Insulation Resistance (R iso ) of Non-Galvanically Isolated PV Plants



Similar documents
Criteria for Selecting a Residual-Current Device

SUNNY TRIPOWER 5000TL 12000TL

Three phase connection

Technical Information Battery Management of the Sunny Island Gentle charging control for lead-acid batteries based on current state of the battery

Communication Interface for SMA Inverters SMA BLUETOOTH PIGGY-BACK

Technical Information Short-Circuit Currents Information on short-circuit currents of SMA PV inverters

Inverters. The product range.

SIMADYN D Digital Control System. Interface module SE21.2. User Manual. Edition DK-Nr

Medium-voltage Transformers

Sunny Boy SB 700. String Inverter 700 W, grid-tied operation, grid frequency 777,00 50 Hz / 60 Hz auto-detection SB 1100LV

ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw

How To Use The Sunny Central Communication Controller

Performance ratio. Contents. Quality factor for the PV plant

/ The personal storage solution for 24H Sun. / Dynamic Peak Manager. / Smart Grid Ready THREE-PHASE

Sunny Family 2012 PRODUCT CATALOG

Yield Reduction due to Shading:

MITSUBISHI ELECTRIC ANNOUNCES PHOTOVOLTAIC INVERTER FOR EUROPEAN MARKET

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

sma FlexIble storage system

2.06. Version. Kinglong New Energy Technology Co.Ltd. Sunteams 1500 Sunteams Sunteams 4000 Sunteams 5000

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2

Monitor Simply and Securely

YSmart Technology Co.,Ltd

User Manual DONGGUAN SHENGYANG INDUSTRIAL CO., LTD. SY WMVC Smart Grid Tie Microinverter. Dongguan Shengyang Industrial Co., Ltd.

PV-Lifeline Safety in case of danger

Residual Current Circuit Breaker

PERFORMANCE OF MPPT CHARGE CONTROLLERS A STATE OF THE ART ANALYSIS

How To Make A Fronius Cl Power Inverter

Electrical safety requirements in DC distribution systems

Insulation resistance

Designing PV Plants Optimised for Economic Efficiency

Guidance for upgrading to GB (IEC : 2005, MOD)

Touch Screen Technology. Taking apart a tablet

A Practical Guide to Dielectric Testing

Firmware Update with SD Card SUNNY BOY WINDY BOY SUNNY TRIPOWER

Resistors in Series and Parallel

Electrical and mechanical interface requirements for separable HR, LR and LRM voltage detecting systems

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

SUNNY BOY 2000HF / 2500HF / 3000HF

SIMATIC S Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E

PID - The Problem and How to Solve It

PV Inverter SUNNY TRIPOWER 8000TL/10000TL/12000TL/15000TL/17000TL

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

The full wave rectifier consists of two diodes and a resister as shown in Figure

CURRENT ELECTRICITY INTRODUCTION TO RESISTANCE, CAPACITANCE AND INDUCTANCE

ABB central inverters PVS to 1000 kw

CUTES Solar Power System

Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL

PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power:

SolarMax P series The power package for residential solar plants

Application Note, V1.0, Nov AN Using the NTC inside a power electronic module IMM INP LP

Sunny Boy Accessories SMA POWER BALANCER


Measuring Biased Inductors with the GenRad Digibridge

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

PV And Storage: Solutions with Potential

Service & Support. Higher-level safe switch-off of the power supply of functionally nonsafe standard modules? Wiring Examples.

Romana Brentgens / photon-pictures.com (2)

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

WVC300 Micro-inverter solar grid system (Power line communications)

8 Ways Power Optimizers are Better by Design

THE SUPERFLEX DESIGN OF THE FRONIUS SYMO INVERTER SERIES

HIGH FREQUENCY TRANSFORMER WITH TRANSFORMER SWITCHOVER

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS:

Line Reactors and AC Drives

Cable Discharge Event

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC)

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

Simple and secure monitoring

Modeling Grid Connection for Solar and Wind Energy

32/1/ /PVSE(Part-II) Ministry of New and Renewable Energy SPV Off Grid Division

SMA Bluetooth. Content. SMA Bluetooth Wireless Technology in Practice. Further Documents on SMA Bluetooth

Measurement of Capacitance

Power Management & Supply. Design Note. Version 1.0, Nov DN-EVALMF2ICE2A CoolSET 35W DVD Power Supply with ICE2A265.

