CALEFFI. SATK wall-mounted Heat Interface Unit - HIU Instantaneous domestic hot water production. SATK20 - SATK30 series 01209/13 GB

Size: px
Start display at page:

Download "CALEFFI. SATK wall-mounted Heat Interface Unit - HIU Instantaneous domestic hot water production. SATK20 - SATK30 series 01209/13 GB"

Transcription

1 SATK wall-mounted Heat Interface Unit - HIU Instantaneous domestic hot water production SATK20 - SATK30 series ACCREDITED CALEFFI 01209/13 GB ISO 9001 FM ISO 9001 No The latest generation heat interface units SATK20 and SATK30 regulate user heat requirements and instantaneous DHW production. The SAK20, SATK30 heat interface units, being two-way systems with modulating control of the heating medium (VFR - variable flow rate system), are particularly suitable for centralised systems with condensing boilers and for centralised systems served by remote district heating. Design Improving the performance and energy efficiency of systems can help to reduce the energy consumption of buildings and reduce environmental pollution. VF (variable flow) systems can play an important part in this. The design and sizing of VF system distribution networks can be split into three stages. words, only heating (Q HEAT, H HEAT ) requirements need to be considered in selecting the dimensions of the network. These dimensions vary on account of the fact that the services required evolve differently depending on the number of homes served. In particular, DHW production needs high medium outputs and flow rates if a small number of homes are supplied, but low outputs and flow rates if many homes are served, as illustrated in the diagrams on the next page. In the first stage, the network must be sized on the basis of the flow rate and heat required to produce DHW: in other words, only DHW (Q DHW, H DHW ) requirements need to be considered in selecting the dimensions of the network. In the second stage, the network must be sized on the basis of the flow rate required for heating and the heat required to produce DHW: in other words, it needs to be the right size to handle both heating and DHW requirements (Q HEAT, H DHW ). In the third and final stage, the network must be sized on the basis of the flow rate and heat required for heating: in other 1

2 System design diagrams An example of how to design a system is provided below. System features and design choices: Home heating requirement: 5500 kcal/h Radiator systems Design thermal head - heating: DT = 10 C Hot medium design temperature: T = 65 C Heat interface unit characteristics (in relation to the design temperature of the hot medium): Dp min = mm w.g. Min. required Dp Q n = l/h primary circuit nominal flow rate H n = kcal/h primary circuit nominal output H n.dhw = 0,29 l/s max. DHW produced Flow rate required [l/h] FLOW RATES REQUIRED IN RELATION TO NUMBER OF DWELLINGS Flow rate required for DHW production (Q DHW ) Flow rate required for heating (Q HEAT ) Flow rate required by system Number of dwellings Heat required [kcal/h] HEAT REQUIRED IN RELATION TO NUMBER OF DWELLINGS Heat required for DHW production (H DHW ) Heat required for heating (H HEAT ) Heat required by system Number of dwellings 2

3 Main features of VFR systems VFR systems (controlled by two-way valves, see relative diagram below) work by moving only the amount of medium needed to provide the requested amount of heat. Benefits of VFR systems: variable flow rate No risk of legionnaires disease In VFR systems, bacteria cannot develop in the production of DHW and in the internal water supply systems inside apartments. Single meter In VFR systems, zone heating costs are measured by a single heat meter. When DHW production is centralised, consumption is calculated by a heat meter for heating and by a volume meter for DHW, i.e. by direct and indirect methods, which can often be a source of debate and dispute. Much lower return temperatures In VFR systems, the return temperature of the medium in the boiler drops as the external temperature rises, whereas in conventional (constant flow) systems, it rises. In this regard, the diagram below shows how these temperatures vary in a system with design temperatures of 65 and 10 C for the hot medium and radiator thermal head respectively. Lower return temperatures allow: better performance of condensation boilers; less heat loss from return pipes; more cost-efficient use of renewable energies. These are primarily: 1 - energy saving 2 - thermal comfort 3 - installation and running costs 4 - accurate heating metering Possibility of using thermostatic valves. In brief, only VFR systems allow a rational and economic use of thermostatic valves. In fact, only VFR systems (without having to use penalizing bypasses and pumps which work continuously at full capacity) can control the imbalances introduced into circuits by the constant opening and closing of thermostatic valves: these imbalances can seriously impair system function and cause serious damage. Hence unlike conventional systems (with constant flow), with VFR systems you can more efficiently: Heating medium temperature Constant-flow system return temperature select the temperature required in each room in the various zones, for example C in bedrooms, 8 10 C in technical rooms and in other rooms not normally used; benefit from the heat obtained from internal and external energy sources, i.e. from sunlight or the heat from human bodies, artificial lighting, home appliances, ovens and hobs; obtain the temperature requested in each room without any potential thermal imbalances generated by sunlight hitting rooms to different degrees or other impediments (curtains or niches) that block the heat issued by radiators. Lower pump operating costs Lower pump operating costs due to the fact that VFR systems always work with the minimum flow rate needed to transfer the required heat, whereas conventional systems always work with the maximum flow rate: this difference can save on average from 40 to 55% in the pump running costs. Less heat loss from distribution networks In VFR systems there are two hot medium pipes whereas in constant-flow systems there are 4 (2 for heating and 2 for DHW and recirculation). Lower distribution networks installation costs For the reasons outlined above. VFR system return temperature External temperature Less danger of limescale blockages Less danger of limescale blockages and therefore less risk of a partial or total blockage of exchangers producing DHW. It should in fact be noted that in VFR systems (controlled by modulating valves), heat exchange temperatures are on average lower than those in conventional constant flow systems (controlled by ON/OFF valves). For this reason, there is less risk of limescale obstructions in VFR systems, which become a hazard at exchange temperatures above C. DHW production The electronic regulato rfor SATK20, SATK30 heat interface units, which assimilates information on the required domestic hot water flow rate, maximises the primary circuit exchange temperature difference following extreme splitting in the vector medium flow rate. In this functional context, the SATK20, SATK30 heat interface units also make DHW production consistent with low temperature returns. 3

4 Use of alternative energies The two-way conformation of the SATK series heat interface units, combined with the role played by the electronic regulators which guarantee very cold return flows, allows much more use to be made of alternative energies in the central heating context. The use of stored energy increases due to the effect of accepting lower medium temperatures compared to those of traditional DHW tank. The amount of stored domestic water is basically replaced by technical water. Central heating system diagram for VFR systems with boiler and integrated solar power The system comprises: - boiler; - a solar power system consisting of solar manifolds, coil accumulator, circulator, electronic regulator, - two three-way diverter valves (V1 and V2); - a variable-flow twin circulator; - differential thermostat (Tt, Tr); - expansion, safety and control devices. When the tank temperature (Tt) rises above the temperature returning from the system (Tr), the differential thermostat commands a three-way valve (V1) that diverts circulation of the medium towards the boiler heated by the solar system; otherwise, the medium is sent directly to the boiler. The thermostat on the boiler (T) commands a second three-way diverter valve (V2) that diverts the flow directly into the delivery section of the system when the design temperature is exceeded; otherwise the flow is diverted to the boiler. Note: The control, expansion and safety devices must be of an appropriate size to reflect the characteristics and capacity of the system, in accordance with applicable legislation. Application diagram V2 I T P P V1 Tr T T T T Tt T T A F V.E. 4

5 WALL-MOUNTED HEAT INTERFACE UNIT INSTANTANEOUS DOMESTIC HOT WATER PRODUCTION - SATK20/HE SERIES BOILER COMMUNAL AREAS HOUSING UNIT DISTRICT HEATING SUBSTATION Being compact in size, the wall-mounted heat interface units are suitable for in-home installation and concealed inside a kitchen cupboard. This makes it much easier for landlords to manage their own temperature regulation and domestic hot water production, freeing up space in communal landing enclosures which can be used to house meters instead. Moreover, this also extends the line from the main community supply into the dwelling, reducing the need for joints and fittings. Pipes heat losses remain within the dwelling, and given that they are metered, actual use made and meter readings produced will be more consistent. 5

