SECTION 15200 GRAVITY SANITARY SEWERS. A. Gravity sanitary sewers and appurtenances, including stacks and service connections.



Similar documents
SECTION GRAVITY SANITARY SEWERS

SECTION POINT REPAIRS TO SANITARY SEWERS. A. Repairs to existing sewer lines by replacing short lengths of failed pipe.

San Antonio Water System Standard Specifications for Construction ITEM NO POINT REPAIRS AND OBSTRUCTION REMOVALS

STANDARD SPECIFICATIONS SECTION INSTALLATION OF GRAVITY SEWER PIPELINES. 1. Trenching, Backfilling and Compacting: 02223

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

Section 402. STORM SEWERS

SANITARY SEWER SPECIFICATIONS

ARTICLE II (2) ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH Purpose and Application.

Beacon Hill Sewer District Standard Specifications

SECTION ABANDONMENT OF SEWER MAINS

San Antonio Water System Standard Specifications for Construction ITEM 866 SEWER MAIN TELEVISION INSPECTION

FY11 Sanitary Sewer Main Rehab and Point Repair Bid Tabulation

FY08 SEWER POINT REPAIRS BID TABULATION

The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.

CLEANING, INSPECTION, AND TESTING OF SEWERS

CITY OF BEVERLY RULES AND REGULATIONS - SEWER SYSTEM TESTING. General

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES SITE UTILITIES

San Antonio Water System Standard Specifications for Construction ITEM NO SLIP-LINING SANITARY SEWERS

3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.

Exhibit A. Rules and Regulations for House Connections and Sewer Extensions

DESCRIPTION OF WORK:

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

Special Specification 7021 Water Main and Sewer Line Replacements

A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.

SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS

Section 2651 Television Inspection

Storm Sewer Trenchless Upgrade Alternatives and Recommendations

53.03 MATERIALS FOR SEWER LINER PIPE AND FITTINGS: The following materials are approved for installation in sanitary sewer lines:

SECTION STORM DRAIN SYSTEM

CHAPTER 6 - SANITARY SEWER

SANITARY SEWER SERVICE CONNECTION INSTRUCTIONS

City of Virginia Beach Public Utilities HRPDC Regional Construction Standards, 5 TH Edition Amendments May 19, 2014

STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY

DIVISION 4300 STORM DRAINAGE

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

Section 2100-Trenching and Tunneling

SECTION POLYVINYL CHLORIDE (PVC) PIPE

SECTION SITE PREPARATION

Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL

SECTION POLYVINYL CHLORIDE (PVC) PIPE

CCTV INSPECTION OF SEWER LINES. A. Section Sanitary Gravity Sewer Lines. B. Section Sanitary Gravity Sewer Line Testing

LS 2540 SEWER LATERALS AND INSPECTION TEES

TABLE OF CONTENTS. Manhole, Frame, and Cover Installation (includes Drop Manhole) Additional Manhole Depth

SECTION ABANDONMENT OF WATER MAINS. A. Conform to requirements of Section Submittals.

SECTION STORM DRAINAGE TABLE OF CONTENTS

SECTION 21 REHABILITATION OF SANITARY SEWER MAINS BY THE PIPE BURSTING AND TRENCHLESS PIPE REPLACEMENT METHOD

PART 6 - STANDARD DESIGN AND CALCULATION FORMS 6.1 SANITARY SEWER DATA SHEET

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

SECTION IV - TESTS AND INSPECTIONS PART 1 - GENERAL Testing - General

ARTICLE VI (ALTERNATE) STANDARD SPECIFICATIONS. for (PVC) SANITARY SEWER MAIN CONSTRUCTION

STANDARD SPECIFICATIONS SECTION CLOSED CIRCUIT TELEVISION INSPECTION OF SEWER MAINS, MANHOLES AND LATERALS

TECHNICAL SPECIFICATIONS GRAVITY AND PRESSURE SEWER LINE AND MATERIALS

Section SEWER PIPE INSTALLATION AND TESTING

SECTION CLEANING AND CLOSED CIRCUIT TELEVISION (CCTV) INSPECTION OF SEWER PIPE

APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT

STANDARD SPECIFICATIONS SECTION CLEANING AND LINING WATER MAINS

SECTION 5 DRAFTING STANDARDS

STANDARD SPECIFICATIONS SECTION CLOSED CIRCUIT TELEVISION INSPECTION OF SEWER MAINS, MANHOLES AND LATERALS

CW GRAVITY SEWERS TABLE OF CONTENTS

SECTION REINFORCED CONCRETE PIPE. A. The following is a list of SPECIFICATIONS, which may be related to this section:

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

Wastewater Capital Projects Management Standard Construction Specification

INSTALLATION OF INSITUFORM LINER

SECTION ACCEPTANCE TESTING FOR SANITARY SEWERS

APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 21

BMP-7. A sediment filter or an excavated impounding area around a storm drain drop inlet or curb inlet.

