COLD. Basic Training Course III. November ESSE - Wilhelm Nießen

Similar documents
How To Design A Refrigeration System

UNIT 2 REFRIGERATION CYCLE

Split units TH with hermetic compressors

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING. Fitters notes

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

How Ground/Water Source Heat Pumps Work

Increasing the evaporation temperature with the help of an internal heat exchanger

Cooling system components, removing and installing

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight Temperature glide o C Boiling point (1 atm)

Energy savings in commercial refrigeration. Low pressure control

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Refrigeration Compressed Air Dryer Buran Ultrapulse

Fully automatic air conditioning service! Bosch ACS 600, 601 and 650 for the workshop

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

HVAC-02, Air Conditioning Troubleshooting and Repair

Rusty Walker, Corporate Trainer Hill PHOENIX

High Pressure Ammonia Systems New Opportunities

ON-VEHICLE INSPECTION

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July Prepared by

REFRIGERATION (& HEAT PUMPS)

Refrigeration Basics 101. By: Eric Nelson

Test Code: 8297 / Version 1

Chapter 3.4: HVAC & Refrigeration System

How To Understand Evaporator

A/C refrigerant system, overview

MP-4000 Alarm List (Software version or later)

Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system

High School Graduation years 2013, 2014, Unit/Standard Number

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

PREMIUM SERVICE. Service Manual. Water Dispenser. Model : PWC215T

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

Refrigeration Air Dryers. Catalogue

POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil

Product overview Air conditioning service units

Failure code manual. content

Characteristics of Evaporators

Refrigerated Air Dryers. Catalogue

Open Cycle Refrigeration System

COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 OBJECTIVES

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

SEALED SYSTEM DIAGNOSIS

How To Calculate The Performance Of A Refrigerator And Heat Pump

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing )

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, Table of Contents

New Trends in the Field of Automobile Air Conditioning

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30,

Waste Heat Recovery through Air Conditioning System

Refrigeration and Air Conditioning Mechanic On-the-Job Training Guide

UNDERSTANDING REFRIGERANT TABLES

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Heat Recovery In Retail Refrigeration

How To Know If A Refrigeration System Is Efficient

13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit

Central Air Conditioning Plants

System Diagnosis. Proper vehicle diagnosis requires a plan before you start

How to choose a heat pump and use it wisely

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!

Optimization of combined heating and cooling in Supermarkets

Refrigerant Choices for Commercial Refrigeration. Finding the Right Balance

HOW HVAC WORKS. How HVAC. Works PAGE 1

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Thermodynamics - Example Problems Problems and Solutions

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS

ENERGY SAVING WORT BOILING SISTEM IN BREWING FACTORY

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

The paper addresses the boil-off in the cryogenic industry and details the specifics of it when applied to vehicle LNG tanks.

ECOCIAT. Domestic hot water heat recovery unit

THE REPLACEMENT OF R-22

Boiler Calculations. Helsinki University of Technology Department of Mechanical Engineering. Sebastian Teir, Antto Kulla

Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR İ-COLD Rev. 00

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS

ThermoStar Refrigeration Air Dryers

Fully automatic air conditioning service! Bosch ACS 600, 601 and 650 for the workshop

Research on the Air Conditioning Water Heater System

Octopus for a sustainable future

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

P. A. Hilton Ltd REFRIGERATION & AIR CONDITIONING VAPOUR COMPRESSION HEAT PUMPS VENTILATION VOCATIONAL

AUTOMOTIVE AIR CONDITIONING

AIR CONDITION & REFRIGERATION INSTALLATION & REPAIR

WASHING PROCESS OF CARGO TANKS ON TANKERS FOR TRANSPORTATION OF CRUDE OIL

Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling

Home inspectors are not mold inspectors, however they do inspect for defects that

How air conditioning works

Guide to Good Commercial Refrigeration Practice. Part 2. System Design and Component Selection

User manual. Solid (FR 98,),

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

Perkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet

Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

HEATER, AIR CONDITIONING AND VENTILATION

Transcription:

COLD Basic Training Course III 1

COLD Measuring Temperature and Pressure for diagnosis 2

Temperatures in refrigeration circuit Surface temperature of the evaporator Surface temperature of the condensor Sub-cooled temperature Hot gas temperature Return gas temperature 3

h log p Diagram 2-2 = Super heating 2-3 = Condensing 3-3 = Subcooling 3-4 = Expansions Device 4-1 = Evaporating 1-1 = Suction pipe inside Fridge 1-1 = Suction pipe outside Fridge 1-2 = Compress power 4-1 = Refrigerating capacity qo 2-3 = Condencer capacity 1 Suction tube 20 C 2 Discharge tube 110 C 2-3 Condensing t 55 C 3-3 Subcooling 32 C 4-1 Evaporating t -25 C 1-1 Fridge/Freezer t 5 C/-18 C 1-1 Super heating 20 C 4

Temperatures in refrigeration circuit 5

Temperatures in refrigeration circuit Meassuring the return gas temperature: In the sucking pipe there should be vapour gas. The temperature is normally a bit warmer than the room temperature. When the sucking line is covered with hair frost or humidity there is a overfilling of the refrigeration cycle. 6

Temperatures in refrigeration circuit Meassuring the hot gas temperature: R12, R134a 50 C - 70 C R600a 40 C - 60 C Is only the hot gas temperature significant higher the sucking gas cooling of the compressor is not enough. The compressor carries to less refrigerant which can be caused by a leakage, partial blockade or air in the refrigeration circle. 7

