3873P01. Room controllers. For fan-coil applications FC-10, FC-11, FC12 with Konnex bus communications (S-mode and LTE mode)



Similar documents
For UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only.

Digital input modules

Building Technologies

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

TX OPEN RS232/485 module

PCS0100en Persy Control Services B.V. Netherlands

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

HERZ-Thermal Actuators

SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use

VAV compact controller KNX / PL-Link

PHOENIX CONTACT Features

Electronic Control Devices The European Product Catalogue 2007

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

T7560A,B,C Digital Wall Module

Adjustable room thermostat for heating only or cooling only systems

VAV compact controller KNX / PL-Link

Modular I/O System Analog and Digital Interface Modules

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

Cooling with CHW (fan coil Heating with LTHW radiator Modulating control of heating and cooling valve Automatic or manual fan control

Electronic Control Devices The European Product Catalogue 2007

Duct Humidity Transmitter

48 SERIES Relay interface modules 10 A

Air damper actuators

MINI MCR-SL-R-UI(-SP)

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

RRV934. Multi-controller. Synco living

ACS-30-EU-EMDR-10-MOD

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

OZW30. Central Unit SYNERGYR

instabus KNX / EIB System System E F G H

Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date:

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

VEO. V4PF480Y/277VSYTK02 Art.Nr.: V4PF480Y/277VSYTK02P Art.Nr.: TECHNICAL DATA

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

38 Series - Relay interface modules A

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

SYSTEM DESCRIPTION Termination Boards

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

49 Series - Relay interface modules A. Features

SKR - industry relay

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Product and functional description

Voltage Regulator SPAU 341 C. Product Guide

ABB Drives. User s Manual HTL Encoder Interface FEN-31

ABB i-bus KNX SA/S Switch Actuators Product Manual

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

OZW V2.0. Web server. Synco TM, Synco TM living

KNX. Siemens Building Technologies HVAC Products. Synco Konnex bus. For devices of the Synco 700 / RXB ranges

HCR3.2/.. Chipcard reader HOTEL SOLUTION

Data sheet GIOD.1 Input/output module with CAN bus. ERP no.: Data sheet GIOD.1 V_3.0

38 Series - Relay interface modules A

Three-phase monitoring relay CM-PFE

SYSTEM 45. C R H Electronics Design

Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems

IO-RM3 3-Stage Relay Module

ABB i-bus KNX Fan Coil Controller FC/S 1.1

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

SYSTEM 4C. C R H Electronics Design

Type: DILM50(230V50HZ,240V60HZ) Article No.:

Match. GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match UPS. GE Digital Energy.

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

MasterINTERFACE 39 Series - Relay interface modules

Redundancy Module QUINT-DIODE/40

Air damper actuators Rotary version, two-position control, with spring return, AC 24 V or AC 230 V

Contents. Document information

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

RM4TG20 three-phase network control relay RM4-T - range V

Rack mounted telephone- and leased line modem for industrial applications

Type: DILM32 10(24V50HZ) Article No.:

Type: DILM9 10(24VDC) Article No.:

Automation stations modular model

DCS Input/Output Relay Card Series

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

MasterINTERFACE 39 Series - Relay interface modules

OZS Web server. For LPB/BSB plants

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

CompactLogix Power Supplies Specifications

is then retained absolutely without interruption.

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2CDG1101xxR0011

40 Series - Miniature PCB/Plug-in relays A. Features

SIMATIC. ET 200S distributed I/O Digital electronic module 8DO DC24V/0.5 A (6ES7132-4BF00-0AA0) Preface. Properties 1. Diagnostics 2.

SINEAX U553 Transducer for AC Voltage

PCAN-B10011S Bus Converter High-speed CAN to Truck Trailer CAN. User Manual. Document version ( )

NC-12 Modbus Application

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Frequency Converter Fv

Emergency lighting units EM powerled

Transcription:

3 873 3873P01 RXB Room controllers For fan-coil applications FC-10, FC-11, FC12 with Konnex bus communications (S-mode and TE mode) RXB211 RXB221 The RXB211 and RXB221 room controllers are used for temperature control in individual rooms For 2-pipe or 4-pipe fan-coil systems, with or without change-over PI control Konnex bus communication (S-mode and TE mode) Integration into the DESIGO building automation and control system via PX KX Integration into Synco Control of AC 24 V PDM 1) thermic valve actuators, 3-position AC 24 V motorized valve and damper actuators, or electric heating coils Use of motorized KX / EIB bus valves Volt-free relay contacts for control of fans and electric heating coils Commissioning with ETS3 Professional, Synco ACS or "HandyTool" AC 230 V operating voltage Plug-in screw terminals 1) PDM = Pulse Duration Modulation CM23873en_04 14032008 Building Technologies

