Flow-compensated temperature controller AVTQ DN 15

Similar documents
Thermostatic actuator RAVV - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16)

Thermostatic actuator RAVI - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16)

Thermostatic actuator RAVK - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16)

Thermostatic actuator RAVK - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16)

Flow controller with integrated control valve (PN 16, 25, 40*) AFQM, AFQM 6 - return and flow mounting

Thermostatic element RAVV for 2-way valves

Assisted lift operated 2/2-way solenoid valves Type EV250B

Self-operated Temperature Regulators Temperature Regulator Type 1u

MAKING MODERN LIVING POSSIBLE. Thermostatic valve AVTA. Technical brochure

Automatic Bypass Control AVDO

Thermostatic valve Type AVTA

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

Thermostatic Sensor RAS-C² with RA-FN Radiator Valve (Fixed Capacity)

3/2- and 2/2-way cartridge valve type BVE

Integrated Presetting Valves for Normal 013G0372 and Small 013G0373 Volume Flows

Integrated Presetting Valves - for Normal Volume Flows RA-N and for Small Volume Flows RA-U

V5001S. Kombi-S Shutoff Valve. Product specification sheet

Butterfly Valves PN 6/10/16 for flanged connection

4. Combi valves. 7. Fire hydrants. 8. Check valves. 9. Air valves

Mikrotherm. Manual radiator valves. To be precise.

Data sheet ECC 12 and 22

CALEFFI. Compact automatic flow rate regulator with polymer cartridge. 127 series 01166/09 GB

2-Port Self-acting Temperature Control Valve Selection for Heating and Cooling Applications

Solenoid valves 2/2-way direct-operated Type EV210A

Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II

Pressure switches and thermostats, type KPS

SISTO-16TWA/HWA/DLU. Type Series Booklet

Self-operated Temperature Regulators Type 1 to Type 9. PN 16 to 40 Class 125 to 300 DN 15 to 250 NPS ½ to 10 G ½ to 1 Up to 350 C Up to 660 F

Digital inductive conductivity transmitter

Type 3353 Angle Seat Valve

30% Safe. DESIGN GUIDE The Danfoss EvoFlat system from A-Z Take lead on your project with an efficient system concept. evoflat.danfoss.

S GATE KNIFE GATE VALVE WITH PNEUMATIC ACTUATOR

Data sheet Radiator Thermostats type RA 2000 Valve bodies type RA-FN and RA-G

Thermostatic Actuators

VAD Variable Area Desuperheaters

Water valves REFRIGERATION AND AIR CONDITIONING. Fitters notes

Type overview. Technical data

TN2000 Series Pneumatic Piston Actuators for DN125 to DN300 SPIRA-TROL Series Control Valves

VAD. Variable Area Desuperheaters

CALEFFI. SATK wall-mounted Heat Interface Unit - HIU Instantaneous domestic hot water production. SATK20 - SATK30 series 01209/13 GB

RADIATOR VALVES / MANIFOLD ASSEMBLIES AND DIVERTERS

Solenoid valves Type EVU

Overview of types. Technical data

Laddomat Charging unit

3/2-way Solenoid Valve, direct-acting, NC or NO

TA-FUS1ON. Fully adjustable Kvs control and balancing valves. That s just two good.

VdS en. VdS Guidelines for water extinguishing systems. Non-return valves. Requirements and test methods. VdS en : (01)

HERZ-Thermal Actuators

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS

Series 240 Type and Type Pneumatic Control Valves Type 3244 Three-way Valve

Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant).

