Novel Air Treatment Technology for Reducing HVAC Energy Use

Size: px
Start display at page:

Download "Novel Air Treatment Technology for Reducing HVAC Energy Use"

Transcription

1 By M. Fisher and Y. Bouskila, enverid Systems Overview Modern buildings rely upon central heating, ventilating and air conditioning (HVAC) systems for maintaining the comfort, wellbeing and productivity of their occupants and it s not just in the developed world. HVAC increasingly is being embraced by most emerging economies for the attendant productivity and lifestyle benefits. The consequence of this convenience is that in much of the world, cooling systems are the largest single contributor to the energy budget of buildings and one of the largest loads on the entire electrical grid, especially during times of peak heat and humidity. Heating buildings in cold weather demands very large amounts of energy as well. Reducing the power consumption of HVAC is therefore an important goal in the overall energy efficiency strategy of any economy. A new, commercially available technology can significantly reduce the energy consumption of HVAC in commercial and public buildings by diminishing the volume of outside air that needs to be brought in, and then heated or cooled. The technology is implemented via a device called an HLR Module, explained below, which brings together chemical engineering, mechanical innovation and software technology. The development of the HLR module was spearheaded and orchestrated by our company, enverid Systems, working together with some very well-known players in the HVAC, chemical and air quality industries, as well as the U.S. Department of Energy and a number of universities. The central concept is that selective removal of gas contaminants from indoor air is a practical and costeffective substitute for air replacement. The key lies in novel sorbents, originally invented by U.S. government research scientists to address greenhouse gas emissions. These adsorbent materials can perform low-energy cyclical capture and release of indoor contaminants. The technology can be integrated as a simple add-on retrofit into most existing central HVAC systems to provide immediate reduction in cooling power consumption, lowering it by more than 40% during peak hours. The technology also can be incorporated at the design stage for new installations and reduce the overall cooling capacity required. Motivation The key to understanding HVAC load reduction (HLR) technology and its benefits begins with understanding the way ordinary central HVAC systems address indoor air quality (Figure 1). In most central systems today, air circulates throughout a building by means of ducts and fans. Air collected by manifolds or plenums returns though the central air-handling unit where it is cooled or heated as necessary. The air handler typically also filters the air for dust and other particles. As air is recirculated, its molecular composition changes -- predominantly due to human respiration and the evaporation of organic

2 molecules in the building. That means carbon dioxide (CO 2 ) concentrations increase, and a host of other contaminants, mostly volatile organic compounds (VOCs), also accumulate, albeit the latter at much lower levels than CO 2. The relative importance of these contaminants in commercial buildings has been a subject of debate and changing viewpoints over the years, but their collective role in indoor air quality is universally recognized. The most prevalent and least understood contaminant is CO 2, a naturally occurring gas in the atmosphere that is exhaled by all living creatures as a natural byproduct of metabolism. CO 2 builds up indoors typically 1000 times faster than all other indoor contaminants combined. Because CO 2 is colorless and odorless, it is easy to ignore until it becomes toxic to humans at concentrations of about 0.5% to 1%. However, recent studies indicate that CO 2 is detrimental to human brain function at much lower concentrations -- as low as 0.1% a concentration level found in many buildings and considered normal. VOCs span a wide gamut (hexane, limonene, ethanol, formaldehyde and many others) and occur at much lower levels in buildings, typically in the few parts per billion. Some have odors, and some, including formaldehyde, can be toxic or carcinogenic over extended exposure. Inorganic contaminant gases are rarely generated inside a building, but radon can enter from the ground, and outdoor pollutants such as ozone, NOx and SOx can be a concern in some urban environments. Interestingly, oxygen depletion is seldom an issue, given the natural abundance of oxygen and the negligible depletion that can be induced by normal human activity. The banning of indoor cigarette smoking has led to improved air quality in buildings, but the need to remove contaminants and offset the buildup of CO 2 and VOCs is still imperative for indoor air management. To maintain wholesome air quality, current HVAC systems are designed to gradually replace the indoor air with outside air. Typically, the entire volume of air in a building is replaced 10 or more times per day by drawing outside air into the building after passing it through an air handler for conditioning and pretreatment. The conditioning of the outside air results in a significant incremental thermal load on the HVAC system; in fact, in warm and humid climates, air replacement is the single largest contribution to cooling load and can account for 40% to 50% of the cooling power consumption. Figure 1: Schematic of a Central HVAC System A number of companies, led by enverid Systems, have been collaborating on solutions that reduce the rate of air replacement and the energy waste associated with it, while maintaining optimal indoor air quality (IAQ). The novel approach diverts part of the return airflow through a unique air treatment module designed to remove CO 2 and VOCs, and send the treated indoor air back into circulation. With this method, the intake of outside air is substantially reduced, by as much as 80% to 90%, depending on the original outside air intake rate and the minimum exhaust requirements. The residual amount of outside air intake, required for 2