Application The RXB211 and RXB221 room controllers are optimized for control of fan-coil systems in individual rooms The following options are available with fan-coil systems: RXB211: Single-speed to 3-speed automatic fan control RXB221: Single-speed to 3-speed automatic fan control with integrated relay for electric re-heater The application of each controller is determined by the application software The controllers are delivered with a fixed set of applications, each of which contains various individual applications The relevant application is selected and activated during commissioning using one of the following tools: ETS3 Professional (EIB / KX Tool Software) Synco ACS "HandyTool" (the QAX343 room unit includes a tool function allowing you to parameterize the connected RXB controller) Use of spare inputs/outputs Some of the applications do not make full use of all the inputs and outputs These I/Os can be used freely in conjunction with a building automation and control system to register digital signals, for example, or to control various items of equipment (O/OFF or pulse control with AC 24 V or volt-free relay contacts) The inputs can then be read and the outputs controlled via the building automation and control system ote ot suitable for time-critical processes <1 s Functions The room controller functions are determined by the selected application and its parameters, and by the input/output configuration For details, refer to the FC description of functions, document CA110385 When DESIGO RXB controllers are integrated into a building automation and control system, or into a Synco system, additional functions become available such as time scheduling, central control of setpoints, etc 2/16 Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008

Applications The following applications are available for the RXB2 room controllers: Application group (type) FC-10 (with RXB211) FC-11 (with RXB211) FC-12 (with RXB221) Fan-coil applications FC02 FC04 FC08 FC20 FC10 FC12 FC18 FC03 FC05 2-pipe system with changeover 4-pipe system 4-pipe system and room/supply air cascade control 4-pipe system with single damper control 2-pipe system with changeover and outside air damper 4-pipe system with outside air damper 2-pipe system with changeover and radiator 2-pipe system with changeover and electric re-heater 4-pipe system with electric re-heater ote Only one application at a time can be activated with the tool (ETS3 Professional, Synco ACS or "HandyTool") Types The RXB211 and RXB221 room controllers differ only in the number of outputs available: Type AC 24 V triac outputs Relay outputs RXB211 RXB221 For 2 thermic valve actuators or two 3-position actuators For 2 thermic valve actuators or one 3-position actuator For 3-speed fan control For 3-speed fan control internal relay for electric heating coil RXZ201 Accessories: Terminal covers Ordering When ordering please specify the quantity, product name, type code and application group Example: 30 Room controllers, type RXB211/FC-10 Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008 3/16

Compatibility The RXB2 room controller is compatible with field devices from Siemens Building Technologies and with KX / EIB-compatible third-party devices For details, refer to the DESIGO RX hardware overview, CA23804 Design The RXB2 controllers consist of a housing base, a housing cover and the printed circuit board with connection terminals The controllers also have a tool socket, a service ED and a programming pin Plug-in connection terminals Cable restraints Plug-in connection terminals for KX / EIB bus Housing cover 3873J01 Housing base Plug-in connection terminals Service ED Programming pin Tool socket Service ED The programming ED shows the operational status of the room controller as follows: Green flashing Red O Orange / green flashing OFF Other patterns OK, device is in operation Addressing mode (ACS / ETS) Fault Parameter download o supply voltage Fault Service ED disabled by software Start-up (approx 5sec) Fault Programming pin The programming pin is used to identify the controller in the commissioning phase Pressing this pin causes the red programming ED to light up and remain on until identification of the controller is complete Once the programming pin has been pressed, the tool overwrites the hardware address in the room controller If there are no terminal covers fitted, the programming pin may be operated only by a qualified electrician The adjacent terminal may be a live mains voltage conductor 4/16 Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008

Terminal cover Terminal covers (RXZ201) are available as an option, to protect the connection terminals from physical contact and dirt The programming ED remains visible when the terminal covers are in place, and the programming pin can be operated with a pointed implement The cable is connected to the room controller by breaking out the perforated cable entry guide 3873J02 Removing the terminal cover abel (example for RXB211) Identification number (unique serial number) ID in bar-code form, code 128 3873Z04 Protection standard Temperature range (0 50 C) Serial o Test date, series (Z, A, B, C ) Observe notes in this document 060215B 513 010025CA9900 Activated application ocation ote Options for use of the labeling fields Appl and oc : Handwritten identification of the location and the activated application group Connection terminals All terminals are detachable plug-in screw-terminals To avoid incorrect wiring, terminals which can be connected to AC 230 V (relay outputs) are physically separate from the other terminals The cable restraints on the housing base must be used for the connections to terminals 19 28 (AC 230 V) The conductors must be secured with cable ties (see diagram) 3873J04 Warning! Ensure that the power is off before inserting or removing plug-in terminals connected to a mains voltage Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008 5/16

