Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL



Similar documents
Medium-voltage Transformers

Together we create reliable products, thus ensuring development of power industry of continents.

SUNNY TRIPOWER 5000TL 12000TL

Technical Information Short-Circuit Currents Information on short-circuit currents of SMA PV inverters

PV And Storage: Solutions with Potential

Step Voltage Regulators

/ The allrounder with maximum yield. / WLAN interface / Smart Grid Ready

GUIDE FOR TESTING POWER TRANSFORMERS

DS 600. A contact free flux gate based current measurement sensor 600A rms

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Power transformers. Special transformers Railway

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a

Unified requirements for systems with voltages above 1 kv up to 15 kv

How To Choose A Transformer

Current and voltage measuring relays

Central Inverter Planning of a PV Generator

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / SC / SC / 1250SC / 1600SC / 1800SC / 2000SC

Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS)

Technical Information POWER PLANT CONTROLLER

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

INTERNATIONAL STANDARD

GS Semiconductor Fuselinks. GE Power Controls. GS Semiconductor fuselinks

Short Circuit Current Calculations

ABB turnkey stations ULTRA-MVC-S 770 to 3110 kw

Three phase connection

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

BB800 Off-Grid Solar System

Rule Fast Track Analysis for National Life Insurance Co.

How To Understand The Electrical Power Supply Of A Power Supply System

Thermistor motor protection

Presentation of the France Transfo factories

Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply.

ABB central inverters PVS to 1000 kw

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Low Voltage Transformer Through-Fault Protection: A System Approach

Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva

INTERNATIONAL STANDARD

2.06. Version. Kinglong New Energy Technology Co.Ltd. Sunteams 1500 Sunteams Sunteams 4000 Sunteams 5000

Three-phase monitoring relay CM-PFE

Transformer Design & Design Parameters

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

TDA4605 CONTROL CIRCUIT FOR SWITCH MODE POWER SUPPLIES USING MOS TRANSISTORS

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

Register of Completed Embedded Generation Projects (Non-registered, typically 30kW to 5000kW)

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.

EssPro Energy Storage Grid Substation The power to control energy

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Technical Information Battery Management of the Sunny Island Gentle charging control for lead-acid batteries based on current state of the battery

Cahier technique no. 196

Application Information Improving Efficiency in Smart Grid Applications With Fully Integrated Current Sensing ICs

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission

Product Data Bulletin

PIN CONFIGURATION FEATURES ORDERING INFORMATION ABSOLUTE MAXIMUM RATINGS. D, F, N Packages

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

Chapter 24. Three-Phase Voltage Generation

Design Considerations for an LLC Resonant Converter

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Testing of Power Transformers. Routine tests, Type tests and Special tests

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

4KVA/5KVA Parallel Installation Guide

SOLAR MICRO INVERTER 260 COMMUNICATION GATEWAY. Apparent Power Control (APC) unique micro inverter with

Criteria for Selecting a Residual-Current Device

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Thyristor-controlled power supplies and battery chargers

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

TRAMS TROLLEY-BUSES SUBWAY

WIND TURBINE TECHNOLOGY

3 Calculation of Short-Circuit Currents in Three-Phase Systems

The following table shows approximate percentage wise the

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

T Substation Maintenance and Commissioning Test Equipment

Understanding Delta Conversion Online "Power Regulation" - Part 2

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Properties of electrical signals

Catalog EN. Content Transformers for industrial applications

Protection of a Three- Winding Transformer

Transformer protection

SYNCHRONOUS MACHINES

THE VALUE OF POWER FACTOR TESTING

Type SA-1 Generator Differential Relay

Table of Contents. TransformerIQ FAQs 1

YSmart Technology Co.,Ltd

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

7. Reactive energy compensation

> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.

Three-phase AC circuits

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

Safety technique. Emergency stop module BO 5988 safemaster

Photovoltaic Solar Energy Unit EESFB

TESTS OF 1 MHZ SIGNAL SOURCE FOR SPECTRUM ANALYZER CALIBRATION 7/8/08 Sam Wetterlin

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

Transcription:

Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL SC_Trafo-TI-en-62 Version 6.2 ENGLISH