Pneumatic Shut-off Butterfly Valve Type 3335/31a SRP or DAP

Automatic balancing valves ASV

RUBBER SLEEVE KNIFE GATE VALVE

Cable Plug acc. to DIN EN , Form A

Description of functions

QLM and QLD Series Three-port Control Valves

V47 Series Temperature Actuated Modulating Water Valves

ARI-DP30 / DP32 / DP33 / DP34 / DP34T / DP34Tri / DP35 Pneumatic actuator ARI-DP Pneumatic actuator ARI-DP

series Materials Body: 1/2, 3/4 and 1 : dezincification resistant alloy brass EN CW617N

Electrically operated valves Series M-05, 3/2-, 5/2- and 5/3-way G1/8 650 and 750 Nl/min (0.661 and Cv)

VALVES FOR REFRIGERATING SYSTEMS

Installation and Operation Instructions Domestic hot water modules: FriwaMidi DN 20 FriwaMaxi DN 25

Pneumatic Control and Shut-off Butterfly Valve Pfeiffer Type BR 14b/31a and Type BR 14c/31a

DN [mm] [m 3 /h] Characterizing disk Dimensions / Weights see «Dimensions and weights», page 3 Motorizing

Data Sheet VITOSOL 100. Flat collectors for the utilisation of solar energy. Vitosol 100. Part nos. and prices: see price list

HEAT INTERFACE UNITS (Modular)

2- and 3-port valves with flanged connections, PN 10

kymanual or Automatic - it s your Choice

4/2-Way Pneumatic Solenoid Valve

V1810. Alwa-Kombi-4 Circulation throttle valve. Product data

Threaded Resistance Thermometers Model TR10-D, Miniature Design

PRESSURE REDUCING VALVES

How To Use A Corona Mdi 110

stainless steel pre-assembled manifolds

Grey cast iron Fig. 600 Page 2. Forged steel High temperature steel Stainless steel Fig. 600/601 (Y) DN15-25 Page 4 DN40-50 Page 6

Valve systems Base plates, according to standard ISO Brochure

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

Technical data. Danfoss DHP-A

Pilot Operated Pressure Reducing Valve PRV 47 (Steel) PRV47I (St.Steel)

SQUARE D INDUSTRIAL CONTROL PRODUCTS

REGULATORS 175/153 Series

Type 92S Pilot-Operated Steam Regulator

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

Spira-trol TM Two-port Control Valves EN Standard KE, KF and KL DN15 to DN300 and ASME Standard KEA, KFA and KLA ½" to 12"

ARI-ASTRA / ASTRA Plus Combinend flow regulating valve

Ball valve C 16 valve ball completely moulded in place, extremely low clearance volume, high k v value

MULTICAL 21 DATA SHEET. Electronic ultrasonic cold and hot water meter

PRESSURE REDUCING CONTROL VALVE

Series description: Wilo-Star-Z

1.1 Z 011-A WAFER PATTERN BUTTERFLY TYP Z 011-A TECHNICAL DATA

MAKING MODERN LIVING POSSIBLE. Instantaneous Water Heaters. Instructions for installation and use. Danfoss District Energy

Data sheet Thermostatic sensors type RA 2000

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Electro-hydraulic pressure switches type DG

PRO-CLEAN. Technical Description. Specifications. Space-saving design with minimum heat loss (melamine resin insulation)

ISORIA. Centered disc butterfly valves with AMRING elastomer liner. 240 PSI: 1½ to PSI : 10 to 24

Geberit Mapress Catalogue 2008 / Valid from 1 April 2008

Heating, air-conditioning, cooling

Transcription:

