply System

7. Reactive energy compensation

Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

Survey of Harmonics Measurements in Electrical Distribution Systems

Harmonic Distortion and Variable Frequency Drives

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

Line Reactors and AC Drives

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

POWER FACTOR CORRECTION

Harmonics in your electrical system

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

FACTS. Solutions to optimise network performance GRID

The design and performance of Static Var Compensators for particle accelerators

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Power System Harmonics

The Different Types of UPS Systems

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES

Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM. Technical Note No. 7 August 2003

Engineering innovation

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

Investigation of Power Quality In Health Care Facility

Project description. Power Electronics for Reliable and Energy efficient Renewable Energy Systems

Power Quality Standards for Electric Service

Paralleling Power Sources Which Share a Common Neutral

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

The Different Types of UPS Systems

Application Guide. Power Factor Correction (PFC) Basics

The following table shows approximate percentage wise the

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC

Survey of Harmonics Measurements in Electrical Distribution Systems

Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile

SYNCHRONOUS MACHINES

HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS

System Standard For the Installation of New Loads

DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

Improvement of Power Factor for Industrial Plant with Automatic Capacitor Bank

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

CERN Accelerator School. Electrical Network and Power Converters. Hans Ulrich Boksberger Paul Scherrer Institute 5232 Villigen PSI Switzerland

High Frequency Power Quality

The Different Types of UPS Systems

Power Factor Correction for Power Systems First Semester Report Spring Semester 2007

Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power

Power Quality Analysis and Evaluation at Water Pumping Station Supplied by Medium Voltage

Power Supplies. 1.0 Power Supply Basics. Module

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

Sensitivity Analysis of Waveform Distortion Assessment for Wind Plants

Nuclear Power Plant Electrical Power Supply System Requirements

Power Quality Paper #3

Transformers. Special transformers Reactors products

Fusible Disconnect Switch

Relationship between large subject matter areas

APPLICATION OF IEEE STD HARMONIC LIMITS

EMI in Electric Vehicles

How To Understand And Understand The Theory Of Electricity

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

F05D Meeting on Damped AC Voltage Testing

13. Electrical network design methodology and application example

Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009

SPECIFICATION COG-2007

Developing a Utility/Customer Partnership To Improve Power Quality and Performance

Survey of Harmonics Measurements in Electrical Distribution Systems

21 st Century Facilities

Advantages of 6-Pulse VFD with Lineator AUHF vs Active Front End (AFE) Drives

Voltage Tolerance Boundary

Analysis of AC-DC Converter Based on Power Factor and THD

NO-BREAK KS 7e. Concentrated Energy kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM

EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC)

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

The electrical energy produced at the gen

Data center power dynamics within the settings of regional power grid

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

HARMONICS AND HOW THEY RELATE TO POWER FACTOR. W. Mack Grady The University of Texas at Austin Austin, Texas 78712

Considering the effects of UPS operation with leading power factor loads

FREQUENCY CONTROLLED AC MOTOR DRIVE

Part 1 System Modeling & Studies for Existing Systems

Transcription:

ETASR - Engineering, Technology & Applied Science Research Vol. 3, No. 4, 2013, 467-472 467 Design Practices in Harmonic Analysis Studies Applied to Industrial Electrical Power Systems S. F. Mekhamer Faculty of Engineering, Ain Shams University Cairo, Egypt saidfouadmekhamer@yahoo.com A. Y. Abdelaziz Faculty of Engineering, Ain Shams University Cairo, Egypt almoatazabdelaziz@hotmail.com S. M. Ismael Electrical Engineering Division, ENPPI Cairo, Egypt shriefmohsen@enppi.com Abstract Power system harmonics may cause several problems, such as malfunctions of electrical equipment, premature equipment failures and plant shutdowns. Accordingly, mitigation of these harmonics is considered an important target especially for industrial applications where any short downtime period may lead to great economic losses. Harmonic analysis studies are necessary to analyze the current and voltage harmonic levels and check if these levels comply with the contractual or international standard limits. If the studies reveal that the preset limits are exceeded, then a suitable harmonic mitigation technique should be installed. Harmonic analysis studies in the industrial electrical systems are discussed in many references. However, a comprehensive procedure for the steps required to perform a harmonic study is rarely found in the literature even though it is strongly needed for design engineers. This paper provides a comprehensive procedure for the steps required to perform a harmonic study in the form of a flowchart, based on industrial research and experience. Hence, this paper may be considered as a helpful guide for design engineers and consultants of the industrial sector. Keywords-harmonic analysis study; distortion; point of common coupling (PCC); variable frequency drive (VFD); resonance I. INTRODUCTION Due to the dramatic increase in the usage of nonlinear loads in industrial applications (mainly regarding Variable Frequency Drives or VFDs), the power system harmonics problems has gain in significance, representing a big obstacle against the wide application of VFDs although they enhance system efficiency and provide great energy saving. The power system harmonics cause many harmful effects including: Overheating of generators, motors, transformers, and power cables that lead to early equipment failures Failure of capacitor banks Nuisance tripping to protection relays Interference to communication systems and sensitive electronic devices Accordingly, the mitigation of the power system harmonics is of great importance in industrial electrical systems in order to increase system reliability, enhance operation economics, avoid unwanted equipment failure and process downtimes [1]. Nowadays, industrial electrical systems contain a valuable amount of nonlinear loads. Accordingly, power system studies for industrial plants should contain harmonic analysis studies beside short circuit, load flow and motor starting studies. The harmonic analysis studies for the industrial systems are discussed in [2], but the author did not focus on the guidelines of the harmonic study. Also the authors did not introduce the various international standards that set the limits of the harmonic distortions. The goals of this paper can be summarized as follow: 1. To highlight the purpose of a harmonic analysis study 2. To highlight some guidelines for harmonic analysis studies 3. To provide a comprehensive description of the procedure required to perform a harmonic study 4. To introduce the international standards limits for the harmonic distortions II. PURPOSE OF A HARMONIC ANALYSIS STUDY Nowadays, the applications of the nonlinear loads in the industrial plants grow rapidly and the percentage of these loads may be in the range of 30% to 50% of the total plant load. Accordingly, the effects of harmonics within the electrical system and their impact on the electric utility and neighboring plants should be examined to avoid equipment damage and plant shutdowns. The following cases may necessitate performing a harmonic study [3]: 1. During the design stage of a project, if the amount of the nonlinear loads exceeds 25% of the total loads on a bus or a system, a harmonic analysis study is required to check the compliance with the contractual/ international harmonic limits 2. To solve harmonic-related problems such as failure of electrical equipment or malfunction of protective relays 3. If an existing plant is going to be expanded and a significant amount of nonlinear loads is going to be added, then a harmonic analysis study is required to verify the plant performance after the addition of these loads