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Checklist Testing and inspection without interconnection

Thyristor-controlled power supplies and battery chargers

Application Note: String sizing Conext CL Series

WHITEPAPER CABLE CONDUCTOR SIZING

User Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1

Ministry of New and Renewable Energy. Jawaharlal Nehru National Solar Mission SOLAR PHOTOVOLTAIC WATER PUMPING SYSTEMS ( )

Solar Kit. Complete solution to optimize your photovoltaic system

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx

ABB Drives. User s Manual HTL Encoder Interface FEN-31

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

EE301 Lesson 14 Reading: , , and

Energy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management

User Manual of Grid Tie Inverter with Limiter

Technical Information POWER PLANT CONTROLLER

/ Our accessories complement all PV systems, simplify installation and ensure that the system meets the required safety standards.

/ The allrounder with maximum yield. / WLAN interface / Smart Grid Ready

SOLAR MICRO INVERTER 260 COMMUNICATION GATEWAY. Apparent Power Control (APC) unique micro inverter with

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

Design qualification and type approval of PV modules

CHANGING THE WORLD WITH COMPELLING IDEAS. German Indian Renewable Energy Dialogue 1st of October 2008

Photovoltaic Solar Energy Unit EESFB

DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Transcription:

Insulation Resistance (R iso ) of Non-Galvanically Isolated PV Plants with SUNNY MINI CENTRAL 9000TL/10000TL/11000TL Content PV plants with transformer-less inverters are not galvanically isolated from the grid in feed-in operation. As per the standard DIN VDE 0126-1-1, they must not exceed a certain threshold before grid connection. The prescribed threshold for such PV plants during the creation of this standard was based on established installation specifications (for example 1 k Ω /V). At the time of the creation of this standard the typical output magnitudes of the PV plants were significantly lower than today. With the increasing size of a PV plant, the insulation resistance (R iso ) has become smaller and smaller as a result of the necessary larger generator area and the parallel switching of many PV modules. This can lead to the inverter not connecting to the grid due to the insulation resistance of the entire PV plant being too low, even though all components work without problems. Together with the professional association, SMA Solar Technology AG developed a solution that takes into account the reduced insulation resistance of larger PV plants. At the same time, this solution meets the protection target of the standard, identifying insulation failures. Riso-UEN123622 Version 2.2 1/5

What is meant by R iso? 1 What is meant by R iso? Every PV plant has both before grid connection and in feed-in operation a distinct potential against ground. Only sufficient insulation against ground prevents current from the PV plant leaking to ground and rules out the dangers associated with touching and additional losses. The total ground current, also known as leakage current, is made up of the contribution of all system components together: PV modules DC cable Inverter For a given system voltage, this leakage current translates into an effective insulation resistance, which is designated by R iso. In transformer-less inverters, the continuous measurement of R iso in operation is not possible due to this missing galvanic isolation. Thus transformer-less inverters must measure the R iso before grid connectionand monitor the residual current during operation. SMA Solar Technology AG 2/5