6 WALL-MOUNTED HEAT INTERFACE UNIT INSTANTANEOUS DOMESTIC HOT WATER PRODUCTION - SATK20/HE SERIES SATK20103 LOW temperature HIU SATK20103HE LOW temperature HIU with high-efficiency pump SATK20203 MEDIUM temperature HIU SATK20203HE MEDIUM temperature HIU with high-efficiency pump Set point regulation or modulating temperature regulation with compensated set point Heating range C DHW production range C Set point regulation Heating range C DHW production range C Optional functions water cycle: Heating cycle: SATK domestic water preheating function - modulating regulation with compensated set point - floor slab heating function HIGH temperature heat interface unit Optional functions water cycle: Heating cycle: SATK domestic water preheating function - modulating regulation with compensated set point HIGH temperature HIU SATK20403HE HIGH temperature HIU with high-efficiency pump ON/OFF regulation Max. temperature heating 85 C DHW production range C ON/OFF regulation Max. temperature heating 85 C DHW production range C Optional functions water cycle: - domestic water preheating function Optional functions water cycle: - domestic water preheating function 6

7 Technical data SATK20 Medium: water Max. percentage of glycol: 30% Max. medium temperature: 85 C Max. working pressure: - primary circuit: 10 bar - domestic hot water circuit: 10 bar Nominal DHW exchanger capacity: 40 kw Max. recommended primary circuit flow rate: 1,2 m 3 /h DHW circuit max flow rate: 18 l/min (0,3 l/s) Min. flow to activate domestic flow meter: 2,7 l/min ±0,3 Max. differential pressure on domestic water modulating valve: 0,9 bar Max. differential pressure on mixing valve: 0.9 bar Electric supply: 230 V (ac) ±10% 50Hz Power consumption: 105 W (SATK20...HE 75 W) Protection class: IP 40 Pump: UPS (SATK20...HE UPS ) Pump by-pass setting: 0,45 bar Actuators: stepper 24 V Probes: NTC 10 kω Safety thermostat: 55 C ±3 Materials Components: brass EN12165 CW617N Fitting pipes: steel Frame: RAL 9010 painted steel Protective shell cover: PPE Exchanger: braze welded stainless steel Dimensions SATK20 Operating cycles water cycle This cycle always takes priority over the heating cycle. When DHW cycle activation is requested, due to the running of user s tap (detected by the domestic meter), the regulator pilots the modulating valve opening so as to adjust the temperature detected by the domestic water probe to the selected set point value (in the SATK20403/HE the pump is also activated). At the end of the drawing-off procedure, the modulating valve is fully closed (in the SATK20403/HE the pump comes to a stop). The active domestic water cycle is signalled by the yellow DHW LED which comes on. The set point temperature value of the general domestic water cycle can be set using the P1 trimmer to a value within the defined range of C and shown on the display (see page 20). Heating cycle Set point regulation. SATK20103/HE - LOW temperature SATK20203/HE - MEDIUM temperature When heating cycle activation is requested by the room thermostat, the circulation pump is powered while the mixing valve is opened gradually until the set point temperature is reached. At the end of the heating cycle, the circulation pump comes to a stop and the mixing valve is closed. The active heating cycle is signalled by the yellow CH LED which comes on (see page 20). The heating cycle temperature set point can be set using trimmer P2 and shown on the display. Heating cycle ON/OFF regulation SATK HIGH temperature SATK20403/HE - HIGH temperature with pump When the room thermostat requests the start of a heating cycle, the valve is opened completely (in the SATK20403/HE the pump is also activated), allowing water to circulate at the temperature supplied by the central heating system (ON-OFF regulation). The valve is closed on completion of the heating cycle (in the SATK20403/HE the pump comes to a stop). The active heating cycle is signalled by the yellow CH LED which comes on (see page 20). Optional functions water cycle water preheating function The function is enabled by setting DIP switch 5 (see page 20) to the ON position. During periods when the domestic water cycle is not used, if the DHW probe detects a temperature 10 C below the SET value, the regulator partially opens the domestic water modulating valve for the time required (max. 5 mins) to bring the temperature detected up to a value 5 C below the set point value. The active domestic water cycle is signalled by the flashing yellow DHW LED. This function is less of a priority than any domestic water or heating cycles. Heating cycle Modulating temperature regulation with compensated set point. SATK20103/HE - LOW temperature SATK20203/HE - MEDIUM temperature The function is enabled by setting DIP switch 1 (see page 20) to the OFF position. When the function is enabled, the flow temperature is modified according to the temperature detected by the compensation probe (located on the user return pipe). This keeps the actual thermal output of the slab - and therefore the ambient thermal load - under control. The thermal response time of the system is thus minimised. Floor slab heating function SATK20103/HE - LOW temperature This facilitates the laying of underfloor heating systems at low temperatures. This function can only be activated and executed if there are no faults. It can be activated by pressing and holding the RESET button for 8 seconds. The yellow CH LED blinks while the floor slab heating function is in operation (see page 20). The function has a duration of 240 hours, and is carried out by simulating a request to run in heating mode starting from a set point of 25 C and rising in regular intervals to a temperature of 45 C. Once the maximum set point has been reached, the function is executed, following the same procedures, in reverse (from the maximum set point to the minimum set point). This function has priority over heating and hot water cycles, and can be suspended at any time by pressing and holding the RESET button for 8 seconds. 7

8 SATK20103 LOW temperature heat interface unit SATK20103HE LOW temperature heat interface unit with high-efficiency pump Functional characteristics Heating range C Set point regulation DHW production range C Optional functions water cycle: Heating cycle: - domestic water preheating function - modulating regulation with compensated set point - floor slab heating function Characteristic components 1. Frame 2. Electronic regulator 3. Thermal safety relief valve 4. Heating mixing valve 5. DHW production modulating valve 6. Heating flow temperature probe 7. Thermal safety thermostat 8. DHW temperature probe 9. DHW exchanger 10. Drain cock 11. Pump 12. Protective pump by-pass 13. Flow temp. compensation return probe 14. DHW priority flow meter 15. Heat meter template spacer 16. Air vent cock 17. System strainer/heat meter flow probe pocket 18. Primary circuit shut-off valves Hydraulic-functional diagram TS O / RT

9 Hydraulic characteristics Heating function Head available at connections 3rd speed function - primary exchanger 9

10 SATK20203 MEDIUM temperature heat interface unit SATK20203HE MEDIUM temperature heat interface unit with high-efficiency pump Functional characteristics Heating range C Set point regulation DHW production range C Optional functions water cycle: Heating cycle: - domestic water preheating function - modulating regulation with compensated set point Characteristic components 1. Frame 2. Electronic regulator 3. Heating mixing valve 4. DHW production modulating valve 5. Heating flow temperature probe 6. DHW temperature probe 7. DHW exchanger 8. Drain cock 9. Pump 10. Protective pump by-pass 11. DHW priority flow meter 12. Heat meter template spacer 13. Air vent cock 14. System strainer/heat meter flow probe pocket 15. Primary circuit shut-off valves Hydraulic-functional diagram 10

11 Hydraulic characteristics Heating function Head available at connections 3rd speed function - primary exchanger 11

12 SATK20303 SATK20403/HE HIGH temperature HIU HIGH temperature HIU with pump Functional characteristics Max. heating temperature 85 C ON/OFF regulation DHW production range C Optional functions water cycle: - domestic water preheating function Characteristic components 1. Frame 2. Electronic regulator 3. Heating ON/OFF valve 4. DHW production modulating valve 5. Drain cock 6. DHW temperature probe 7. DHW exchanger 8. DHW priority flow meter 9. Heat meter template spacer 10. Air vent cock 11. System strainer/heat meter flow probe pocket 12. Primary circuit shut-off valves 13. Pump (SATK20403/HE) 14. Protective pump by-pass (SATK20403/HE) Hydraulic-functional diagram O SATK20403/HE