ETASR - Engineering, Technology & Applied Science Research Vol. 3, No. 4, 2013, 467-472 468 4. If a capacitor bank is installed in any electrical networks that contain many nonlinear loads, then a harmonic analysis is required to check the possibility of resonance occurrence III. GUIDELINES FOR HARMONIC ANALYSIS STUDIES A. Harmonic Sources All nonlinear loads are defined also as harmonic sources, as clearly shown in Figure 1, because they draw non-sinusoidal currents when a sinusoidal voltage is applied. The nonlinear load acts as a source of harmonic currents in power system, thus causing voltage distortions at the various system buses due to the harmonic voltage drops across the system impedances. Fig. 1. Effect of a nonlinear load on the current waveform To perform a harmonic study, the design engineer must identify the available harmonic sources and the harmonic currents generated by these harmonic sources. There are three options available for the design engineer to determine the harmonic currents, as described below: a. To measure the generated harmonics from each harmonic source (time-consuming option, applicable only in case of existing plants) b. To calculate the generated harmonic currents by using suitable mathematical analysis (may require extensive manual and time-consuming calculations) c. To use typical values based on computerized softwares libraries or based on the available data from the nonlinear load's manufacturer Practically, options (a) and (c) are the most used options and provide reasonable results. The following are the main sources of harmonics in industrial applications [4]: 1) Saturable Magnetic equipment: There are various saturable magnetic equipment that cause harmonic problems such as: a. Rotating machines, rotating machines like induction motors may act as sources of the third harmonic currents when they are operating in abnormal or overloaded conditions. b. Ballasts of discharge lamps, the discharge lamps like mercury vapor, high-pressure sodium and fluorescent lamps are dominant sources of the third harmonic currents. c. Transformer harmonics, transformers create harmonics when they are overexcited. In addition, the transformer inrush currents may contain some even harmonics, but the duration is rather limited. d. Generator harmonics, voltage harmonics are created from the synchronous generators due to the non-sinusoidal distribution of the flux in the air gap. Selection of suitable coil-span factor (called also pitch factor) can significantly reduce the voltage harmonics from the generators. 2) Power Electronic Devices: There are various power electronic devices that cause harmonic problems such as: a. Variable Frequency Drives (VFDs) used in fans and pumps b. Switched mode power supplies (SMPS), used in instruments and personal computers c. High voltage DC transmission stations (HVDC) d. Static VAR compensators e. Uninterruptable power supply systems (UPS) f. Battery charger systems g. Flexible AC transmission systems (FACTS) h. AC and DC arc furnaces in steel manufacturing plants B. Resonance The inductive reactance increases as the frequency increases as follow: 2.. F L XL. where: X L : Inductive reactance F : System frequency L : Inductance While the capacitive reactance decreases as the frequency increases as follows: XC where: X C : Capacitive reactance C : Capacitance 1 / ( 2.. F. C) Due to the opposite characteristics of the inductive and capacitive reactances, there must be a frequency at which X L equals X C. This condition of equal and opposite reactances is called resonance. Most of the power system elements are inductive. Accordingly, the presence of shunt capacitors used

ETASR - Engineering, Technology & Applied Science Research Vol. 3, No. 4, 2013, 467-472 469 for power factor correction or harmonic filtering can increase the probability of resonance occurrence. There are two types of resonance, the series resonance and the parallel resonance. The harmful effect of the series resonance may be the flow of excessive harmonic currents through the network elements. These excessive currents cause nuisance tripping to the protection relays, overheating of cables, motors, and transformers and premature failure to the electrical equipment. The harmful effect of the parallel resonance may be the presence of excessive harmonic voltages across the network elements. These excessive harmonic voltages cause dielectric breakdown of the electrical equipment s insulation [3]. 1) Series Resonance: The series resonance occurs when an inductor and a capacitor are connected in series and they resonate together at a certain resonance frequency. An example of the series resonant circuit is shown in Fig. 2. This AC circuit is said to be in resonance when the inductive reactance X L is equal to the capacitive reactance X C. D. Power System Modeling: At the presence of harmonics, the electrical system elements models must be updated to encounter for the presence of higher frequencies in the system rather than the power frequency (50 Hz or 60 Hz). Details for electrical system elements models under harmonics distortions can be found in [3]. E. Types of Analyses Performed during the Harmonic Analysis: There are two main types of analyses that could be performed during harmonic analysis [2]: a. Current and voltage distortion analysis, in which the individual and total current and voltage harmonic distortions are calculated at the various buses then the results are compared with the relevant contractual limits. b. Impedance versus frequency analysis, in which a plot of the system impedance at various buses is plotted against the frequency. This analysis is important in predicting the system resonances prior to energizing the electrical system. A peak in the impedance plot indicates a parallel resonance while a valley in the impedance plot indicates a series resonance. Fig. 2. AC circuit representing an example for the series resonance 2) Parallel Resonance: The parallel resonance occurs when an inductor and a capacitor are connected in parallel and they resonate together at a certain resonance frequency. There are many forms of parallel resonant circuits. A typical parallel resonant circuit is shown in Figure 3. This circuit is said to be in parallel resonance when X L =X C similar to the series resonance. Fig. 3. AC circuit representing an example for the parallel resonance C. Tools of performing a harmonic analysis study: The harmonic analysis study can be performed by any of the following tools: a. Manual calculations, which are limited to small-size networks since they are very complicated and susceptible to errors. b. Field measurements, which are often used as a verification of the design, or as a preliminary diagnosis of a field problem. c. Digital computer simulations, which nowadays are the most convenient and economical method for analyzing system harmonics IV. STEPS OF PERFORMING A HARMONIC ANALYSIS STUDY If a harmonic analysis study is required to be performed due to any of the cases described in section (II), the following steps should be followed: a. Obtain the electrical system one-line diagram and highlight the available nonlinear loads, capacitor banks and medium voltage cables of long length within the industrial system. b. Highlight the point of common coupling (PCC) which is the point that connects the industrial network with the utility or with the neighboring plant. c. Highlight the in-plant system buses that are expected to be affected from harmonic distortions. d. Gather the harmonics-related data of all nonlinear loads within the plant. e. Obtain, from the utility company, the relevant data of current and voltage harmonics at the contractual PCC including the minimum and maximum short circuit fault levels and the permissible limits on voltage and current harmonics because the allowable harmonic limits vary from country to country. f. Model the electrical network using any of the commercially available softwares such as the electrical transient analyzer program (ETAP). g. Perform the harmonic analysis for the electrical network at the various possible operating scenarios. h. Check the individual and total voltage and current distortion levels at the interested system buses and at the PCC.

