PolyGard Gas Controller System DGC-06

Similar documents
PolyGard Carbon Monoxide CO Transmitter ADTX3 1110

Carbon Monoxide (CO) Gas Detection and Control System

OZW30. Central Unit SYNERGYR

Electronic Control Devices The European Product Catalogue 2007

Temperature & Humidity SMS Alert Controller

Electronic Control Devices The European Product Catalogue 2007

Repeaters and Mimics Data Sheet

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

Vroom Hardware manual ver Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

is then retained absolutely without interruption.

RRV934. Multi-controller. Synco living

Match. GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match UPS. GE Digital Energy.

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

IntesisBox Modbus Server Fidelio IP

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

Duct Humidity Transmitter

SHARKY 775 COMPACT ENERGY METER ULTRASONIC

IntesisBox Modbus Server SAMSUNG Air Conditioners

instabus KNX / EIB System System E F G H

SMS GSM Alarm Messenger

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

PSDC PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.

HARDWARE MANUAL. Ixx24-A 1/20. Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel vc@valcontrols.com

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

ENERGY SOLUTIONS RESIDENTIAL STORAGE BATTERY SYSTEM

Technical Data. back-up time in minutes 100% load % load

APC. DIN Rail Control Panel Mounting Uninterruptible Power Supply. Catalog

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

DC Electronic Loads 8500 series

FX07 Field Controller

Modular I/O System Analog and Digital Interface Modules

Uninterruptible Power Supply

with Electronic Assistant

FX07 Field Controller

Room Controllers. SER8300 Line Voltage Fan Coil Room Controller with SC3000 Relay Pack

IntesisBox KNX Modbus RTU master

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Fiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers

SNMP Web Management. User s Manual For SNMP Web Card/Box

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

Climate Ready Control Systems Technical Specifications

Technical Specifications: The specifications represent a particular hardware platform. Application-specific software is provided.

Product Data. Thermal Comfort Data Logger Type Including Application Software Type 7301

Product Information Sheet UH36 Hi Pot Tester

User manual Rev 1.3 Contents

NC-12 Modbus Application

IntesisBox KNX Modbus TCP master

Automation Unit TM 1703 ACP Flexible automation and telecontrol

Voltage Regulator SPAU 341 C. Product Guide

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

SVR 12/24V and SVR Akku 12V Installation instructions

HMIGTO4310 advanced touchscreen panel 640 x 480 pixels VGA- 7.5" - TFT - 96 MB

MOUNTING AND OPERATING INSTRUCTIONS

SNMP-1000 Intelligent SNMP/HTTP System Manager Features Introduction Web-enabled, No Driver Needed Powerful yet Easy to Use

Always on the Lookout Perfect Protection against Burglary

Lockout Specification BW Clip Maintenance-free single gas detector

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

SHARKY 775 COMPACT ENERGY METER ULTRASONIC

Emergency lighting units EM powerled

Back-UPS Pro 1300/1500 Installation and Operation

Current Monitoring Kit

TCR easy Plus Alarm. Operating Instructions

Unidirectional Transmitter/ Receiver Units Introduction

Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC

PSACH v.1.0 PSACH 24VAC/6A/1x6A HERMETIC AC power supply for CCTV

Buckeye Detection Systems Fixed Detection Systems Application Survey

PCS0100en Persy Control Services B.V. Netherlands

Intelligent chart recorder for compressed air and gases. Measurement - control - indication - alarm - recording - evaluation

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out

BB800 Off-Grid Solar System

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

FIREDEX Conventional Fire Panels

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

Installation and User Guide

MLC TM Maximum Productivity and Versatility for Control without Compromise!

Dupline Car Park System Type GP x 724-US 3-Colour Ultrasonic Sensor

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

MINI MCR-SL-R-UI(-SP)

INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS

Galleon 6-10K Online UPS. Voltronic Power Technology Corporation

Name Description Model Number. Parameters Min. Typ. Max. Note. Vaux Voltage 9.8 V 12 V 13.2 V Auxiliary Supply Voltage

User Manual V SDM220MODBUS. Single-Phase Two Module DIN rail Meters

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

Measurement. SITRANS F US Inline. Transmitter FUS080/FUE080 4/219

EGSTON Standard E2xFxWx 12W

Preset Counter signo 721

WD-AMX Water Detection Controllers

PD 100A. Printing data system

IO-RM3 3-Stage Relay Module

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

M-Bus-Logger Data Logger

Model: DC-A2IO Advanced HVAC Controller

TX OPEN RS232/485 module

HCR3.2/.. Chipcard reader HOTEL SOLUTION

Energy Communication Unit (ECU)

USB-500 Series Stand-Alone, Low-Cost Data Loggers

Transcription:

PolyGard Gas Controller System DGC-06 DESCRIPTION Measuring, warning and controlling device series for toxic, combustible and refrigerant gases and vapours. The gas controller series DGC-06 can monitor and process up to 96 digital (RS 485) PolyGard II sensors and/or analog (4 to 20 ma) µgard II Sensors. Four free adjustable alarm thresholds are provided per Sensors. For the alarm messages, up to 32 alarm relays with potential-free changeover contact and up to 16 analog outputs (4 to 20 ma) are available. The free adjustable parameters and set points enable a very flexible use in the gas measuring technique. Simple and comfortable commissioning, however, is granted by the configuration with default parameters. Configuration, parameterization and operation are easy to do without special programming knowledge due to the logical, simple menu structure directly at the controller. The DGC-06-EasyConf Software enables the loading, changing and storing of the application parameters via a serial interface. The DGC-06 series are equipped with a self-monitoring system, with power failure message as well as with a functional control of the registered digital/ analog Sensors according to the requirements of the gas measuring technique. In addition, the gas controller is available with an uninterruptible power supply supported by a rechargeable battery. The optional data logger function permits to protocol all measured values, alarms and faults. APPLICATION The DGC-06 gas controller series are used for the monitoring and warning of toxic and combustible gases as well as Freon refrigerants within a wide range of the gas measurement technique. Numerous adjustable parameters and set-points permit individual adaptation to many applications. The DGC-06 gas controller fulfils the functions of monitoring carbon monoxide (CO) in garages, tunnels and cart tracks etc. according to the current EN 50545. Additionally, ammonia (NH 3 ) refrigerant plants can be monitored according to the requirements EN 378, VBG 20 and the guidelines "safety requirements for ammonia refrigeration systems". 1 March14

FEATURES For up to max. 96 PolyGard sensors of the PolyGard II and µgard II series Sensors can be connected in digital (RS 485) and/or analog (4 to 20 ma) mode. For monitoring toxic, combustible or refrigerant gases, temperature and humidity Simple and comfortable commissioning by configuration with standard parameters Monitoring of the connected warning devices for functionality and discontinuity Monitoring of the UPS battery for charge condition and functionality Expansion Module with integrated repeater function Logical system menu Flexible configuration thanks to programmable parameters and set-points Four free adjustable alarm thresholds per sensor 6 menu languages free adjustable Several alarm relays configurable per alarm Adaptation of the sensor communication (digital and/or analog) in the menu Stored alarms resettable via a digital input Temporary locking of sensors possible for the customer Alarm release selectable for falling or increasing gas concentrations Connector for DGC 06-EasyConf at the controller module Max. 32 relays with change-over contact, potential-free, max. 250 VAC, 5A Fault relay with change-over contact, potential-free, max. 250 VAC, 5A Max. 16 analog outputs, 4 to 20 ma Max. 7 EP-05 modules (= 32 analog inputs) connectable EN 50545 conform Shapely, durable housing Option: Housing lockable Option: Integrated UPS Option: Flashing light at power failure Option: Integrated buzzer Option: USB port for data logger function, for all measured values and alarms/ faults Option: Serial interface with ModBus protocol for the connection to BMS etc. Option: Serial interface TLS protocol 2 March14

SPECIFICATIONS Electrical Power supply 110/230 VAC 50/60 Hz; 24 VAC/DC -10% + 20% Power consumption (incl. sensors) Min. 30 W, 0.15 A Max. 160 W, 0.7 A Depending on type and configuration Analog input (4 to max. 96) 4 to 20 ma, overload and short-circuit- protected, input resistance 200 Ω Tension for external analog sensors 24 VDC, max. 50 ma /per sensor Analog output (max 12) configurable for each input 4 to 20 ma, overload and short-circuit- protected, max. load 500 Ω Alarm relay (max. 30) 250 VAC, 5 A, potential-free, change-over SPDT Fault relay (1) 250 VAC, 5 A, potential-free, change-over SPDT Visualization LCD Two lines, 16 characters each, illuminated Status LED (4) Operation Fault 1 st alarm 2 nd alarm Operation 6 push-buttons Menu language (selectable) German, English, Dutch, USA, French, Swedish Interface field bus Transceiver RS 485 / 19200 Baud Gases Gas Sensors PolyGard II and µgard II Toxic, combustible and refrigerant gases Environmental Humidity 15 95 % RH non-condensing Working temperature - 5 C to + 40 C (23 F to 104 F) Storage temperature 0 C to + 40 C (32 F to 104 F) Physical Enclosure Plastic housing with view cover Colour RAL 7035 (grey) Protection class IP 65 Weight Min. 2.7 kg (4.4 Ib) Max. 13 kg (28,7 Ib) depending on type Mounting Wall mounting Cable entry M 16; M 20; M 25 Dimension Type 1 (XS) (W x H x D) Dimension Type 2 (S) (W x H x D) Dimension Type 3 (M) (W x H x D) Dimension Type 4 (L) (W x H x D) 298 x 260 x 140 mm (11.7 x 10.2 x 5.5 in.) 298 x 420 x 140 mm (11.7 x 16.5 x 5.5 in.) 298 x 570 x 140 mm (11.7 x 22.4 x 5.5 in.) 410 x 655 x 140 mm (16.1 x 25.8 x 5.5 in.) Wire connection: Power supply Output Guidelines Warranty Input Screw type terminal: 2.5 mm 2 (14 AWG) 2 x spring type terminal: min. 0.5, max. 1.5 mm 2 (22 to 16 AWG) Spring type: 0.5 to 1.5 mm 2 (22 to 16 AWG) EMC Directive 2004/108/EC; Low voltage directive 2006/95/EC VDI 2053 EN 61010-1:2010 ANSI/UL 61010-1 CAN/CSA-C22.2 No. 61010-1 One year on material 3 March14

