WORKER PERFORMANCE AND VENTILATION: ANALYSES OF TIME-SERIES DATA FOR A GROUP OF CALL-CENTER WORKERS
|
|
|
- Gwendolyn Cole
- 10 years ago
- Views:
Transcription
1 WORKER PERFORMANCE AND VENTILATION: ANALYSES OF TIME-SERIES DATA FOR A GROUP OF CALL-CENTER WORKERS WJ Fisk *1, PN Price 1, D Faulkner 1, DP Sullivan 1, DL Dibartolomeo 1 CC Federspiel 2, G Liu 2, and M Lahiff 2 1 Lawrence Berkeley National Laboratory 2 University of California, Berkeley ABSTRACT We investigated the relationship of ventilation rates with the performance of advice nurses working in a call center. Ventilation rates were manipulated; temperatures, humidities, and CO 2 concentrations were monitored; and worker performance data, with 30-minute resolution, were collected. Multivariate linear regression was used to investigate the association of worker performance with building ventilation rate, or with indoor CO 2 concentration (which is related to ventilation rate per worker). Results suggest that the effect of ventilation rate on worker performance in this call center was very small (probably less than 1%) or nil, over most of the range of ventilation rate (roughly 12 L s -1 to 48 L s -1 per person). However, there is some evidence of worker performance improvements of 2% or more when the ventilation rate per person was very high, as indicated by the indoor CO 2 concentration exceeding the outdoor concentration by less than 75 ppm. INDEX TERMS Carbon dioxide, Offices, Productivity, Ventilation rates, Worker performance INTRODUCTION In previous studies, increased ventilation rates and reduced indoor carbon dioxide concentrations have been associated with improvements in health at work (Seppanen et al., 1999) and with increased performance in work-related tasks. Only a few studies have assessed the relationship of ventilation rates with worker performance. In a study of 35 Norwegian classrooms, higher concentrations of CO 2, which indicate lower rates of outside air ventilation per person, were associated with poorer performance (p < 0.01) in computerized tests of reaction time (Myhrvold et al., 1996); however, the percentage change in performance was not specified. In a study by Nunes et al. (1993), workers who reported building-related health symptoms, known to be associated with lower ventilation rates (Seppanen et. al., 1999), took 7% longer to respond in a computerized neurobehavioral test of sustained visual attention (p < 0.001) and had 30% higher error rates in a symbol-digit substitution test of speed and coding ability. In laboratory experiments by Wargocki et al. (2000), increasing the ventilation rate in a room with a carpet from a complaint building was associated with improvements of a few percent in speed or accuracy of several simulated work tasks such as text typing, addition, proof reading, and creative thinking (p < 0.05). The difficulty of defining and measuring the cognitive performance of workers has been one of the barriers to studying worker performance in real work places. However, for a few types of cognitive work, worker performance has been clearly defined and routinely measured by the employer. For example, in call centers, large pools of workers interact with clients via the telephone and enter data or process information associated with the telephone calls. To track * contact author [email protected]
2 worker performance, call centers frequently have automatic systems that record data on worker speed and type or purpose of the calls. Consequently, call centers are an appropriate setting for studies of the dependence of work speed, but not work quality, on indoor environmental quality (IEQ). This paper describes such a study in a call center operated by a health maintenance organization. METHODS The approach employed in this study was to manipulate outside air ventilation rates and monitor indoor air temperatures (which varied naturally), while collecting telephone call data that quantified worker performance at a call center located in the San Francisco Bay Area. Data were collected between July 28 and October 24, 2000 and analyzed with multivariate statistical models. The workforce was blinded regarding all aspects of the study, except that they were aware that indoor air temperatures were being monitored. The call center had a floor area of 4,600 m 2, sealed windows, carpeted floors, a no smoking policy, and a maximum worker density of 6.3 persons per 100 m 2. The call center was heated, cooled, and ventilated by variable air volume (VAV) air handling units (AHUs) that modulated the rates of supply of cool or warm air to maintain indoor air temperatures in the desired range. Each AHU had an economizer control system that modulated the rate of outside air supply, above a minimum rate established by the building code, with the goal of minimizing costs for heating and cooling; however, to prevent unplanned changes in outside air supply the economizer controls were deactivated during most experimental periods. The workers were registered nurses (RNs) who provided medical advice. Each RN had a computer and telephone with a headset. Workers were present in the building at all times and days, although the number of workers was highly variable, with the largest workforce on weekday mornings. The maximum number of RNs in the building during this study was 119. We added equipment to each AHU enabling automatic manipulation and measurement of outside air ventilation rates. AHU supply flow rates were measured using