Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives



Similar documents
Operational Overview and Controls Guide

*.ppt 11/2/ :48 PM 1

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

Safety Requirements Specification Guideline

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

Back-UPS 650 VA 120 V with AVR (BX650CI-LM)

ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual

Diesel Engine Driven Generators Page 1 of 6

GPD 506/P5 Start-up Procedure and Checklist

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Oil and Coolant Circulating Heating System. Model - OCSM

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

SECTION VARIABLE FREQUENCY DRIVES

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

SECTION 13XXX CONTROL DESCRIPTION (DICP Models NC, 412, 622, 826, 1030)

Thermo Top - Troubleshooting Tree

SCORPION. micron security products

User s Manual Before using the inverter, you need to read and save the safety instructions.

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

Technical Information

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

MTS Power Products MIAMI FL ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual

Automatic start of a generator

User Manual. English. APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC. Tower Uninterruptible Power Supply

32VFD Variable Frequency Drives for Centrifugal Chillers

Install the DeviceNet Module using the following procedure:

ODYSSEY. Security System Owner s Manual. Kit No. 08E51-SHJ E55-SHJ American Honda Motor Co., Inc. - All Rights Reserved.

EATON Diesel Plus Diesel Engine Fire Pump Controller

14. Troubleshooting Guide

GSM AUTO DIALER. Remote Monitoring & Control using your mobile phone.

Application Engineering

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) SECTION: 2400

FIRE ALARM SYSTEM RECORD OF COMPLETION

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE

PUSH BUTTON START INSTALLATION MANUAL

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

FIRE ALARM SYSTEM RECORD OF COMPLETION

OPERATING INSTRUCTIONS SECURITY SYSTEM KIT NO.: 08E51-EP American Honda Motor Co., Inc. - All Rights Reserved. 1

USER S MANUAL HSC-24A

How To Set Off An Alarm On A Car With A Car Alarm On It

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

Installation and Operation Back-UPS 1250, 1300, 1500

Control/Communicator Installation Manual

New GSM Alarm System. User s Manual. Profile For a better understanding of this product, please read this user manual thoroughly before using it.

1R / 4-BUTTON SERIES

Doc.No. NDP 192U-02. Electric Pump Controller CE-124P. Instruction Manual

OPL BASIC. Dosing System for Professional Laundry machines. Contents

Limited Service Fire Pump Controllers Features

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

Match. GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match UPS. GE Digital Energy.

Water Priming Mode Purge air from plumbing system. How do I solve ER-3 WATER PRIME: TIPS ON FILLING SPA IMPORTANT NOTE WARNING

Diesel Engine Fire Pump Controllers

PARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS

500r+ Installation and User Guide

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual

MP-4000 Alarm List (Software version or later)

GSM Alarm System User Manual

MANUAL FOR MODEL MP300 to MP700 ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS

Limited Service Pump Controllers (Produced after July 18, 2006) Installation- Start Up - Service

ABNORMAL OPERATION Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target

May, ArACBMENT I. Review of. Diesel Generator Alan and Control Circuitry. Indian Point Units No. 2 and 3. Docket Nos.

1 For All Non-Programmable Digital Thermostat

Annex-A TECHNICAL SPECIFICATION

The Child Reminder System Installation Manual

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04

HEAT PUMP PROGRAMMABLE THERMOSTAT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

Electric Panel Pump Control System. Operation, Maintenance and Installation Manual

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

C3306 LOCKOUT/TAGOUT FOR AUTHORIZED EMPLOYEES. Leader s Guide. 2005, CLMI Training

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

REMOTE CONTROL MANUAL

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Inch PowerVent LED Indicator Explanations & Troubleshooting Table

Additional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits:

USER MANUAL EXTROLLER

Medical Vacuum Systems-PXMI

Generator Differential Relay Electrical Apparatus

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

CA60 Plus Software Version 3.1 User Manual May 2000

Manual for Fire Suppression & Methane Detection System

WIRING HARNESS FOR AS635P4. BLUE PLUG RED, BLUE, BLACK, WHITE - Plug in dual stage sensor harness

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

User Manual for CH-PFC76810

Cat Electronic Technician 2015A v1.0 Product Status Report 6/3/2015 4:41 PM

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER

B/S/H/ Error codes and service programmes PH

PC1130 Electric Air Compressor

Transcription:

DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770) 447-4443. Fax (770) 447-0230 BETTER CONTROL THROUGH SYSTEMS ENGINEERING TABLE OF CONTENTS

I. PUMP SEQUENCING...3 A. RESTART SEQUENCING... 3 B. LEAD PUMP SEQUENCING... 3 C. LAG PUMP SEQUENCING... 3 D. SEQUENCE ALTERNATION... 4 II. SPEED CONTROL...4 III. OPERATOR CONTROLS...4 A. PUMP SELECTOR TOUCH KEYS... 4 D. ALARM SILENCE/RESET PUSH BUTTON... 4 IV. ALARMS...5 A. LOW SUCTION PRESSURE ALARM... 5 B. LOW SYSTEM PRESSURE ALARM... 5 C. HIGH SYSTEM PRESSURE ALARM... 5 D. PRESSURE TRANSMITTER OUT OF RANGE ALARMS... 5 E. INDIVIDUAL DRIVE FAULT ALARMS... 6 F. MANUALLY RESETTING ALARMS... 6 V. PROTECTION DEVICES...6 A. OPERATOR SAFETY... 6 B. MOTOR PROTECTION... 6 C. CONTROL CIRCUIT PROTECTION... 7 D. PUMP OVER-TEMPERATURE PROTECTION... 7 VI. PROGRAMMABLE CONTROLLER...7 A. STATUS LEDS... 7 B. PROGRAM CHANGES... 8 C. MAINTENANCE... 8 D. REPAIRS... 8 APPENDIX 1 - SET POINTS...9 A. NON-ADJUSTABLE SET POINTS... 9 B. ADJUSTABLE SET POINTS... 9 i. Time Delay Set Points... 9 ii. Pressure Set Points... 9 iii. Speed Control... 9 2

I. PUMP SEQUENCING The controller continuously monitors the pressure of the system with the system pressure transmitter and the suction pressure with a suction pressure transmitter. In automatic operation, the controller will signal the appropriate pump(s) to start or stop based upon the sequencing described herein. It should be noted that all pumps follow the same speed control signal produced by the controller. Upon starting, the pumps will slowly ramp up to the appropriate speed. Once this startup sequence is complete, the pumps will always run at whatever speed is required to maintain the set point pressure. All pumps are protected by minimum run timers to prevent unnecessary cycling. Whenever a lag pump stops, a momentary drop in system pressure may occur, resulting in the remaining pump(s) to speed up temporarily to compensate. The pumps will stop in the reverse order from which they started. Please note that many of the set points described below are adjustable through the human machine interface (HMI). This is described in greater detail in both the Appendix 1 - Set Points section of this manual and the HMI manual. A. Restart Sequencing Anytime the system is reset from a complete alarm shutdown or after power is restored, pump sequencing is modified to help prevent water hammer. The lead pump will start on low system pressure as normal. However, there is a 10-second interval before each lag pump may start. B. Lead Pump Sequencing The lead pump will stop during very low demand conditions. This will happen after the lead pump minimum run time has expired, system pressure is maintained within 2 psig of the set point, the lag pump is off, and the VFD speed can be reduced without system pressure dropping for the duration of the adjustable lead stop delay. If there is a HydroCumulator on the system, the operator can enable a charge feature through the HMI that will store up to an additional 10 psig (depending on the pump) in the tank before shutting down. The lead pump will start when system pressure drops several pounds below the desired system pressure (system pressure set point - pressure sequencing deadband). C. Lag Pump Sequencing If the capacity of the lead pump is exceeded, the lag pump will start after an adjustable time delay. Similar to the lead pump, the lag pump(s) will start on low system pressure, but also require the VFD speed to meet or exceed the lag on speed. This helps ensure the running pump(s) are at or near capacity before starting another pump. The lag pump(s) will stop after the minimum run timer has expired, system pressure is maintained, and its speed has reduced enough to ensure the lead pump can handle the flow 3