3 maintaining building pressure, still enables the building air to be replaced, but at a much lower rate, typically just 1 or 2 times per day instead of 10 or more times. This reduction brings about a commensurate 80% to 90% reduction in the thermal load associated with air replacement. The air treatment module is referred to as an HVAC Load Reduction, or HLR, module (Figure 2). Figure 2: A schematic representation of the HLR (HVAC Load Reduction) module for removal of CO 2 and VOCs from indoor air. Technology The HLR module approach to indoor air quality management is based on a combination of unique sorbent materials that are (a) highly targeted at the unwanted contaminants prevalent in indoor air, and (b) easily regenerated for repeated cyclical use in what is essentially a hybrid temperature/concentration swing adsorption (TCSA) cycle. The cycle is comprised of two phases: adsorption and regeneration. In adsorption mode, indoor air flows through the sorbents which capture and hold the contaminants, while clean air flows back into the building; this can continue for several hours until one or more of the sorbents is saturated. In regeneration mode, the module is sealed off from the building by means of automated dampers, and the adsorbents are flushed with heated outside air, purging the contaminants and returning the sorbents to their clean state, so they can be put back to work. The TCSA technology enables the treatment of indoor air using small units that can be easily installed and connected alongside the existing HVAC system. The feasibility of the HLR module solution is based in part on a new generation of CO 2- sorbent materials created through government and university research on carbon capture and sequestration (motivated by concerns about atmospheric greenhouse gases and global climate change). These solid sorbents are chemically designed for highly targeted CO 2 capture at rapid flow rates and at ambient temperatures. No less importantly, captured CO 2 is readily desorbed, or released, from the sorbent material at moderately elevated temperatures, as low as C ( F), thus allowing low energy reconditioning of the CO 2 sorbent materials that can be achieved with inexpensive or even free heat sources. But CO 2 management is only one part of the picture. Most VOC removal is achieved by a different sorbent material, formed in a mesh of high-surface-area carbon fibers which are exceptionally efficient at capturing a wide range of organic and inorganic gas molecules. This technology has seen industrial and military use for years, and can work extremely well for 3

4 many indoor air contaminants. Some VOCs are inadequately captured by this mesh notably and very importantly, formaldehyde. For these VOCs, proprietary adsorbents and catalysts are incorporated into the system to complete the job. The combination of sorbents used in HLR modules are deployed in multiple replaceable cartridges in a compact, modular mechanical layout that easily lends itself to scalability for different airflow rates and building air volumes. The cartridges are held in a sealed chassis with motorized dampers that manage the TCSA cycle. This forms the entire HLR module, which is positioned in the vicinity of the return air flow path, with ducted connections to the return air as well as an inlet and exhaust for outside air used during the reconditioning phase of each cycle. While material science and chemical engineering are the foundation of this technology, operational algorithms and control software that manage the timing of reconditioning cycles and air flow rates make the technology practical and cost effective. Sensors for CO 2 and VOCs are positioned at the inlets and outlets, and their readings are used by a central processor to monitor sorbent performance and determine when regeneration is needed. The sophistication of the software is key in enabling a relatively modest amount of sorbent to maintain desirable air quality in a larger building, without excessive regeneration downtime and energy costs. The combination of unique sorbents, compact mechanical elements and smart algorithms presents a complete and economically viable solution to managing all indoor air gas contaminants. Figure 3. Left: Rooftop installation of two HLR-1000B units. Middle: Mechanical room installation of the HLR-500B in a mechanical room of a high-rise office tower. Right: Mechanical room installation of the ultra-compact HLR-500C in a Houston mid-rise office building in this particular case positioned on top of the existing air handler. Load Reduction and Energy Savings Energy savings can be modeled for any given set of conditions accounting for outdoor temperature and humidity and comparing the amount of outside air intake in conventional ventilation rates corresponding to ASHRAE Guideline 62.1 versus the reduction in outside air intake enabled with the HLR module. enverid has calculated these savings, and in a wide range of summer climates we ve determined that cooling loads can be reduced by 20% to 50%. The reduction is most impressive when humidity levels are high and latent heat is the dominant driver of the cooling load. Savings are lower in temperate and dry climates, and the 4