arrays of pitot tubes in supply ducts, with the pressure differences logged. The outside air flow rate in each AHU was computed as the product of the supply airstream flow rate and the fraction of outside air (FOA) in this airstream. We used a CO 2 monitor calibrated weekly to measure concentrations of CO 2 every 7.2 minutes in the outside air, return, and supply airstreams and employed a simple mass balance calculation to compute the FOA. The AHUs had dampers for modulation of the FOA. Fixed damper positions for low ventilation rate periods were selected to match the code-minimum outside air supply rate of 12.0 L s -1 per occupant at maximum occupancy (0.76 L s -1 per square meter of floor area and 292 persons). The fixed damper positions for medium and high ventilation rates were selected to provide approximately twice and four-times the code minimum. In a fourth ventilation setting, the normal control systems for the AHU s outside air supply, including the outside air economizers, were activated. We anticipated that this mode of operation (called economizer mode) would typically provide a ventilation rate greater than eight times the code minimum. In practice, ventilation rates in economizer mode varied considerably. Using these methods, we scheduled periods of ventilation in each of the four control modes: low, medium, high, and economizer mode. The intent to have randomized ventilation rates that changed daily during weeks 3 6 and 8 10 was met reasonably well. During weeks 1, 2, 7, 11 and 13, we intended to fix the ventilation rates at the low, medium, high, or
3 economizer setting for one-week periods; however, the control system failed during some periods. The resulting schedule of ventilation control modes is provided in Table 1. The control system resulted in a wide range of ventilation rates; however, these ventilation rates were not sufficiently repeated to use the control mode as a categorical surrogate for the ventilation rate. Thus, measured ventilation rates and carbon dioxide concentration were used in analyses of the worker performance data. Table 1. Ventilation control schedule. L, M, and H refer to fixed damper positions for low, medium, and high ventilation rates. E refers to control of ventilation rates by the economizer. Week Day F L H E H L E M M H M E E E Sa L H L E H M M M M L E E E Su L H H L M L M M E M E E E M L H E H L M M M M H E E L Tu L H M E H L M L H E H H E W L H H L E H M M L E H E -- Th L H M H M E M L E E H E -- Air temperatures were measured, with an accuracy of approximately 0.3 o C, every one minute at 25 locations approximately one meter above floor level. The call center s automated call distribution (ACD) system monitored several performancerelated parameters. Worker performance for each half-hour period was summarized with the average handle time (AHT) of all of the calls that ended during that period. The AHT is the average time (averaged over all RNs and over the entire half hour) taken for each call, starting when the call was answered and ending when the RN completely finished all tasks associated with the call. For each half-hour period, the call center's computer calculated a number, called "nets", that estimated (based on prior experience and current number of incoming calls) how many extra RNs were on hand, compared to the number needed to have the average wait experienced by callers equal to a target wait time. For periods when the target wait times were exceeded, nets was negative. Nets was used as a variable in the data analyses, as a measure of the work demand on RNs. Our primary interest was the relationship between ventilation rate and RN performance measured by AHT. We expected ventilation rate to influence AHT by at most a few percent, which is less than the variation due to several other sources. To estimate effects of ventilation rate on performance with useful precision, we excluded some data from the analyses and controlled for other sources of variation in AHT using multivariate regression models. We discarded data outside the normal work week (Monday Friday, 7:30 a.m. 6:00 p.m.) when few workers were present. Data from a holiday (Labor Day) and the following day were excluded, and data from two additional days were excluded due to changes in computer software. As a proxy for ventilation per agent, we used the difference between the indoor and outdoor concentration of CO 2 ( CO 2 ) [linear, categorical, or piecewise linear] as the explanatory variable of primary interest. Linear regression was our main tool for analyzing the data: we regressed log(aht) on explanatory variables that were expected to be relevant. To control for potential confounding, we included a number of other variables in the regression models: number of RNs present, average relative humidity, a time-of-week indicator variable for each