Table of Contents SMA Solar Technology Table of Contents 1 Information on this Document... 3 1.1 Validity... 3 1.2 Limited statutory warranty... 3 1.3 Nomenclature... 3 2 Technical requirements for the MV transformer... 4 2.1 General requirements... 4 2.2 Requirements for two-winding transformers used to connect one inverter... 5 2.3 Requirements for three-winding transformers used to connect two inverters... 5 2.4 Requirements for four-winding transformers used to connect two inverters... 8 3 Technical requirements for the transformer for internal power supply... 11 3.1 Requirements for the connection to the park-side utility grid... 11 3.2 Requirements for the connection to the AC output of the inverter... 11 4 Appendix... 13 4.1 Technical data of the inverter... 13 4.2 Technical data of the transformers... 14 2 SC_Trafo-TI-en-62 Technical Information

SMA Solar Technology 1 Information on this Document 1 Information on this Document 1.1 Validity This document applied to all device types of the Sunny Central inverter. It describes the requirements for MV transformers and transformers for internal power supply that are connected to Sunny Central inverters. 1.2 Limited statutory warranty SMA Solar Technology AG only provides statutory warranty for transformers purchased from SMA Solar Technology AG. SMA Solar Technology AG America LLC only provides statutory warranty for transformers purchased from SMA Solar Technology AG America LLC. 1.3 Nomenclature Complete designation SMA Solar Technology America LLC SMA Solar Technology AG Sunny Central Designation in this document SMA SMA Inverter Technical Information SC_Trafo-TI-en-62 3

2 Technical requirements for the MV transformer SMA Solar Technology 2 Technical requirements for the MV transformer 2.1 General requirements The MV transformer can be of the liquid-immersed transformer type (for example, with mineral oil or biodegradable oil) or of the dry-type transformer. The MV transformer must be designed at its low-voltage windings for voltages that arise during pulsed mode of the inverter. The power connection used must have suitable insulation resistance since voltages to ground of ±2,400 V at the most occur when the inverter is in pulsed mode (see Section 4.1 "Technical data of the inverter", page 13). Figure 1: AC voltage level for SC 2500-EV The low voltage windings of the MV transformer must be designed for voltages that are capable of a rate of rise in voltage dv/dt of up to 500 V/µs to ground. The line-to-line voltages are sinusoidal. A shield winding grounded on the tank must be provided between the low voltage windings and the high voltage windings. This serves as an additional dv/dt filter. Each inverter requires a separate, galvanically insulated low-voltage winding. Therefore, the parallel operation of several inverters on one low-voltage winding is not permissible. The voltages at the low-voltage windings of the MV transformer must match the AC output voltage of the inverter (see Section 4.1 "Technical data of the inverter", page 13). The voltage level on the high-voltage side of the MV transformer must be selected according to the gridconnection point. The MV transformer must be connected to the medium-voltage grid or the high-voltage grid. Connection to the low-voltage grid is not permissible. When connecting to the medium-voltage grid, the use of a MV transformer with tap changer on the high voltage side is recommended. MV transformer with tap changer on the high-voltage side enables an adaptation to the voltage level of the medium-voltage grid. The MV transformer must be rated according to the temperature-dependent power behavior of the inverter. For thermal design, the load curve of the MV transformer and the ambient conditions at the respective mounting location must be taken into account. When operating with an additional reactive power supply, the increased loads in the design of the MV transformer are to be observed (for information about the reactive power supply of the inverter, see the inverter documentation). When designing the MV transformer for use with the Sunny Central Storage, it is important to remember that due to battery operation the MV transformer hardly cools down at all at night. 4 SC_Trafo-TI-en-62 Technical Information

SMA Solar Technology 2 Technical requirements for the MV transformer The MV transformer must be designed for the AC output currents of the inverter (see Section 4.1 "Technical data of the inverter", page 13). If grounding of the MV transformer on the medium voltage side is required, the type of grounding regarding the entire system including the MV transformer must be taken into consideration. The consequences of any error, such as a short circuit, ground fault or voltage failure, must be taken into account when considering the overall system. The country-specific power frequency must be taken into account. The applicable country-specific standards and directives must be taken into account. 2.2 Requirements for two-winding transformers used to connect one inverter The following vector groups are recommended for handling the corresponding neutral points. Insulated neutral point on medium-voltage side Dy11, Dy5, Dy1, Dd0, Dd6 Yd11, Yd5, Yd1 Resonant grounding on mediumvoltage side YNy0 YNd11, YNd5, YNd1 Low-resistance grounded neutral point YNy0 If there is a neutral-point terminal on the low-voltage side, this neutral-point terminal must not be grounded or connected. Figure 2: Circuit diagram of two-winding transformers (example) The relative impedance voltage V k of the MV transformer between grid-connection point and AC output of the inverter must be between the minimum value V k min and the maximum value V k max. The nominal power of the MV transformer (see Section 4.2 "Technical data of the transformers", page 14) is the basis of the relative impedance voltage. 2.3 Requirements for three-winding transformers used to connect two inverters A three-winding transformer (low-high-low) consists of one high-voltage winding and two low-voltage windings. Only three-winding transformers with LHL windings are permitted. In such MV transformers, the high-voltage winding is located between two low-voltage windings. Technical Information SC_Trafo-TI-en-62 5