5 solution is not applicable when no cooling is required or when the HVAC is operated in economizer mode (maximizing outside air). The HLR s operation does require some energy, which is subtracted from the gross savings to yield the net energy savings. Much of the annual HVAC costs accrue when cooling loads are highest and the relative potential savings are correspondingly high. Accordingly, the annualized savings can come in at 20% or more in many large cities around the world. In one carefully monitored installation of the HLR, a very precise week-to-week comparison of heat load was performed on a single rooftop air handling unit (AHU) rated at about 10,000 cubic feet per minute (CFM) that was supplied chilled water from a central chiller plant. Heat load was determined by constantly measuring the flow rate and temperature of the incoming and outgoing chilled water. On alternating weeks, the AHU was operated (a) with normal intake of outside air and (b) with minimal intake (enough to maintain building pressure), while treating contaminants with a prototype HLR module. The total chilled water energy consumption was summed for each week. The experiment was conducted over a seven-week period in the summer of 2012, and the results show approximately 50% reduction in heat load during the weeks where the outside air intake was minimized (Figure 4). Figure 4: Results from the first HLR prototype test, comparing weekly cooling power under conventional operation (shown in gray) with reduced outside air intake enabled by the HLR module (shown in green). Load is reduced by as much as 50%. In another installation this one in an office building in central Texas in late summer 2013 a more granular comparison of energy consumption was performed, day by day, over the course of a six-week period from mid-august to late-september. The climate was moderately dry, with peak daytime temperatures between 90 F and 100 F or 32 to 38 C, and with coinciding relative humidity in the range of 25% to 40%. What made this test particularly interesting is that, unlike the first installation, it was a 24 7 facility that ran its air conditioning around the clock, so energy impact was relative to a full 24-hour cycle. Night temperatures dropped significantly and the air often would reach dew point by dawn. Here too, chilled water was metered 5

6 to measure the cooling power load. Over the course of the six-week period, a 39% reduction in cooling power per day was realized when operating in HLR mode. While the aggregate energy savings throughout the year translates into the annual financial savings associated with the electricity bill, the reduction in peak load is a very important consideration for a number of reasons. First, peak demand drives grid overload and the economic cost of peak power is extremely high whether or not it is passed on to the end user in the form of demand charges or variable rates. Second, peak load is the driver of design specifications for all HVAC systems. A substantial reduction in peak load cascades into reduced and less expensive design requirements for the entire cooling infrastructure. As a result, it also allows the HVAC to operate for longer durations at optimal, full loading conditions, which generally yields higher efficiency. In the Texas installation, air quality remained very good with the HLR module. CO 2 levels were continuously monitored in several locations and were successfully maintained near or below 800 ppm at all times, which was a very good result given the high occupant density. VOC levels were monitored continuously with a VOC sensor, and air samples were taken at multiple times and dates, and sent to analytical labs for comprehensive, highly granular analysis and comparison. Total VOC levels, as well as specific levels for the most salient VOCs, were similar to the levels seen under conventional ventilation. Formaldehyde levels were actually lower under HLR treatment than under ventilation. Importantly, the HLR system has built-in feedback mechanisms that can keep up with changing levels of contaminants inside the building, so contaminant levels are always controlled for satisfactory air quality. It is interesting to note that the substantial reduction of outside air intake actually has the potential to deliver some important indoor air quality improvements, particularly in heavily polluted urban environments. It also reduces the particle contamination load on the HVAC filtration systems, which can be quite pronounced due to natural outdoor dust and/or man-made smoke and fumes. A further benefit is less water condensation on the main coils. Economic Analysis For the purpose of this analysis we focus only on direct cost savings and net annual energy savings, without factoring in secondary benefits or utility incentives like differential rates, rebates or penalties. Here it is important to distinguish two different use cases for the HLR module: As an integrated feature included in a new installation As a retrofit to an existing HVAC system The economics in the first case new installations are helped by two factors: minimal incremental costs associated with the installation, and reduced cooling capacity requirements due to peak load reduction. The latter offsets the entire incremental cost of the HLR module(s), making for a very compelling economic value proposition. In retrofit situations, we examine the most common case of a retrofit by focusing on the segment of mid-size to large commercial buildings, including office buildings, hotels, malls, and other public venues. The following case analysis applies to a 100,000 sq ft commercial building which would typically be served by 5 to 10 air handlers and a corresponding number of HLR modules. In this example, typical airflow could be 100,000 CFM and maximum design occupancy might be approximately 6