4 half-hour period [which accounted for about 35% of the variation in log(aht)], buildingaverage temperature (Celsius) minus 23 o C, and (building-average temperature minus 23 o C) 2 to account for the possibility of a non-linear relationship between temperature and performance. We also included a piecewise linear normalized nets variable, normalized to the number of workers on duty. Each data point was weighted by the number of calls received during the half hour, although the weights were not highly variable, nor were they very influential. As described in Fisk et al (2001), the linear regressions adjusted for the temporal correlation of the residuals. RESULTS CO 2 concentrations were rarely below 100 ppm or above 450 ppm. CO 2 values tended to cluster into three wide clumps, corresponding to low, medium, and high damper settings, with economizer settings also tending to lead to fairly low or very low values of CO 2. The AHUs held the building-average temperature within a very narrow range during working hours. Ninety percent of the half-hourly work-day temperatures were between between 22.9 o C and 23.5 o C. Building average humidity almost never strayed outside the range 46% to 47%. Unsurprisingly, then, the regression coefficients associated with temperature variables and relative humidity, were all very small compared to their uncertainties. We fit several dozen regression models, using different definitions for the bin boundaries for number of calls, normalized nets, and CO 2, and using different subsets of the data. Measures of model fit were very similar for all models that included the full set of explanatory variables. In every model, the nets variables were highly influential. We now discuss two specific models for log(aht) in some detail. Each model includes the time-of-week, temperature, and nets variables. The two models differ in their handling of CO 2. Model B includes three CO 2 categorical variables, indicating whether CO 2 for each half hour was: ppm, ppm, or over 300 ppm. In Model C, the two lower CO 2 categories within Model B have been split, thus, Model C has five CO 2 categorical variables: 0-75 ppm, ppm, ppm, ppm, or over 300 ppm. Figure 1 shows the estimated model coefficients associated with each CO 2 bin, for Models B (lower plot) and C (upper plot). For each bin, the horizontal bar shows the range of CO 2 spanned by the bin, and the vertical error bar covers plus or minus one standard error. In each case, the lowest bin is defined to have no effect, a coefficient of In Model B with only three CO 2 bins, there is no evidence that lower CO 2 is associated with lower (faster) AHT -- indeed, the relationship points the other direction: the estimate for the high- CO 2 bin is about 1% faster than that for the lowest bin. (An effect of on log(aht) corresponds to a factor of exp(-0.009)=0.991 on AHT, which is very close to a 1% speed-up). However, this estimate is not very precise, with an uncertainty (one standard error) of approximately ± 0.6 percentage points. In contrast, the results from Model C with five bins suggest that very low CO 2 concentrations are associated with lower AHT (faster work) than are higher concentrations. All of the estimated coefficients for CO 2 concentrations over 75 ppm are around to 0.035, corresponding to handle times that are 2.5% to 3.5% slower than at the lowest CO 2. Moreover, these effects are all statistically significant (p < 0.05 for all bin coefficients). However, as we discuss below, we think the relationship between AHT and CO 2 is still far from conclusive.
5 Neither the Model B nor Model C results provide evidence that handle time increases with CO 2 over most of its range. A dependence of log(aht) on CO 2 is apparent only for CO 2 below about 150 ppm. When the ppm CO 2 category in Model B is split into two categories to produce Model C, the 0-75 CO 2 category has the lowest (fastest) values of log(aht), after adjusting for the other explanatory variables. Figure 1. Model coefficients for bins of CO 2 concentration, indicating the effect of CO 2 on log(aht) with the lowest CO 2 bin used as the reference. The lower and upper plots are results of Model B and Model C, respectively. Horizontal bars indicate CO 2 bin boundaries and vertical error bars represent ± one standard deviation. We also performed regressions using ventilation rate categories rather than CO 2 categories. There is no evidence for a dependency of AHT on ventilation rate. Even for the highest ventilation rates there is no evidence of reduced AHT. To the extent that there is an apparent ventilation-related effect in this study, it is due to ventilation rate per person (as indicated by CO 2 ) rather than ventilation per unit indoor volume. DISCUSSION We anticipated that performance differences associated with ventilation would be a few percent at most. It is very hard to study causes of such small performance differences in real work. The present study has inadequate statistical power to find effects smaller than about 2%; however, such small changes in productivity could still be economically important. In the present study, there were only forty half-hour periods (out of 1051) in which CO 2 was below 75 ppm. Nineteen of these periods occurred on a single day (the 78 th day of the study, a Friday), and all of the rest occurred during the following week. The entire apparent speedup in AHT indicated by Model C, for the below-75 ppm bin relative to the other bins, is based on data from only six different days, and 65% of those data are from two consecutive Fridays. Consequently, in spite of the low p-values, we do not consider the results of Model C to conclusively indicate a faster work-rate when CO 2 was very low and ventilation per worker