2 Technical requirements for the MV transformer SMA Solar Technology Figure 3: Design of a three-winding transformer Position A Designation Core B Low-voltage winding 1 C High-voltage winding D Low-voltage winding 2 E Shield winding Three-winding transformers may only be used with the following inverters starting from the specified production version. The production version can be found on the type label of the inverter. Inverter Sunny Central CP XT Sunny Central CP-US Starting from production version A4 B9 Sunny Central CP-JP Sunny Central Storage Three-winding transformers with varying vector groups can be used. The following vector groups are recommended for handling the corresponding neutral points. Insulated neutral point on medium-voltage side Dy11y11, Dy5y5, Dy1y1, Dd0d0, Dd6d6 Yd11d11, Yd5d5, Yd1d1 Resonant grounding on mediumvoltage side YNy0y0 YNd11d11, YNd5d5, YNd1d1 Low-resistance grounded neutral point YNy0y0 If there is a neutral-point terminal on the low-voltage side, this neutral-point terminal must not be grounded or connected. 6 SC_Trafo-TI-en-62 Technical Information

SMA Solar Technology 2 Technical requirements for the MV transformer Figure 4: Circuit diagram of three-winding transformers (example) Three-winding transformers must be designed for an asymmetrical load flow in the low-voltage systems. This means that to ensure permanent operation, the transformer must be designed for feed-in with one inverter. Three-winding transformers must be designed for the use of inverters of the Sunny Central Storage series so that full power can be fed in at one of the low-voltage windings and that full power can be used at the other lowvoltage winding. The transformer must be designed for continuous operation in this operating state. The relative impedance voltage V k of the MV transformer between grid-connection point and AC output of the inverter must be between the minimum value V k min and the maximum value V k max. The relative impedance voltage is based on half the nominal power of the MV transformer (see Section 4.2 "Technical data of the transformers", page 14). The difference of the relative impedance voltages between the grid-connection point of the AC outputs of the two inverters must not exceed 2.0% (see Section 4.2 "Technical data of the transformers", page 14). Example: permissible difference of impedance voltages V k dif max The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 1 is 5.8%. The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 2 is 4.0%. The deviation of the relative impedance voltages is permissible since the difference amounts to 1.8% and is thus smaller than 2.0%. Example: non-permissible difference of impedance voltages V k dif max The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 1 is 6.2%. The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 2 is 4.0%. The deviation of the relative impedance voltages is not permissible since the difference amounts to 2.2% and is thus greater than 2.0%. The value of the relative impedance voltage V k 1-2 between the two low-voltage winding must be higher than 8%. The impedance voltage is based on half the nominal power of the MV transformer. This value can be determined by shorting a low-voltage winding and increasing the voltage on the other low-voltage winding until the nominal current of a low-voltage system flows. During this time, the high-voltage windings are in no-load operation. Technical Information SC_Trafo-TI-en-62 7

2 Technical requirements for the MV transformer SMA Solar Technology Figure 5: Circuit diagram for determining the impedance voltage V k 1-2 in three-winding transformers (example) 2.4 Requirements for four-winding transformers used to connect two inverters A four-winding transformer (double-decker transformer) consists of two high-voltage windings and two low-voltage windings. For four-winding transformers, a separate shield winding, grounded on the tank, is to be provided between each low-voltage winding and high-voltage winding. Figure 6: Four-winding transformers with separate shield winding Position A Designation Core B Low-voltage winding 1 C High-voltage winding D Low-voltage winding 2 E Shield winding 8 SC_Trafo-TI-en-62 Technical Information

