USER MANUAL. Longo programmable controller LPC-2.C05 module. Version 4



Similar documents
EZmoto V2. Product description Rev. 6 10/01/2014. EZmoto V2 Product description Rev.6 10/01/2014

ZC-24DO CANopen I/O Module: 24 Digital Outputs

GSMPBX version 1.3 Datasheet

Application. Characteristics RTU560. Data Sheet Communication Unit 560CMD11. Communication Unit 560CMD11

SYSTEM DESCRIPTION Termination Boards

Modular I/O System Analog and Digital Interface Modules

=============================== WARNING

T-BOXN12R. First steps with T-BOXN12R. You can make it wireless. Date: Version 1.0

User Manual Revision English

SMS GSM Alarm Messenger

User Manual Revision English

GSM HOME SECURITY SYSTEM

Telephone- and leased line modem for industrial applications TD-36

NC-12 Modbus Application

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

FM4100 USER MANUAL V1.4

TX OPEN RS232/485 module

connecdim Gateway G1 Ethernet TCP/IP to DALI

Technical description MX-1 VB Edge

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

INTELLIGENT CONTROL MODULE SA-2000-II HARDWARE MANUAL. Access Technologies International, Inc.

PCS0100en Persy Control Services B.V. Netherlands

VOICE RECORDING SYSTEM ISDN PRI / BRI

DMX2PWM 9 Channel Dimmer Setup Manual

Rack mounted telephone- and leased line modem for industrial applications

F2103 GPRS DTU USER MANUAL

User Manual Revision English

Digital input modules

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

User Manual for CH-PFC76810

CelluLine CGW-TS GSM Cellular Gateway. Installation and Programming Manual

Current Monitoring Kit QUICK START GUIDE

GSM ATT Modules Simply effective remote control

GSM Interfacing Board

IntesisBox KNX LG Air Conditioning

Current Monitoring Kit

User Manual Revision English

Temperature & Humidity SMS Alert Controller

CompactLogix Power Supplies Specifications

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX M1 02 E MES FLOW CALCULATOR /1

LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34)

How To Set Up An Inverter

Communication Unit 560CMU05 Data sheet

Installation Instructions. Thermo Call TC3

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

AXIS T81B22 DC 30W Midspan

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Installation Instructions. ThermoCall TC4. Entry/Advanced

ADM1TE 5/30A DIN rail single phase two wire energy meter

Modbus Server SAMSUNG Air Conditioners

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

alpha DSL WTM HS Instructions for use ADSL modem alpha DSL WTM HS

User Manual Revision English

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

MCR1900 Media Converter 19-Slot Chassis

USER MANUAL. PingBrother EPIW104 managed passive poe switch & IP watchdog

Elvey is a leading distributor of electronic security equipment in Africa. Our vision is to assist in the protection of people and property by

Unidirectional Transmitter/ Receiver Units Introduction

IntesisBox. KNX SAMSUNG Air Conditioning. Gateway for integration of Samsung air conditioners into KNX control systems. RS485.

IntesisBox KNX Modbus RTU master

RN-XV-RD2 Evaluation Board

TK800-Series Industrial GPRS / UMTS / LTE Router

IntesisBox Modbus Server Fidelio IP

GV-Keyboard. User's Manual V2.0

Quick Connect. quick - simple - efficient.

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

IntesisBox ASCII Server - LON

EPGM1 HARDWIRED ZONE & PGM OUTPUT EXPANSION MODULE

User Manual Revision English

CPU PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU PN/DP: Configuring an ET 200S as PROFINET IO device

1 Application Description Objective Goals... 3

IMR 6000/10../20../30

Moxa EtherDevice Switch

Operating Instructions

Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION

Technical data. General specifications. Signal voltage V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.

1. SAFETY INFORMATION

Rev GSM base station. Installation instructions

User Manual Revision English

User Manual Revision English

Vroom Hardware manual ver Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

User Manual Revision English

User Manual Revision English

Industrial RS-232/ RS-422/ RS-485 over Ethernet Media Converter

Instruction Manual Copy Adapter "CPAD-C1A" "CP Fuji Electric Systems Co., Ltd. INR-SI a-EU Rev

Kvaser Mini PCI Express User s Guide

PSDC PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

User Manual Revision English

Bluetooth UART/RS232 Module

Bullet Camera. Installation Guide. Hangzhou Hikvision Digital Technology Co., Ltd.

