200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

Similar documents
KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

KNOW YOUR OPTIONS: 230 KV POWER CABLES

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

ELASTIMOLD CATALOG SP2. Issue Date: 03/2003

Section kv Power Cables

Medium Voltage Terminations, 5 kv 46 kv

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

Product Selection Guide

RayClic Connection System Installation Instructions

I-Line. Accessories. Essential cable installation products for corrugated, smooth wall, and braided cables

No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint

Arbiter Systems Test Leads: Engineered for Optimum Performance and Safety

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities

Section 21. Telecommunication Hardware. BuyLog Catalog 21-1

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

How To Test A Power Cable For Power And Safety

Cable Accessories. for Extruded Dielectric Cable 69kV - 230kV Rated. Catalog Python13

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS

DC disconnects for solar photovoltaic installations. Connecting the. power of the sun

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide

RayClic Connection System Installation Instructions

TMC CableReady Connectors For Jacketed Metal Clad Cable TMC For Non-Hazardous Locations

Type MOST oil switch. Technical Data Contents. Effective October 2013 Supersedes March 2000

3M Scotchcast Mine and Portable Cable Splice Kit

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

Jack to Jack adapters Plug to Plug U-Link connectors PCB Right angle plastic PCB Right angle - metal. Ordering Codes

100% EMI Emission Containment

Safetran TYPE ST1 AND ST2 VITAL PLUG-IN RELAYS I-1-1. Relays SIZE 1 AND SIZE 2 READILY MOUNTS TO EXISTING SOCKETS

KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES

Power Cable Splicing & Terminating. edited by Robert Goodman and William Osborn

AMPSEAL* Automotive Plug Connector and Header Assembly

2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits, 7620-S, 7680-S and 7690-S Series 5, 8, 15, 25/28 and 35 kv

SECTION MEDIUM VOLTAGE CABLE

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

Position Cat5e (EMT) Modular Plug Connectors. Application Specification

Installation Instructions DTS-HAZ DTS-HAZ-DC. for Use with Self-Regulating & Constant Wattage Heating Cables

Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

1ZSC AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

Cables. Accessories. For Force, Torque and Strain Sensors

General Calculations. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE

Secondary Unit Substations

ENGINEERING COMMITTEE

Fault location on power cables. Fault location on power cables

Heat Tracing Sales Mt. Airy, Maryland Installation Instructions

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014)

SMA Interface Mating Dimensions (Per MIL-STD-348)

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Hook-Up and Lead Wire

Medium Voltage Joints & Terminations

STREETLIGHT SYSTEM GROUNDING AND BONDING

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

RAY-MAX Integrated Solar Power Strip

ELECTRICAL: WIRE, CABLE, AND TERMINATIONS

COAXICON Contacts. RF Coax Connectors. Product Facts

PROFIBUS cable. for PROFIBUS-PA and -DP 10/ EN

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

USA: 866.LAWSON4U ( ) Canada: lawsonproducts.com. Electrical Industrial and Fleet Solutions

Type K current limiting fuse canister Technical information and installation guide

TubeTrace, ThermoTube

Instrumentation Cable Power Cable Assembly Solutions...32

DTS-HAZ DTS-HAZ-DC. Installation Instructions. for use with Self-Regulating, Constant Wattage & Mineral Insulated Electric Heating Cables

Transformer Bushings for GIS

Universal Vehicle Power Supply 9007AX01. Installation Instructions

16300 MEDIUM VOLTAGE DISTRIBUTION

RE-ENTERABLE SPLICE CLOSURE KITS. (For Air Core None Pressurized Cable)

Series 8146/5-V37 and Series 8150/5-V37

Caledonian Submersible Pump Cables for Oil Industry >> IEEE 1018 >> IEEE 1019 >> API RP 11S5

User s Manual. BNC Mini-High Res, 75 Ohm Termination Kit Connector Installation Guide ( )

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

SECTION SANITARY SEWER AND STORM DRAIN SYSTEMS

Exane 125 Drilling Rig and Commercial Marine Cable

MCR1900 Media Converter 19-Slot Chassis

Industrial Cable Solutions for Variable Frequency Drives

Toroidal Conductivity Sensor

Times Microwave Systems Hermetically Sealed Assemblies

APPLICATION ORIENTED DESIGN OF CABLES

Gexol. Gexol. The Global Cable Solutions Company. Designed for safe, reliable performance in the harshest oil and gas operating environments