ETASR - Engineering, Technology & Applied Science Research Vol. 3, No. 4, 2013, 467-472 470 i. Check the harmonic frequency spectrum, which is a plot of each individual harmonic value with respect to the fundamental value versus frequency. j. If the harmonic distortion results exceed the allowable limits, select an appropriate harmonic mitigation solution and the optimum insertion point for that solution. Further details about this point are introduced in section (V). k. Re-perform the harmonic analysis study after adding the harmonic mitigation technique to ensure compliance with the contractual / international harmonic limits. An extensive literature review over the past twenty years leads to the fact that there is no single article that summarizes the steps required to perform a harmonic analysis study even though the importance of this procedure for the design engineers. The comprehensive flowchart presented in Figure 4 provides this novel helpful approach. V. SELECTION OF THE HARMONIC FILTER'S INSERTION POINT Even if the design engineer selects the optimum harmonic mitigation technique for his plant, among the available harmonic mitigation solutions in the market [5], then the filter insertion point should be studied carefully as it greatly affects system performance [6]. As shown in Figure 5, the possible filter insertion points can be classified into three categories as follow: A. Local Harmonic Mitigation In this mode of mitigation, the shunt type (passive or active) harmonic filter is directly connected to the nonlinear load terminals. This mode is efficient if the number of nonlinear loads is limited and the power of each nonlinear load is significant compared to the total plant power. Circulation of harmonic currents in the electrical network is avoided, thus the harmonic impact on the upstream network elements is minimized. B. Semi-Global Harmonic Mitigation In this mode of mitigation, the shunt type (passive or active) harmonic filter is connected to the input of the LV subdistribution switchboard. Accordingly, the filter treats several sets of nonlinear loads. This type of compensation is ideal in presence of multiple nonlinear loads each having low rated power. A practical example of this mode is found in commercial buildings where a harmonic filter may be found on each floor of the building. C. Global Harmonic Mitigation This mode of mitigation is more concerned with meeting the contractual harmonic limits at the (PCC) than the reduction of the in-plant harmonics. The major drawback of this mitigation mode is that the harmonic currents are allowed to circulate in the electrical network. Thus, the various electrical elements within the plant will be subjected to harmful harmonic impact. VI. INTERNATIONAL HARMONIC STANDARDS The purpose of imposing strict limits on the harmonics emissions is to ensure that the current and voltage distortions at the PCC are kept sufficiently low. Thus, the other customers connected at the same point are not disturbed. The international standards related to harmonic distortion limits can be classified as follows: A. Standards specifying limits for individual nonlinear equipment IEC 61000-3-2 [7], which specifies the current harmonic limits for low voltage equipment that has an input current less than 16 A. IEC 61000-3-12 [8], which specifies the current harmonic limits for an equipment that has an input current between 16A and 75A IEC 61800-3 [9],which specifies the electro-magnetic compatibility (EMC) requirements of the adjustable speed drive systems As noticed, the above standards are for small rating and low voltage harmonic loads only. In addition, the above standards do not set limits on the overall distribution network. B. Standards specifying limits for electrical networks IEEE 519-1992 [10], this document introduces many useful recommended practices for harmonics control in electrical networks. This document is widely used in the industrial sector and many consultants/clients use the limits indicated in it as contractual limits within their specifications. IEC 61000-3-6 [11], this specification performs an assessment of the harmonic emission limits for distorting loads in medium voltage and high voltage power systems. Up till now, this specification is not widely used in the industrial sector because it is rather new (punlished in 2008). British engineering recommendation G5/4-1 [12], this document provides some helpful engineering recommendations for establishing the allowable harmonic limits of the voltage distortions in the United Kingdom. VII. IEEE 519-1992 HARMONIC LIMITS A. Harmonic current distortion limits Harmonic current distortion limits are introduced in the IEEE 519-1992. A summary of these current harmonic limits is shown in Table I. Setting limits for the current harmonic levels protects the utility company and the other utility consumers connected on the same feeder. where: I SC : maximum short circuit current at PCC I 1 or I L : maximum demand load current (fundamental frequency component) at PCC