SIMATIC NET. CP AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

GSM Gate Opener GSM Remote Switch RTU5015 User Manual

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

2014 GSM SHIELD COMPATIBLE WITH ARDUINO GSM SHIELD USING SIMCOMM (SIM900A)

IntesisBox KNX - LON

IntesisBox Modbus Server SAMSUNG Air Conditioners

PixelController II Art-Net controller for LED pixels

Transcription:

USER MANUAL Longo programmable controller LPC-2.C05 module Version 4 SMARTEH d.o.o. / Trg tigrovcev 1 / 5220 Tolmin / Slovenia / Tel.: +386(0) 388 44 00 / e-mail: info@smarteh.si / www.smarteh.si

Written by SMARTEH d.o.o. Copyright 2005, SMARTEH d.o.o. User Manual Document Version: 004 June 30, 2005 i

STANDARDS AND PROVISIONS: Standards, recommendations, regulations and provisions of the country in which the devices will operate, must be considered while planning and setting up electrical devices. Work on 230 VAC network is allowed for authorized personnel only. DANGER WARNINGS: Devices or modules must be protected from moisture, dirt and damage during transport, storing and operation. WARRANTY CONDITIONS: For all modules LONGO LPC-2 if no modifications are performed upon and are correctly connected by authorized personnel in consideration of maximum allowed connecting power, we offer warranty for 24 months from date of sale to end buyer. In case of claims within warranty time, which are based on material malfunctions the producer offers free replacement. The method of return of malfunctioned module, together with description, can be arranged with our authorized representative. Warranty does not include damage due to transport or because of unconsidered corresponding regulations of the country, where the module is installed. This device must be connected properly by the provided connection scheme in this manual. Misconnections may result in device damage, fire or personal injury. Hazardous voltage in the device can cause electric shock and may result in personal injury or death. NEVER SERVICE THIS PRODUCT YOURSELF! This device must not be installed in the systems critical for life (e.g. medical devices, aircrafts, etc.). If the device is used in a manner not specified by the manufacturer, the degree of protection provided by the equipment may be impaired. Waste electrical and electronic equipment (WEEE) must be collected separately! LONGO LPC-2 complies to the following standards: EMC:EN 61000-6-2 (EN 50082), EN 61000-6-4 (EN 50081) LVD: IEC 61131-2 Vibrations and climatic-mechanical: EN 60068-2-6, EN 60068-2-27, EN 60068-2-29 MANUFACTURER: SMARTEH d.o.o. Trg tigrovcev 1 5220 Tolmin Slovenia ii

Longo programmable controller LPC-2.C05 module 1 DESCRIPTION...1 2 FEATURES...2 3 INSTALLATION...3 3.1 Connection scheme...3 3.2 Mounting instructions...5 3.3 Module labeling...7 4 TECHNICAL SPECIFICATIONS...8 APPENDIX A: PROGRAMMERS GUIDE...9 5 CHANGES...11 6 NOTES...12 iii

1 DESCRIPTION LPC-2.C05 module is used for communication with mobile GSM equipment, like GSM phone or GSM modem. The communication between LPC-2 system and mobile equipment is established through SMS messages. Up to eight digital and eight analog values could be represented from LPC-2 system as well as up to eight digital and eight analog commands could be sent from GSM phone or other mobile equipment. This commands could act direct to digital and analog outputs or can be used for parameter settings. LPC-2 system can works also in alarming mode, where SMS alarm message is sent in case of abnormal situation (temperature too high, water leakage, etc.). The SMS alarm messages are sent recurrently every hour on first three phone numbers stored on the SIM card. If the phone numbers are stored in the international notation (with country code) then the prefix must start with 00 and not with + symbol (e.g. Slovenian international code is 00386). When LPC-2.C05 module is correctly installed, then is ready to operate. In this case status LED1 must blink (refer to the Table 6). The starting sequence is executed once after reset. Complete time base is 40 sec (see below). a) b) c) a) LED1 blinks once after reset and then is off SIM card not inserted or SIM card PIN still enabled b) LED1 blinks once after reset and then is on GSM network problem; check antenna and GSM signal level with the mobile phone c) LED1 blinks once after reset and then start blinking normal starting sequence; everything OK IMPORTANT: The PIN number of the SIM card must be disabled otherwise LPC-2.C05 will not be connected to the GSM network! Module is powered from internal BUS. NOTE: For proper system configuration and data allocation please refer to LPC Composer software help menu. 1

2 FEATURES Figure 1: LPC-2.C05 communication module Table 1: Technical data Dual band 900/1800 MHz Optional RS232 communication port, 9600 bps, 8 bits, one stop bit, no parity, no flow control, reserved for external AT command Standard DIN EN50022-35 rail mounting 2

3 INSTALLATION 3.1 Connection scheme Figure 2: Connection scheme K1 K2 Addr.: ANT. SIM CARD LPC-2.C05 GSM module LED status LED1 Table 2: ANT. ANT. Antenna connector FME/M (GSM antenna FME/F) Table 3: SIM CARD SIM CARD SIM card connector Table 4: K1 Internal BUS Data & DC power supply Connection to I/O module Table 5: K2 Internal BUS Data & DC power supply Connection to I/O module 3