7 500 persons. We compare three sub-cases in terms of energy cost per sq ft, but assume 20% savings in all three cases. As demonstrated below (Table 1), the total annual savings are significant. A complete economic analysis would have to take into consideration the cost of the HLR unit as well as the installation expenses and the annual maintenance costs, which are outside the scope of this paper. However, based on these anticipated savings and with a relatively compact and simple mechanical design of an HLR module, the economic case for an after-market retrofit looks very advantageous, especially in regions where there are long cooling seasons or where electricity rates are high. The authors estimate the return on investment (ROI) period will typically fall within a two- to three-year timeline in most warm and/or humid climate zones. Climate Case: Temperate Warm Tropical / Hot Annual Cooling Cost per sqft $1.50 $2.5 $4.00 Annual Cost of Power $150,000 $250,000 $400,000 Annual Percent Savings 20% 20% 20% Gross Savings per year $3,000 $50,000 $80,000 Table 1: Economics of the HLR system for a 100,000 sqft zone, comparing three representative climate scenarios. The case for new installation is even more compelling. Consider a 100,000 CFM installation requiring 250 tons of peak cooling power. Because peak load reduction is so significant, even a conservative estimate would allow a design with 20% less cooling power, namely only 200 tons. This results in smaller chillers, water lines, transformers, lesser weight, and more. These savings alone would cover the incremental cost of installing the HLRs, and would create a positive economic case for virtually any climate and utility rate. Comparison to Current Technologies The energy cost of air replacement has been a challenge for many decades, but two existing approaches provide partial relief to this challenge. The first is energy recovery ventilation (ERV) and the second is demand-controlled ventilation (DCV). ERV maintains the conventional amount of ventilation, but uses various types of heat exchange elements to transfer energy between the exhaust air leaving the building and the incoming fresh air. The more sophisticated of these systems use enthalpy wheels that transfer heat and humidity between the two air streams. However, even in the most advanced of these systems, only a fraction of the heat is successfully transferred. Additionally, the amount of energy that can be recovered is limited by the amount of exhaust air available in the vicinity of the fresh air inlet. Adding together the cost and the maintenance required for these systems, they have demonstrated fairly poor ROI. Many decades after their introduction, the adoption rate of ERVs remains very low. HLR promises to offer substantially higher energy savings and a simpler and more reliable mechanical solution. DCV is a method of reducing ventilation without treating the air, simply by monitoring CO 2 levels in the building and adjusting ventilation rates accordingly. Energy savings are achieved when occupancy is 7

8 substantially lower than that for which the building was designed. While easier to retrofit than ERV, this approach does not have the ability to reduce peak load or peak design requirements, and perhaps more troubling, it generally ignores VOCs. Since the source of many VOCs is not the human occupants but rather inanimate objects and materials in the building, these are not correlated with CO 2 and therefore in most settings a passive DCV system does not really have the ability to guarantee acceptable IAQ. Indeed, some practitioners view HLR as an advanced form of DCV, not only for actively mitigating CO 2 accumulation but also for monitoring and actively managing VOCs. Summary A new technology is now commercially available for HVAC load reduction and energy savings, by means of selective removal of CO 2 and VOCs from indoor air. Eliminating these indoor contaminants enables high indoor air quality with less outside air ventilation, thereby saving 20% or more of the energy consumed. The HLR module can be retrofitted onto a wide variety of existing HVAC systems and promises a very attractive ROI, especially in warmer and humid climates where cooling costs are high. The excellent economics and a number of secondary benefits position this new technology as a superior solution to energy recovery systems, setting a new standard for green buildings. 8

2015 North American HVAC Technology Innovation Award

2015 North American HVAC Technology Innovation Award 2015 2015 North American HVAC Technology Innovation Award Contents Background and Company Performance... 3 Industry Challenges... 3 Technology Attributes and Future Business Value of enverid Systems...