Communication The RXB2 controllers communicate with other devices via the following interfaces: PPS2 interface (proprietary) for the exchange of data with the room units KX / EIB bus (terminals CE+ and CE-) for communication with: PX/KX interface (to DESIGO ISIGHT) Interface OCI700 (to Synco) Other DESIGO RXB controllers KX / EIB compatible field devices (eg temperature sensor) The tool socket (RJ45) must be connected only by a qualified electrician The adjacent terminal may be a live mains voltage conductor Connecting the tool To facilitate commissioning, the tools ETS3 Profession or Synco ACS can be connected at three different points (marked (A) in the diagram) in the plant: to the KX / EIB bus cable at any point to the RXB2 controller (RJ45 tool socket) to the room unit (RJ45 tool socket) PPS2 KX KX bus A 3873A05 en CP CP+ C+ C QAX3 RXZ901 RXB2 CP CP+ CE+ CE CE+ CE A KX RS232 V24 Siemens 148 / UP146 / UP152 ETS PPS2 B PPS2 Tool KX A HandyTool QAX343 Siemens Anschlusskabel KX PPS2 PPS2 B Tool KX A HandyTool QAX343 Siemens Anschlusskabel A KX USB Siemens OCI700 ETS / ACS otes Caution! The tool socket is a proprietary socket A Siemens connecting cable must be used (eg PXA-C1) When connected to Ethernet, the device on the other end may be damaged! The tools ETS3 and ACS, even if connected to a tool socket, require an interface: RS232 KX/EIB interface (ETS3) OCI700 USB-KX / EIB interface (ETS3, ACS) The "HandyTool" is connected to the tool socket of the room controller or to the tool socket of the room unit (QAX3, RXZ901) (B) If you use OCI700 as an interface, it is connected to the service plug of the controller or of the room unit As long as the OCI700 is connected to the service plug, it must be supplied by the computer via the USB interface Otherwise the CD display of the room unit will turn dark and the controller will switch to addressing mode 6/16 Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008

Disposal The device includes electrical and electronic components and must not be disposed of as domestic waste Current local legislation must be observed Engineering notes The KX / EIB Building Services Management Manual and system principles supplement (see "Reference documentation", page 10) contains the information relevant for the engineering of the KX / EIB bus (topology, bus repeaters, etc) and for the selection and dimensions of connecting cables for the supply voltage and field devices AC 230 V supply cables Volt-free relay outputs AC 230 V The RXB2 room controllers operate with a mains supply voltage of AC 230 V The controlled devices (valves and damper actuators) receive their power directly from the room controller This means that a separate AC 24 V supply is not necessary for the controllers and associated field devices The sizing and fuse protection of the power supply cables depends on the total load and on local regulations The power supply cables connected to the room controller must be secured with cable restraints If serial wiring is applied on the terminal block 19/21, the connection will be interrupted if the block is removed from the controller (the jumpers 19-19 and 21-21 are on the PCB, not in the block, see terminal diagrams on pages 11 and 12) The supply cables must be secured with cable restraints The volt-free relay outputs allow the switching of loads up to AC 250 V, 5 A (4 A) The heating coil relay in the RXB221 switches resistive loads up to 18 kw The cable dimensions depend on the connected load and the local installation regulations The circuits must be externally fused ( 10 A) as there are no internal fuses The cables connected to the room controller must be secured with cable restraints The fans must not be connected in parallel AC 24 V triac outputs Example: The simultaneous load on outputs Y4 must not exceed 95 VA (heating) 2 thermic valve actuators, type STP72E 5 W Y2 (cooling) 2 thermic valve actuators, type STP72E 5 W Y3, Y4 (outside air) 3-position damper actuator 45 VA 45 VA The maximum load is 95 VA for the heating sequence and 95 VA for the cooling sequence This is acceptable because the two sequences never operate at the same time With low loads (< 2VA) the voltage tolerance may be greater than +20% (see technical data) Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008 7/16