13 Hydraulic characteristics Heating function function - primary exchanger Pump characteristics (SATK20403/HE) p (kpa) 6 H (mm w.g.) rd speed nd speed st speed G (l/h) 13

14 WALL-MOUNTED INDIRECT HEAT INTERFACE UNIT INSTANTANEOUS DHW PRODUCTION - SATK30 SERIES/HE DISTRICT HEATING COMMUNAL AREAS PRIVATE RESIDENCE SATK30103 Indirect heat interface unit SATK30103HE Indirect heat interface unit with high-efficiency pump The SATK30 satellite HIU is the most compact, complete and efficient solution for enclosures in individual dwellings for use in: - district heating - centralised heating systems which require a high static pressure and high temperature medium, characteristics which could cause injury. The SATK30 heat interface unit offers the unusual feature of keeping the primary and secondary water completely separate. This type of device is useful when designing or redesigning the heating and domestic hot water systems of apartment buildings under renovation, as well as facilitating any maintenance required in the individual dwellings without the risk of impurities entering their systems. It makes no difference how the domestic hot water in dwellings is produced when a SATK30 satellite HIU is used. Furthermore, the modulating heating and DHW valves on the primary circuit minimise return temperatures in the substation or central source of a central heating systems through the modulating action of the regulator. Minimising the return temperatures by exaggerating the difference between flow and return temperatures, is therefore compliant with remote heating rules and condensation requirements. Set point regulation or modulating temperature regulation with compensated set point Heating range - LOW temperature setting C - MEDIUM/HIGH temperature setting C DHW production range C Optional functions water cycle: - domestic water preheating function Heating cycle (at LOW temperature setting): - modulating regulation with compensated set point - floor slab heating function 14

15 Technical data SATK30 Medium: water Max. percentage of glycol: 30% Maximum medium temperature: 85 C Max. working pressure: - primary circuit: 16 bar - secondary circuit: 3 bar - domestic hot water circuit: 10 bar Nominal heating exchanger capacity: 15 kw Nominal DHW exchanger capacity: 40 kw Max. recommended primary circuit flow rate: 1,2 m 3 /h DHW circuit max flow rate: 18 l/min (0,3 l/s) Min. flow to activate domestic flow meter: 2,7 l/min ±0,3 Modulating valve max differential pressure: Dp 0,9 bar Power supply: 230 V (ac) ±10% 50Hz Power consumption: 105 W (SATK30...HE 75 W) Protection class: IP 40 Pump: UPS (SATK30...HE UPS ) Pump bypass setting: 0,45 bar Actuators: stepper 24 V Probes: NTC 10 k Ω Safety relief valve setting: 3 bar Safety thermostat: 55 C ±3 Expansion vessel: 7,5 l Pressure switch: opening 0,4 bar - closing 0,8 bar Materials Components: Fitting pipes: Frame: Protective shell cover: Exchanger: Dimensions SATK30 brass EN12165 CW617N steel RAL 9010 painted steel PPE braze welded stainless steel Operating cycles water cycle This cycle always takes priority over the heating cycle. When DHW cycle activation is requested, due to the running of user s tap (detected by the domestic meter), the regulator pilots the modulating valve opening so as to adjust the temperature detected by the domestic water probe to the selected set point value. At the end of the drawing-off procedure, the modulating valve is fully closed. The active domestic water cycle is signalled by the yellow DHW LED which comes on. The set point temperature value of the general domestic water cycle can be set using the P1 trimmer to a value within the defined range of C and shown on the display (see page 20). Heating cycle Set point regulation When heating cycle activation is requested by the room thermostat, the circulation pump is powered while the modulating valve is opened gradually until the set point temperature is reached. At the end of the heating cycle, the circulation pump comes to a stop and the modulating valve is closed. The active heating cycle is signalled by the yellow CH LED which comes on (see page 20). The heating cycle temperature set point can be set using trimmer P2 and shown on the display. Optional functions water cycle water preheating function The function is enabled by setting DIP switch 5 (see page 20) to the ON position. During periods when the domestic water cycle is not used, if the DHW probe detects a temperature 10 C below the SET value, the regulator partially opens the domestic water modulating valve for the time required (max. 5 mins) to bring the temperature detected up to a value 5 C below the set point value. The active domestic water cycle is signalled by the flashing yellow DHW LED. This function is less of a priority than any domestic water or heating cycles. Heating cycle Modulating temperature regulation with compensated set point. (at LOW temperature setting) The function is enabled by setting DIP switch 1 (see page 20) to the OFF position. When the function is enabled, the flow temperature is modified according to the temperature detected by the compensation probe. This keeps the actual thermal output of the slab - and therefore the ambient thermal load - under control. The thermal response time of the system is thus minimised. Floor slab heating function (at LOW temperature setting) This facilitates the laying of underfloor heating systems at low temperatures. This function can only be activated and executed if there are no faults. It can be activated by pressing and holding the RESET button for 8 seconds. The yellow CH LED blinks while the floor slab heating function is in operation (see page 20). The function has a duration of 240 hours, and is carried out by simulating a request to run in heating mode starting from a set point of 25 C and rising in regular intervals to a temperature of 45 C. Once the maximum set point has been reached, the function is executed, following the same procedures, in reverse (from the maximum set point to the minimum set point). This function has priority over heating and hot water cycles, and can be suspended at any time by pressing and holding the RESET button for 8 seconds. 15

16 1 0 2 CALEFFI 4 3 SATK30103 Indirect HIU SATK30103HE Indirect HIU with high-efficiency pump Functional characteristics Heating range - LOW temperature setting C - HIGH temperature setting C Set point regulation DHW production range C Optional functions water cycle: - domestic water preheating function Heating cycle at LOW temperature setting: - modulating regulation with compensated set point - floor slab heating function Characteristic components 1. Frame 2. Expansion vessel 3. Electronic regulator 4. 2-way modulating valve (primary heating) 5. Heating flow temperature probe (secondary) 6. Heating exchanger 7. 2-way modulating valve - DHW 8. Thermal safety thermostat 9. Secondary heating drain cock 10. DHW temperature probe 11. Filling unit with backflow preventer 12. Safety relief valve 13. Flow temp. compensation return probe 14. Primary circuit drain cock 15. Pump 16. Protective by-pass 17. DHW priority flow meter 18. Pressure switch 19. Secondary heating filter 20. DHW exchanger 21. Heat meter template spacer 22. Primary circuit strainer/flow probe pocket 23. Primary air vent cock 24. Primary circuit shut-off valves Hydraulic-functional diagram TS 2 7 O / RT P

17 Hydraulic characteristics Heating function Head available at connections 3rd speed function - primary exchanger Δp (kpa) Δp (mm w.g.) 17

18 SATK20 - SATK30 series domestic hot water performance at 48 C Flow Temp. Primary Circuit Primary Circuit Flow Rate DHW Circuit Flow Rate Q (l/min) Return Temperature Primary Circuit Flow Temp. Primary Circuit DHW Circuit Flow Rate Q (l/min) 18