Customer Procedures and General Information for Sewer Customers

SANITARY SEWER SERVICE LEADS OR RECONNECTIONS CITY OF PEARLAND. Section G E N E R A L 1.01 SECTION INCLUDES

SECTION STORM DRAINAGE SYSTEM

Town House Center Highway North Huntingdon, PA 15642

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS

Section Installation of pipe and casing for sanitary sewer by methods of augering.

The checklist utilized by the Authority will be similar to that which is shown below. Project Name: Location: Consulting Engineering Firm:

Sewer Line Rehabilitation

SECTION 5: SANITARY SEWER SYSTEM DESIGN

CHAPTER 5. Storm Sewer

Technical Specifications For Sewing Enveilment Plans

SECTION 9.02 BUILDING SUBSURFACE DRAINS (PERIMETER, ETC.)

SECTION 200: STORM SEWER CONSTRUCTION STANDARDS

1.3.2 Method of construction and restoration of existing water service connections. This shall include:

CHAPTER 11 STORM DRAINAGE

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS

550 PIPE CULVERTS, SEWERS AND DRAINS

LOGAN TOWNSHIP MUNICIPAL UTILITIES AUTHORITY DESIGN, CONSTRUCTION, INSPECTION AND TESTING MANUAL

Civil. 2. City of Seattle Supplement to the Specification for Road, Bridge and Municipal Construction, most current addition.

CITY OF ANN ARBOR PUBLIC SERVICES PLAN REVIEW CHECKLIST

Indiana State Department of Health Construction Guidelines for Gravity and Flood-Dose Trench Onsite Systems

SECTION SANITARY SEWER PIPE

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

March 2006 DIVISION 3 - CW 2140-R3 TABLE OF CONTENTS

CHAPTER 11 STORM DRAINAGE

CONSTRUCTION PERMIT REQUIREMENTS

900 SEWERAGE WORK ITEM PIPE SEWERS COMPLETE IN PLACE

SECTION 6A STORM DRAIN DESIGN Mar S E C T I O N 6A STORM DRAIN - DESIGN

SECTION 724 PIPE CULVERTS

Transcription:

SECTION 15200 GRAVITY SANITARY SEWERS PART 1 GENERAL.01 SCOPE A. Gravity sanitary sewers and appurtenances, including stacks and service connections..02 SUBMITTALS A. Conform to requirements of Section 01300 Submittals. B. Submit proposed methods, equipment, materials and sequence of operations for sewer construction. Plan operations to minimize disruption of utilities to occupied facilities or adjacent property. C. Test Reports: Submit test reports and inspection videos as specified in Part 3 of this Section. Video tapes become property of AW..03 QUALITY ASSURANCE A. Qualifications. Install sanitary sewer that is watertight both in pipe-to-pipe joints and in pipeto-manhole connections. Perform testing in accordance with Section 15250 - Acceptance Testing for Sanitary Sewers. B. Regulatory Requirements. 1. Install sewer lines to meet minimum State mandated separation distance from potable water line, as scheduled below. Separation distance is defined as distance between outside of water pipe and outside of sewer pipe. Install new sanitary sewers no closer to water lines than 10 feet in all horizontal directions. Where water and sanitary sewer lines cross, a minimum of 2 feet of vertical seperation is required when the water line passes above the sanitary sewer main. Where separation distance cannot be achieved, sanitary sewers shall be constructed of ductile iron sanitary sewer piping or encased in reinforced concrete encasement (as detailed on the plans) for a minimum distance of 10 feet either side of the crossing. 2. Make notification to AW Project Manager when water lines are uncovered during sanitary sewer installation where minimum separation distance cannot be maintained. 3. Lay gravity sewer lines in straight alignment and grade. 15200-1