SMA Solar Technology 2 Technical requirements for the MV transformer Four-winding transformers may only be used with Sunny Central CP XT / CP-US / CP-JP / Storage. Four-winding transformers with varying vector groups can be used. The following vector groups are recommended for handling the corresponding neutral points. Insulated neutral point on medium-voltage side Dy11y11, Dy5y5, Dy1y1, Dd0d0, Dd6d6 Yd11d11, Yd5d5, Yd1d1 Resonant grounding on mediumvoltage side YNy0y0 YNd11d11, YNd5d5, YNd1d1 Low-resistance grounded neutral point YNy0y0 If there is a neutral-point terminal on the low-voltage side, this neutral-point terminal must not be grounded or connected. Figure 7: Circuit diagram of four-winding transformers (example) Four-winding transformers must be designed for an asymmetrical load flow in the low-voltage systems. This means that for long-term operation, the transformer must be designed for the feed-in of one inverter only. Four-winding transformers must be designed for the use of inverters of the Sunny Central Storage series so that full power can be fed in at one of the low-voltage windings and that full power can be used at the other low-voltage winding. The transformer must be designed for continuous operation in this operating state. The relative impedance voltage V k of the MV transformer between grid-connection point and AC output of the inverter must be between the minimum value V k min and the maximum value V k max. The relative impedance voltage is based on half the nominal power of the MV transformer (see Section 4.2 "Technical data of the transformers", page 14). The difference of the relative impedance voltages between the grid-connection point of the AC outputs of the two inverters must not exceed 2.0% (see Section 4.2 "Technical data of the transformers", page 14). Example: permissible difference of impedance voltages V k dif max The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 1 is 5.8%. The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 2 is 4.0%. The deviation of the relative impedance voltages is permissible since the difference amounts to 1.8% and is thus smaller than 2.0%. Technical Information SC_Trafo-TI-en-62 9

2 Technical requirements for the MV transformer SMA Solar Technology Example: non-permissible difference of impedance voltages V k dif max The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 1 is 6.2%. The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 2 is 4.0%. The deviation of the relative impedance voltages is not permissible since the difference amounts to 2.2% and is thus greater than 2.0%. The value of the relative impedance voltage V k 1-2 between the two low-voltage winding must be higher than 8%. The impedance voltage is based on half the nominal power of the MV transformer. This value can be determined by shorting a low-voltage winding and increasing the voltage on the other low-voltage winding until the nominal current of a low-voltage system flows. During this time, the high-voltage windings are in no-load operation. Figure 8: Circuit diagram for determining the impedance voltage U k 1-2 in four-winding transformers (example) 10 SC_Trafo-TI-en-62 Technical Information

SMA Solar Technology 3 Technical requirements for the transformer for internal power supply 3 Technical requirements for the transformer for internal power supply 3.1 Requirements for the connection to the park-side utility grid The inverters Sunny Central CP XT / CP-US / CP-JP and Sunny Central Storage require an external AC voltage supply. The voltage for the inverters can be supplied by a transformer for internal power supply. The Sunny Central 2200 / 2500-EV / 1850-US / 2200-US inverter have an integrated transformer for internal power supply with a power of 8.4 kva and are not dealt with here. The transformer for internal power supply must be of three-phase design. The secondary side of the transformer for internal power supply must supply a voltage of 230 V/400 V (3/N/PE) to connect to the inverter. For the connection to the park-side utility grid, the primary voltage of the transformer for internal power supply must be equal to the grid voltage. Figure 9: Connection of the transformer for internal power supply to the park-side utility grid The transformer for internal power supply must provide a power of at least 2.8 kva per inverter. Several inverters can be supplied by one transformer for internal power supply if this transformer can provide a power of at least 2.8 kv per inverter. The transformer for internal power supply must be designed for an asymmetric load of 80%. A transformer for internal power supply with the Dyn5 vector group is recommended. The transformer for internal power supply must be equipped with an external protection against overload. The transformer for internal power supply must have external short-circuit protection ensuring that any potential short-circuit currents are limited to 6 ka at the inverter. To protect the inverter, overvoltage protection must be provided between the inverter and the transformer for internal power supply. The ambient conditions of the transformer for internal power supply must be taken into account. The country-specific power frequencies must be taken into account. The applicable country-specific standards and directives must be taken into account. 3.2 Requirements for the connection to the AC output of the inverter The inverters Sunny Central CP XT / CP-US / CP-JP and Sunny Central Storage require an external AC voltage supply. The voltage for the inverters can be supplied by a transformer for internal power supply. Technical Information SC_Trafo-TI-en-62 11