6 was very high. If the very high values of ventilation had occurred on 6 days spread throughout the study period, and the same results were found, we would have confidence that the observed effect was really due to ventilation rate. In the present case, though, we are not sure that ventilation is really affecting performance because some uncontrolled and unknown condition, coincident with the periods of very high ventilation rate, could have caused the increased performance. A limitation of these analyses is the incomplete separation of time of day from CO 2. As time of day increases, CO 2 generally increases (then decreases late in the day); therefore; controlling for time of day via the regression models could have partially obscured a relationship of CO 2 with worker speed. Including nets in the regression models may also have partially obscured a relationship of CO 2 with worker speed, because a decrease in work speed caused by higher CO 2 would result in a decrease in nets. The results of the present analysis may not apply to other buildings. For instance, it may be that in this building there are no strong indoor sources of pollutants that influence performance, but that in other buildings such sources exist. CONCLUSIONS If we exclude periods of very high ventilation rates per occupant (indicated by very low CO 2 ), we can conclude that the effect of ventilation rate on AHT was less than about 2%. There is some evidence that very high ventilation rates per occupant (very low CO 2 ) may lead to lower AHT (faster work rates), but the possibility of uncontrolled confounding makes this result less than conclusive in spite of high statistical significance (p < 0.05). ACKNOWLEDGMENTS This work was supported by the Assistant Secretary for Energy Efficiency and Renewable Energy, Office of Building Technology, State, and Community Programs, Office of Building Research and Standards of the U.S. Department of Energy (DOE) under contract No. DE- AC03-76SF00098 and by the Center for the Built Environment at U.C. Berkeley. REFERENCES Fisk WJ, Price PN, Faulkner D, et al Worker Productivity and Ventilation Rate in a Call Center: Analyses of Time-Series Data for a Group of Workers, Lawrence Berkeley National Laboratory Report, LBNL 49356, Berkeley, CA Myhrvold AN, Olsen E, Lauridsen O Indoor environment in schools pupils health and performance in regard to CO 2 concentrations. Proceedings of the 7 th International Conference on Indoor Air Quality and Climate - Indoor Air 1999, Vol. 4, pp SEEC Ishibashi Inc., Japan. Nunes F, Menzies R, Tamblyn RM, et al The effect of varying level of outside air supply on neurobehavioral performance function during a study of sick building syndrome. Proceedings of the 6th International Conference on Indoor Air Quality and Climate - Indoor Air 1993, Vol. 1, pp Indoor Air 1993, Helsinki. Seppanen OA, Fisk WJ, Mendell MJ Association of ventilation rates and CO 2 - concentrations with health and other responses in commercial and institutional buildings. Indoor Air Vol. 9(4), pp Wargocki P, Wyon DP, Sundell J, et al The effects of outdoor air supply rate in an office on perceived air quality, sick building syndrome (SBS) symptoms, and productivity. Indoor Air Vol.10(4), pp
Effect of Temperature on Task Performance in Offfice Environment
Effect of Temperature on Task Performance in Offfice Environment Olli Seppänen 1, William J Fisk 2, QH Lei 2 1 Helsinki University of Technology, Laboratory for Heating Ventilating and Air conditioning,
Catalyst RTU Controller Study Report
Catalyst RTU Controller Study Report Sacramento Municipal Utility District December 15, 2014 Prepared by: Daniel J. Chapmand, ADM and Bruce Baccei, SMUD Project # ET13SMUD1037 The information in this report
Causes and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators
Causes and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators Mark J. Mendell, Richard C. Diamond, William J. Fisk Environmental
Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues
LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental
Information paper 20. Prepared by: David Clark. book:
Information paper 20 Ventilation rates in offices and natural mechanical Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information
Quantification Methods for Employee Health and Productivity Rates based on Indoor Environmental Quality
Review Article ISSN 2278 1331 International Journal of Environmental Engineering Research, Volume 1, Issue 3, 2012, 104-114 Copyright 2012, All rights reserved Research Publishing Group www.rpublishing.org
COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI
Proceedings of Healthy Buildings 2000, Vol. 2 675 COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI Mikko Saari 1, Juhani Laine 1, Sami Karjalainen 1 and Klaus Hamström
APPLICATION OF DATA MINING TECHNIQUES FOR BUILDING SIMULATION PERFORMANCE PREDICTION ANALYSIS. email [email protected]
Eighth International IBPSA Conference Eindhoven, Netherlands August -4, 2003 APPLICATION OF DATA MINING TECHNIQUES FOR BUILDING SIMULATION PERFORMANCE PREDICTION Christoph Morbitzer, Paul Strachan 2 and
Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program
Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality
Indoor environment and productivity in office environment
Indoor environment and productivity in office environment summary of the key contents of REHVA Guidebook no 6 Olli Seppänen, professor Helsinki University of Technology Federation of European Heating and
Variable Air Volume - VAV
Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:
AP Physics 1 and 2 Lab Investigations
AP Physics 1 and 2 Lab Investigations Student Guide to Data Analysis New York, NY. College Board, Advanced Placement, Advanced Placement Program, AP, AP Central, and the acorn logo are registered trademarks
HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.
HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains
Analysis of HVAC Control Strategies
PUBLICATION DATE: Q1 2009 REF NUMBER: HVAC SWGII 006 03 HVAC SPECIAL WORKING GROUP Analysis of HVAC Control Strategies 06 Table of Contents 1 Introduction 2 2 Scope 3 3 Analysis 4 3.1 Strategy 1 4 3.2
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take
EXPERIMENTAL ERROR AND DATA ANALYSIS
EXPERIMENTAL ERROR AND DATA ANALYSIS 1. INTRODUCTION: Laboratory experiments involve taking measurements of physical quantities. No measurement of any physical quantity is ever perfectly accurate, except
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
Fairfield Public Schools
Mathematics Fairfield Public Schools AP Statistics AP Statistics BOE Approved 04/08/2014 1 AP STATISTICS Critical Areas of Focus AP Statistics is a rigorous course that offers advanced students an opportunity
Adequacy of Biomath. Models. Empirical Modeling Tools. Bayesian Modeling. Model Uncertainty / Selection
Directions in Statistical Methodology for Multivariable Predictive Modeling Frank E Harrell Jr University of Virginia Seattle WA 19May98 Overview of Modeling Process Model selection Regression shape Diagnostics
IBM SPSS Statistics 20 Part 4: Chi-Square and ANOVA
CALIFORNIA STATE UNIVERSITY, LOS ANGELES INFORMATION TECHNOLOGY SERVICES IBM SPSS Statistics 20 Part 4: Chi-Square and ANOVA Summer 2013, Version 2.0 Table of Contents Introduction...2 Downloading the
By Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates
Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb
OPTIMIZATION OF VENTILATION SYSTEMS IN OFFICE ENVIRONMENT, PART II: RESULTS AND DISCUSSIONS
OPTIMIZATION OF VENTILATION SYSTEMS IN OFFICE ENVIRONMENT, PART II: RESULTS AND DISCUSSIONS Liang Zhou, and Fariborz Haghighat Department of Building, Civil and Environmental Engineering Concordia University,
MEASURING RATES OF OUTDOOR AIRFLOW INTO HVAC SYSTEMS
LBNL-51583 MEASURING RATES OF OUTDOOR AIRFLOW INTO HVAC SYSTEMS William J. Fisk, David Faulkner, Douglas P. Sullivan, and Woody Delp Indoor Environment Department Environmental Energy Technologies Division
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?