UGVCL/SP/591/11KV HT AB CABLE

a Nexans company Catalogue 2013

5.2. Overview. The better method to install solderless compression connectors on power cable

Figure 1 (end) Updated document to corporate requirements Added text to Paragraph 2.4

WIRE AND CABLE ENGINEERING GUIDE

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

Installation instruction CASAFLEX - Connecting piece DN 100

white paper Ferrules: Your Best Insurance Against Costly Connection Failure Executive Summary

Lighting Packages. 230 VAC Fluorescent Enclosure Light:

INSTALLATION MANUAL ELECTRIC RANGE. Please read these instructions thoroughly before installing and operating the range.

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

Arktite Heavy Duty Circuit Breaking Plugs and Receptacles

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

Lightning Arresters P KVA P KVA. Description & Installation

Transcription:

Loadbreak Connectors Catalog Data CA650062EN Supersedes 500-10-7 November 2011 COOPER POWER SERIES 200 A 15 kv class loadbreak elbow connector with optional integral jacket seal General Eaton s Cooper Power series loadbreak elbow connector is a fully-shielded and insulated plug-in termination for connecting underground cable to transformers, switching cabinets and junctions equipped with loadbreak bushings. The elbow connector and bushing insert comprise the essential components of all loadbreak connections. The loadbreak elbow connector is a fully rated 200 A switching device, designed in accordance to IEEE Std 386-2006 standard. Eaton s loadbreak elbows are molded using high quality peroxide-cured insulating and semiconducting EPDM rubber. Standard features include a coppertop connector, tin-plated copper loadbreak probe with an ablative arc-follower tip and stainless steel reinforced pulling-eye. An optional capacitive test point, made of corrosion resistant plastic, is available for use with fault indicators (see Catalog Sections CA320002EN and CA320003EN). Cable ranges are designed to accept a wide range of cable conductor and insulation sizes with just three elbows and accommodate cable manufactured to either AEIC or ICEA standards. The coppertop compression connector is a standard item to transition from the cable to the loadbreak probe. An aluminum crimp barrel is inertia-welded to a copper lug. The aluminum barrel makes the connector easy to crimp and the copper lug ensures a reliable, tight, cool operating connection with the loadbreak probe. (Photo on left is shown with the integral jacket seal without test point. Photo on right is shown without jacket seal with test point.) Optional integral jacket seal The provides a quick and easy means to sealing the cable jacket to prevent moisture ingress. Our jacket seal is molded to the loadbreak elbow eliminating the need for separate cable sealing products. It s available with braided ground strap/bleeder wire for terminating Tape shielded cable. (See Figure 4.)

Catalog Data CA650062EN 200 A 15 kv class loadbreak elbow connector with SEMI-CONDUCTIVE INSERT High-quality peroxide-cured EPDM rubber creates a smooth surface around the current interchange to evenly distribute electrical stress within the insulation. PULLING EYE Stainless steel reinforced for positive hotstick switching operations. TEST POINT (OPTIONAL) Corrosion-resistant, conductive electrode provides consistent capacitive voltage for application of fault indicators and determining if the circuit is energized (cap not shown). LOADBREAK BAND UV resistant nylon band identifies the elbow as three-phase loadbreak rated and is field replaceable. INSULATION High-quality peroxide-cured EPDM rubber formulated, mixed, and milled in-house for consistent and reliable field performance. SEMI-CONDUCTIVE SHIELD High-quality peroxide-cured EPDM rubber provides protective deadfront shield that meets requirements of IEEE Std 592-2007 standard. LOADBREAK PROBE Tin-plated copper probe with arc-ablative tip (arc follower) provides dependable loadbreak switching characteristics. COPPERTOP COMPRESSION CONNECTOR Inertia-welded aluminum barrel and threaded copper lug makes crimping easy and ensures a tight, reliable electrical connection with loadbreak probe. GROUNDING TABS Molded into semi-conductive shield for the attachment of a ground wire to maintain deadfront safety. CONDUCTIVE INSERT ENDS Encapsulated with insulating rubber. Reduces cable extrusion and distortion that can be caused by thermocycling. Mitigates the effects of the electrical stresses along the cable to elbow interface, greatly reducing the possibility of interface tracking. OPTIONAL INTEGRAL JACKET SEAL The provides a quick and easy means to sealing the cable jacket to prevent moisture ingress. Also available with braided ground strap/bleeder wire for terminating tape shielded cable. Figure 1. Cutaway drawing shows design detail. 2