Differentiating from other phenomena 2 Differentiating from other phenomena The measurement of the R iso may not be confused with the problem of the capacitive discharge currents (see technical information "Capacitive Discharge Currents" at www.sma.de/en). Prerequisite for the latter is the reaction of the grid frequency on the PV plant. Hence, capacitive discharge currents only occur during operation. The R iso is measured, however, before connecting to the grid. In operation, the residual current monitoring runs via the all-current sensitive residual current monitoring unit (RCMU). Hence, it is a question of two different phenomena. 3 Standard specifications for the R iso The following regulations exist for the R iso : For PV modules (DIN EN 61646; DIN IEC 61215): Per m² module surface area: R iso > 40 M Ω m² This means that a PV module with a module surface area of 1 m² must have a minimum insulation resistance of 40 M Ω, a PV module with a surface area of 2 m², however, only a minimum of 20 M Ω. For inverters without galvanic isolation (transformer-less) in accordance with DIN VDE 0126-1-1: As the heart of the PV plant, the inverter monitors the insulation resistance of the entire system (all PV modules, DC cabling, installation and inverter). As mentioned above, this is particularly important in PV plants without galvanic isolation from the grid, since a single short circuit can lead to personal injury or damage. Since the magnitude of the currents is decisive in the event of such damages, the prescribed R iso is dependent on the maximum input voltage of the inverter. As per DIN VDE 0126-1-1, the following applies: R iso > 1 k Ω / V, but at least 500 k Ω. DIN VDE 0126-1-1 does not include any specifications for the insulation resistance of PV plants with galvanic isolation from the grid. SMA Solar Technology AG 3/5

R iso of several PV modules 4 R iso of several PV modules In a PV plant, the insulation resistances of all PV modules of an inverter form a parallel connection against ground and can therefore be added reciprocally: For identical PV modules this equation simplifies to: The overall resistance of the PV plant against ground lowers with the quantity of connected PV modules. Standard conflict In a typical PV plant with a system voltage of 700 V the standard for PV modules above a module surface area of around 60 m² comes into conflict with the standard for inverters (40 M Ω m²/60 m² = 667 k Ω ). Even with faultless functional capability the prescribed R iso can no longer be achieved under certain conditions. With a module efficiency of 10 %, 60 m² only corresponds to 6 kw, with a module efficiency of 5 %, this figure is only 3 kw. 5 New formula for the R iso threshold The previous specifications of the standards disregard relevant factors such as the efficiency of PV modules or the power of the inverter. For this reason, efforts are being made on a national and international level (IEC) to harmonize the existing insulation specifications in the standards. Together with the German professional association, SMA Solar Technology AG developed a formula different to DIN VDE 0126-1-1 for the insulation resistance. The new R iso threshold is inversely proportional to the power of the inverter and corresponds to the R iso threshold of 40 M Ω m² required by DIN EN 61646 and DIN IEC 61215 with a module efficiency of 5 %: R iso = 2000 k Ω * kw/p DC_inverter This power-dependent R iso, which deviates from the standard VDE 0126-1-1, was accepted by the professional association, as it fulfils the underlying standard protection target. However, the value has to be at least 200 kω, as smaller insulation resistances can cause dangerous residual current. Particularly with PV plants with over 10 kw and with additional insulation problems in the cables and plug connectors, disturbances may occur from time to time, even with the new regulation. SMA Solar Technology AG 4/5

What was measured until now? 6 What was measured until now? The PV plant is a system made up of many components, all of which make a contribution to the above defined R iso. A determination of this value is thus dependent on measurement algorithm and measurement circuit. In addition an integrated measurement technology must operate low-loss. Furthermore, there are further measurement errors as a result of the tolerances of the installed electronic components. The inverter type Sunny Mini Central SMC 9000TL/10000TL/11000TL is equipped with a measurement technology that goes well beyond the test conditions demanded in the standard and is capable of identifying insulation errors that can be difficult to detect. In order to meet the limiting value of 700 k Ω required by DIN VDE 0126-1-1, the devices were delivered with a limiting value of 900 k Ω. SMA inverters with transformers can also measure the insulation resistance. As other regulations apply for galvanic isolation, they do not refuse the grid connection, but only display a warning message. 7 What has changed? As of December 1, 2010, SMA Solar Technology AG delivers the Sunny Mini Central 9000TL/10000TL/ 11000TL with a firmware where the limiting values for the insulation resistance were adapted to the new general conditions. SMA Solar Technology offers this firmware as a free update on request for all previously delivered inverters. The new thresholds ensure that the PV plants run safely and only actual insulation failures (module break, marten bites) are reported as a disturbance. If required, please contact the SMA service line: Serviceline@SMA.de. SMA Solar Technology AG 5/5