Topic B3: Control of indoor environment CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Axel CABLE 1,*, Mads MYSEN 1,2, Kari THUNSHELLE 1 1 SINTEF,
BNG 202 Biomechanics Lab. Descriptive statistics and probability distributions I
BNG 202 Biomechanics Lab Descriptive statistics and probability distributions I Overview The overall goal of this short course in statistics is to provide an introduction to descriptive and inferential
Univariate Regression
Univariate Regression Correlation and Regression The regression line summarizes the linear relationship between 2 variables Correlation coefficient, r, measures strength of relationship: the closer r is
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,
Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window
Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window Ahsan Iqbal #1, Alireza Afshari #2, Per Heiselberg *3, Anders Høj **4 # Energy and Environment, Danish Building Research
5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment
5.6 Technical Specification: Premium Efficiency Electric Conditioning Equipment Small Premium Project Type: For Premium Conditioning Retrofit Projects: Projects that voluntarily replace existing unitary
Why Taking This Course? Course Introduction, Descriptive Statistics and Data Visualization. Learning Goals. GENOME 560, Spring 2012
Why Taking This Course? Course Introduction, Descriptive Statistics and Data Visualization GENOME 560, Spring 2012 Data are interesting because they help us understand the world Genomics: Massive Amounts
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
Short-Term Forecasting in Retail Energy Markets
Itron White Paper Energy Forecasting Short-Term Forecasting in Retail Energy Markets Frank A. Monforte, Ph.D Director, Itron Forecasting 2006, Itron Inc. All rights reserved. 1 Introduction 4 Forecasting
Investigation into the energy consumption of a data center with a thermosyphon heat exchanger
Article Mechanical Engineering July 2011 Vol.56 No.20: 2185 2190 doi: 10.1007/s11434-011-4500-5 SPECIAL TOPICS: Investigation into the energy consumption of a data center with a thermosyphon heat exchanger
Pacific Gas & Electric Company s 2012 Value of Service Study
Pacific Gas & Electric Company s 2012 Value of Service Study May 17, 2012 Prepared for: Pacific Gas & Electric Co. Prepared by: Michael Sullivan, Ph.D. Michael Perry, Ph.D. Josh Schellenberg, M.A. Jason
RESULTS OF ICARUS 9 EXPERIMENTS RUN AT IMRA EUROPE
Roulette, T., J. Roulette, and S. Pons. Results of ICARUS 9 Experiments Run at IMRA Europe. in Sixth International Conference on Cold Fusion, Progress in New Hydrogen Energy. 1996. Lake Toya, Hokkaido,
Indoor air quality monitoring made easy
Indoor air quality monitoring made easy with the Fluke 985 Particle Counter Application Note Introduction Energy savings is top of facilities owners agenda. HVAC system tends to be the largest contributor
2. Simple Linear Regression
Research methods - II 3 2. Simple Linear Regression Simple linear regression is a technique in parametric statistics that is commonly used for analyzing mean response of a variable Y which changes according
RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA.
1. There is verbiage in the hazardous material report referring to a state licensed abatement contractor. Within the recommendations part of the report (page 64 of 111 of the specification pdf) is the
Lean Six Sigma Analyze Phase Introduction. TECH 50800 QUALITY and PRODUCTIVITY in INDUSTRY and TECHNOLOGY
TECH 50800 QUALITY and PRODUCTIVITY in INDUSTRY and TECHNOLOGY Before we begin: Turn on the sound on your computer. There is audio to accompany this presentation. Audio will accompany most of the online
Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids
Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids Dr. J. M. Meyers Dr. D. G. Fletcher Dr. Y. Dubief 1. Introduction Last lab you investigated flow loss in a pipe due to the roughness
Guidance for Industry
Guidance for Industry Q2B Validation of Analytical Procedures: Methodology November 1996 ICH Guidance for Industry Q2B Validation of Analytical Procedures: Methodology Additional copies are available from:
3. Data Analysis, Statistics, and Probability
3. Data Analysis, Statistics, and Probability Data and probability sense provides students with tools to understand information and uncertainty. Students ask questions and gather and use data to answer
How To Forecast Solar Power
Forecasting Solar Power with Adaptive Models A Pilot Study Dr. James W. Hall 1. Introduction Expanding the use of renewable energy sources, primarily wind and solar, has become a US national priority.
VALIDATION OF ANALYTICAL PROCEDURES: TEXT AND METHODOLOGY Q2(R1)
INTERNATIONAL CONFERENCE ON HARMONISATION OF TECHNICAL REQUIREMENTS FOR REGISTRATION OF PHARMACEUTICALS FOR HUMAN USE ICH HARMONISED TRIPARTITE GUIDELINE VALIDATION OF ANALYTICAL PROCEDURES: TEXT AND METHODOLOGY