19 SATK20 - SATK30 series domestic hot water performance table Primary circuit flow rate = 1000 l/h Δp= 20kPA / domestic water inlet temperature 13 C water production temperature 44 C 48 C 52 C 56 C 60 C Primary circuit temperature C 65 15,4 33,3 12,6 30,8 10,4 28,3 8,5 25,5 7,0 23, ,0 38,9 16,1 35,9 13,2 35,9 10,9 32,7 9,0 29, ,0 38,9 18,0 41,1 15,1 41,1 12,8 38,4 10,8 35, ,0 38,9 18,0 43,8 16,1 43,8 14,5 43,5 13,2 43, ,0 38,9 18,0 45,7 16,8 45,7 15,6 46,8 14,5 47,5 Primary circuit flow rate = 1100 l/h Δp= 25kPA / domestic water inlet temperature 13 C water production temperature 44 C 48 C 52 C 56 C 60 C Primary circuit temperature C 65 17,3 37,5 13,8 33,7 11,3 30,7 9,2 27,6 7,5 24, ,0 38,9 18,0 44,0 14,7 40,0 12,0 36,0 9,8 32, ,0 38,9 18,0 44,0 15,5 42,2 13,4 40,2 11,7 38, ,0 38,9 18,0 44,0 16,7 45,4 15,4 46,2 14,2 46, ,0 38,9 18,0 44,0 17,6 47,9 16,8 50,4 15,5 50,8 Primary circuit flow rate = 1200 l/h Δp= 30kPA / domestic water inlet temperature 13 C water production temperature 44 C 48 C 52 C 56 C 60 C Primary circuit temperature C 65 18,0 38,9 14,8 36,1 12,0 32,7 9,7 29,1 7,8 25, ,0 38,9 18,0 44,0 15,0 40,8 12,5 37,5 10,4 34, ,0 38,9 18,0 44,0 15,9 43,3 14,1 42,3 12,7 41, ,0 38,9 18,0 44,0 17,3 47,1 16,4 49,2 15,3 50, ,0 38,9 18,0 44,0 17,9 48,7 17,4 52,2 16,5 54,1 19

20 Electronic regulator RESET key This key allows you to restore normal function after a safety thermostat has been triggered (SATK20103/HE-SATK30103 at low temperature setting). Trimmers set point settings The set point values for heating and domestic hot water cycles can be set using the two trimmers on the front of the regulator This allows you to set the temperature setpoint for the heating cycle and view the relative value set on the display. This allows you to set the temperature setpoint for the domestic hot water cycle and view the relative value set on the display. Operation All heating and domestic hot water functions offered by SATK20, SATK30 satellite HIUs are controlled by a digital regulator. The regulator is factory set with different standard parameters depending on the model (Table 1). There are a number of specific DIP SWITCHES on the regulator circuit board; the way these are configured will determine the settings of the various models and the optional functions enabled. User interface The user interface, built into the PCB, consists of the following devices: Indicator LED The following functions and faults are signalled by either flashing or permanent illumination of the LEDs: LCD display The LCD display is normally used to show heating and domestic water set points for the functions described below. Stand-by: The following alternate every 5 seconds on the display: Heating temperature set point water temperature set point LED ON STATUS OFF No electric supply STEADY ON STATUS Electric supply present FLASHING ON STATUS Heating cycle ON: 60 The temperature set point is shown while the symbol flashes: DHW water cycle OFF water cycle ON Preheat function in progress water cycle ON: CH FAULT Heating cycle OFF No fault Heating cycle ON Safety thermostat cut-in Floor slab heating function running Pressure switch fault Probe fault 48 The temperature set point is shown while the symbol flashes: Table 1 factory default settings CODE SWITCH SETTINGS SET HEATING DHW SATK20103/HE LOW temperature SATK20203/HE MEDIUM temperature SATK SATK20403/HE HIGH temperature SATK30103/HE LOW temperature setting SATK30103/HE HIGH temperature setting C C MAX 85 C C C C C C C C Factory setting (do not modify) Can be modified to enable optional functions Switch 1: Modulating temperature regulation with compensated set point. Switch 5: water preheating function 20

21 Safety and alarms Error codes associated with faults signalled by the lighting up of the FAULT LED are also shown on the display. Heating circuit pressure switch fault (SATK30103/HE) Error code 4 4 FAULT SATK30103 series indirect HIU continuously monitor the status of the pressure switch controlling the pressure of the water in the closed heating circuit. If this pressure switch is activated, the heating circulation pump immediately comes to a stop and the modulating valve is fully closed. This fault presupposes that only the heating cycle is locked. water drawing requests can continue to be served normally. Removing a fault A return to operating mode is subordinate to the correct water pressure value being restored in the secondary heating circuit. Safety thermostat cut-in SATK20103/HE - LOW temperature SATK30103/HE - at LOW temperature setting Error code FAULT The HIUs configured to support low temperature heating continuously monitor the safety thermostat controlling the flow temperature. If the safety thermostat is activated during a general cycle, the circulation pump immediately comes to a stop and the modulating/mixing valve is completely closed. The thermal safety lock valve (SATK20103/HE) is closed. In the event of a power failure, the thermal safety valve prevents hot water for heating purposes from entering the system. After the user has reset the block imposed by the safety thermostat, the shut-off valve can only be re-enabled when the mixing/modulating valves are completely closed again. This means that if a domestic water cycle is in progress, the activation of the shut-off valve will be postponed until the end of that domestic water cycle. Removing a fault Restoring operating mode is subordinate to the execution of the manual reset by the user via the pressing of the Reset button provided for this purpose. Probe fault If a temperature probe fails, the associated cycle would be stopped immediately and prevented from continuing. Any requests to run cycles not associated to the previous one would continue to run normally. Heating probe fault Error code: 5 5 FAULT Safety valve fault SATK20103/HE - LOW temperature Error code FAULT water probe fault Error code: 6 6 FAULT Removing a fault Normal operating conditions are restored automatically once the faulty safety valve is working properly again. Compensation probe fault SATK20103/HE - LOW temperature SATK30103/HE - at LOW temperature setting Error code: FAULT Removing a fault Normal operating conditions are restored automatically once the faulty probe is working properly again. Automatic regulator functions Reset mixing/modulating valve to zero Immediately after the electric supply has been switched on, the position of the installed mixing/modulating valves is reset to zero. Pump anti-clog When the pump is not in use, it is powered on for a period of 5 seconds every 24 hours. Mixing valve/modulating valve anti-clog The anti-clogging cycle for the mixing/modulating valve is run every 24 hours. 21

22 Finishing parts for SATK20 - SATK30 series Meter box K CONTECA direct heat meter Direct heat meter for SATK series and/or meter box code Equipped with an 8-digit liquid crystal display. 24 V (ac) 50 Hz - 1 W centralized electric supply. Recessed meter box with galvanized base and painted door for interiors (RAL 9010) and finishing frame. Includes: - pair of 3/4 M manual shut-off valves, - pair of temperature pockets, - heat meter template, - fittings for DCW. Complies with directive 2004/22/EC (MI004) Code Connection Size (mm) /4 350 x 380 Code K K Connection 1/2 3/4 Meas. type single nozzle single nozzle Q nom m 3 /h 1,5 2,5 Q min l/h Meter plate Galvanized sheet metal meter plate Includes: - pair of manual 3/4 M shut-off valves - pair of temperature pockets, - heat meter insertion template, - fittings for DCW. Code Use SATK20 SATK Hydraulic backplate Hydraulic backplate painted in RAL9010, including bottom-up system connection pipes. Includes: - frame - steel pipes - air vent - pair of 3/4 M manual shut-off valves Depth: 60 mm Code Connection Size (mm) /4 276 x water function water cut-off consisting of: - BALLSTOP shut-off valve with check valve; - flow meter (MI001); - shut-off ball valve with male terminal; - flushing pipe; - mounting bracket. Code * ** 7891 Differential pressure regulating kit. Brass body. Including capillary for connection to flow pipe. Max. working pressure: 10 bar. Differential pressure fixed setting: 15 kpa - 30 kpa. Length of capillary pipe Ø 3 mm: 1,5 m. Dp regulating kit - 15 kpa Dp regulating kit - 30 kpa * 15 kpa suitable for radiator heating ** 30 kpa suitable for radiant panels and convectors Code DCW 3/4 with local reading DCW 3/4 with pulse output H unit flushing valve with manual by-pass. System connection: 1 M. User connection: 3/4 M. Complies with directive 2004/22/EC (MI001) Code Use SATK20 - SATK30 22