Mounting instructions The room controllers can be mounted in any orientation, and fixed as follows: 3873J07 3873J06 Rail mounting The housing base is designed for snapmounting on DI rails, type E50022-35 x 75 (can be released with a screwdriver) Surface mounting There are two drill holes for screw-mounting (see Dimensions for drilling template) The housing base is fitted with raised supports Screws: Max diameter 35 mm, min length 38 mm STOP ote! Tightening torque for fixing screws max 15 m When mounting note the following: The controller should not be freely accessible after mounting It must be mounted in a cabinet or behind a cover that can only be opened / removed with a key or a tool Ensure adequate air circulation to dissipate heat generated during operation Easy access is required for service personnel ocal installation regulations must be observed Mounting instructions and a drilling template are printed on the controller packaging Commissioning The RXB2 room controllers are commissioned with either the ETS3 Professional or the Synco ACS tool via the RS232-KX / EIB interface, or via the USB-KX / EIB interface (OCI700), or with the HandyTool" via PPS2 abeling Function test The definitive application and the controller's location are handwritten in the labeling fields "Appl" and "oc" in the commissioning stage A special test mode (ETS3 Professional or "HandyTool") is available for operation of the outputs Further, if the digital inputs have been activated, they can be interrogated 8/16 Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008

In the event of a long-term short circuit (approx 4 minutes) or overload, the thermal fuse in the transformer may trip Subsequently, the device must be exchanged There is no protection against accidental connection on the AC 24 V side Mains AC 230 V for the supply and for the relays must be disconnected before plugging and unplugging the terminal blocks (danger of electric shock!) If serial wiring is applied on the terminal block 19/21, the connection will be interrupted if the block is removed from the controller (the jumpers 19-19 and 21-21 are on the PCB, not in the block, see terminal diagrams on pages 11 and 12) Technical data Power supply Operating voltage AC 230 V ± 10 % Frequency 50/60 Hz Power consumption with connected field devices Max 12 VA Internal fuse Thermal, non-resetting Operating data Control algorithm PI Inputs Signal inputs D1, D2 Quantity 2 (for volt-free contacts) Contact voltage DC 16 V Contact current DC 5 ma Contact transfer resistance Max 100 Ω Contact insulation resistance Min 50 kω Switch time: min 20ms O, min 20ms OFF Measured value input B1 Compatible temperature sensors G-i 1000 Quantity 1 measuring range 0 50 C Sensor current 05 ma Resolution 01 K Measuring error at 25 C sensor temp (without cable) max 05 K Outputs AC24 V triac outputs, Y4 Quantity 2 (RXB221) 4 (RXB211) Output voltage AC 24 V O/OFF, PWM or 3-position: +/ 20% (May exceed +20% with loads under 2VA) Output current Max 05 A Total nominal load (at both outputs simultaneously) Max 95 VA (eg 2 thermic valves, type STP72E per heating and cooling sequence + 1 damper actuator 45 VA) Relay outputs Q14, Q24, Q34 Quantity 3 Relay type Monostable Contact rating with AC voltage Switching voltage Max AC 250 V, min AC 19 V ominal current, resistive/inductive Max AC 5 A/4 A (cos ϕ = 06) Making current 200 ms half-time Max 20 A Switching current at AC 29 V Min AC 10 ma Contact rating with DC voltage Switching voltage Max DC 250 V, min DC 5 V Switching current at DC 5 V Min DC 100 ma Switching capacity Max 20 W Inductive load /R Max 7 ms Q44 Relay type Monostable Contact rating with AC voltage Max admissible load (resistive only) Max 18 kw External fuse (essential) Max 10 A Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008 9/16

