AE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6



Similar documents
Application Engineering

Why and How we Use Capacity Control

Compressors, Chillers & Condensers

*.ppt 11/2/ :48 PM 1

Application Feature Valve Nominal Liquid Capacity R-22 (in tons)*

Solenoid Valves and Their Importance in Refrigeration Systems. October 2007

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

LOBOY 16 AIR CONDITIONERS

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Oil and Coolant Circulating Heating System. Model - OCSM

12V Portable Diaphragm Compressor Operating and Maintenance Instructions

ECOCIAT. Domestic hot water heat recovery unit

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.


R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

Scroll Compressors for Air Conditioning ZR18K* to ZR380K*, ZP24K* to ZP485K*

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL

Technical Information

, User s Manual

ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES

Portable Evaporative Air Cooler. OWNER S MANUAL Read and save these instructions before use. Model: CL30XC

10ACC WARNING WARNING. Service Literature 10ACC SERIES UNITS

MAC-120HE-01 Air-Cooled Chiller

COMPRESSOR REPLACEMENT PROCEDURE

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

Application Engineering

Dehumidifier Users manual. For Models: DH45S DH65S

Your safety and the safety of others are very important.

HENRY TECHNOLOGIES - OIL LEVEL REGULATORS (CONVENTIONAL)

PORTABLE AIR CONDITIONER

A/C refrigerant system, overview

USER S MANUAL HSC-24A

Application Engineering

Failure to comply with the following cautions and warnings could cause equipment damage and personal injury.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

DESIGN STANDARDS SECTION

Owners Manual. Refrigerated Air Dryer. HX75 thru HX2400

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

PANASONIC TROUBLE SHOOTING GUIDE

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Scroll Digital Compressors for Refrigeration ZBD21K* to ZBD76K* & ZFD18KVE

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

SSB*H4. Service Literature. SSB*H4 Commercial Air Conditioner

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

Occupational Health Program Safety Training Series. Lockout/Tagout Safety Awareness Training

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Why Daikin? 2015 Houston, Texas USA

WHOLESALE DIRECT INC WEST 65TH STREET

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

Engineering Specifications

Low Profile Unit Cooler

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Ceiling Mount Air Handler Manual

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split

AIR-CONDITIONER SPLIT TYPE

Rotary Screw Compressor. MSM MINI 2, ,5 kw

HEAT SIPHON ANSWERBOOK

HYDROSTATIC TEST PUMPS

STC 2P050 Series Solenoid Valves NSF Compliant Materials, 2 Way, Direct Acting

D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction

Owners Manual 2009 PRICE LIST DRYMAXTM. Compressed Air Treatment Products. Refrigerated Air Dryers

How To Size A Stenner Pump

Air Conditioning 101. STN Presentation AC101

Miami Heat Pump HP Series Installation Guide

XE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY

STC 3S A Series Solenoid Valves

PC1131 Electric Air Compressor

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

Installation Instructions for Alarm Module Kit A043F059

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Installation Instructions for Solar Pumps USER MANUAL FOR SPS, SPC, SPSC SPQB, SPGJ SERIES SOLAR PUMPS AND PUMP CONTROLLERS

SERVICE MANUAL FOR 6700, 7000, 8000 & 9000 SERIES AIR CONDITIONERS (MECHANICAL CONTROLS ONLY)

Maxi Pressurisation Units (Maxi, Maxi Plus & HP)

COMPRESSED AIR DRYER

DEALER SERVICE BULLETIN

AutoRanging Digital MultiMeter

Lockout - Tagout. Control of Hazardous Energy OSHA Standard

Zenith Controls ISO R-1000C 5/99

SMM. Installation Operation Maintenance

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

Technical Specification. Generating Set with Waukesha engine burning natural gas

MDT5N25 & MTD5N40 SERVICE PARTS

Transcription:

AE21-1319 R6 December 2013 Digital Capacity Control for Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons...3 Safety Statements...3 Introduction Theory of Operation...4 Nomenclature...4 Digital Performance...4 Operating Envelopes...4 Restricted Operating Envelope...4 7.5 to 15 HP Digital Scroll Restrictions...4 Control...5 Recommended Application Settings...5 Control Requirements With Control Module...5 Control Requirements Without Control Module...5 Inputs...5 Outputs...5 Oil Management...5 Solenoid Valve...5 Solenoid Valve Mounting...6 Thermistor...6 Discharge Line Check Valve...6 Multiple Compressor Application...6 Scroll Reference Material...6 Figures and Tables Digital Solenoid Valve and Coil Kits...7 Example of Digital Compressor Selection...7 Operating Envelopes...8 20 Second Operating Cycle...8 Injection Assembly Diagram with Sweat Connections...9 Injection Assembly Diagram with Rotalock Connections...10 Unloaded Operation Solenoid Valve Energized (Open)...11 Loaded Operation Solenoid Valve De-Energized (Closed)...11 Typical Modulated Power Reduction...12 1

Safety Instructions Safety Instructions Copeland Scroll compressors are manufactured according to the latest U.S. and European Safety Standards. Standards. Particular emphasis Particular has emphasis been placed has been on the placed user's on safety. the user's Safey safety. icons Safey are explained icons are below explained and safety below and instructions safety instructions applicable to applicable the products to the in products this bulletin this are bulletin grouped are on grouped page 3. on These Page instructions 3. These should instructions be retained throughout should be retained the lifetime throughout of the compressor. the lifetime You of the are compessor. strongly advised You are strongly to follow advised these safety to instructions. follow these safety instructions. Safety Icon Explanation DANGER WARNING CAUTION NOTICE CAUTION DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE is used to address practices not related to personal injury. CAUTION, without the safety alert symbol, is used to address practices not related to personal injury. 2

Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons WARNING ELECTRICAL SHOCK HAZARD Disconnect and lock out power before servicing. Discharge all capacitors before servicing. Use compressor with grounded system only. Molded electrical plug must be used when required. Refer to original equipment wiring diagrams. Failure to follow these warnings could result in serious personal injury. WARNING PRESSURIZED SYSTEM HAZARD System contains refrigerant and oil under pressure. Remove refrigerant from both the high and low compressor side before removing compressor. Never install a system and leave it unattended when it has no charge, a holding charge, or with the service valves closed without electrically locking out the system. Use only approved refrigerants and refrigeration oils. Personal safety equipment must be used. Failure to follow these warnings could result in serious personal injury. WARNING BURN HAZARD Do not touch the compressor until it has cooled down. Ensure that materials and wiring do not touch high temperature areas of the compressor. Use caution when brazing system components. Personal safety equipment must be used. Failure to follow these warnings could result in serious personal injury or property damage. CAUTION COMPRESSOR HANDLING Use the appropriate lifting devices to move compressors. Personal safety equipment must be used. Failure to follow these warnings could result in personal injury or property damage. Safety Statements Refrigerant compressors must be employed only for their intended use. install, commission and maintain this equipment. All valid standards and codes for installing, servicing, and maintaining electrical and refrigeration equipment must be observed. 3