200 A 15 kv class loadbreak elbow connector with Catalog Data CA650062EN S4 S3 S6 S Dim. 15 kv S3 3.4 (86 mm) S4 4.2 (106 mm) S5 2.7 (68 mm) S6 1.2 (30 mm) NNote: Dimensions given are for reference only. S5 Figure 2. Elbow profile and stacking dimensions as referenced in IEEE Std 386-2006 standard. Installation Cable stripping and scoring tools, available from various tool manufacturers, are recommended for use when installing loadbreak elbows. After preparing the cable, the elbow housing is pushed onto the cable. The loadbreak probe is threaded into the coppertop connector using the supplied installation tool or an approved equivalent. Use a hotstick to perform loadmake and loadbreak operations. Refer to Installation Sheet S500-10-7 for details. Production tests Tests conducted in accordance with IEEE Std 386-2006 standard: ac 60 Hz 1 Minute Withstand 34 kv Minimum Corona Voltage Leve 11 kv Test Point Voltage Test Tests conducted in accordance with Eaton requirements: Physical Inspection Periodic Dissection Periodic Fluoroscopic Analysis Table 1. Voltage Ratings and Characteristics Description kv Standard Voltage Class 15 Maximum Rating Phase-to-Phase 14.4 Maximum Rating Phase-to-Ground 8.3 ac 60 Hz 1 Minute Withstand 34 dc 15 Minute Withstand 53 BIL and Full Wave Crest 95 Minimum Corona Voltage Level 11 Voltage ratings and characteristics are in accordance with IEEE Std 386-2006 standard. Table 2. Current Ratings and Characteristics Description Amperes Continuous 200 A rms Switching 10 operations at 200 A rms at 14.4 kv Fault Closure 10,000 A rms symmetrical at 14.4 kv for 0.17 s after 10 switching operations Short Time 10,000 A rms symmetrical for 0.17 s 3,500 A rms symmetrical for 3.0 s Current ratings and characteristics are in accordance with IEEE Std 386-2006 standard. 3

Catalog Data CA650062EN 200 A 15 kv class loadbreak elbow connector with Ordering information The elbow kits are packaged in a heavy duty polyethylene bag. There are 20 bagged kits to a carton. Individual boxed kits are also available by special part number. To order a 15 kv Class loadbreak elbow kit follow the easy steps below. Each kit contains: Standard Elbow Body or Elbow Body with Jacket Seal Coppertop Compression Connector Loadbreak Probe Probe Installation Tool Silicone Lubricant Mastic Strips (Jacket Seal Elbow Only) Installation Instruction Sheet STEP 1e: Determine the cable s diameter over the electrical insulation as shown in Figure 3 (including tolerances) from cable manufacturer. Then identify a cable range from Table 3 that brackets the minimum and maximum insulation diameters. Select the CABLE RANGE from the far right column. STEP 2e: Identify the conductor size and type in Table 4 and select the from the far right column. STEP 3e: For an elbow kit with a capacitive test point order: LE215 CABLE RANGE For an integral jacket seal elbow kit with a capacitive test point order: T DIAMETER OVER OUTER JACKET OUTER JACKET METAL NEUTRAL OR SHIELD INSULATION SHIELD INSULATION DIAMETER OVER INSULATION SHIELD Figure 3. Illustration showing typical construction of high voltage underground cable. Table 3. Cable Range Code (Insulation Diameter) for Loadbreak Elbow Inches Millimeters Cable Range Code 0.495-0.585 12.6-14.9 CCA* 0.575-0.685 14.6-17.4 CCB* 0.610-0.970 15.5-24.6 AB 0.750-1.080 19.1-27.4 CC 0.890-1.220 22.6-30.0 DD * Uses 5 kv cable adapter. (For use with CC range elbow only.) LEJ215 CABLE RANGE T For an elbow kit without a capacitive test point order: LE215 CABLE RANGE For an integral jacket seal elbow kit without a capacitive test point order: LEJ215 CABLE RANGE For an elbow kit without a compression connector, use 00 for the conductor code. For an elbow kit with a hold down bail assembly included, insert a B after the test point option code. Step 4e: For optional braided ground strap/bleeder wire for terminating tape shielded cable, insert GS after test point and/or bail option code. (Integral Jacket Seal Elbow Only) Step 5e: (Optional) For an elbow kit individually packaged in a corrugated cardboard box, insert an X as the last character in the part number. 4