Table 6: LED1 Status Green LED: indicates C05 state OFF: power off Blink once: SIM card not inserted or PIN enabled Blink once & ON: Low GSM signal Blink: Normal starting sequence 4

3.2 Mounting instructions Figure 3: Housing dimensions Dimensions in millimeters. All connections, module attachments and assembling must be done while module is not connected to the main power supply. Mounting instructions: 1. Switch OFF main power supply. 2. Mount LPC-2.C05 module to the provided place inside an electrical panel (DIN EN50022-35 rail mounting). 3. Screw antenna (delivered together with LPC-2.C05 module) to the antenna connector. 4. Mount other LPC-2 modules (if required). Mount each module to the DIN rail first, then attach modules together through K1 and K2 connectors. 5. Switch ON main power supply. 5

Dismount in reverse order. For mounting/dismounting modules to/from DIN rail a free space of at least one module must be left on the DIN rail. NOTE: LPC-2.MC3 main control module should be powered separately from other electrical appliance connected to LPC-2 system. Signal wires must be installed separately from power and high voltage wires in accordance with general industry electrical installation standard. 6

3.3 Module labeling Figure 5: Labels on housing Label 1 (MC3 sample): Label 2 (MC3 sample): Label 1 description: 1. LPC-2.MC3 is the full product name. 2. P/N:225MC3040001001 is the part number. 225 general code for product family, MC3 short product name, 04001 sequence code, 04 year of code opening 001 derivation code 001 version code (reserved for future HW and/or SW firmware upgrades). 3. D/C:16/05 is the date code. 16 week and 05 year of production. Label 2 description: 1. S/N:MC3-S9-0500000190 is the serial number. MC3 short product name, S9 user code (test procedure, e.g. Smarteh person xxx), 0500000190 year and current stack code, 05 year (last two cyphers) 00000190 current stack number; previous module would have the stack number 00000189 and the next one 00000191. 7

4 TECHNICAL SPECIFICATIONS Table 7: Technical specifications Power supply Power consumption Communication Antenna connector Antenna impedance from internal BUS 1 W Optional RS232 communication port, 9600 bps, 8 bits, one stop bit, no parity, no flow control, reserved for external AT commands FME/M 50 Ω Phone book capacity 100 SMS storage capacity 40 in ME (mobile equipment) up to 25 in SIM (SIM dependent) Frequency range GSM 900 and GSM 1800 Dimensions (L x W x H) Weight 90 x 53 x 60 mm 120 g Ambient temperature 0 to 50 C Ambient humidity Transport and storage temperature -20 to 60 C Pollution degree 2 Protection class IP 30 max. 95 %, no condensation 8

APPENDIX A: PROGRAMMERS GUIDE Memory allocation Tables below shows the example of memory allocation for C05 on position #1. Boolean variables Rx: I/O Module FBOOL8 I/O Name BIT0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Range 0..1 Address MC3: 0x1069 + (N * 0x0040) MC7: 0x0702 + (N * 0x0040) Boolean variables Tx used to select the number of analogue (BIT0-BIT3) and digital (BIT4-BIT7) input signals: I/O Module FBOOL8 I/O Name BIT0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Range 0..1 Address MC3: 0x1438 + (N * 0x0040) MC7: 0x0101 + (N * 0x0040) Boolean variables Tx: I/O Module FBOOL8 I/O Name BIT0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Range 0..1 Address MC3: 0x1439 + (N * 0x0040) MC7: 0x0102 + (N * 0x0040) 9

Word variables Rx: I/O Module FWORD16 I/O Name WORD1 WORD2 WORD3 WORD4 WORD5 WORD6 WORD7 WORD8 Range 0..65535 Address MC3: 0x160a + (N * 0x0040) MC7: 0x0703 + (N * 0x0040) Word variables Tx: I/O Module FWORD16 I/O Name WORD1 WORD2 WORD3 WORD4 WORD5 WORD6 WORD7 WORD8 Range 0..65535 Address MC3: 0x143a + (N * 0x0040) MC7: 0x0103 + (N * 0x0040) Boolean variable Tx used for alarming of the LPC-2 system(s): I/O Module FBOOL8 I/O Name BIT0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Range 0..1 Address MC3: 0x144e + (N * 0x0040) MC7: 0x0117 + (N * 0x0040) N = module position number; N of Main control unit is 0 and counts up by 1 with every next module 10

5 CHANGES The following table describes all the changes to the document. Date V. Description 30.6.2005 003 The initial version, issued as LPC-2.C05 module UserManual. 11.5.2010 004 Updated warranty permanence. 11

6 NOTES 12