ETASR - Engineering, Technology & Applied Science Research Vol. 3, No. 4, 2013, 467-472 471 Start C 1. Gather all the required data about the existing harmonic sources. 2. Make a survey about the harmonic related.problems within the plant 3. Define the PCC. 4. Perform site harmonic measurements at the PCC and at the system buses that contain the major nonlinear loads. Existing plant No Existing or new plant New plant 1. Define the harmonic sources within the plant. 2. Define the ratio of the nonlinear loads with respect to the total plant loads as follow: Ratio = nonlinear loads (KVA) / total plant loads (KVA Ratio of nonlinear loads with respect to the total plant loads 25% 1. Evaluate the results of the harmonic study then select the optimum technical and economic harmonic mitigation technique. 2. Select the optimum insertion point for the selected harmonic mitigation technique. 3. For a new plant, Implement the selected harmonic mitigation technique in the network model then re-perform the harmonic analysis study. 4. For an existing plant, model electrical network of the plant after adding the selected harmonic mitigation technique then perform the harmonic analysis study. Harmonic analysis is not required Yes End Harmonic Analysis is required. Perform the following steps: 1. Obtain the electrical system one-line diagram and highlight the available nonlinear loads, capacitor banks and long medium voltage cables within the industrial system. 2. Highlight the point of common coupling (PCC). 3. Highlight the in-plant system buses (or switchgears) that are foreseen to be affected from harmonic distortions. 4. Gather the required equipment data, ratings and the harmonics related data of all the plant nonlinear loads. 5. Obtain, from the utility company, the relevant data of current and voltage harmonics at the contractual PCC including the minimum and maximum short circuit fault levels and the permissible limits on voltage and current harmonics. 6. Model the electrical network using any of the commercially available softwares such as the electrical transient analyzer program (ETAP). 7. Perform the harmonic analysis for the electrical network at the various possible operating scenarios. 8. Check the individual and total voltage and current distortion levels at the interested system buses and the PCC to ensure compliance with the contractual / international harmonic limits. End No Voltage and current harmonic levels exceed the allowable C Yes Fig. 4. A comprehensive procedure for the steps required to perform a harmonic analysis

