TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output



Similar documents
FIREYE FLAME SCANNERS

INSTALLATION INSTRUCTIONS for INSIGHT FIBER OPTIC FLAME SCANNERS

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Inch PowerVent LED Indicator Explanations & Troubleshooting Table

SELECTION, APPLICATION AND MAINTENANCE

TYPE 95IR/95UV/95DS. Integrated Flame Scanner with Internal Flame Relay TUV SIL2 DESCRIPTION MODEL S1, S2. RoHS Compliant to EU Directive 2002/95/EC

Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC)

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

Triple Waveband Infra-Red Flame Detection

Power Supplies 3. SDN-P DIN Rail Series

Isolating Barriers for our sensors A5S1 in Ex-areas Series D461

How To Use A Ds340 (Dsp)

TYPE 25SU3-5166/5168 CONTROL SYSTEM DESCRIPTION FLAME AMPLIFIER, WIRING BASE, SCANNERS, AND DISPLAY

SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

7800 SERIES RM7838B,C Relay Module

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 12/6/10

HENRY TECHNOLOGIES - OIL LEVEL REGULATORS (CONVENTIONAL)

Combustible Gas Transmitter RK-05

7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules

How To Use A Power Supply Unit (Upu)

ACS-30-EU-EMDR-10-MOD

Water Leak Detection System

Pressure Switch for gas and air

PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller

Duct Humidity Transmitter

LevelOne IFE Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual

G670 Intermittent Pilot Ignition Controls

Flow switches Series AD/VH

Paragon Explorer Lite Communication Software

REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN (574) FAX (574) ELKHART BRASS MFG. CO., INC.

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

SMART SENSOR COLLECTION

PROXIMITY CARD READERS C-10, C-20, C60, C70

User s Manual AURORA 1.2K/2.2K

HG600/HG800. Hydro-Power Unit. Installation and Operation Guide

NEXUS FX04 and FX04-1 Servo Motor Installation. Fireye DESCRIPTION SAFETY INFORMATION. FX04-1 Shown

2 WAY (2/2) AND 3 WAY (3/2) BRASS AND STAINLESS STEEL SOLENOID VALVES

FIREDEX Conventional Fire Panels

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Thermatel Model TA1 Mass Flow Transmitter

Technical Data. Dimensions

Model 43AP Pneumatic Controller, Style B

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

E110 FIREYE FLAME-MONITOR BURNER MANAGEMENT CONTROL FOR USE WITH THE MICROPROCESSOR-BASED EP AND EPD STYLE PROGRAMMER MODULES

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

BBWX1 Satellite Weather Receiver. Installation and Maintenance Guide

ZC-24DO CANopen I/O Module: 24 Digital Outputs

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

RADIANT PLASMA 4700 Plasma Spark Generator

IO-RM3 3-Stage Relay Module

Operating Instructions

Drayton Digistat +2RF/+3RF

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

Plastic tube flowmeters Series PT/PS

Air Conditioning Sign-Off Sheet

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm

PART 1 - INTRODUCTION...

4 Posiflow Proportional Solenoid Valves

VLT Series 300 Watt True Sine Wave Inverter

2 & 5-Wire Overfill Sensors

Gas Oven Repair Guide

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY

MULTI-BEAM LS10 Light Screen System

Owner s Manual AWM910 JENSEN AWM910 COMPACT DISC PLAYER RADIO CD COMPACT MUSIC SYSTEM MUTE AUX BAND AUX IN PUSH PUSH PWR VOL ALARM T/F AUD SPK A SPK B

Speed Control Relays SX2


THE INPUT/OUTPUT SYSTEM. Key Points

Oil - kerosene burners

INSTALLATION INSTRUCTIONS

Inductive sensor NI10-M18-Y1X-H1141


RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

PRODUCT PROFILE FEATURES

WD-AMX Water Detection Controllers

ISO-9001:2000 certified. EE300 Series Electromechanical Inventory Level Measuring System. Aplus Finetek Sensor, Inc.

3500/93 System Display

FIREYE MODULAR MicroM FLAME SAFEGUARD CONTROLS

*.ppt 11/2/ :48 PM 1

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12)

Appliance Diagnostic Modes Microwave. GE Consumer & Industrial Technical Training

Electro-Magnetic Flowmeters COPA-XT 2-Wire DT43

Digital inductive conductivity transmitter

Operating Instructions

In-Sight Hardware specifications

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF)

T7560A,B,C Digital Wall Module

Not required for most applications Not required for most applications High pressure ( provided) High pressure ( provided)

Programming Logic controllers

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types

Messko. Messko. MTraB - Maintenance Free Dehydrating Breather Ordering specifications XX - XX - XXX - XX