Introduction On refrigeration applications where the load may vary over a wide range, some means of capacity control is often desirable for optimum system performance and control. In addition, compressor capacity modulation can reduce power and energy consumption, provide better dehumidification, reduce compressor cycling, and decrease the starting electrical load. In order to achieve the above objectives, Emerson Climate Technologies has developed the Copeland Scroll Digital compressors, a unique and highly efficient method for modulating scroll compressors. Digital technology will permit efficient modulation of Copeland Scroll compressors for high, medium, and low temperature applications. Digital technology assures smooth, vibration free operation by axially unloading the compliant scrolls. Theory of Operation Digital capacity control is achieved by axially separating the scroll members. During the time the members are separated, there is no gas compression and approximately 10% power usage. By varying the amount of time the members are separated, capacity control between 10 and 100% can be achieved. The separation is achieved by bypassing a controlled amount of discharge gas to the suction side through a solenoid valve. The lowering of the pressure in the modulating chamber allows the scrolls to separate and as a result no pumping action takes place. The position of the scroll elements during the loaded and unloaded modes of operation are shown in Figures 6 and 7 at the end of this bulletin. Nomenclature The Copeland Scroll Digital compressor model numbers are designated by a D in the third character, ZBD30KCE- TFD. Digital model numbers also includes two digits that indicate the amount of cooling capacity in thousands of Btu/Hr at the 60 Hz ARI rating point in the fourth and fifth digit locations (30K = approximately 30,000 Btu/H). For actual compressor performance information please visit Detailed Product Information at emersonclimate. com. Please refer to the product literature for model number details. The low temperature digital models also offer economizer operation. This is designated by a V after the K in the model number ZFD18KVE-TFD. The requirements for economizer operation are covered in AE4-1327. Digital Performance The power requirements vary as the load varies. The power required as a percent of load is shown in Figure 8. For additional information on this product, please refer to the "Detailed Product Information" at emersonclimate. com. Operating Envelopes The operating envelopes for Copeland Scroll Digital compressors are very similar to standard scroll compressor envelopes. (See Figures 1 and 2 at the end of this bulletin.) However, a 75psi (5.1bar) differential between discharge and suction must be maintained. Therefore, the lower right hand corner of the digital envelope is somewhat restricted. Restricted Operating Envelope The published operating envelopes for the Digital compressors must be strictly followed. Please note in Figure 1, the dotted line on the lower right portion of envelope. The Copeland Scroll Digital compressor will not operate properly below the dotted line. The minimum differential pressure required across the piston is 75 psi (5.1bar). If this is not achieved, then measures such as raising the minimum condensing pressure may have to be considered to increase the differential. *Note that when running an extended unload cycle time at or near the lower right hand corner of the envelope that the condition will actually go beyond the dotted line during the off cycle as the suction pressure rises and the discharge pressure drops 7.5 to 15 HP Digital Scroll Restrictions When operating the 7.5 to 15 HP digital scroll compressors (ZBD**KC, ZRD**KC, ZPD**KC) with R-410A or R-407C in a refrigeration application (i.e. air dryer/ process chillers), Emerson recommends limiting the Digital Unloading at 30% to provide adequate motor cooling within the entire operating envelope of the compressors listed. 20% and even 10% digital loads can be maintained on all models if adequate return gas volume and temperature are available to provide adequate motor cooling to the compressor to prevent nuisance trips on the motors thermal protection circuit. System testing may be required to determine the digital limitation in various applications. Note: The 7.5 hp ZBD57 is not restricted. 4