23 SPECIFICATION SUMMARY Code SATK20103/HE Wall-hanging, two-way heat interface unit for low temperature heating with set point regulation (25 45 C) and instantaneous domestic hot water production (42 60 C), including: electronic regulator, thermal safety relief valve, thermal safety thermostat, heating mixing valve, heating temperature probe, UPS pump with safety by-pass, fittings for heat meter, DHW production modulating valve, DHW temperature probe, plate heat exchanger, flow temperature offset probe, DHW priority flow meter, air vent cock, strainer, domestic water preheating function, dimensions L 450 x H 550 x D 265 mm. Medium: water. Maximum percentage of glycol: 30%. Maximum medium temperature: 85 C. Maximum working pressure: - primary circuit: 10 bar, domestic circuit: 10 bar. Nominal DHW exchanger capacity: 40 kw. Maximum recommended primary circuit flow rate: 1,2 m 3 /h. Maximum DHW circuit flow rate: 18 l/min. Minimum flow to activate domestic flow meter: 2,7 l/min ±0,3. Maximum pressure differential on modulating valve: 0,9 bar. Maximum pressure differential on mixing valve: 0,9 bar. Electric supply: 230 V (ac) ±10% 50Hz. Power consumption: 105 W (SATK20103HE 75 W). Protection class: IP 40. Pump: UPS (SATK20103HE UPS ). Motors: stepper 24 V. Probes: NTC 10 kω. Materials: components: brass EN CW617N. Connection pipes: copper or steel, grey PPE cover. Code SATK20203/HE Wall-hanging, two-way heat interface unit for medium temperature heating with set point regulation (50 75 C) and instantaneous domestic hot water production (42 60 C), including: electronic regulator, heating mixing valve, heating temperature probe, UPS pump with safety by-pass, fittings for heat meter, DHW production modulating valve, DHW temperature probe, plate heat exchanger, DHW priority flow meter, air vent cock, strainer, domestic water preheating function, dimensions L 450 x H 550 x D 265 mm. Medium: water. Maximum percentage of glycol: 30%. Maximum medium temperature: 85 C. Maximum working pressure: - primary circuit: 10 bar, domestic circuit: 10 bar. Nominal DHW exchanger capacity: 40 kw. Maximum recommended primary circuit flow rate: 1,2 m 3 /h. Maximum DHW circuit flow rate: 18 l/min. Minimum flow to activate domestic flow meter: 2,7 l/min ±0,3. Maximum pressure differential on modulating valve: 0,9 bar. Maximum pressure differential on mixing valve: 0,9 bar. Electric supply: 230 V (ac) ±10% 50Hz. Power consumption: 105 W (SATK20203HE 75 W). Protection class: IP 40. Pump: UPS (SATK20203HE UPS ). Motors: stepper 24 V. Probes: NTC 10 kω. Materials: components: brass EN CW617N. Connection pipes: copper/steel, grey PPE cover. Code SATK20303 Wall-hanging, two-way heat interface unit for high temperature heating with ON/OFF regulation and instantaneous domestic hot water production (42 60 C), including: electronic regulator, heating valve, fittings for heat meter, DHW production modulating valve, DHW temperature probe, plate heat exchanger, DHW priority flow meter, air vent cock, strainer, domestic water preheating function, dimensions L 450 x H 550 x D 265 mm. Medium: water. Maximum percentage of glycol: 30%. Maximum medium temperature: 85 C. Maximum working pressure: - primary circuit: 10 bar, domestic circuit: 10 bar. Nominal DHW exchanger capacity: 40 kw. Maximum recommended primary circuit flow rate: 1,2 m 3 /h. Maximum DHW circuit flow rate: 18 l/min. Minimum flow to activate domestic flow meter: 2,7 l/min ±0,3. Maximum pressure differential on modulating valve: 0,9 bar. Electric supply: 230 V (ac) ±10% 50Hz. Power consumption: 20 W. Protection class: IP 40. Motors: stepper 24 V. Probes: NTC 10 kω Materials: components: brass EN CW617N. Connection pipes: steel, grey PPE cover. Code SATK20403/HE Wall-hanging, two-way heat interface unit for high temperature heating with ON/OFF regulation and instantaneous domestic hot water production (42 60 C), including: electronic regulator, heating valve, fittings for heat meter, DHW production modulating valve, DHW temperature probe, plate heat exchanger, DHW priority flow meter, air vent cock, strainer, domestic water preheating function, dimensions L 450 x H 550 x D 265 mm. Medium: water. Maximum percentage of glycol: 30%. Maximum medium temperature: 85 C. Maximum working pressure: - primary circuit: 10 bar, domestic circuit: 10 bar. Nominal DHW exchanger capacity: 40 kw. Maximum recommended primary circuit flow rate: 1,2 m 3 /h. Maximum DHW circuit flow rate: 18 l/min. Minimum flow to activate domestic flow meter: 2,7 l/min ±0,3. Maximum pressure differential on modulating valve: 0,9 bar. Electric supply: 230 V (ac) ±10% 50Hz. Power consumption: 105 W (SATK20403HE 75 W). Protection class: IP 40. Pump: UPS (SATK20403HE UPS ). Motors: stepper 24 V. Probes: NTC 10 kω. Materials: components: brass EN CW617N. Connection pipes: steel, grey PPE cover. 23

24 Code SATK30103/HE Wall-hanging, two-way indirect heat interface unit (double exchanger) for low temperature heating with set point regulation (25 45 C)/medium temperature with set point regulation (50 75 C) and instantaneous domestic hot water production (42 60 C), including: electronic regulator, thermal safety thermostat, heating modulating valve, heating temperature probe, UPS pump with safety bypass, fittings for heat meter, DHW production modulating valve, DHW temperature probe, plate heat exchanger, flow temperature offset probe, DHW priority flow meter, air vent cock, strainer, filling unit with backflow preventer, safety relief valve (3 bar), expansion vessel (7,5l), pressure switch, pressure gauge, domestic water preheating function, dimensions L 550 x H 630 x D 265 mm. Medium: water. Maximum percentage of glycol: 30%. Maximum medium temperature: 85 C. Maximum working pressure: - primary circuit: 16 bar, primary circuit: 3 bar, domestic circuit: 10 bar. Nominal DHW exchanger capacity: 40 kw. Nominal heating exchanger capacity: 40 kw. Maximum recommended primary circuit flow rate: 1,2 m 3 /h, Maximum domestic circuit flow rate: 18 l/min. Minimum flow to activate domestic flow meter: 2,7 l/min ±0,3. Maximum pressure differential on modulating valve: 0,9 bar. Maximum pressure differential on mixing valve: 0,9 bar, Power supply: 230 V (ac) ±10% 50Hz. Electric consumption: 105 W (SATK30103HE 75 W). Protection class: IP 40. Pump: UPS (SATK30103HE UPS ). Motors: stepper 24 V. Probes: NTC 10 kω. Materials: components: brass EN CW617N. Connection pipes: copper or steel, grey PPE cover. We reserve the right to change our products and their relevant technical data, contained in this publication, at any time and without prior notice. Caleffi S.p.A. S.R. 229 n Fontaneto d Agogna (NO) Italy Tel Fax info@caleffi.com Copyright 2013 Caleffi

Electric Flow Boiler

Electric Flow Boiler Electric Flow Boiler EHC offer the most comprehensive range of electric boilers in the market and with our wealth of knowledge and technical expertise we have designed the Slim Jim Electric Flow Boiler

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

CALEFFI. Compact automatic flow rate regulator with polymer cartridge. 127 series 01166/09 GB

CALEFFI. Compact automatic flow rate regulator with polymer cartridge. 127 series 01166/09 GB Compact automatic flow rate regulator with polymer cartridge 127 series REGISTERED BS EN ISO 9001:2000 Cert. n FM 21654 UNI EN ISO 9001:2000 Cert. n 0003 CALEFFI 01166/09 GB Function The AUTOFLOW devices

More information

stainless steel pre-assembled manifolds

stainless steel pre-assembled manifolds TECHNICAL CATALOGUE stainless steel pre-assembled manifolds TEC ITAP SpA, founded in Lumezzane (Brescia) in 1972, is currently one of the leading production companies in Italy of valves, fittings and

More information

ELECTRIC CENTRAL HEATING FLOW BOILER

ELECTRIC CENTRAL HEATING FLOW BOILER ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment

More information

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

RVL470. Heating Controller. Building Technologies HVAC Products. Series B 2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones

More information

HEAT INTERFACE UNITS (Modular)

HEAT INTERFACE UNITS (Modular) HEAT INTERFACE UNITS The Rhico T Fire Modular is probably the most versatile HIU available, the basic unit is a indirect heating only module incorporating a circulation pump on the secondary circuit. (A

More information

SOLAR HEATING SYSTEMS. www.orkli.com

SOLAR HEATING SYSTEMS. www.orkli.com SOLAR HEATING SYSTEMS www.orkli.com // 2 Orkli is one of the main European manufacturers of components for household appliances and innovative solutions for the comfort sector. Its corporate activity is

More information

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R8216470-01EN - Edition 01-26/10/2009

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R8216470-01EN - Edition 01-26/10/2009 Instantaneous Gas Water Heaters Storage Gas Water Heaters SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model R8216470-01EN - Edition 01-26/10/2009 Boilers CUENOD Renewable 3121488 12 EAA1...... 3124527 25

More information

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Technical Information sheet 0001/07/Rev01 ENG FUNCTION Series S001 and S002 circulation units are applied to the primary circuit of solar

More information

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions Alpha Climatic Programmable Modulating Boiler Energy Manager Part No 3.022144 (Hard Wired) Part No 3.022143 (Radio Frequency) Installation and User Instructions 1. Description The Alpha Climatic energy

More information

Automatic control equipment for HVAC systems

Automatic control equipment for HVAC systems Automatic control equipment for HVAC systems Products for domestic and industrial installations In buildings, the main aim of the installations is to guarantee and maintain a comfortable ambient. Watts

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

Heating Controller. Building Technologies HVAC Products

Heating Controller. Building Technologies HVAC Products 2 474 Heating Controller RVP300 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or

More information

PELLEXIA COMFORT ENVIRONMENT COMPATIBLE

PELLEXIA COMFORT ENVIRONMENT COMPATIBLE PELLEXIA COMFORT ENVIRONMENT COMPATIBLE To valorize the pellet MODEL nominal output min/max kw global output min/max % pellet reservoir content kg PELLEXIA 7 8 7 8,8 89 50 PELLEXIA 40 3 39,7 85 90,3 50

More information

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE Fujitsu General realizes considerable energy saving operations by the Heat pump heating system using the ambient

More information

Operating instructions

Operating instructions 6302 6959 02/2006 GB For the user Operating instructions Logano G215 WS Oil and gas-fired boilers Please read thoroughly before use. Overview Regulations and directives Installation: 90/396/EEC gas appliance

More information

series 5350 5351 Materials Body: 1/2, 3/4 and 1 : dezincification resistant alloy brass EN 12165 CW617N

series 5350 5351 Materials Body: 1/2, 3/4 and 1 : dezincification resistant alloy brass EN 12165 CW617N Pre-adjustable pressure reducing valves with self-contained cartridge - series CCREDITED ISO 9 FM ISO 9 No. CLEFFI / GB replaces / GB Function Pressure reducing valves are devices which, when installed

More information

Operation manual. Daikin Altherma hybrid heat pump EHYHBH05AA EHYHBH08AA EHYHBX08AA. Operation manual Daikin Altherma hybrid heat pump.

Operation manual. Daikin Altherma hybrid heat pump EHYHBH05AA EHYHBH08AA EHYHBX08AA. Operation manual Daikin Altherma hybrid heat pump. EHYHBH05AA EHYHBH08AA EHYHBX08AA English Table of contents Table of contents 1 About this document 2 2 About the system 2 2.1 Components in a typical system layout... 2 3 Operation 3 3.1 Overview: Operation...

More information

Daikin Altherma Hybrid Heat Pump

Daikin Altherma Hybrid Heat Pump your comfort. our world. Daikin Altherma Hybrid Heat Pump Smart heating technology for the best of both worlds Heating Integrated Solutions Ventilation Air Conditioning Refrigeration Forward thinking About

More information

SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:

SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to: OPERATING LIMITS Flows up to: m /h* Heads up to: m C Max operating pressure: bars Temperature range: - à + C Max ambient temperature: + C ND of orifices: à * m /h: parallel operation SIRIUX SINGLE AND

More information

Baxi Combi 130 HE. User s Operating Instructions. Gas Fired Wall Mounted Condensing Combination Boiler

Baxi Combi 130 HE. User s Operating Instructions. Gas Fired Wall Mounted Condensing Combination Boiler User s Operating Instructions Baxi Combi 130 HE Gas Fired Wall Mounted Condensing Combination Boiler Please keep these instructions safe. Should you move house, please hand them over to the next occupier.

More information

Luna 3 Comfort Troubleshooting Guide June 2008

Luna 3 Comfort Troubleshooting Guide June 2008 Luna 3 Comfort Troubleshooting Guide June 2008 For Technical Assistance Call: (800)461-4657 WARNING! THIS DOCUMENT IS INTENDED ONLY AS AN EDUCATIONAL TOOL This Troubleshooting Guide, and the instructions

More information

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

TANKLESS WATER HEATER INSTALLATION DIAGRAMS TANKLESS WATER HEATER INSTALLATION DIAGRAMS Installation Diagrams Tankless Installation / Optional Return Small 10-15 Gallon Point-of-Use Water Single and Optional Return : One single, small capacity water

More information

Air Source Heat Pump Installation and Maintenance Manual

Air Source Heat Pump Installation and Maintenance Manual Air Source Heat Pump Installation and Maintenance Manual Model Numbers: RC090MHXEA RC160MHXEA January 2013 www.samsungehs.co.uk Hendra - January 2013 1 The outdoor unit (boiler) Deciding on Where to Install

More information

Daikin Altherma Hybrid Heat Pump

Daikin Altherma Hybrid Heat Pump your comfort. our world. Daikin Altherma Hybrid Heat Pump The natural combination Heating Integrated Solutions Ventilation Air Conditioning Refrigeration About Daikin Forward thinking... Daikin has a worldwide

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

Link-Up. Solid Fuel Association Guide to Central Heating. www.solidfuel.co.uk

Link-Up. Solid Fuel Association Guide to Central Heating. www.solidfuel.co.uk Solid Fuel Association Guide to Central Heating Link-Up Combining solid fuel with other central heating technologies using various methods ranging from a simple link-up to a fully integrated thermal store

More information

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp. EGLISH 1 Product description exchanger equipped with an electronic control unit and circulation pump for the primary circuit. All Aqua-Mex variants can be ordered with an interior coil of either titanium

More information

LG Electronics AE Company, Commercial Air Conditioning

LG Electronics AE Company, Commercial Air Conditioning www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,

More information

RRV934. Multi-controller. Synco living

RRV934. Multi-controller. Synco living s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard

More information

Daikin Altherma Hybrid Heat Pump

Daikin Altherma Hybrid Heat Pump Daikin Altherma Hybrid Heat Pump Smart technology for the best of both worlds NATIONAL HEAT PUMP 19 JUNE 2014 ICC BIRMINGHAM WINNER Forward thinking Now is the time to rethink the way we heat our homes

More information

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents

More information

LK Electric Boiler - 4,5

LK Electric Boiler - 4,5 LK Electric Boiler -, Design LK Electric Boiler, kw is a wall-mounted electric boiler, intended primarily for low-temperature heating systems, e.g. under floor heating. LK Electric Boiler, kw is delivered

More information

For installation guide see reverse of book

For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems 3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost

More information

Natural geothermal energy.

Natural geothermal energy. ROTEX ground source heat pump Natural geothermal energy. ROTEX HPU ground the ground source heat pump that heats with free geothermal energy. Compact, environmentally responsible and uniquely efficient.