demand. D. Sequence Alternation The pumps will switch starting positions each time the lead pump either runs for 24 hours or has a non-alarm shutdown. If the lead pump is running at the time of alternation, it will continue to run for 10 seconds more with the new lead pump to help prevent water hammer. II. SPEED CONTROL For normal operation, the speed control should be set to automatic on the HMI. In automatic, this system will automatically adjust the VFD speed as required to maintain system pressure. The system pressure set point is set by the operator using the touch screen. As the pressure in the pipe decreases, the pump speed will increase until the pressure is returned to its set point value. If the pressure begins to rise above the set point, the pump speed will decrease until the set point is reached. If the operator chooses or if the system pressure transmitter fails, the system will run in manual control at a fixed speed. Minimum and maximum speed set points can also be set in the touch screen. III. OPERATOR CONTROLS A touch screen is provided for control of pump operation, display of system pressure, suction pressure, VFD speed, alarm status, and allow adjustment of certain parameters. If an alarm should occur, an alarm horn will sound and an alarm message will be displayed on each screen of the HMI. The operator can review the alarm by looking at the alarm list. This is described further in the Human machine interface Manual. A. Pump Selector Touch Keys The pump selector touch keys are on the Main screen of the HMI. HAND - Use for manual operation only - to start up, restart and reset, or test each pump. No pump should run in this position without supervision. OFF - Pump will not run at all. Use during start up, restart and reset, or when a pump is down for service. AUTO - Automatic position for each pump, which allows the controller to have full control over the pumps operation. D. Alarm Silence/Reset Push Button 4

This button is on each of the alarm status screens of the HMI. Push once to silence the alarm horn, wait five seconds and push a second time to reset the system from alarm mode back to normal automatic operation. The system will not reset unless the original cause of the alarm(s) has been corrected or removed. This button can also be used to defeat the minimum run time of the pumps and allow the lag pumps to turn off if they are not required to be running. This is a useful feature when testing or monitoring the system. IV. ALARMS Several of the alarms described below feature adjustable set points. These can be adjusted using the HMI. This is described in greater detail in both the Appendix 1 - Set Points section of this manual and the HMI manual. Please note that each of the alarms described below will be displayed on the HMI. A. Low Suction Pressure Alarm If the low suction pressure transmitter signals a loss of supply water pressure for 5 seconds (default), all pumps will be locked off. This alarm and the system will be disabled in the event of a suction pressure transmitter failure. This alarm requires manual resetting as described below. B. Low System Pressure Alarm If system pressure drops to or below the low system pressure set point for 30 seconds (default), this alarm will activate. System performance will not be affected by this alarm. It is used to alert the operator that a problem occurred. This alarm will be disabled in the event of a system pressure transmitter failure. The alarm requires manual resetting as described below. C. High System Pressure Alarm If system pressure rises above the high system pressure set point for 5 seconds (default), this alarm will activate and all pumps will be locked off until manually reset. This alarm will be disabled in the event of a system pressure transmitter failure. The alarm requires manual resetting as described below. D. Pressure Transmitter Out of Range Alarms The correct output range of the pressure transmitter(s) is 1-6 khz. The pressure transmitter failed low alarm will activate if the controller receives an abnormally low signal for 2 seconds. The pressure transmitter failed high alarm will activate if the controller receives an abnormally high signal for 8 seconds. The system will run at the manual speed set point if the system pressure transmitter fails. If the suction pressure transmitter fails, the system will be disabled. 5

These alarms will automatically reset when the transmitter operates in its correct range. E. Individual Drive Fault Alarms If a fault occurs in the drive when it is being called to run, the VFD failure alarm will be activated. This alarm will stop the pump with the failed drive and start the next available pump if it is not currently running. The alarm requires manual resetting with the alarm silence / reset push button as described below. F. Manually Resetting Alarms Most of the alarms require manual resetting before returning to normal automatic operation. This ensures proper troubleshooting, problem solving, and a smooth return to normal automatic operation by the operator. Before resetting an alarm, the alarm horn must first be silenced by pressing the reset touch key on the HMI (on the alarm list screens). Five seconds after silencing the alarm horn, the system can be reset (provided the original reason for the alarm has been corrected). V. PROTECTION DEVICES A. Operator Safety The enclosure features door-interlocking motor disconnecting devices (motor starter protectors, fused disconnect switches, or circuit breakers). These prevent the opening of the panel while the motors are running. To open the control panel, turn off each of the motor disconnecting devices. Please note, high voltage may still exist in the panel. B. Motor Protection Anytime a motor protection device trips, the cause of the problem should be determined before returning the motor to service. Each motor will be protected against overload and short circuit current by one of the following devices: Motor Starter Protectors If a MSP should trip due to over-current, the MSP handle will turn to an intermediate position between ON and OFF. To reset the MSP, turn the handle to the OFF position and then back to ON, similar to a tripped circuit breaker. Fused Disconnect Switches Dual-element fuses are provided for over-current protection. Circuit Breakers 6