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

PROCESS AUTOMATION MANUAL OVERSPEED/UNDERSPEED MONITOR KF**-DWB-(EX)1.D ISO9001

Transcription:

133-683 JUNE 28, 2006 TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output DESCRIPTION APPLICATION The Fireye 65UV5-1004 flame scanner is a microprocessor based flame scanner utilizing an ultraviolet tube-type sensor, and electro-mechanical self-checking shutter mechanism. The Fireye 65UV5-1004 flame scanner incorporates an internal flame relay with a fixed ON/OFF threshold thereby eliminating the need for an external flame amplifier. Models are available with a four-second or a one-second flame failure response time (FFRT). The 65UV5-1004 model also provides an analog 4 to 20mA output referenced to flame signal strength. The Fireye 65UV5-1004 flame scanner is powered by 24 vdc. CEX models are wired directly via a terminal rail located within the CEX housing. Suitable glands must be used to terminate the cable at the housing. The picture above depicts the CEX scanner mounted on a heater. Fireye 65UV5 self-checking scanners are used to detect ultraviolet emissions from fossil fuel flames such as natural gas, coke oven gas, propane, methane, butane, kerosene, light petroleum distillates and diesel fuels. PRINCIPLE OF OPERATION The 65UV5 scanners use a UV-eye detector. This detector is a sealed, gas filled, UV-sensitive tube containing two electrodes connected to a source of DC voltage. When UV radiation of sufficient energy falls upon the electrodes, electrons are released and the inter-electrode gas becomes conductive, resulting in an electric current flow from one electrode to the other. The current flow starts and ends abruptly and is known as an avalanche. A very intense source of UV radiation will produce several hundred avalanches or pulses per second. With less radiation there will be fewer pulses per second. Upon total disappearance of flame, the detector output ceases. Thus, the presence or absence of pulses is an indication of the presence or absence of flame; the frequency of the pulses is a measure of flame intensity. When the pulses reach a sufficient level, the internal flame relay is energized. FEATURES The scanner includes an electro-magnetic shutter that permits a self-checking circuit to verify that the scanner and signal circuits are producing valid flame presence or absence information. During the shutter closed period, the detector s optical path is blocked from flame radiation, allowing the internal microprocessor to verify the proper operation of the ultraviolet tube. While the shutter is open, flame presence or absence is detected. The self-check shutter operation and fault diagnostics are fully described later in this bulletin. 1

SPECIFICATIONS FIGURE 1. SIMPLICITY SCANNER in CENELEC HAZARDOUS AREA HOUSING (mounting flange kit ordered separately) FOR WIRING INSTRUCTIONS REFER TO FIGURE 3 0.35 (9) MOUNTING SCREWS (4 PLC.) 3/8" THREADED OPENING FOR COOLING AIR 5.28 (134) 4.41 (112) 1" FEMALE THREAD SIGHT PIPE MOUNT FLANGE GASKET 4.53 (115) 4.41 (112) 8.94 (227) 3.56 (90) *HOUSING FLANGE KIT DIMENSIONS IN INCHES (MM) ASSEMBLY SHOWN WITH HOUSING FLANGE KIT, ORDERED SEPARATELY *HOUSING FLANGE KIT, ORDERED SEPARATELY (INCLUDES NPT OR BSP FLANGE, GASKET, MOUNTING P/N 129-168-1 (NPT) P/N 129-168-2 (BSP) NOTE: All models of the Simplicity 65UV5-1004 CEX flame scanners are housed within a CEN- ELEC and ATEX approved housing for application in EExd IIC T6 hazardous rated environment. In addition the CENELEC housing is designed to meet the requirements of IP66 (NEMA 4X). SPECIFICATIONS MECHANICAL: Hazardous Classifications: EExd IIC T6 ATEX Cooling / Purge Air Requirements: Source: Clean, dry, cool Volume: 4 SCFM (113 l/min) at 3/4" threaded mounting flange, or 1 inch Y fitting, mounted on scanner sight pipe. Temperature near the upper limit of the scanner operating range and/or use with dirty/dusty fuels may require up to 15 SCFM (425 l/min). Pressure: Adequate to overcome furnace or windbox pressure Temperature Rating: -40 F to + 150 F (-40 C to +65 C) maximum dependent on T classification Humidity: 0% to 95% relative humidity, non-condensing ELECTRICAL: Input Power: 24 Vdc, +10%, -15% supply current 100 ma Electrical Connection: Internal terminal rail Relay Output FLAME RELAY, SPST (N.O.) Contact Rating: Minimum: 10 ma @ 5 Vdc Maximum: 2 A @ 30 Vdc 2 A @ 240 Vac Status Indication: Internal LED: Flame Signal, Fault Indication 2