Ports/interfaces Interface to room unit umber of room units connectable 1 Interface type for room unit for ETS3 Professional / ACS PPS2 KX / EIB bus PPS2 baud rate 48 kbit/s Baud rate on KX / EIB bus 96 kbit/s KX / EIB bus Interface type KX / EIB (electrically isolated) Transceiver TP-UART Bus current 5 ma Baud rate 96 kbit/s Bus topology Refer to KX / EIB manual (Reference documentation, see next page) Cable connections Connection terminals for signals and power supply (plug-in screw terminals) Solid or stranded conductors 025 25 mm 2 or 2 x 15 mm 2 KX / EIB bus connection terminals (plug-in screw terminals) Solid or stranded conductors 2 x max10 mm 2 eg YCYM 2x2x08 Single cable lengths For field devices, see also the RXC installation guide, CA110334 Signal inputs D1, D2 Max 100 m with diameters 06 mm Measured value input B1 Max 100 m AC24 V triac outputs, Y4 Max 100m where A 15 mm 2 Relay outputs Q14, Q24, Q34, Q44 Depends on load and local regulations Interface to room unit Max 115 m where A= 075 mm 2 (including connecting cable for tool) Cable type 4-core, twisted pair, unscreened KX / EIB bus Max 500 m Cable type Refer to KX / EIB manual (see "Reference documentation" below) Tool connecting cable Max 3 m Housing protection standard Protection standard to E 60529 IP30 with terminal cover fitted and wall mounted without DI rail IP00 for all other mounting arrangements Protection class Suitable for use in systems with protection class I or II Ambient conditions ormal operation Class 3K5 to IEC 60721-3-3 Temperature 0 50 C Humidity < 85 % rh Transport Class 2K3 to IEC 60721-3-2 Temperature 25 65 C Humidity < 95 % rh Industry standards Product safety Automatic electronic controls for household and similar use E 60730-1 Special requirements for energy regulators E 60730-2-11 Electromagnetic compatibility Interference immunity in industrial environment E 61000-6-2 Emitted interference in domestic environment E 61000-6-3 CE marking: EMC Directive 89/336/EEC ow Voltage Directive 73/23/EEC Home and Building Electronic Systems (HBES) E 50090-2-2 Konnex compliance Certified Dimensions See dimension diagrams Weight excluding packaging 0,640 kg including packaging 0670 kg Reference documentation Building Services Management Manual Fundamental principles Building Services Management Manual Applications Zentralverband Elektrotechnik- und Elektronikindustrie ev (ZVEH) (Central association for the electrical and electronic engineering industry) Stresemannallee 19D-60596 Frankfurt a M, Germany 10/16 Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008

Connection terminals RXB211 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 CP CP + CE + CE 3873A08 B1 M D1 GD D2 G Y2 T EIB / KX M 2 1 4 3 QAX AC 230V Q13 Q14 Y3 G Y4 M AC 230V 5(4)A Q24 Q34 C CE + CE 19 19 21 21 25 26 27 28 Measured value input B1 1 Measured value input for G-i 1000 sensors M 2 Measured value input ground Signal inputs D1 4 Signal input GD 5 Signal ground D2 6 Signal input Triac outputs 7 AC 24 V, 05 A switching output G 8 AC 24 V actuator supply Y2 9 AC 24 V, 05 A switching output Y3 10 AC 24 V, 05 A switching output G 11 AC 24 V actuator supply Y4 12 AC 24 V, 05 A switching output Room unit CP 13 PPS2 ground CP+ 14 PPS2 data CE+ 15 KX / EIB data cable CE 16 KX / EIB data cable KX / EIB bus (plug-in connection) CE+ 17 KX / EIB data cable CE 18 KX / EIB data cable Power supply 19 eutral conductor R 21 Phase conductor AC 230 V +/- 10 % Relay outputs Q13 25 Common feed for Q14, Q24 and Q34 Q14 26 ormally-open contact, max AC 250 V, 5 (4) A (Stage 1) Q24 27 ormally-open contact, max AC 250 V, 5 (4) A (Stage 2) Q34 28 ormally-open contact, max AC 250 V, 5 (4) A (Stage 3) Caution Observe the technical data for the relay outputs: max AC 250 V, 5 (4) A ocal installation regulations must be observed Tool socket Proprietary RJ45-type tool socket 1 2345678 1 KX / EIB data cable (CE+) 2 KX / EIB data cable (CE ) 3 ot used 4 ot used 3206Z01 5 +12VDC 6 RxD 7 PPS2 (CP+) / TxD 8 PPS2 (CP ) Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008 11/16