Data sheet Flow-compensated temperature controller AVTQ DN 15 Description AVTQ prevents high temperatures in the heat exchanger when no hot water is tapped by rapidly shutting off the heat supply (e.g. hot district heating water). AVTQ can be used with most plate heat exchangers. However, the heat exchanger manufacturer should be contacted to ensure that the chosen heat exchanger has been approved for use with the AVTQ. Pressure-controlled opening/closing on start/stop tapping. Infinite adjustment of operating temperature. AVTQ controller consist of a thermostatic actuator, diaphragm element, main valve and pilot valve. Thermostatic actuator with diaphragm element and main valve are installed on the district heating (primary) side. The diaphragm element is, via impulse tubes, connected to the pilot valve on the domestic hot water (secondary) side. AVTQ is a self-acting flow-compensated temperature controller primarily for use in district heating systems with plate heat exchangers for instantaneous hot water production. It closes on rising sensor temperature. It has permanent no-load (idle) temperature setting on about 40 C which is offset by a pilot valve using flow-compensation principle during tapping. Tapping temperature can be set individually. Main data: DN 15 k VS 1.6 PN 16 - Main valve PN10 - Diaphragm element and pilot valve Suitable for domestic hot water (DHW) production in range of 45... 60 C Permanent no-load (idle) temperature (approx. 40 C) Temperature (primary): - Circulation water / glycolic water up to 30%: 2 100 C Connections: - Ext. thread (weld-on and thread tailpieces) Return mounting Ordering AVTQ controller Example: Flow-compensated temperature controller, DN 15, k VS 1.6, PN 16, setting range 45 60 C, t max 100 C, ext. thread Picture DN k vs Connection (mm) (m 3 /h) Main valve ISO 228/1 Pilot valve ISO 228/1 15 1.6 G ¾ A G 1 A (DN 20) Code No.* 003L7015-1 AVTQ controller, 45 60 C Code No: 003L7015 Option: - 1 Weld-on tailpieces Code No: 003H6908 * Controller incl. gland and compression fittings for mounting on Ø6 0.8 mm copper impulse tube. Accessories Picture Type designation DN Connection Code No. Weld-on tailpieces External thread tailpieces 15 Conical ext. thread acc. to EN 10226-1 003H6908 R ½ 003H6902 DH-SMT/SI VD.LJ.A1.02 Danfoss 10/2006 1

Ordering (continuous) Service kits Picture Type designation Code No. Gasket for diaphragm housing 003L3154 Thermostatic actuator incl. sensor stuffing box 003L7100 Compression fittings for Ø6 mm copper tube (4 ferrules and 4 nuts) 003L7101 Pilot valve excl. compression fittings 003L7108 Main valve incl. complete valve insert 003L7109 Diaphragm element excl. compression fittings 003L7111 Sensor stuffing box incl. gasket 003L7120 Technical data Nominal diameter DN 15 k VS value m 3 /h 1.6 Control ratio 100 : 1 Cavitation factor z 0.6 Leakage acc. to standard IEC 534 < 0.05 % 4) Nominal pressure Max. differential pressure 6 bar Max. closing pressure 12 Medium Materials Temperature controller Diaphragm housing stuffing box Sensor Pilot valve Valve body RG5, DIN 1705, W.no. 2.1096.01 Valve insert and valve cone Dezincification resistant brass BS 2874 Valve seat, pressure relief cylinder CrNi steel, DIN 17440, W.no. 1.4404 Valve spindle CrNi steel, DIN 17440, W.no. 1.4435 Valve plate, O-ring, diaphragm EPDM Diaphragm housing CrNi steel, DIN 17440, W.no. 1.4435 Diaphragm plate CrNi steel, DIN 17440, W.no. 1.4436 Diaphragm spindle Dezincification resistant brass BS 2874 Housing Dezincification resistant brass BS 2874 Spindle CrNi steel, DIN 17440, W.no. 1.4401 Sensor Copper Sensor stuffing box Dezincification resistant brass BS 2874 Gasket EPDM Charge Carbon dioxide (CO 2 ) Valve body Dezincification resistant brass BS 2872 Valve base Dezincification resistant brass BS 2874 Valve spindle CrNi steel, DIN 17440, W.no. 1.4401 Setting spring CrNi steel, DIN 17440, W.no. 1.4568 Cone, spring retainer PPS-plastic O-ring EPDM 1) Valid for primary side (main valve) 2) Valid for secondary side (pilot valve and diaphragm element) 3) In case of domestic hot water (secondary side) ph lower than 7 -> the hardness of the water must be larger than the sulphate element HCO3 1 SO4 4) at T idle nom. + 10 C PN 16 1) 10 2) Medium ph Min. 7, max. 10 1),2),3) Medium temperature Connections C valve tailpieces Circulation water / glycolic water up to 30% 1) Domestic hot water (chlorine (cl) content max. 200 ppm) 2) 2 100 1) 2 90 2) Ext. thread Setting range Xs C 45 60 Time constant T acc. to EN 14597 s 4 Max. adm. temperature at sensor C 130 Max. water velocity around the sensor m/s 1.5 Capillary tube length m 1 Weld-on and external thread 2 VD.LJ.A1.02 Danfoss 10/2006 DH-SMT/SI