UPS Battery backed supply for controller and sensors Options Supply duration 60 minutes, maintenance-free rechargeable batteries with functional monitoring and deep discharge protection Plastic housing with view cover Housing Colour RAL 7035 Protection class IP 65 Weight Min. ca. 3.8 kg (6.6 lb) Max. ca. 7.2 kg (15.4 lb) (depending on type) Mounting Wall mounting Cable entry M 16; M 20 Dimensions: (W x H x D) 298 x 260 x 140 mm (11.7 x 10.2 x 5.5 in.) 410 x 285 x 140 mm (16.1 x 25.8 x 5.5 in.) (depending on type) Flashing light at power failure Operation duration Warning buzzer Acoustic pressure Frequency Data Logger Function Log rate Data format Interface ModBus RTU RS 485 Function Communication module BACnet 05 Print Communication module PR-05 Battery backed LEDs 10 h (flashing) 85 db (distance 1000 mm) 3.5 khz Storage of measured values, of alarm status and faults with time and date stamp on an USB stick Log rate adjustable from 10 to 10,000 sec. Output of the data in standard Excel format Transmission of all current and average values, of status alarm relays and analog inputs to external devices in ModBus RTU RS 485 protocol format Technical data, function and protocol see datasheet DB-BAC Technical data, function and protocol see datasheet DBPrint05 4 March14

Options 1XXXXXX Power failure flashing light X1XXXXX Warning buzzer XX1XXXX Cable entry from below 2 XX2XXXX Cable entry from below and above 2 XXX1XXX Housing lockable XXXX1XX Data Logger function & USB stick XXXXX1X Interface ModBus RTU RS 485 XXXXX4X Interface TLS protocol RS 485 XXXXXX? Communication module BacNET 05 3 XXXXXX? Print communication module PR-05 3 ORDERING INFORMATION DGC-X6-XX-X-X-0-X-XXXXXXX-XX 2 Standard is from above 3 Respect place requirement in the housing, number code see data sheet Special versions 4 4 Is defined by MSR-E Number of EP05 modules Opotion Alarmrelays Analog inputs Analog outputs Housing dimension 0 04 04 02 0 1 2 3 4 8 1 08 08 04 3 2 8 14 23 --- 2 12 12 16 6 Max. space unit 3 16 16 08 9 Space unit A 4 20 20 10 12 5 24 24 12 15 6 28 28 14 18 7 32 32 16 21 Per LON Coupler 3 Communic. Module BacNET 1 Print Module PR 05 1 Space unit B UPS 1 Connector Module Repeater Modules Max. space unit = space unit A & space unit B Integrated in GC-06 module Integrated in EP-06 module 7 Metal housing on request Field bus / Protocol 05 RS 485 / DGC06 15 RS 485 / MSR_D_Bus Power unit/ UPS 8 1 2 3 4 Number of PolyGard II Pow.unit 4.5 A Pow.unit 6.5 A UPS 2.2 Ah UPS 7.2 Ah µgard II sensors Max. current for supply of external devices (ma) 9 16 2000 3400 600 3000 32 1000 2700 2400 48 4.5 A 2000 2.2 Ah 1700 64 power 1200 UPS not 1000 80 unit not 500 allowed 300 96 allowed 0 0 8 Higher capacity or without power unit on request 9 Only for supply of external warning buzzers and warning lights. 5 March14

WIRING CONFIGURATION (Example DGC-06) 230VAC PE N L Supply 230 VAC +24V 20V 1 X1 Power + 1-2 X2 R 01 R 02 R 03 R 04 R 05 1 2 3 4 5 6 X2 7 8 9 101112131415 D1 D2 D3 D4 D5 Digital Output Digital Gas Controller DGC 05 Analog Input RS 485 Bus Bus_A Bus_B Digital Input + DI 01 + DI 02 + DI 03 + DI 04 Option ModBus Interface X1110 1112 Analog Output + AO 01 X10 1 2 3 4 5 6 7 8 9 10 1112 X11 1 2 3 4 5 6 7 8 MOD_A 9 < 4-20 ma > < 4-20 ma +24 V 0 V Bus_A Bus_B MOD_B + AO 02 MP01 MP02 MP03 MP04 Field Bus 6 March14