3 Technical requirements for the transformer for internal power supply SMA Solar Technology The Sunny Central 2200 / 2500-EV / 1850-US / 2200-US inverter have an integrated transformer for internal power supply with a power of 8.4 kva and are not dealt with here. The transformer for internal power supply must be of three-phase design. The secondary side of the transformer for internal power supply must supply a voltage of 230 V/400 V (3/N/PE) to connect to the inverter. Figure 10: Connection of the transformer for internal power supply to the inverter's AC output The primary voltages of the transformer for internal power supply must correspond to the AC output voltages of the inverter (see Section 4.1 "Technical data of the inverter", page 13). The transformer for internal power supply must provide a power of at least 2.8 kva per inverter. Several inverters can be supplied by one transformer for internal power supply if this transformer can provide a power of at least 2.8 kv per inverter. The transformer for internal power supply must be designed for an asymmetric load of 80%. A transformer for internal power supply with the Dyn5 vector group is recommended. The transformer for internal power supply must be equipped with an external protection against overload. The transformer for internal power supply must have external short-circuit protection ensuring that any potential short-circuit currents are limited to 6 ka at the inverter. To protect the inverter, overvoltage protection can be provided between the inverter and the transformer for internal power supply. The ambient conditions of the transformer for internal power supply must be taken into account. The country-specific power frequencies must be taken into account. The applicable country-specific standards and directives must be taken into account. On the primary side, the transformer for internal power supply must be suitable for the pulsed mode of an inverter. On the primary side, the transformer for internal power supply must be suitable for voltages that arise from pulsed mode of the inverter. The power connection used must have suitable insulation resistance since voltages to ground of ±2,400 V at the most occur when the inverter is in pulsed mode (see Section 4.1 "Technical data of the inverter", page 13). On the primary side, the transformer for internal power supply must be designed for voltages reaching a rate of rise in voltage dv/dt of up to 500 V/µs to ground. The line-to-line voltages are sinusoidal. The windings of the transformer for internal power supply must be galvanically insulated. Do not use autotransformers. 12 SC_Trafo-TI-en-62 Technical Information

SMA Solar Technology 4 Appendix 4 Appendix 4.1 Technical data of the inverter Sunny Central CP XT and Sunny Central 2200 / 2500-EV Type of the inverter DC- Voltage AC Voltage AC peak voltage to ground AC current at 25 C at 40 C at 50 C SC 500CP XT 1,000 V 270 V ±1,450 V 1,176 A 1,113 A 1,070 A SC 630CP XT 1,000 V 315 V ±1,450 V 1,283 A 1,202 A 1,155 A SC 720CP XT 1,000 V 324 V ±1,450 V 1,411 A 1,335 A 1,283 A SC 760CP XT 1,000 V 342 V ±1,450 V 1,411 A 1,335 A 1,283 A SC 800CP XT 1,000 V 360 V ±1,450 V 1,411 A 1,335 A 1,283 A SC 850CP XT 1,000 V 386 V ±1,600 V 1,411 A 1,335 A 1,283 A SC 900CP XT 1,000 V 405 V ±1,600 V 1,411 A 1,335 A 1,283 A SC 1000CP XT 1,000 V 405 V ±1,600 V 1,586 A 1,426 A 1,283 A SC 2200 1,100 V 385 V ±1,800 V 3,300 A 3,120 A 3,000 A SC 2500-EV 1,500 V 550 V ±2,400 V 2,624 A 2,467 A 2,362 A Sunny Central CP US and Sunny Central 1850-US / 2200-US Type of the inverter DC- Voltage AC Voltage AC peak voltage to ground AC current at 25 C at 40 C at 50 C SC 500CP-US 600 V 200 V ±800 V 1,588 A 1,502 A 1,444 A SC 500CP-US 1,000 V 270 V ±1,450 V 1,176 A 1,113 A 1,070 A SC 630CP-US 1,000 V 315 V ±1,450 V 1,283 A 1,202 A 1,155 A SC 720CP-US 1,000 V 324 V ±1,450 V 1,411 A 1,335 A 1,283 A SC 750CP-US 1,000 V 342 V ±1,450 V 1,411 A 1,335 A 1,283 A SC 800CP-US 1,000 V 360 V ±1,450 V 1,411 A 1,335 A 1,283 A SC 850CP-US 1,000 V 386 V ±1,600 V 1,411 A 1,335 A 1,283 A SC 900CP-US 1,000 V 405 V ±1,600 V 1,411 A 1,335 A 1,283 A SC 1850-US 1,000 V 385 V ±1,700 V 2,774 A 2,774 A 2,774 A SC 2200-US 1,000 V 385 V ±1,700 V 3,300 A 3,120 A 3,000 A Technical Information SC_Trafo-TI-en-62 13