3. Pre-design applications
3. Pre-design applications 7S9X0 Environmental Performance of Buildings TU/e Dept. of the Built Environment Building Performance group Environmental Performance of Buildings 7S9X0 TU/e TU/e Building Building
Big Data, Socio- Psychological Theory, Algorithmic Text Analysis, and Predicting the Michigan Consumer Sentiment Index
Big Data, Socio- Psychological Theory, Algorithmic Text Analysis, and Predicting the Michigan Consumer Sentiment Index Rickard Nyman *, Paul Ormerod Centre for the Study of Decision Making Under Uncertainty,
AG-TQS-IAQ-00 March 4, 2002. Application Guide. TQS with IAQ Inlet
Application Guide TQS with IAQ Inlet Table of Contents Introduction 2 ASHRAE Standard 62 2 Outdoor Air Requirements For Ventilation For Commercial Buildings 3 EPA Report Energy Costs and IAQ Performance
EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010
EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a
Descriptive Statistics
Descriptive Statistics Descriptive statistics consist of methods for organizing and summarizing data. It includes the construction of graphs, charts and tables, as well various descriptive measures such
Example G Cost of construction of nuclear power plants
1 Example G Cost of construction of nuclear power plants Description of data Table G.1 gives data, reproduced by permission of the Rand Corporation, from a report (Mooz, 1978) on 32 light water reactor
American Society of Heating Refrigeration and Air Conditioning Engineers (ASHRAE) Procedures for Commercial Building Energy Audits (2004)
Excerpt from: American Society of Heating Refrigeration and Air Conditioning Engineers (ASHRAE) Procedures for Commercial Building Energy Audits (2004) 2004 American Society of Heating, Refrigerating and
Data Analysis Tools. Tools for Summarizing Data
Data Analysis Tools This section of the notes is meant to introduce you to many of the tools that are provided by Excel under the Tools/Data Analysis menu item. If your computer does not have that tool
Simple Linear Regression
STAT 101 Dr. Kari Lock Morgan Simple Linear Regression SECTIONS 9.3 Confidence and prediction intervals (9.3) Conditions for inference (9.1) Want More Stats??? If you have enjoyed learning how to analyze
Air Conditioning in Green Office Buildings?
Air Conditioning in Green Office Buildings? How to implement Demand Controlled Ventilation Stuttgart Rechte allein bei ICEBO 08 10.10.2008 CI / DrRo 1 Air Conditioning in Green Office Buildings ventilation
Technology: Heating, Ventilation and Air Condition (HVAC) Zone Controls
Accelerated Capital Allowances Eligibility Criteria Ref No.: HZC C2.1 Category: Process and Heating, Ventilation and Air conditioning (HVAC) Control Systems Technology: Heating, Ventilation and Air Condition
Data Center Energy Efficient Cooling Control Demonstration PIR 10 052. (formerly Federspiel Controls)
Data Center Energy Efficient Cooling Control Demonstration PIR 10 052 (formerly Federspiel Controls) Background 2009 PIER sponsored project resulted in the installation of intelligent supervisory control
SIMULATION OF RADIANT COOLING PERFORMANCE WITH
SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE
OMCL Network of the Council of Europe QUALITY MANAGEMENT DOCUMENT
OMCL Network of the Council of Europe QUALITY MANAGEMENT DOCUMENT PA/PH/OMCL (12) 77 7R QUALIFICATION OF EQUIPMENT ANNEX 8: QUALIFICATION OF BALANCES Full document title and reference Document type Qualification
Using Time-of-Day Scheduling To Save Energy
The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.
INVESTIGATION OF INDOOR AIR QUALITY PROBLEMS IN UNIVERSITY OFFICES WITH A QUESTIONNAIRE
INVESTIGATION OF INDOOR AIR QUALITY PROBLEMS IN UNIVERSITY OFFICES WITH A QUESTIONNAIRE Maneerat Ongwandee a, Namphung Dungkokkruad b a Faculty of Engineering, Mahasarakham University, Mahasarakham 44150,
J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design
Copyright 24, American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 79 Tullie Circle NE, Atlanta, GA. 3329. Reprinted by permission from the September 24 Issue of ASHRAE Journal
The Finnish Classification of Indoor Environment and Material Emissions
The Finnish Classification of Indoor Environment and Material Emissions Jorma Säteri Finnish Society of Indoor Air Quality and Climate, FiSIAQ Finnish Classification of Indoor Environment 2008 An update
Building Energy Management: Using Data as a Tool
Building Energy Management: Using Data as a Tool Issue Brief Melissa Donnelly Program Analyst, Institute for Building Efficiency, Johnson Controls October 2012 1 http://www.energystar. gov/index.cfm?c=comm_
Building HVAC Load Profiling Using EnergyPlus
Building HVAC Load Profiling Using EnergyPlus Dong Wang School of EEE Nanyang Technological University Singapore Email: [email protected] Abhisek Ukil, Senior Member, IEEE School of EEE Nanyang Technological