If a circuit breaker should trip due to over-current, the handle will turn to the TRIP position. To reset the circuit breaker, turn the handle to the OFF position and then back to ON. C. Control Circuit Protection The control power transformer is sized according to the consumption of power of the controls. Circuit breakers that are sized according to N.E.C. requirements for transformers protect the primary and secondary circuits. D. Pump Over-Temperature Protection Each pump is fitted with a temperature purge valve. If the water in a pump becomes too hot (at low flow), the valve will open. The hot water is then dumped to drain, allowing cool water to enter the pump from the suction side. Once the pump is cool again, the temperature purge valve will close. VI. PROGRAMMABLE CONTROLLER The controller features both non-adjustable and adjustable timers. The adjustable timers can be changed using the HMI. Please refer to the Human machine interface Manual for instructions on how to do this. A listing of the set points for all timers is provided in Appendix 1 - Set Points. A. Status LEDs The status of the PC can be determined by observing the LEDs on the face of the PC. To do this, the control panel door must be opened and the control circuits must be energized. The function of each LED is described below. POWER - This LED should be illuminated continuously if control power is on. RUN - This LED should be illuminated during normal operation. If this LED is off, make sure the switch under the small door to the left of the HMI connection is in the RUN position. ERROR - If this LED is flashing, then a program error is indicated. If it stays on continuously, a processor error is indicated. If turning power off and on cannot clear either of these errors, consult the factory. 7

IN / OUT - These individually numbered red LEDs turn on when their corresponding INput or OUTput point is on. B. Program Changes SyncroFlo will do all programming for the PC. Every phase of the program will have been tested with the entire machine at the factory. Final adjustments are made at start-up by factory trained personnel. If a program change is required, it will be made by SyncroFlo and transmitted to the field via a program loader or chip. SyncroFlo keeps a copy of the program at the factory so that any changes can be made and transmitted immediately. C. Maintenance The PC requires no routine maintenance. The program is stored on an EEPROM chip so that it will not be lost due to loss of power no matter how long the power is off. A periodic check of the PC status lights will be sufficient to check for correct operation. The power and run status LEDs should always be on when control power is available. Testing all control functions to see if the PC performs as described can check the inputs and outputs. Remember that when an input or output contact is on, its status LED will be on. D. Repairs It is unlikely that a problem will develop with the PC itself. If a problem seems to be evident, call the factory for assistance. If it is determined that a problem does exist, a new unit can usually be shipped in 24 hours. Please note that if, for example, lightning struck the control panel and destroyed the PC, the pumps can still be run in the hand position while repairs are underway. 8

Appendix 1 - Set Points A. Non-Adjustable Set Points Reset Delay after Alarm Silence Pressure Transmitter Failed Low Delay Pressure Transmitter Failed High Delay VFD Fault Delay Lead Pump Start Delay 5 sec. 2 sec. 8 sec. 0 sec. 2 sec. B. Adjustable Set Points i. Time Delay Set Points Default Range Low System Press. Alarm Delay 30 sec. 1-999 sec. High System Press. Alarm Delay 5 sec. 1-60 sec. Low Suction Press. Alarm Delay 10 sec. 1-30 sec. Lead Pump Minimum Run Time 30 sec. 30-600 sec. Low Demand Lead Shutdown Delay 30 sec. 24-99 sec. Lag Pump Start Time Delay 5 sec. 2-30 sec. Lag Pump Minimum Run Time 30 sec. 30-600sec. Lag Pump Stop Delay Delay 15 sec. 1-99 sec. ii. Pressure Set Points Default Range System Pressure (See Sys. Data Sheet) 0-999 psig Pressure Sequencing Deadband -5 psid below SP -1 to -15 psid Low System Pressure Sys. Pr. - 10 psig 1-999 psig High System Pressure Sys. Pr. + 30 psig 1-999 psig Low Suction Press. Alarm 5 psig 5-999 psig iii. Speed Control Default Range VFD Minimum Speed 30 Hz 0 60 Hz VFD Manual Speed 45 Hz (Min Max Spd.) Hz VFD Maximum Speed 60 Hz 0 60 Hz VFD Lag on Speed 50 Hz 0 60 Hz 9