Connection terminals RXB221 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 3873A09 T EIB / KX M 2 1 4 3 QAX AC 230V AC 230V 10A AC 230V 5(4)A C Q43 Q44 Q13 Q14 Q24 Q34 B1 M C D1 GD D2 G Y2 C C C CP CP + CE + CE CE + CE 19 19 21 21 22 23 24 25 26 27 28 Measured value input B1 1 Measured value input for G-i 1000 sensors M 2 Measured value input ground Signal inputs D1 4 Signal input GD 5 Signal ground D2 6 Signal input Triac outputs 7 AC 24 V, 05 A switching output G 8 AC 24 V actuator supply Y2 9 AC 24 V, 05 A switching output Room unit CP 13 PPS2 ground CP+ 14 PPS2 data CE+ 15 KX / EIB data cable CE 16 KX / EIB data cable KX / EIB bus (plug-in connection) CE+ 17 KX / EIB data cable CE 18 KX / EIB data cable Power supply 19 eutral conductor R 21 Phase conductor AC 230 V +/- 10 % Relay outputs Q13 25 Common feed for Q14, Q24 and Q34 Q14 26 ormally-open contact, max AC 250 V, 5 (4) A (Stage 1) Q24 27 ormally-open contact, max AC 250 V, 5 (4) A (Stage 2) Q34 28 ormally-open contact, max AC 250 V, 5 (4) A (Stage 3) Q43 23 ead wire for Q44 Q44 21 /O contact AC max 250 V, 10 A(electric heating coil) Caution Observe the technical data for the relay outputs: Max AC 250 V, 5 (4) A and 10 A, respectively ocal installation regulations must be observed Tool socket Proprietary RJ45-type tool socket 1 2345678 1 KX / EIB data cable (CE+) 2 KX / EIB data cable (CE ) 3 ot used 4 ot used 3206Z01 5 +12VDC 6 RxD 7 PPS2 (CP+) / TxD 8 PPS2 (CP ) 12/16 Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008

Connection diagrams Connection of field devices, room unit, KX / EIB bus and power supply 1 B1 M D1 GD D2 1 2 4 5 6 T B1 D1 D2 3873A11 G Y2 7 8 9 Y2 G M 1 Y3 G Y4 10 11 12 Y3 Y4 G M Y31 CP CP + CE + CE 13 14 15 16 2 1 4 3 PPS2 KX / EIB B2 CE + CE 17 18 KX / EIB 19 19 21 21 AC 230 V C Q43 Q44 22 23 24 Q2 Q13 Q14 Q24 Q34 25 26 27 28 1 2 3 Q1 1 Q11 1 RXB211, RXB221 B1 G-i 1000 temperature sensor D1, D2 Volt-free contacts (window contact, occupancy sensor, etc) Y4 AC 24 V thermic valve actuators 1 Motorized AC 24 V, 3-position valve or damper actuator Y31 Motorized AC 24 V, 3-position valve or damper actuator B2 QAX3 room unit Q1 3-speed fan Q11 1-speed fan Q2 Electric heating coil Twisted pair Fans connected to relay outputs Q14 Q34 must not be operated in parallel For parallel operation use cut-off relays or slave room controllers At Q2 (18 kw max resistive load), use additional external fuses of max 10 A to protect the pcb tracks ote For information on the compatibility of field devices with the RXB211 and RXB221 room controller, refer to the various application descriptions (see the FC description of functions, document CA110385) Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008 13/16

Parallel connection of several thermic valve actuators Up to two thermic actuators per sequence may be connected directly to the room controller With more than two thermic actuators, a UA1T power amplifier is required The principle is the same for output Y2 Do not exceed the maximum simultaneous load on outputs and Y2 (max 95 VA) Power consumption at input X1 of the UA1T: 05 VA Mixed operation: It is not permissible to connect thermic actuators both to the controller and to the power amplifier Owing to the difference in voltage between the controller's internal transformer and the power supply of the UA1T, this could cause the valve positions to deviate substantially Connection to the controller 1 AC 230 V G 1 3873Z12 Connection to the power amplifier 1 AC 230 V AC 24 V G G0 3873Z13 G 2 1 S COM 8 1 3 2 3 S COM COM 7 6 2 4 4 X1 5 2 1 S COM 8 5 7 2 3 S COM COM 7 6 6 8 4 X1 5 1 2 x Room controller RXB211, RXB221 UA1T power amplifier (see data sheet CA23591) AC 24 V thermic valve actuators connected to the controller AC 24 V thermic valve actuators (max 2 STA71/STP71 actuators per output on the UA1T) otes The UA1T requires an AC 24 V supply voltage The UA1T is not suitable for the connection of 3-position actuators 14/16 Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008

Dimensions Dimensions in mm Without terminal cover 3873M14 35,3 3,9 62 1 3,3 133,2 4,4 With terminal covers 51,5 5 35,3 167 3873M15 3,9 62 1 112,4 107,8 Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008 15/16

Drilling diagram (1:1) 3,6 3873M16 39 78 43,2 86,3 2006-2008 Siemens Switzerland td Subject to alteration 16/16 Siemens RXB211, RXB221 Room controllers CM23873en_04 Building Technologies 14032008