More information

ALFEA HYBRID DUO GAZ. New Model 2011

ALFEA HYBRID DUO GAZ. New Model 2011 ALFEA HYBRID DUO GAZ New Model 2011 1 Context Market: The renovation market for heat pumps stagnates since 2 years whereas the gas condensing market remains dynamic Interest of Alfea Hybrid Duo Gas: Regarding

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump. English Table of contents Table of contents 1 About this document 2 2 About the system 2 2.1 Components in a typical system layout... 2 3 Operation 3 3.1 Overview: Operation... 3 3.2 The user interface

More information

User manual and Installation instructions

User manual and Installation instructions Wall hung, fanflue, roomsealed, high efficiency gas boiler User manual and Installation instructions Riva Plus HE Models G.C. Appl. No. M296.24SM/C 47-583-24 Combi boiler M296.28SM/C 47-583-25 Combi boiler

More information

1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None

1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None 1-Way Chilled Water Cassettes KCO 60, 90 & 120 Technical Brochure TM KCO-W.1GB Date : November 2005 Supersedes : None General Features Control valve (optional) Air vent In-tube electric heating elements

More information

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

1. RANGE OF APPLICATION 3. SAFETY INSTRUCTIONS 4 4. DESIGN 4

1. RANGE OF APPLICATION 3. SAFETY INSTRUCTIONS 4 4. DESIGN 4 Henco Snelselectie kaart EN IMPORTANT! Before starting work the fitter must carefully read this installation and operation manual, understand and observe its conditions. The water floor heating control

More information

The natural ombination

The natural ombination The natural ombination DAikin Altherma Hybrid heat pump system The future is now The new hybrid system Heat pump solution for gas boiler replacement market Daikin Altherma hybrid combines heat pump technology

More information

Visions become real. Temperature control and cooling systems. The innovative and reliable solution

Visions become real. Temperature control and cooling systems. The innovative and reliable solution Temperature control and cooling systems The innovative and reliable solution With our PulseTemp equipment you have the option of up to 72 cooling circuits in the impulse cooling, temperature control, temperature

More information

8 716 473 216-00.3O. Gas boiler. Gaz 6000 W WBN 6000-30-H-E-N/L-S2400. Operating instructions for the end customer. 8 716 473 217 (2014/07) en

8 716 473 216-00.3O. Gas boiler. Gaz 6000 W WBN 6000-30-H-E-N/L-S2400. Operating instructions for the end customer. 8 716 473 217 (2014/07) en 8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................

More information

Operation manual. Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3

Operation manual. Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3 EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3 English Table of Contents Table of Contents 1 About this document 2 2 About the system 2 2.1 Components in a typical system layout... 2 3 Operation 3 3.1 Overview:

More information

Smile. The All-In-One Heating Controller

Smile. The All-In-One Heating Controller Smile EVERYTHING UNDER CONTROL The All-In-One Heating Controller Versatile, energy-efficient heating control. The All-In-One Heating Controller Smile controllers are ideal to gain maximum efficiency from

More information

1 General information

1 General information 1 General information 1.1 About this manual This manual describes the installation, function and operation of an integrated solar control system, which is suitable for split pressurized solar heating system.

More information

Price List Rev.2. AGUIDROVERT S.L. c/ Cervantes 20, Zaragoza 50.006 (Spain) Tel.: 976302135 Fax: 976468085 www.aguidrovert.com info@aguidrovert.

Price List Rev.2. AGUIDROVERT S.L. c/ Cervantes 20, Zaragoza 50.006 (Spain) Tel.: 976302135 Fax: 976468085 www.aguidrovert.com info@aguidrovert. Price List Rev.2 2010 AGUIDROVERT S.L. c/ Cervantes 20, Zaragoza 50.006 (Spain) Tel.: 976302135 Fax: 976468085 www.aguidrovert.com info@aguidrovert.com SOMMARIO INDEX SOLAR SYSTEMS... page 10 COMPONENTS

More information

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2

More information

Daikin Altherma hybrid heat pump. The natural combination

Daikin Altherma hybrid heat pump. The natural combination Daikin Altherma hybrid heat pump The natural combination Daikin Altherma hybrid heat pump, the natural combination Why choose Daikin Altherma hybrid heat pump? What the customer wants: more energy efficient

More information

Session 2: Hot Water Supply

Session 2: Hot Water Supply MEBS6000 Utility Services http://www.hku.hk/mech/msc-courses/mebs6000/index.html Session 2: Hot Water Supply Dr. Benjamin P.L. Ho Department of Mechanical Engineering The University of Hong Kong E-mail:

More information

RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary

RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary January 2013 TABLE OF CONTENTS INTRODUCTION... 3 GENERAL RECOMMENDATIONS... 3 Communication with customers in the field of environmental sustainability...

More information

Baxi Combi 80e & 105e

Baxi Combi 80e & 105e Baxi Combi 8e & 15e Please keep these instructions safe. Should you move house, please hand them over to the next occupier. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Natural

More information

Installation and Operation Instructions Domestic hot water modules: FriwaMidi DN 20 FriwaMaxi DN 25

Installation and Operation Instructions Domestic hot water modules: FriwaMidi DN 20 FriwaMaxi DN 25 PAW GmbH & Co. KG Böcklerstr. 11, D-31789 Hameln, Germany Phone: +49-5151-9856-0, Fax: +49-5151-9856-98 E-mail: info@paw.eu, Web: www.paw.eu Installation and Operation Instructions Domestic hot water modules:

More information

Product and Application Description

Product and Application Description Technical Product - Information Product and Application Description The room temperature controller UP 237K and UP 252K are available in the following colors, matching the design of the wall switch design

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support

More information

Spare Parts List M96A.24SM/B M96A.28SM/B

Spare Parts List M96A.24SM/B M96A.28SM/B *16202390* 162.0239.0 REV5 14/04 2015 Spare Parts List M96A.24SM/B M96A.28SM/B Issue Table description Issue n. of pages Overall view 09/2008 1 C.h. return group and d.h.w. heat exchanger 09/2008 1 C.h.

More information

Contents. Introduction

Contents. Introduction TION Contents Introduction...1 Basics...2 Main Menu Structure...3 Time Schedule Menu...4 Settings Menu...5 Reports Menu...6 Date / Time Adjustment Menu...7 Introduction TION is an advanced control device

More information

HEAVY DUTY STORAGE GAS

HEAVY DUTY STORAGE GAS Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many

More information

Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, 1060. Instruction No.

Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, 1060. Instruction No. Instruction No. AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA PIPING GUIDE GF-115-P Modulex Gas Fired Boiler Systems Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909,

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries

More information

COMPUTHERM Q7 Programmable, digital room thermostat. Operating Instructions

COMPUTHERM Q7 Programmable, digital room thermostat. Operating Instructions COMPUTHERM Q7 Programmable, digital room thermostat Operating Instructions GENERAL DESCRIPTION OF THE THERMOSTAT The COMPUTHERM Q7 type switched-mode room thermostat is suitable to regulate the overwhelming

More information

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

Ergo-Pro Single Line Solar Station Installation and Operating Instructions Rp 3/4 Ergo-Pro Single Line Solar Station Installation and Operating Instructions Item No Pump type 677.21.70 WILO ST 15/6 13 2 4 11 Technical Specifications Max. operating pressure: 6 bar Max. operating

More information

Zenith Solar thermal 4.5m pump station Installation manual

Zenith Solar thermal 4.5m pump station Installation manual Zenith Solar thermal 4.5m pump station Installation manual Product code: 20026145 INSTALLATION MANUAL WATER RETURN GROUP This instruction manual is an integral part of the installation and maintenance

More information

Heating, air-conditioning, cooling

Heating, air-conditioning, cooling Series description Design High efficiency, single stage, low pressure, inline centrifugal pump Supplied with EC motor and electronic duty adaptation Available in glanded construction, mechanical shaft

More information

Spare Parts List Activ A 25C Activ A 30C Activ A 35C Activ A 18S Activ A 25S Activ A 30S

Spare Parts List Activ A 25C Activ A 30C Activ A 35C Activ A 18S Activ A 25S Activ A 30S *1756202470* 17562.0247.0 REV3 06/09 2012 Spare Parts List Activ A 25C Activ A 30C Activ A 35C Activ A 18S Activ A 25S Activ A 30S Issue Table description Issue n. of pages Overall view 06/2009 1 C.h.