Application principle The controller AVTQ must be installed in the return pipeline only. When domestic hot water (DHW) is tapped, flow through the pilot valve creates a pressure drop (force in the diaphragm housing) which is used to increase the temperature level from no-load (idle) to set tapping temperature. This temperature increase causes the main valve to open for flow on the district heating side and close when the temperature level again falls to the no-load operating level. No-load operation prevents the district heating line becoming cold. Tapping temperature can be set individually. Design 1. Thermostatic actuator with sensor stuffing box 2. Pressure spindle 3. Diaphragm housing stuffing box 4. Nut 5. Diaphragm housing 6. Diaphragm spindle 7. Control diaphragm 8. Compression connection for impulse tube 9. Intermediate ring 10. Nameplate 11. Main spring 12. Damping + teflon ring 13. Valve spindle 14. Valve insert 15. Pressure relief cylinder 16. Valve body (main valve) 17. Handle for temperature setting 18. Spindle 19. Valve base 20. Spring retainer 21. Setting spring 22. Pressure equalizing hole 23. Valve cone 24. Valve body (pilot valve) 25. Compression connection for impulse tube 26. Sealing bolt of sensor stuffing box 27. Gasket of sensor stuffing box 28. Housing of sensor stuffing box DH-SMT/SI VD.LJ.A1.02 Danfoss 10/2006 3

Installation One-way heat exchanger Two-way heat exchanger Three-way heat exchanger Fig. 3 AVTQ can be used with most types of plate heat exchangers. The AVTQ manufacturer should be contacted to ensure: - that the AVTQ is approved for use with the chosen heat exchanger - the correct material selection when connection the heat exchangers - the correct connection of one pass plate heat exchangers; layer distribution might occur, i.e. reduced comfort The system functions optimal when the sensor is installed right inside the heat exchanger (see page 3). However, the sensor head should be placed approx. 5 mm from the plate which divides the primary and the secondary side of the exchanger. If the sensor head is placed too close to the dividing plate, the sensor might measure the temperature of the plate and not the temperature of the medium. For correct noload operation, thermal flow should be avoided since hot water rises and increases the no-load consumption. Note: water velocity around the sensor must be in accordance with the requirements for copper tube. The temperature controller (main valve): - must be installed in the return pipeline on the district heating (primary) side of the heat exchanger - the diaphragm element can be turned in any position in relation to the valve body so that impulse tube can be connected in the required direction The pilot valve: - must only be installed in the flow pipeline on the secondary side of the heat exchanger - in systems where it cannot be excluded that drinking water is contaminated with fine dust from time to time, it is recommended not to mount the pilot valve with the impulse tube connections downwards (fig.2) to avoid dirt ingress in the impulse tubes and diaphragm housing The sensor can be installed in any position (fig.1) It is strongly recommended that: - the primary and secondary sides of the heat exchanger should be flushed through before the heating system is used the first time. In addition the (+) and ( ) side of the diaphragm should be vented. - dirt strainers with a mesh size of max. 0.6mm should be installed in both, the cold tap water pipeline ahead of the pilot valve and in the flow pipeline from the district heating network. Fig. 1 Fig. 2 4 VD.LJ.A1.02 Danfoss 10/2006 DH-SMT/SI