Adapting to Change: New Thinking on Comfort Natural ventilation in UK schools: design options for passive cooling Steven Firth* and Malcolm Cook
Proceedings of Conference: Adapting to Change: New Thinking on Comfort Cumberland Lodge, Windsor, UK, 9-11 April 2010. London: Network for Comfort and Energy Use in Buildings, http://nceub.org.uk Natural
ENERGY SAVING BY COOPERATIVE OPERATION BETWEEN DISTRICT HEATING AND COOLING PLANT AND BUILDING HVAC SYSTEM
Proceedings of Building Simulation 211: ENERGY SAVING BY COOPERATIVE OPERATION BETWEEN DISTRICT HEATING AND COOLING PLANT AND BUILDING HVAC SYSTEM Yoshitaka Uno 1, Shinya Nagae 1, Yoshiyuki Shimoda 1 1
Predicting Successful Completion of the Nursing Program: An Analysis of Prerequisites and Demographic Variables
Predicting Successful Completion of the Nursing Program: An Analysis of Prerequisites and Demographic Variables Introduction In the summer of 2002, a research study commissioned by the Center for Student
More efficiency in schools with HVAC, lighting and security
The worldwide standard for home and building management More efficiency in schools with HVAC, lighting and security Simply first class: Higher energy efficiency and more flexibility thanks to Synco HVAC
DK2 IEA. Replacing mechanical ventilation with natural ventilation at Enghøjskolen school in Denmark
IEA Energy Conservation in Buildings and Community Systems, Annex 36 Case studies overview Replacing mechanical ventilation with natural ventilation at Enghøjskolen school in Denmark 1 Photos DK2 Figure
Section 14 Simple Linear Regression: Introduction to Least Squares Regression
Slide 1 Section 14 Simple Linear Regression: Introduction to Least Squares Regression There are several different measures of statistical association used for understanding the quantitative relationship
A Primer on Forecasting Business Performance
A Primer on Forecasting Business Performance There are two common approaches to forecasting: qualitative and quantitative. Qualitative forecasting methods are important when historical data is not available.
MTH 140 Statistics Videos
MTH 140 Statistics Videos Chapter 1 Picturing Distributions with Graphs Individuals and Variables Categorical Variables: Pie Charts and Bar Graphs Categorical Variables: Pie Charts and Bar Graphs Quantitative
Simple Linear Regression Inference
Simple Linear Regression Inference 1 Inference requirements The Normality assumption of the stochastic term e is needed for inference even if it is not a OLS requirement. Therefore we have: Interpretation
MONITORING SCHOOL ENERGY CONSUMPTION
MONITORING SCHOOL ENERGY CONSUMPTION Goal(s): The mains goal of the energy monitoring activity are: To make the pupils and all school staff aware of school energy consumption; and To show how changes in
EVALUATING SOLAR ENERGY PLANTS TO SUPPORT INVESTMENT DECISIONS
EVALUATING SOLAR ENERGY PLANTS TO SUPPORT INVESTMENT DECISIONS Author Marie Schnitzer Director of Solar Services Published for AWS Truewind October 2009 Republished for AWS Truepower: AWS Truepower, LLC
Attached is a link to student educational curriculum on plug load that provides additional information and an example of how to estimate plug load:
Energy Conservation Tip #1 Always turn off all lights when you leave a room or when they are not needed. It is estimated that 26% of a building s electricity is used for lighting. For D-11 this equals
Gerard Mc Nulty Systems Optimisation Ltd [email protected]/0876697867 BA.,B.A.I.,C.Eng.,F.I.E.I
Gerard Mc Nulty Systems Optimisation Ltd [email protected]/0876697867 BA.,B.A.I.,C.Eng.,F.I.E.I Data is Important because it: Helps in Corporate Aims Basis of Business Decisions Engineering Decisions Energy
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Basics of HVAC Cleaning
Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project
Sound Power Measurement
Sound Power Measurement A sound source will radiate different sound powers in different environments, especially at low frequencies when the wavelength is comparable to the size of the room 1. Fortunately
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Example Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
The Effect of Schedules on HVAC Runtime for Nest Learning Thermostat Users
WHITE PAPER SUMMARY The Effect of Schedules on HVAC Runtime for Nest Learning Thermostat Users Nest Labs, Inc. September 2013! 1 1. Introduction Since the launch of the Nest Learning Thermostat in October
Sustainable construction criteria to evaluate the thermal indoor climate - further development of the BNB assessment tool and practical implementation
Fraunhofer Institute for Building Physics IBP Directors Univ. Prof. Dr. Ing. Gerd Hauser Univ. Prof. Dr. Ing. Klaus Sedlbauer Holzkirchen Branch Fraunhoferstrasse 10 83626 Valley / Germany IBP-Abstract