4 Appendix SMA Solar Technology Sunny Central CP JP Type of the inverter DC- Voltage AC Voltage AC peak voltage to ground AC current at 25 C at 40 C at 50 C SC 500CP-JP 600 V 205 V ±800 V 1,411 A 1,335 A 1,283 A SC 630CP-JP 1,000 V 315 V ±1,450 V 1,283 A 1,202 A 1,155 A SC 800CP-JP 1,000 V 360 V ±1,450 V 1,411 A 1,335 A 1,283 A Sunny Central Storage Type of the inverter DC- Voltage AC Voltage AC peak voltage to ground AC current at 25 C at 40 C at 50 C SCS 500 850 V 270 V ±1,450 V 1,411 A 1,113 A 1,070 A SCS 630 850 V 315 V ±1,450 V 1,411 A 1,202 A 1,155 A SCS 720 850 V 324 V ±1,450 V 1,411 A 1,335 A 1,283 A SCS 760 850 V 342 V ±1,450 V 1,411 A 1,335 A 1,283 A SCS 800 950 V 360 V ±1,450 V 1,411 A 1,335 A 1,283 A SCS 850 950 V 386 V ±1,600 V 1,411 A 1,335 A 1,283 A SCS 900 950 V 405 V ±1,600 V 1,411 A 1,335 A 1,283 A SCS 1000 900 V 405 V ±1,600 V 1,568 A 1,426 A 1,283 A 4.2 Technical data of the transformers Sunny Central CP XT and Sunny Central 2200 / 2500-EV Type of the Inverter Two-winding transformers Three-winding and four-winding transformers V k min V k nom V k max V k min V k nom V k max V k dif max V k 1-2 min SC 500CP XT 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SC 630CP XT 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SC 720CP XT 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SC 760CP XT 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SC 800CP XT 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SC 850CP XT 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SC 900CP XT 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SC 1000CP XT 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SC 2200 5.0% 6.0% 8.5% SC 2500-EV 5.0% 6.0% 8.5% 14 SC_Trafo-TI-en-62 Technical Information

SMA Solar Technology 4 Appendix Sunny Central CP US and Sunny Central 1850-US / 2200-US Type of the Inverter Two-winding transformers Three-winding and four-winding transformers V k min V k nom V k max V k min V k nom V k max V k dif max V k 1-2 min SC 500CP-US* 5.4% 6.0% 6.6% 5.4% 6.0% 6.6% 2.0% 8.0% SC 500CP-US** 5.4% 6.0% 6.6% 5.4% 6.0% 6.6% 2.0% 8.0% SC 630CP-US 5.4% 6.0% 6.6% 5.4% 6.0% 6.6% 2.0% 8.0% SC 720CP-US 5.4% 6.0% 6.6% 5.4% 6.0% 6.6% 2.0% 8.0% SC 750CP-US 5.4% 6.0% 6.6% 5.4% 6.0% 6.6% 2.0% 8.0% SC 800CP-US 5.4% 6.0% 6.6% 5.4% 6.0% 6.6% 2.0% 8.0% SC 850CP-US 5.4% 6.0% 6.6% 5.4% 6.0% 6.6% 2.0% 8.0% SC 900CP-US 5.4% 6.0% 6.6% 5.4% 6.0% 6.6% 2.0% 8.0% SC 1850-US 5.4% 6.0% 6.6% SC 2200-US 5.4% 6.0% 6.6% * DC voltage = 600 V ** DC voltage = 1,000 V Sunny Central CP JP Type of the Inverter Two-winding transformers Three-winding and four-winding transformers V k min V k nom V k max V k min V k nom V k max V k dif max V k 1-2 min SC 500CP-JP 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SC 630CP-JP 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SC 800CP-JP 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% Sunny Central Storage Type of the Inverter Two-winding transformers Three-winding and four-winding transformers V k min V k nom V k max V k min V k nom V k max V k dif max V k 1-2 min SCS 500 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SCS 630 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SCS 720 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SCS 760 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SCS 800 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SCS 850 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SCS 900 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% SCS 1000 4.0% 6.0% 7.0% 4.0% 6.0% 7.0% 2.0% 8.0% Technical Information SC_Trafo-TI-en-62 15

SMA Solar Technology www.sma-solar.com