ETASR - Engineering, Technology & Applied Science Research Vol. 3, No. 4, 2013, 467-472 472 TABLE II. HARMONIC VOLTAGE DISTORTION LIMITS FOR LOW VOLTAGE DISTRIBUTION SYSTEMS (SYSTEM VOLTAGES: BELOW 1 KV) Allowable voltage THD Special systems General distribution systems Dedicated systems Voltage THD (%) 3% 5% 10% TABLE III. HARMONIC VOLTAGE DISTORTION LIMITS FOR MEDIUM AND HIGH VOLTAGE DISTRIBUTION SYSTEMS Bus voltage Individual voltage harmonic distortion (%) Total voltage harmonic distortion (%) 69 kv and below 3 % 5 % From 69 kv to 161 kv 1.5 % 2.5 % 161 kv and above 1 % 1.5 % Fig. 5. Various insertion points for the harmonic filters It should be noted that all the power generation equipment are limited to these values of current distortion, regardless of the actual I SC /I 1 ratio. The ratio I SC /I L is the ratio of the short circuit current available at the (PCC) to the maximum fundamental load current. It is recommended that the load current (I L ) be calculated over any (15) or (30) min period and then averaged over the next (12) month period. TABLE I. HARMONIC CURRENT DISTORTION LIMITS FOR GENERAL DISTRIBUTION SYSTEMS (SYSTEM VOLTAGES: FROM 120V TO 69 KV) I SC / I 1 Odd harmonic order h (%) Individual current harmonic distortion (%) h < 11 11 h < 17 17 h < 23 23 h <35 h 35 Total harmonic distortion THD I % < 20 * 4 2 1.5 0.6 0.3 5 20-50 7 3.5 2.5 1 0.5 8 50-100 10 4.5 4 1.5 0.7 12 100-1000 12 5.5 5 2 1 15 >1000 15 7 6 2.5 1.4 20 B. Harmonic voltage distortion limits: The IEEE 519-1992 defines the allowable voltage harmonic limits at the PCC. Table II summarizes the limits for the low voltage systems and Table III summarizes the limits for the medium and high voltage systems. Where: Special systems: critical applications like hospitals and airports Dedicated systems: systems that contain only nonlinear loads It is important to highlight that the limits listed in Table III should be used as system design values for normal operation conditions (lasting more than one hour). For shorter operation periods, during start-ups or unusual transient conditions, these harmonic limits may be allowed to exceed by 50%. VIII. CONCLUSIONS Harmonic analysis studies are necessary to analyze the current and voltage harmonic levels within any industrial electrical system and to check if these levels comply with the contractual or international standard limits. This paper provides a comprehensive approach for performing a harmonic study, presented in the form of a flowchart. In addition, this paper presents the current and voltage harmonic limits used in industrial systems. REFERENCES [1] M. Z. El-Sadek, Power system harmonics, 2nd edition, Mukhtar Press, Egypt, 2007 [2] R. G. Ellis, Harmonic analysis of industrial power systems, IEEE Transactions on Industry Applications, Vol. 32, No. 2, pp. 417-421, 1996 [3] IEEE Std 399-1997, Recommended practice for industrial and commercial power systems analysis, ANSI/IEEE, 1997 [4] J. P. Nelson, A Better understanding of harmonics distortions in the petrochemical industry, IEEE Transactions on Industry Applications, Vol. 40, No. 1, pp. 220-231, 2004 [5] S. F. Mekhamer, A. Y. Abdelaziz, S. M. Ismael, Technical comparison of harmonic mitigation techniques for industrial electrical power systems, MEPCON 2012, Fifteenth International Middle East Power Systems Conference, Paper ID: 214, Alexandria, Egypt, 2012 [6] E. Bettega, J. N. Fiorina, Cahier Technique no. 183: Active harmonic conditioners and unity power factor rectifiers, Schneider Electric, 1st edition, 1999 [7] IEC Std 61000-3-2, Electromagnetic compatibility (EMC)-Part 3-2: Limits for harmonic current emissions (equipment input current 16 A per phase, IEC, 2009 [8] IEC Std 61000-3-12, Electromagnetic compatibility (EMC)-Part 3-12: Limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16 a and 75 a per phase, IEC, 2011 [9] IEC Std 61800-3, Adjustable speed electrical power drive systems-part 3: EMC requirements and specific test methods, IEC, 2004 [10] IEEE Std 519, Recommended practice and requirements for harmonics control in electrical power systems, ANSI/ IEEE, 1992 [11] IEC Std 61000-3-6, Electromagnetic compatibility (EMC)-Part 3-6: Assessment of emission limits for the connection of distorting installations to MV, HV and EHV power systems, IEC, 2008 [12] British Engineering Recommendation, Planning levels for harmonic voltage distortion and the connection of nonlinear equipment to transmission systems and distribution networks in the United Kingdom, G5/4-1, 2001