200 A 15 kv class loadbreak elbow connector with Catalog Data CA650062EN Table 4. Conductor Size and Type Class B Stranded or Compressed Compact or Solid AWG mm 2 AWG mm 2 No Connector 00 #6 16 #4 01 #4 #3 25 02 #3 25 #2 35 03 #2 35 #1 04 #1 1/0 50 05 1/0 50 2/0 70 06 2/0 70 3/0 07 3/0 4/0 95 08 4/0 95 250 120 09 250* 120 300 10 * Compressed stranding only. Conductor Code EXAMPLEe: Select an integral jacket seal elbow kit with a capacitive test point for use on a #1 compact cable with a minimum insulation diameter of 0.770 and a maximum diameter of 0.830. STEP 1e: From Table 3, identify the cable range 0.750 1.080 and select the CC CABLE RANGE. STEP 2e: The conductor size is a #1 and the type is compact. From Table 4, under the column Compact or Solid identify #1 and select the 04 conductor code. STEP 3e: Order catalog number. LEJ215CC04T 5

Catalog Data CA650062EN 200 A 15 kv class loadbreak elbow connector with Table 5. Replacement 2.88 Long Coppertop Connectors Conductor Size Concentric or Compressed Compact or Solid AWG mm 2 AWG mm 2 #6 16 #4 CC2C01T #4 #3 25 CC2C02T #3 25 #2 35 CC2C03T #2 35 #1 CC2C04T #1 1/0 50 CC2C05T 1/0 50 2/0 70 CC2C06T 2/0 70 3/0 CC2C07T 3/0 4/0 95 CC2C08T 4/0 96 250 120 CC2C09T 250* 120 300 CC2C10T * Compressed stranding only. Catalog Number Notee: Coppertop compression connector may be used on both aluminum and copper cable conductors. Table 6. Replacement Parts Description Hold Down Bail Assembly 5 kv Cable Adapter (for use with C Elbow size only),.495.585.575.685 Loadbreak Band (package of 25) Probe Kit (includes Probe, Installation Tool, Silicone Lubricant, Installation Instruction Sheet) Loadbreak Probe Installation Tool Loadbreak Probe Only Silicone Grease 0.175 oz tube (5 grams) 5.3 oz tube (150 grams) Includes Ground Braid, Constant Force Spring and Mastic Catalog Number 2638351C01B CA225A CA225B 2639139B01B PK215 2602733A01 2637552C03 2603393A03 2605670A02M GRDBRAIDKIT Accessories Figure 4. Braided ground strap accessories (see Table 6). Figure 5. 5 kv cable adapter (see Table 6). Figure 6. Optional bail assembly (see Table 6). 6

200 A 15 kv class loadbreak elbow connector with Catalog Data CA650062EN This page intentionally left blank. 7

Catalog Data CA650062EN 200 A 15 kv class loadbreak elbow connector with Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Cooper Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2015 Eaton All Rights Reserved Printed in USA Publication No. CA650062EN Eaton, and Cooper Power are valuable trademarks of Eaton in the U.S. and other countries. You are not permitted to use these trademarks without the prior written consent of Eaton. IEEE Std 386-2006 and Std 592-2007 standards are trademarks of the Institute of Electrical and Electronics Engineers, Inc., (IEEE). This publication is not endorsed or approved by the IEEE. For Eaton's Cooper Power series loadbreak elbow connector product information call 1-877-277-4636 or visit:.