PERFORMANCE OF DEMAND CONTROLLED VENTILATION : CASE STUDY

Similar documents
Using Time-of-Day Scheduling To Save Energy

Applying Schedules and Profiles in HAP

Rev. No. 0 January 5, 2009

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation The Building Regulations 2010

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

HVAC Processes. Lecture 7

Mechanical and Natural Ventilation

ASTACEA4 Inspect complex/central air conditioning systems

for K-12 School Buildings


COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI

Impact of Infiltration on Heating and Cooling Loads in U.S. Office Buildings

Essam E. Khalil

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment

Mistrale. Fusion Terminal

Dual Maximum VAV Box Controls

CASE STUDY: NEW NCAA DIV. I COLLEGE BASKETBALL ARENA

Variable Air Volume - VAV

Flexibility, Efficiency In San Antonio Arena

SECTION TESTING, ADJUSTING, AND BALANCING

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX

Bring the fresh in. Dedicated Outside Air Systems

Glossary of HVAC Terms

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

Technology: Heating, Ventilation and Air Condition (HVAC) Zone Controls

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

Carbon Dioxide (CO2) HVAC Basics

Glossary of Heating, Ventilation and Air Conditioning Terms

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

Florida Power & Light Company. Business Heating Ventilation & Air Conditioning ( HVAC ) Program Standards. Effective: November 9, 2015

Attached is a link to student educational curriculum on plug load that provides additional information and an example of how to estimate plug load:

HVAC Systems: Overview

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

Infrastructure & Cities Sector

Element D Services Heating, Ventilating, and Air Conditioning

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

AMCA International. Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL

Catalyst RTU Controller Study Report

An update on acoustics designs for HVAC (Engineering)

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

More efficiency in office buildings with HVAC, lighting and security

HEAVY DUTY STORAGE GAS

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

HVAC Checklist - Long Form

Fire Protection Of Ventilation Systems DAMPERS & AIR TRANSFER GRILLES A PRESENTATION BY PHILLIP HORTON OF FIRE ENGINEERING SOLUTIONS

Fan Applications & System Guide

BUILDING PERFORMANCE METRICS

Ventilation Retrofit Opportunities for Packaged HVAC

Drives and motors. A guide to using variable-speed drives and motors in car parks

Heating, Ventilation and Air Conditioning Rebate Catalog Saving energy for a brighter future

Information paper 20. Prepared by: David Clark. book:

More efficiency in schools with HVAC, lighting and security

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Novel Air Treatment Technology for Reducing HVAC Energy Use

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

CFD Grows Up! Martin W. Liddament Ventilation, Energy and Environmental Technology (VEETECH Ltd) What is Computational Fluid Dynamics?

A Prototype Alternative Ventilation System for Retrofit, Rehab and Renovation of Rural Alaska Houses

- White Paper - Data Centre Cooling. Best Practice

CONTROL STRATEGIES FOR HVAC SYSTEMS

Guide Specification SECTION COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY

Drives and motors. A guide to using variable-speed drives and motors in retail environments

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

Zhao et al. 2.2 Experimental Results in Winter Season The analysis given below was based on the data collected from Nov to Mar. 15, 2004.

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

Fundamentals of Acoustics & Practical HVAC Design Considerations. Demir Doken Acoustic Engineer

HVAC Systems in Schools & Commercial Buildings and Radon

Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances

How To Design A Room Air Conditioning System

ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS.

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Lesson 36 Selection Of Air Conditioning Systems

Pool Dehumidification Basics

How To Get A Passive House

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

IEQ-15 Air Distribution System

ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems

HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE

THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING. R.M.J. Bokel

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

WORKER PERFORMANCE AND VENTILATION: ANALYSES OF TIME-SERIES DATA FOR A GROUP OF CALL-CENTER WORKERS

MEASURING RATES OF OUTDOOR AIRFLOW INTO HVAC SYSTEMS

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

Validation of CFD Simulations for Natural Ventilation

Energy Saving Tips. Adjust set point temperature up a few degrees... Window contact. Occupancy sensor. A Programmable Thermostat

DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple

Transcription:

Proceedings of Healthy Buildings 2000, Vol. 2 693 PERFORMANCE OF DEMAND CONTROLLED VENTILATION : CASE STUDY Anne-Marie Bernard 1, Michaël Blazy 1 and Marie-Claude Lemaire² 1 CETIAT, France ²ADEME, France ABSTRACT In order to assess the real performances of different demand controlled ventilation systems, two of them were installed in meeting rooms of an office building. The first system is controlled by movement detection on terminal units and has been installed in a small meeting room (10 persons) which is regularly used. The second system is controlled by CO 2 detection and frequency variation on fan. It has been installed in a large meeting room (30 persons seated, up to 50 persons standing). Occupancies rates, airflows, CO 2, humidity and temperature (inside and outside) have been monitored during 3 months for both rooms. System reaction as well as comparison between measured values and expected ones have been studied. The systems have proved to be energy saving (up to 85%) with correct CO 2 levels. Meeting rooms have low occupation rate due to the fact there are generally less people in meetings than the maximum allowed. Simulations have also been run considering full office buildings to estimate the variation of savings for different occupation rates. KEYWORDS Ventilation rate Control Energy conservation Air Quality Air change rate. INTRODUCTION Demand controlled ventilation (DCV) is an important solution for energy conservation in buildings due to the importance of Air change losses. Various systems are available on the market. After a bibliographic review on DCV, the aim of the study was to experiment two different systems on site, in order to assess their real performances. METHODS We have installed two meeting rooms, one with CO 2 controlled and one with movement detection DCV. The size and the occupation of these rooms are strongly different. Each meeting room was monitored during three months on several parameters: airflow, absorbed fan power as well as CO 2 levels and outside temperatures and humidity both inside and outside. As measurements were taken every 10 seconds, polynomial regression and average values are used for results presentation.

694 Design and operation of HVAC systems RESULTS Movement detection controlled ventilation The system was installed in a small meeting room for 10 persons. The room is largely occupied. It was occupied during 19 meetings lasting 1 to 3 hours in the monitoring period of 11 working days. Yet the occupation rate, including the number of occupants as well as the time of occupation, happens to be only of 15% during this period. The movement detection system integrates movement on a detection lens during a period of 3 minutes and correlates it to the number of occupants. This information is processed to determine opening or closing of the Air Terminal Device's damper which position (5 positions are possible) is visualized by LED. The full system (detection lens, signal processing, visualization LED, with 5 positions damper) is integrated in each Air Terminal Device. The room was installed with three units covering the total surface and each of them varying from 0 to 75 m3/h. The ventilation system is a single exhaust one with air inlets on the windows and an extraction fan covering both this meeting room and a set of offices with constant airflow. Average airflows and CO 2 levels in permanent mode are reported in figures 1 and 2. Figure 1 : average airflow depending on occupation Figure 2 : average CO 2 levels depending on occupation

Proceedings of Healthy Buildings 2000, Vol. 2 695 We can note that the system reacts correctly to the real occupation of the room although position of occupants (the detection cones of the three ATDs cross each other) and their activity have sometimes induced different airflows for the same occupation. As the controlled airflow in the room (that has varied from 50 to 200 m 3 /h) is quite low compared to the permanent airflow coming from offices (585 m 3 /h) the fan absorbed power (270 W) varied very little (± 10 W). French thermal regulation in buildings requires the ventilation stops during non-occupied periods (nights, week-ends ). The mean airflow obtained on the measuring period of occupation (11 working days of 10 hours occupation) is 46 m 3 /h which is to compare to a permanent designed ventilation rate of 300 m 3 /h. We can conclude that energy savings are important (85%) due to the fact that even when a room is widely occupied, it is not fully occupied. Health regulation in France requires a maximum level of CO 2 of 1000 ppm (± 300 ppm for non smoking rooms). Required airflows per person have been calculated to achieve this value with 300 ppm outdoor CO 2 level. The indoor levels measured are therefore correct and higher values are mainly due to the fact that this building is close to an highway in city environment which induced outdoor rates from 450 to 500 ppm CO 2, and to the measured airflows. CO 2 controlled ventilation This second system was installed in a large meeting room (30 persons seated and up to 50 standing). This room is very seldom used and not fully occupied. Test were made during two periods. The first period of 17 working days was in summer. The room was used 8 times for short meetings (less than two hours). The occupation rate noted was 1.7%. The second period, in September, was more representative of standard room occupation. On 14 working days, the room was used for 5 meetings but on wider periods (2 to 7 hours). Therefore, the occupation rate was of 4.2%. The CO 2 controlled system is composed of : - a CO 2 sensor situated in the occupied zone close to the exhaust grill - a frequency converter to regulate fan speed. The system is a supply mechanical ventilation designed for 1500 m 3 /h. Fan and ducts supply only this meeting room. Although all parameters can be adjusted, the regulation parameters were to have a proportional response starting from 400 ppm indoor CO 2 to the maximum as indicated in figure 3. Frequency (Hz) Concentration in CO2 Figure 3 : frequency regulation parameters