More information

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,

More information

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality

More information

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager

More information

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng. HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains

More information

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM 1 Application Note AT-102 THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM Lawrence B. Kilham 1 and Randall M. Dodd 2 1 Eco Sensors, Inc. Santa Fe, New Mexico, USA larry@ecosensors.com

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

Indoor Air Quality FILL YOUR HOME WITH AIR THAT IS AS CLEAN AS IT IS COMFORTABLE. READ ONLY

Indoor Air Quality FILL YOUR HOME WITH AIR THAT IS AS CLEAN AS IT IS COMFORTABLE. READ ONLY Indoor Air Quality FILL YOUR HOME WITH AIR THAT IS AS CLEAN AS IT IS COMFORTABLE. QUALITY AIR STARTS HERE. AccuExchange Energy Recovery Ventilator Improve your home s indoor environment by exchanging stale

More information

How To Design A Building In New Delhi

How To Design A Building In New Delhi ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption

More information

Guide to Minimizing Compressor-based Cooling in Data Centers

Guide to Minimizing Compressor-based Cooling in Data Centers Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi

More information

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce

More information

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J. Reducing Building HVAC Costs of site rec By Stephen J. Pargeter Building owners are caught between two powerful forces the need to lower energy costs and the need to meet or exceed outdoor air ventilation

More information

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming

More information

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Optimization of Water - Cooled Chiller Cooling Tower Combinations Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable

More information

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

Description of Thermal Oxidizers

Description of Thermal Oxidizers Description of Thermal Oxidizers NESTEC, Inc. is a full service equipment supplier specializing in solutions for plant emission problems. The benefit in working with NESTEC, Inc. is we bring 25+ years

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)

CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning) CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning) Objectives Survey current HVAC system(s), operating procedures, and maintenance schedule. Analyze results of energy audit for HVAC system(s)

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

HVAC Basic Science - System Capacity

HVAC Basic Science - System Capacity HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414

More information

What is LEED? Why pursue LEED accreditation? How does LEED accomplish these goals? Sustainable sites Water efficiency Energy and Atmosphere

What is LEED? Why pursue LEED accreditation? How does LEED accomplish these goals? Sustainable sites Water efficiency Energy and Atmosphere Green AAON for What is LEED? Sustainability and green have recently become terms used within the building industry (and others) to refer to a construction project that has low environmental impact, or

More information

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS William K. Scullion, Application Engineering Leader, MEGTEC Systems, De Pere, WI Introduction Competitive pressures continuously motivate us to examine our

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

Bring the fresh in. Dedicated Outside Air Systems

Bring the fresh in. Dedicated Outside Air Systems Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Drives and motors. A guide to using variable-speed drives and motors in retail environments

Drives and motors. A guide to using variable-speed drives and motors in retail environments Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility

More information

Ventilation Solutions Fresh Air Solutions for Ductless Heating & Cooling. fantech

Ventilation Solutions Fresh Air Solutions for Ductless Heating & Cooling. fantech Ventilation Solutions Fresh Air Solutions for Ductless Heating & Cooling 2 Ductless Ventilation & Fresh Air Solutions We can fill your home with healthy, fresh air Indoor Air Pollution is real, and it

More information

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is

More information

HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons

HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Award-Winning Innovation in Data Center Cooling Design

Award-Winning Innovation in Data Center Cooling Design Award-Winning Innovation in Data Center Cooling Design Oracle s Utah Compute Facility O R A C L E W H I T E P A P E R D E C E M B E R 2 0 1 4 Table of Contents Introduction 1 Overview 2 Innovation in Energy

More information

SAM HOUSTON STATE UNIVERSITY

SAM HOUSTON STATE UNIVERSITY PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle

More information

Using Time-of-Day Scheduling To Save Energy

Using Time-of-Day Scheduling To Save Energy The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.