Temperatures in refrigeration circuit Meassuring the sub-cooled temperature: In comparision to the hot gas temperature it should be 10 K - 15 K colder. If the condensor is not cooled enough (bad air circulation, pollution) the temperature increases as a consequence the pressure increases. The cooling power decreases 8

Fault diagnosis Average store temperature Enough air circulation Frost on evaporator (or measure it) Return gas temperature Hot gas temperature Sub-cooled temperature Everything okay? Yes No End of diagnosis. Open refrigeration circuit 9

Fault diagnosis R600a The following instruction is based to the refrigerant R600a. Regarding to the different steam - pressure values you can transfer R600a instruction to the other refrigerants. 10

Fault diagnosis R600a 1.Step (compressor out of function) Connect the suction gauge with the pipe of the sucking side. 11

Fault diagnosis R600a 2.Step (compressor out of function) Suction gauge displays positive pressure. Diagnosis: Coolant in the system. Attention: When the compressor is cold there can be a lot of coolant dissolved in the compressor oil. 12

Fault diagnosis R600a 3.Step (compressor is running) The normal pressure on the sucking side is lower than 0 bar. Suction gauge: -0,1 to -0,6 bar Torr gauge: 400 to 900 mbar Diagnosis: The refrigeration cycle is okay. 13

Fault diagnosis R600a 4.Step (compressor is running) The suction gauge displays pressure > 0 bar. Diagnosis: The compressor is defect. 14

Fault diagnosis R600a 5.Step (compressor is running) The suction gauge displays -0,1 to -0,6 bar. Diagnosis: The refrigeration cycle is okay. Attention: Even with the torr gauge it is not possible to detect a overfilling. 15

Fault diagnosis R600a 6.Step (compressor is running) The suction gauge displays << 0 bar. Diagnosis: Either the refrigeration cycle is blocked or underfilled. 16

Fault diagnosis R600a Filling the circuit with a bit of refrigerant (10 g). Blocked system: The system is blocked when after a short running time the same pressure is measured as before filling. 17

Fault diagnosis R600a Filling the circuit with a bit of refrigerant (10 g). Underfilled system: The system is underfilled when after a short running time a higher pressure is measured as before filling. 18

Fault diagnosis R600a Underfilled system: The cause of a underfilling is mostly a leakage. Use Leak Tester Search to find the leakage. On the pressure side the compressor must run. On the sucking side the compressor must not run. 19

Fault diagnosis Consider that R12 and R134a Refrigerant displays other pressure and temperature values 20

Refrigerant vapour pressure tables Temperature t [ C] absolute pressure pabs [bar] R12 R22 R134a R600a -60 0,226 0,376 0,163 0,08957-55 0,300 0,497 0,223 0,12201-50 0,392 0,646 0,299 0,16356-45 0,505 0,830 0,396 0,21604-40 0,642 1,053 0,516 0,28144-35 0,807 1,321 0,666 0,36196-30 1,000 1,640 0,848 0,45998-25 1,237 2,016 1,067 0,57807-20 1,510 2,455 1,330 0,71894-15 1,827 2,964 1,642 0,88548-10 2,193 3,550 2,008 1,0807-5 2,612 4,219 2,435 1,3077 0 3,089 4,980 2,929 1,5698 5 3,629 5,839 3,497 1,8703 10 4,238 6,803 4,146 2,2125 15 4,921 7,882 4,883 2,6001 20 5,682 9,081 5,716 3,0366 25 6,529 10,41 6,651 3,5254 30 7,465 11,88 7,698 4,0704 35 8,498 13,50 8,865 4,6750 40 9,634 15,27 10,16 5,3431 45 10,88 17,21 11,59 6,0784 50 12,24 19,33 13,17 6,8846 55 13,72 21,64 14,91 7,7657 60 15,33 24,15 16,81 8,7257 21

Refrigerant vapour pressure diagrams p abs [bar] 25,0 20,0 15,0 10,0 5,0 R22 R134a R12 R600a 0,0-60 -40-20 0 20 40 60 Temperature [ C] 22

Refrigerant Properties Refrigerant R12 R134a R600a Evaporating point - 30 C - 26 C - 12 C Condensing 55 C Pabs 13.72 bar 14.91 bar 7.77 bar Enthalpy by Evap. 166 KJ/Kg 215 KJ/Kg 367 KJ/Kg Evap. Enthalpy 32/-25 C 122 KJ/Kg 156 KJ/Kg 274 KJ/Kg Density of Vapour-25 C 7.69 Kg/m³ 5.56 Kg/m³ 1.67 Kg/m³ Evap. Pressure-25 C Pabs 1.24 bar 1.07bar 0.56bar Volume of Vapour -25 C 130 dm³/kg 180 dm³/kg 600 dm³/kg 23

Fault diagnosis Status of the cooling circuit by Less Refrigerant Air in refrigeration circuit Fault condenser ventilation 24

Less Refrigerant less refrigerant = not all refrigerant will be condensed = less refrigeration capacity 3 3 2 2 4 1 1 1 loss 25

Air in refrigeration circuit 3 3 2 2 4 1 1 1 Air in refrigeration circuit = pressure will be increased = power consumption increased = temperature on discharge tube increased = less refrigeration capacity = lifetime decreased loss loss efficiency 26

Fault condenser ventilation 3 3 2 2 4 1 1 1 Fault condenser ventilation = pressure will be increased = power consumption increased = temperature on discharge tube increased = less refrigeration capacity = lifetime decreased loss loss efficiency 27

Refrigeration Circuit 28