696 Design and operation of HVAC systems Average airflows and CO 2 levels in permanent mode are reported in figures 4 and 5. 1400 1200 1000 800 600 400 200 0 0 10 20 30 40 50 Occupation permanent average airflow ( m3/h ) 30 m3/h/pers. permanent average CO2 ( ppm )/10 Série4 Figure 4 : average airflows depending on occupation 1200 1000 800 600 400 permanent average CO2/10 ( ppm ) Delta CO2 indoor/outdoor ( ppm ) 200 0 0 10 20 30 40 50 Occupation Figure 5 : average CO 2 levels depending on occupation This system also reacts correctly to real occupation. We have noted that due to the high outdoor CO 2 levels (340 to 500 ppm), even at night, the airflow very seldom came back to zero (in average, zero was reached only 12% of scrutation time). Figure 6 reports the fan mean absorbed power versus occupation of the room. When airflow was zero, a residual power of 17 W was measured due to the frequency converter.

Proceedings of Healthy Buildings 2000, Vol. 2 697 Medium power 600 500 400 300 200 100 0 0 200 400 600 800 1000 1200 1400 average airflow (m3/h) Figure 6 : mean fan absorbed power depending on occupation Energy savings can be calculated on both periods. During the summer period, the ventilation run during 16 hours with an average airflow of 580 m 3 /h.in September, it ran 18.30 hours with an average airflow of 670 m 3 /h. The energy savings due to the CO 2 controlled ventilation were of 75%. CO2 levels simulations The CO 2 indoor level can be easily calculated from mass conservation equation knowing ventilation rate, outdoor level and assuming an average production rate of 16.2 l/h/person. These calculations have been made for the 19 meetings of the first measurement campaign. Generally, a very good correlation was found between calculations and measurements as indicated, for example, in figure 7. Figure 7 : example of correlation measurement / simulation on indoor CO 2 level

698 Design and operation of HVAC systems Yet, in 6 cases out of 19 the correlation was not found. Measurements could be explained only by a double production of CO 2. Although bibliography reports variation of CO 2 production on persons and activity, it is quite unlikely that these variations would only be noted as doubled of the average values. Other explanations such as door opening on corridor also remains unsatisfactory and these divergences have not been explained. DISCUSSION DCV systems appear to be really interesting for energy savings (75 to 85% savings) in intermittent occupation rooms while maintaining correct CO 2 levels. Different systems exist [1,2] and can be employed. This study is now continuing on energy simulations of air systems in a full office building during heating season and on a practical guide for owners on how to realise a correct DCV system. ACKNOWLEDGEMENTS This study was sponsored by ADEME (French Agency for Environment and Energy Management), ABB VIM, ALDES and CETIAT members Companies. REFERENCES 1. W.J. Fisk, A.T. De Almeida, Sensor-based demand-controlled ventilation : a review, Energy and buildings, 29, p. 35-45, 1998. 2. S.J. Emmerich, A.K. Persily, Literature review on CO 2 -based demand-controlled ventilation, ASHRAE Transactions : Research, p. 229-243, 1997.