.04 PRODUCT DELIVERY, STORAGE, AND HANDLING A. Inspect pipe and fittings upon arrival of materials at job site. B. Handle and store pipe materials and fittings to protect them from damage due to impact, shock, shear or free fall. Do not drag pipe and fittings along ground. Do not roll pipe unrestrained from delivery trucks. C. Use mechanical means to move or handle pipe. Employ acceptable clamps, rope or slings around outside barrel of pipe and fittings. Do not use hooks, bars, or other devices in contact with interior surface of pipe to lift or move lined pipe. PART 2 PRODUCTS.01 PIPE A. Provide piping materials for gravity sanitary sewers of sizes and types indicated on Drawings or as specified. B. Unlined reinforced concrete pipe is not acceptable. C. All gravity sewer at Fort Leavenworth shall be SDR 26 PVC or better. SDR 35 pipe shall not be accepted at this location..02 PIPE MATERIAL SCHEDULE A. Unless otherwise shown on Drawings, use pipe materials that conform to requirements specified in one or more of following Sections: 1. Section 15105 - Ductile Iron Pipe and Fittings. 2. Section 15120 - Polyvinyl Chloride Pipe. B. Where shown on Drawings, provide pipe meeting minimum class, dimension ratio, or other criteria indicated. C. Pipe materials other than those listed above shall not be used for gravity sanitary sewers..03 APPURTENANCES A. Stacks. Conform to requirements of Section 15260 - Sanitary Sewer Service Stubs. B. Service Connections. Conform to requirements of Section 15260 - Sanitary Sewer Service Stubs. C. Roof, street or other type of surface water drains shall not be connected or reconnected into sanitary sewer lines. 15200-2

.04 BEDDING AND BACKFILL MATERIAL A. Bedding and Backfill: Conform to requirements of Section 02317 - Excavation and Backfill for Utilities and Section 02320 - Utility Backfill Materials. PART 3 EXECUTION.01 PREPARATION A. Prepare traffic control plans and set up street detours and barricades in preparation for excavation when construction will affect traffic. Conform to requirements of Traffic Control and Regulation. B. Provide barricades, flashing warning lights, and warning signs for excavations. Conform to requirements of Traffic Control and Regulation. Maintain barricades and warning lights where work is in progress or where traffic is affected. C. Perform work in accordance with OSHA standards. Employ trench safety system for excavations over 5 feet deep. D. Immediately notify agency or company owning utility line which is damaged, broken or disturbed. Obtain approval from AW Project Manager and agency or utility company for repairs or relocations, either temporary or permanent. E. Remove old pavements and structures including sidewalks and driveways in accordance with requirements of Section 02614 Curbs, Driveways, and Sidewalks. F. Install and operate dewatering and surface water control measures in accordance with contract document requirements. G. Do not allow sand, debris or runoff to enter sewer system..02 DIVERSION PUMPING A. All divsersion and bypass pumping shall be performed in accordance with Section 15290 Pumping and Bypassing..03 EXCAVATION A. Earthwork. Conform to requirements of Section 02317 - Excavation and Backfill for Utilities. Use bedding as indicated on Drawings. B. Line and Grade. Establish required uniform line and grade in trench from benchmarks identified by AW Project Manager. Maintain this control for minimum of 100 feet behind and ahead of pipe-laying operation. Use laser 15200-3

beam equipment to establish and maintain proper line and grade of work. Use of appropriately sized grade boards which are substantially supported is also acceptable. Protect boards and location stakes from damage or dislocation. C. Trench Excavation. Excavate pipe trenches to depths shown on Drawings and as specified in Section 02317 - Excavation and Backfill for Utilities..04 PIPE INSTALLATION BY OPEN CUT A. Install pipe in accordance with pipe manufacturer's recommendations and as specified in following paragraphs. B. Install pipe only after excavation is completed, bottom of trench fine graded, bedding material is installed, and trench has been approved by Project Manager. C. Install pipe to line and grade indicated. Place pipe so that it has continuous bearing of barrel on bedding material and is laid in trench so interior surfaces of pipe follow grades and alignment indicated. Provide bell holes where necessary. D. Install pipe with spigot ends toward downstream end of flow such that water flows into bell and out the spigot. E. Form concentric joint with each section of adjoining pipe so as to prevent offsets. F. Keep interior of pipe clean as installation progresses. Remove foreign material and debris from pipe G. Provide lubricant, place and drive home newly laid sections with come-along winches so as to eliminate damage to sections. Install pipe to "home" mark where provided. Use of back hoes or similar powered equipment will not be allowed unless protective measures are provided and approved in advance by Project Manager. H. Keep excavations free of water during construction and until final inspection. I. When work is not in progress, cover exposed ends of pipes with approved plug to prevent foreign material from entering pipe. J. Where gravity sanitary sewer is to be installed underexisting water line with separation distance of less than 2 feet, construct new sewer pipe so that 20 feet of ductile iron pipe is centered on water line crossing or encase the sewer line with reinforced concrete encasement as detailed on the plans. If gravity sanitary sewer is to be installed above existing water line, construct new sewer pipe so that 20 feet of ductile iron pipe is centered on water line crossing or encase the sewer line with reinforced concrete encasement.. 15200-4