More information

Baxi Combi Instant 80e & 105e. User s Operating Instructions. Gas Fired Wall Mounted Combination Boiler

Baxi Combi Instant 80e & 105e. User s Operating Instructions. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Baxi Combi Instant 8e & 15e Gas Fired Wall Mounted Combination Boiler Please keep these instructions safe. Should you move house, please hand them over to the next occupier.

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer

More information

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER

More information

Power consumption (kw)

Power consumption (kw) OS Series Series description LIT OS systems are applied to wastewater disinfection. The models of this series were developed on base of high-efficiency low-pressure amalgam lamps and have all components

More information

Installation and maintenance instructions. Danfoss Vent

Installation and maintenance instructions. Danfoss Vent Installation and maintenance instructions Danfoss Vent 1 Unit design... 2 2 Project planning and installation instructions... 3 2.1 Ventilation...3 2.2 Piping installation....3 2.3 Condensation line...4

More information

Technical Data Manual Model Nos. and pricing: see Price List

Technical Data Manual Model Nos. and pricing: see Price List VITOCELL-V 00 Indirect-fired domestic hot water storage tank 4 to 0 / 60 to Technical Data Manual Model Nos. and pricing: see Price List Vitocell-V 00 4 to / 60 to Vitocell-V 00 0 / Vitocell-V 00 CVA Series

More information

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle

More information

THERMOSTATIC ACTUATORS WITH LIQUID-FILLED SENSITIVE ELEMENTS AND TEMPERATURE LOCKING

THERMOSTATIC ACTUATORS WITH LIQUID-FILLED SENSITIVE ELEMENTS AND TEMPERATURE LOCKING 0A-GB THERMOSTATIC ACTUATORS WITH LIQUID-FILLED SENSITIVE ELEMENTS AND TEMPERATURE LOCKING SERIES SD - CD - GA MAIN CHARACTERISTICS - Available in the versions: Standard With Remote Sensor With Remote

More information

The natural ombination

The natural ombination The natural ombination DAIKIN ALTHERMA HYBRID HEAT PUMP 2 A new pportunity in residential heating! There is a growing demand from home owners to replace heating systems, especially replacing of gas boilers,

More information

CM702 PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

CM702 PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET CM702 PROGRAMMABLE THERMOSTAT FEATURES Attractive slim, modern styling makes it ideal for location in any type of home. 24-hour heating program. Up to 4 daily independent time and temperature level changes

More information

Single Zone LCD Thermostat Operating Instructions

Single Zone LCD Thermostat Operating Instructions Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip

More information

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual Speedflow Undersink Unvented Water Heater Models SF10K and SF15K Instruction Manual Version 2.0 May 2009 Hyco SpeedFLOW UnVENTED WATER HEATER Models SF10K (10 Litres) and SF15K (15 Litres) 1. Introduction

More information

type UTA Technical information manual

type UTA Technical information manual type UTA Technical information manual 2 > UTA ECHOS Ductable direct expansion fan coil unit 3 GENERALlTY Units for applications of residential and commercial type, characterised by reduced dimensions and

More information

RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions

RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions RVR Hybrid System Controller Installation Instructions 1 Introduction to Hybrid Systems The RVR Hybrid system uses a combination of the Immergas Audax range of heat pumps with gas or oil boilers to create

More information

Operating instructions

Operating instructions Operating instructions Gas condensing boilers MGK-130 MGK-170 MGK-210 MGK-250 MGK-300 Wolf GmbH Postfach 1380 D-84048 Mainburg Tel. +49 8751/74-0 Fax +49 8751/741600 Internet: www.wolf-heiztechnik.de Document

More information

OZW30. Central Unit SYNERGYR

OZW30. Central Unit SYNERGYR 2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control

More information

A Class Air Source Heat Pump User Guide

A Class Air Source Heat Pump User Guide A Class Air Source Heat Pump User Guide IMPORTANT THIS MANUAL MUST BE LEFT WITH THE USER AFTER INSTALLATION 8/60476/0 Issue 1.03 Contents 1: Introduction 1 2: How the Heat Pump Works 1 2.1 Tips and advice

More information

30% Safe. DESIGN GUIDE The Danfoss EvoFlat system from A-Z Take lead on your project with an efficient system concept. evoflat.danfoss.

30% Safe. DESIGN GUIDE The Danfoss EvoFlat system from A-Z Take lead on your project with an efficient system concept. evoflat.danfoss. MAKING MODERN LIVING POSSIBLE DESIGN GUIDE The Danfoss EvoFlat system from A-Z Take lead on your project with an efficient system concept Safe and comfortable EvoFlat systems provide heating and domestic

More information

SWIMMING POOL HEAT PUMP Owners Manual

SWIMMING POOL HEAT PUMP Owners Manual SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 17.0kw and 21.0kw models only. The heat pump unit is sold with a 1 year warranty. In addition there is a 2 year parts warranty on the compressor

More information

Range Tribune HE Solar Unvented Direct and Indirect Cylinders

Range Tribune HE Solar Unvented Direct and Indirect Cylinders Range Tribune HE Solar Unvented Direct and Indirect Cylinders Range Tribune HE Solar cylinders have been designed specifically with Solar applications in mind and are based on the highly successful Range

More information

Series description: Wilo-Star-Z

Series description: Wilo-Star-Z H[m] Series description: Wilo-Star-Z 4 3 Wilo-Star-Z Star-Z 2/5 2/4 2 1 Star St ar- Z1 5T Design Glandless circulation pump with threaded connection Application Potable water circulation systems in industry

More information

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings.

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings. 1100 & 1400 Energy Controllers Satchwell 1100 & 1400 for energy-efficient temperature control in smaller buildings. 02 1100 & 1400 Energy Controllers Features he 1100 and 1400 Energy Controllers are self-configuring

More information

HDA -----------------------------------------------------------

HDA ----------------------------------------------------------- ----------------------------------------------------------- Lightstrips ---------------------------------------------------------------------- Ceiling system for heating and cooling LIGHTSTRIPS LIGHTSTRIPS

More information

Technical data. Danfoss DHP-A

Technical data. Danfoss DHP-A Technical data Danfoss DHP-A An air heat pump which produces both heat and hot water Can operate efficiently down to -0 C Danfoss TWS tank gives plenty of hot water quickly and with low operating costs

More information

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS Electronic thermostatically controlled Low power consumption Compact space saving size Short heat-up times Dehumidification of the cabin Quiet when running Combustion

More information

Overheating limit control

Overheating limit control Pahlén electric heater Maxi Heat with digital control is a compact and effective heater for swimming pools. It consists of a glassfibre reinforced polypropylene tank containing resistance-type heating

More information

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump MAINTENANCE INSTRUCTIONS Thermia Robust heat pump 9 6 8 0-5 4 7 4 5 0 0 1 R e v. 3 Table of contents 1 Important information.................. 2 1.1 Product description....................... 2 1.2 General................................

More information

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C COOLS conditioned server - racks for direct installation into the room COOLSIDE box INVERTER R410A E C 2 COOLSIDE box GENERAL FEATURES COOLSIDE BOX is a split system consisting of an outdoor motocondensing

More information

ASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

ASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International Presentation Overview Water Heater Piping Strategies How to size a water heater?

More information

Thermo Siphon Solar Systems

Thermo Siphon Solar Systems Thermo Siphon Solar Systems Thermo Siphon Solar Systems are a very cost effective way of producing hot water due to their simplicity in design and installation requirements. Usually more common in hotter

More information

Sizing and Selection of Hot Water Generating Plant. Presentation by: Rob Larner & David Dutch

Sizing and Selection of Hot Water Generating Plant. Presentation by: Rob Larner & David Dutch Sizing and Selection of Hot Water Generating Plant Presentation by: Rob Larner & David Dutch SIZING HOT WATER PLANT - agenda Consider different sizing methods. Arrive at a design example for a 200 bed

More information