FIGURE 2. MOUNT 1 STANDARD UNION APERTURE #53-121 1 NIPPLE A STANDARD MOUNTING RETAINER B 1 SIGHT PIPE (BY OTHERS) MOUNT 1 NIPPLE 1 STANDARD UNION COOLING AIR/ENTRY WYE #35-200 (NPT) WYE #35-239 (BSP) 1 STANDARD UNION MOUNTING FOR HIGH TEMP. APPLICATIONS C ALTERNATE MOUNTING (NOT ADJUSTABLE) MOUNT 1 NIPPLE COOLING AIR/ENTRY FULL PORT BALL VALVE MOUNT #60-1199 (NPT) D WYE #35-200 (NPT) WYE #35-239 (BSP) MOUNTING FOR SPECIAL APPLICATIONS - HIGH PRESSURE SEALING UNION WITH QUARTZ WINDOW. REQUIRED WHEN SCANNER LENS IS EXPOSED TO EXCESSIVE PRESSURE FURNACE OR WINDBOX PRESSURE 1 SIGHT PIPE (BY OTHERS) CEX MOUNTING SCANNER WIRING NOTE: Due to the 65UV5 s integrated cable, it is recommended that a union always be installed in the mounting pipe to facilitate scanner removal. The 65UV5-1004 CEX scanner includes an internal terminal rail. The two red leads provide the 24 vdc power. The two black leads access the normally open flame relay contact. The yellow lead provides the positive connection for the 4 to 20mA signal referenced to 24 volt vdc ground. A ground screw is provided on the front of the scanner and internally to cross bond. To reduce electrical noise interference, take precautions to keep the scanner cable away from any high inductive wiring associated with high inductive loads or high voltage, high energy spark ignition systems. CEX models are wired directly and have a terminal rail to connect which is located within the CEX housing. Suitable EX glands must be used to terminate the cable at the housing. 3

WARNING: Unit should be electrically protected by external fuses (see Fig. 3 for rating) to prevent damage to unit in case of a short or overload. FIGURE 3. SCANNER WIRING 65UV5-1004 SCANNER SCANNER MUST BE CONNECTED TO GROUND ELECTRONIC CIRCUIT FLAME RELAY SAFETY RELAY SAFETY GROUND SCREW 24VDC INPUT YELLOW RED RED BLACK BLACK (0v) 24VDC SUPPLY (+v) 1 AMP SLOW BLOW * 3 AMP SLOW BLOW * 4 to 20 ma ANALOG OUT TO BURNER MANAGEMENT SYSTEM *EXTERNAL FUSES FIGURE 4. WIRING OF SIMPLICITY MODEL 65UV5-1004 CEX SCANNERS TERMINAL FUNCTION INTERNAL FACTORY WIRE COLOR 1 FLAME RELAY BLACK 2 FLAME RELAY BLACK 3 24 VOLT RED 4 0 VOLT RED 5 4 to 20mA YELLOW INTERNAL SAFETY GROUND SCREW BLK BLK RED RED Y 1 2 3 4 5 (KEYPAD END OF SCANNER) INTERNAL SCANNER ASSEMBLY 60-2759-4 INTERNAL FACTORY WIRING SELF-CHECK SHUTTER OPERATION The 65UV5 self-check shutter mechanism is a powered-open, powered-closed device (no return spring). The open/closed shutter period is variable and controlled by the scanner s microprocessor. Upon initial 24 vdc power application, the shutter will close and open once to verify proper operation. The shutter will then remain open until a UV flame source is present and the internal flame relay (RF) is energized. When the flame relay (RF) is energized, the shutter will be driven closed once every 13.5 seconds. The amount of time the shutter will remain closed is determined by the scanner s microprocessor and is dependent upon the UV tube s response. The amount of time closed can vary between 50 ms and 300 ms. In the event of a self-check failure the flame relay will de-energize. 4

INDICATION LEDs The 65UV5 contains a color coded internal LED that indicates flame status and alarm condition per the following table. Table 1: LED STATUS CONDITION GREEN OFF NO FLAME DETECTED OFF RAPID FLASHING RATE MARGINAL FLAME SIGNAL ON SLOW FLASHING RATE NORMAL FLAME SIGNAL STEADY ON HIGH FLAME SIGNAL ON RED OFF NORMAL ON FLASHING *SELF-CHECK FAILURE (observe shutter position) OFF ON MICROPROCESSOR ERROR OFF FLAME RELAY (RF) STATUS OPEN *SHUTTER POSITION Important Note: Removing the power will reset the LED and shutter diagnostic indication. ON SHUTTER FAILURE CLOSED UV TUBE FAILURE 5

FIREYE 133-683 3 Manchester Road JUNE 28, 2006 Derry, New Hampshire 03038 USA www.fireye.com 6