More information

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range

More information

warm air for the healthiest, most comfortable home environment possible. This occurs with a system efficiency of up to 90%.

warm air for the healthiest, most comfortable home environment possible. This occurs with a system efficiency of up to 90%. Lifebreath delivers a complete indoor climate control package Indoor comfort in a small package The patented Lifebreath Clean Air Furnace combines the fresh air benefits of the Heat Recovery Ventilator

More information

Preliminary Final Proposal

Preliminary Final Proposal 1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient

More information

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition IEQ Management Plan GH Phipps Construction Companies 5995 Greenwood Plaza Blvd., Suite 100 Greenwood Village, Colorado 80111-4710 303.571.5377 PHONE www.ghphipps.com Denver Museum of Nature and Science

More information

Energy Efficiency. Energy Efficient Home Cooling:

Energy Efficiency. Energy Efficient Home Cooling: Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb

More information

Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord 09-20-2012

Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord 09-20-2012 Air Side Economizers and Energy Recovery - Improvements and New Regulations Richard Lord 09-20-2012 Introduction For commercial buildings the use of outside air for cooling and ventilation is an important

More information

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy

More information

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Because HVAC systems comprise a large amount of a building s operating costs, it makes sense to ensure these systems

More information

for K-12 School Buildings

for K-12 School Buildings Advanced Energy Design Guide for K-12 School Buildings HVAC Section John Murphy Applications Engineer, LEED AP Trane La Crosse, Wisconsin jmurphy@trane.com www.trane.com AEDG-K12 HVAC Subcommittee John

More information

SIMULATION OF RADIANT COOLING PERFORMANCE WITH

SIMULATION OF RADIANT COOLING PERFORMANCE WITH SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

Energy Efficiency in Industrial HVAC Systems

Energy Efficiency in Industrial HVAC Systems Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards

More information

Specification. Indoor Air Quality Management

Specification. Indoor Air Quality Management GREENGUARD Environmental Institute 2211 Newmarket Parkway, Suite 110 Marietta, GA 30067 1.800.427.9681 Specification Indoor Air Quality Management This Master Specification section is intended for use

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

WHOLE-HOUSE VENTILATION SYSTEMS

WHOLE-HOUSE VENTILATION SYSTEMS Technology Fact Sheet WHOLE-HOUSE VENTILATION SYSTEMS Improved control of air quality Buildings for the 21st Century Buildings that are more energy efficient, comfortable, and affordable that s the goal

More information

Catalyst RTU Controller Study Report

Catalyst RTU Controller Study Report Catalyst RTU Controller Study Report Sacramento Municipal Utility District December 15, 2014 Prepared by: Daniel J. Chapmand, ADM and Bruce Baccei, SMUD Project # ET13SMUD1037 The information in this report

More information

Year project completed or estimated year of completion: October 2014

Year project completed or estimated year of completion: October 2014 Name (Mr/Ms/Dr): Mr Rainer Tenius Job title: General Manager Company s name: Swissôtel Merchant Court, Singapore Award won: BCA Green Mark Award (Platinum) Name of Project that won the award, if applicable:

More information

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some

More information

Tim Facius Baltimore Aircoil

Tim Facius Baltimore Aircoil Presented By: Tim Facius Baltimore Aircoil Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for the benefit of

More information

OptiNet Applications. A Review of the Unique Requirements for a Facility Monitoring System. White Paper Series

OptiNet Applications. A Review of the Unique Requirements for a Facility Monitoring System. White Paper Series OptiNet Applications A Review of the Unique Requirements for a Facility Monitoring System White Paper Series A Review of the Unique Requirements for a Facility Monitoring System Overview The surging cost

More information

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN?

GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN? GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN? Richard C. Niess 1 Gilbert & Associates / Apogee Interactive, Inc., Gloucester Point, Virginia 23062 Phone & Fax (804) 642 0400 ABSTRACT

More information

Air-Conditioning Buying Guide

Air-Conditioning Buying Guide Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence

More information

Flexibility, Efficiency In San Antonio Arena

Flexibility, Efficiency In San Antonio Arena 2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not

More information

Robert McCabe Director, Health Care Solutions HTS Chicago. Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade

Robert McCabe Director, Health Care Solutions HTS Chicago. Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade Robert McCabe Director, Health Care Solutions HTS Chicago Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade Biography Robert McCabe has been involved in commercial

More information

A MAJOR STEP IN APPLIED INNOVATION. KCC Climate Management System. Powered by

A MAJOR STEP IN APPLIED INNOVATION. KCC Climate Management System. Powered by A MAJOR STEP IN APPLIED INNOVATION KCC Climate Management System Powered by KCC Climate Management System Powered by THE POWER OF DISRUPTIVE TECHNOLOGY YIELDS A CUSTOMER-FIRST HVAC DESIGN STRATEGY REDUCES

More information

Top 10 Energy Efficiency Opportunities

Top 10 Energy Efficiency Opportunities Top 10 Energy Efficiency Opportunities 1 Federal Utility Partnership Working Group San Francisco, 5/22/2013 Siva Sethuraman Customer Energy Solutions PG&E 2 Whole Building A comprehensive, performance-based

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied

More information

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,

More information

White Paper: Free Cooling and the Efficiency of your Data Centre

White Paper: Free Cooling and the Efficiency of your Data Centre AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS

CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS by Dr. Bing Chen and Prof. John Bonsell Passive Solar Research Group University of Nebraska-Lincoln Omaha campus and Richard

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air 0 Optimal Air Quality: Critical to Hotels Provides comfortable environment for guests no overcooling Protects building, carpets

More information

ECHO System for Basements

ECHO System for Basements ECHO System for Basements Homeowners looking for more space are all too familiar with the cold, damp and dingy basement. Now, the Enclosure Conditioned Housing (ECHO) System TM, winner of the Ottawa-Carleton

More information

Energy Saving Fact Sheet Air Conditioning

Energy Saving Fact Sheet Air Conditioning Energy Saving Fact Sheet Air Conditioning Get your air conditioning into better shape Everyone wants air conditioning. But don t let your existing system, or one that you re considering installing, burn

More information

Quick wins for energy savings in buildings

Quick wins for energy savings in buildings Quick wins for energy savings in buildings Choosing low energy air filters for both optimized energy performance and indoor air quality Executive Summary HVAC systems heat, cool and clean the air within

More information

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s

More information

34% 81% 84% 19% GOLD PROJECT HIGHLIGHTS. LEED Facts. Stubbs Laboratory

34% 81% 84% 19% GOLD PROJECT HIGHLIGHTS. LEED Facts. Stubbs Laboratory HARVARD UNIVERSITY FACULTY OF ARTS AND SCIENCES LEED-CI V3.0 STUBBS LABORATORY GORDON MCKAY LABS BUILDING Gordon McKay Building, 9 Oxford Street, Cambridge, MA 02138 GOLD The Stubbs Laboratory is a 2,035

More information

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent

More information

CONTROL STRATEGIES FOR HVAC SYSTEMS

CONTROL STRATEGIES FOR HVAC SYSTEMS CONROL SRAEGIES FOR HVAC SYSEMS ZBIGNIEW POPIOLEK Department of Heating, Ventilation and Dust Removal echnology Silesian University of echnology, Poland 1 Definition of control: to apply a regulating influence

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

A heat pump system with a latent heat storage utilizing seawater installed in an aquarium

A heat pump system with a latent heat storage utilizing seawater installed in an aquarium Energy and Buildings xxx (2005) xxx xxx www.elsevier.com/locate/enbuild A heat pump system with a latent heat storage utilizing seawater installed in an aquarium Satoru Okamoto * Department of Mathematics

More information

Radford University. Indoor Air Quality Management Plan

Radford University. Indoor Air Quality Management Plan Radford University Indoor Air Quality Management Plan Spring 2015 Introduction Concerns with Indoor Air Quality (IAQ) have increased since energy conservation measures were instituted in office buildings

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST Guruprakash Sastry, Senior Manager Green Initiatives Infosys Limited, Bangalore, INDIA ABSTRACT Radiation

More information

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem

More information

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation

More information

Answers to Your Questions from the Webinar

Answers to Your Questions from the Webinar 2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in

More information

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building. MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating

More information