Sizing Example Given data: T 1 = 65 C T 3 = 50 C T 4 = 10 C Q 2 = 0.3, 0.6, 0.9 m 3 /h (300, 600, 900 l/h) T 1 - District heating water flow temperature T 3 - Hot water temperature T 4 - Cold water temperature Q 2 - Hot water service flow Primary Secondary District heating flow line Hot water District heating return line Cold water Fig. 4 The maximum heating power P max is calculated according to formula: Q2 x T2 Q2 x T3 T 0.86 0.86 900 x 50 10 42 kw 0.86 4 pmax p max Based on max. heating power heat exchanger could be selected. Information about the cooling across the primary side of heat exchanger can be acquired either by contacting the manufacturer of the heat exchanger or by using the manufacturer s dimensioning diagram. Chosen AVTQ main valve has k vs 1.6 m 3 /h and therefore is big enough. Values for flows of 300 and 600 l/h are calculated on the same way and entered in the table. Tab.1 W (kw) Secondary flow Q 2 (l/h) Primary flow Q 1 (l/h) k v (m 3 /h) Cooling T 1 ( C) 14 300 280 0.39 43 28 600 600 0.85 40 42 900 925 1.31 39 In the example chosen cooling on primary side (ΔT 1 ) is 43 C, 40 C or 39 C, the differential pressure across the AVTQ main valve (Δp v ) is 0.5 bar. The primary flow Q 1 can be calculated according to formula: P Q x 0.86 T max 1 1 Q 1 925 l / h Using the above data, the needed capacity of the main valve (k v ) can be calculated: k v k v = 1.31 m 3 /h v 42 x 0.86 39 3 Q1 m / h 0.925 p bar 0. 5 DH-SMT/SI VD.LJ.A1.02 Danfoss 10/2006 5

Sizing (continuous) The pressure drop across the pilot valve can be read from the diagram below Pressure drop (Δp pilot ) across pilot valve as a function of the setting value and secondary flow 6 VD.LJ.A1.02 Danfoss 10/2006 DH-SMT/SI

Setting The AVTQ controller can be used with plate heat exchangers of up to 75 kw. As a result of the flow compensation principle an actual dimensioning of the valve is unnecessary, because the valve will always adjust around the required temperature without regard to the flow. Typical settings: This means that if the controller is set to 50 C (this is done at 75% of max. tapping flow to obtain optimum control), then this temperature will be maintained whether or not the actual flow is 120 l/h, 900 l/h or more. Between 120 l/h and 900 l/h the temperature will vary approx. 4 C. Minimum: Designation Application values Pilot valve setting Flow temperature, primary Tp = 65 C Differential pressure across the AVTQ main valve p = 0.5 bar Hot water temperature, secondary Ts (hot) = 50 C 3.0 Cold water temperature, secondary Ts (cold) = 10 C Secondary flow Qs = 750 l/h Maximum: Designation Application values Pilot valve setting Flow temperature, primary Tp = 100 C Differential pressure across the AVTQ main valve p = 6.0 bar Hot water temperature, secondary Ts (hot) = 50 C 2.0 Cold water temperature, secondary Ts (cold) = 10 C Secondary flow Qs = 750 l/h The values mentioned above are reference values and therefore corrections of pilot valve settings might be necessary in order to obtain the required temperature. Other approx. setting values: Tapping temperature = 50 C Tapping flow = 750 l/h T primary p (bar) 0.5 1.0 3.0 6.0 65 C 3.0 2.5 2.5 2.5 80 C 2.75 2.5 2.25 2.25 100 C 2.5 2.5 2.25 2.0 DH-SMT/SI VD.LJ.A1.02 Danfoss 10/2006 7

Dimensions R 1/2 DN (mm) L 1 (mm) L 2 (mm) L 3 (mm) a ISO 228/1 b ISO 228/1 Weight (kg) 15 65 25.5 35 G ¾ A G ¾ A 3.57 8 VD.LJ.A1.02 Danfoss 10/2006 DH-SMT/SI