K. Where gravity sanitary sewer is to be installed under existing water line, install new sewer using ductile iron or encased in reinforced concrete encasement as shown on Drawings. Maintain minimum 2-feet separation distance. L. Where the length of the stub is not indicated, install the stub to the right-ofway line and seal the free end with an approved plug..05 PIPE INSTALLATION OTHER THAN OPEN CUT A. For installation of pipe by augering, jacking, or tunneling, conform to requirements of specification sections on tunneling augering, jacking and microtunneling work as appropriate..06 INSTALLATION OF APPURTENANCES A. Service Connections. Install service connections to conform to requirements of Section 15260- Sanitary Sewer Service Stubs. B. Stacks. Construct stacks to conform to requirements of 15260- Sanitary Sewer Service Stubs. C. Construct manholes to conform to requirements of Section 03450 - Precast Concrete Manholes..07 INSPECTION AND TESTING A. Visual Inspection: Check pipe alignment in accordance with Section 15250 - Acceptance Testing for Sanitary Sewers. B. Mandrel Testing. Use Mandrel Test to test flexible pipe for deflection. Refer to Section 15250 - Acceptance Testing for Sanitary Sewers. C. Pipe Leakage Test. After backfilling line segment and prior to tie-in of service connections, visually inspect gravity sanitary sewers where feasible, and test for leakage in accordance with Section 15250 - Acceptance Testing for Sanitary Sewers..08 BACKFILL AND SITE CLEANUP A. Backfill and compact soil in accordance with Section 02317 - Excavation and Backfill for Utilities. B. Backfill trench in specified lifts only after pipe installation is approved by Project Manager. C. Repair and replace removed or damaged pavement, curbs, gutters, and sidewalks as specified in Section 02614 Curbs, Driveways, and Sidewalks. 15200-5

D. Provide hydromulch seeding in areas of commercial, industrial or undeveloped land use over surface of ground disturbed during construction and not paved or not designated to be paved. Grade surface at uniform slope to natural grade as indicated on Drawings. Provide minimum of 4 inches of topsoil as specified in Section 02911 - Topsoil and apply hydromulch according to requirements of Section 02921 - Hydromulch Seeding. E. Provide sodding in areas of residential land use over surface of ground disturbed during construction and not paved or not designated to be paved. Grade surface at uniform slope to natural grade as indicated on Drawings. Restore disturbed lawn areas in accordance with Section 02820 Lawn Restoration..09 POST-INSTALLATION TELEVISION INSPECTION A. Prior to final acceptance of newly constructed gravity sanitary sewers, perform cleaning and closed circuit television inspection. Cleaning shall include utilizing variable pressure water nozzles (3000 psi) and collection, removal, transportation and disposal of sand, debris, and liquid wastes to legal disposal sites. B. Select and use closed-circuit television equipment that will produce color video tape. Produce video tape using pan-and-tilt, radial viewing, pipe inspection camera that pans plus and minus 275 degrees and rotates 360 degrees. Use camera with accurate footage counter which displays on monitor exact distance of camera from starting manhole. Use camera with camera height adjustment so that camera lens is always centered at onehalf inside diameter, or higher, in pipe being televised. Provide lighting system that allows features and condition of pipe to be clearly seen. Reflector in front of camera may be necessary to enhance lighting in dark or large diameter pipe. C. Perform television inspection of gravity sanitary sewers as follows: 1. Videos shall pan beginning and ending manholes to demonstrate that debris has been removed. Camera operator shall slowly pan each service connection and where sewer transitions from one pipe material to another. 2. Video shall be continuous for pipe segments between manholes. Do not leave gaps in video taping of segment between manholes and do not show single segment on more than one video tape. 3. No flow is allowed in gravity sanitary sewer while performing postinstallation television inspection. D. Provide video tapes in DVD format, recorded at Standard Play (SP). Labels are required. Place one label on jewel case and other on face of DVD. Permanently label each video with following information. 15200-6

Spine of Tape Wastewater File No.: Contractor s Name: Inspection Type: [ ] Survey [ ] Pre-Installation [ ] Post-Installation Tape No.: Date Televised: Date Submitted: Basin No: Face of Tape Manhole No. From Manhole No. To Pipe Diameter Pipe Length Street E. For each video provide completed TV Inspection Report. TV Inspection Report is written/narrated log of pipe conditions and service connections, indexed to footage counter. F. Upon completion of video reviews by AW Project Manager, Contractor will be notified regarding final acceptance of sewer segment. END OF SECTION 15200 15200-7