Control Capacity modulation is achieved by energizing and de-energizing the solenoid valve. When the solenoid valve is de-energized, the compressor capacity is 100%. When the solenoid valve is energized, the compressor capacity is zero. Therefore, the capacity achieved is the time average capacity, which is a variable from 10 100%. Example: If you have a 20-second cycle and the solenoid is de-energized for 16-seconds, and then energized for 4-seconds, the resulting capacity will be 80%, see Figure 3. Caution: To minimize valve cycling and maximize system responsiveness, cycle times between 10 and 30 seconds should be used. Cycle time is defined as energized plus de-energized time. The minimum deenergized (loaded) time is 10% of the cycle time. This is required to provide gas flow for motor cooling. There is no maximum de-energized time. Recommended Application Settings for the Modulation on Copeland Scroll Digital Compressors The pulse width modulation cycle time recommended is 20 seconds; for other values, check with your Application Engineer. The minimum load and unload times will be limited to 2 seconds. These described load and unload times will give the compressor an operating range during a 20 second cycle from 10% load up to 90% load. The compressor can also operate at a 100% load for the full modulation sequence. The 2 seconds minimum times will give the unloader piston assembly time to both load and unload the scroll sets fully. If the load reduces past the 10% load the compressor motor should be shut down. Restarting of the compressor will be governed by the capacity rising above the 10% or more based on a modulation time of 20 seconds, and by the motor starting logic. The system design should follow the required and recommended guidelines as detailed in the various Application Engineering Bulletins, which can be found on the website at emersonclimate.com. The compressor motor will only be restarted after an appropriate time delay. The time delay will begin at the most recent moment that the motor has stopped. The amount of delay will not be adjustable. The motor will have a start delay of 2 minutes. This will prevent a short cycling effect of more than 30 starts per hour. Start up and Shut Down To improve the starting characteristics of the scroll compressor, the Copeland Digital Compressor Controller (see AE8-1328) delays loading the compressor for.1 seconds at start up. Likewise, to eliminate the reverse rotation sound at shut down the compressor is unloaded 0.5 seconds before shut down. This should be taken into consideration when implementing a digital control sequence that does not include the Copeland Digital Compressor Controller. Control Requirements With Control Module Refer to AE8-1328 for the digital control module that can be used with this compressor. Control Requirements Without Control Module In order to control the digital modulation, two inputs and one output are required. Inputs 1. A discharge temperature thermistor is required on all compressors. The cut out temperature is to be set at 280 F (138 C). 2. Control can be done by any normal control parameter (i.e. suction pressure, air temperature, humidity, etc.) Outputs There must be a 15 watt output to the solenoid valve at the appropriate chosen solenoid voltage. Oil Management In a Copeland Scroll Digital compressor, oil leaves the compressor only during the loaded state when compression is taking place. During this loaded state, since the compressor is operating at full capacity, the gas and oil flow velocities are the same for a digital and fixed capacity compressor. Hence, no special oil management requirements exist for a Copeland Scroll Digital compressor. Using a 20lb check valve to deliver low pressure oil back to the digital compressor is not recommended. During digital operation with long unloaded cycles, the pressure in the crankcase will rise and the 20lb pressure differential for oil feed may not feed adequate oil. A high pressure oil feed is recommended for Copeland Scroll Digital compressors. Of course, when the compressor is in an unloaded state, no refrigerant or oil is passed through. The oil therefore travels through the system in a pulsing mode and returns to the compressor. Refer to AE17-1320 for additional details on oil management with multiple compressor applications. Solenoid Valve Due to the high life cycle requirements in a hot gas 5

environment, a special valve has been developed. A screen is provided in the digital solenoid valve to prevent debris from damaging valve operation. Due to reliability requirements, only Emerson approved solenoid valves may be used for this application. All compressor warranties are null and void if the Emerson approved valve is not used. For valve kit part numbers refer to Online Product Information at emersonclimate.com. Solenoid Valve Mounting While mounting the solenoid valve on the compressor, there are several different ways to support the weight of the valve coil to assist in eliminating the vibrations and resonance frequencies which might cause premature tubing fractures. See Table 1 for solenoid valve mounting kits available through Emerson Climate Technologies, Inc. Some recommendations to use when installing the valve are as follows; 1. The valve operation is directional. 2. Solenoid valve must be mounted within 15 of vertical. Horizontal mounting is not permitted. 3. Mount the solenoid valve to the suction line. The tube from the solenoid to the suction should be as short as possible, less then 3 (76mm). 4. Mount the solenoid valve as close as possible to the compressor. 5. Do not restrict the inlet or outlet line size of the solenoid. Use 3/8 (9.5mm) soft drawn copper. 6. From the top cap to the solenoid a series of bends and or shock loops are required to dampen vibrations and resonance frequencies the assemblies might see during operation and start up. See Figures 4 and 5. 7. Solenoid tubing mounting kits, including solenoid valves are available from Emerson Climate Technologies, Inc. Discharge Line Check Valve In multiple compressor applications an external check valve is required in the discharge line of the Digital compressor. A recommended check valve is: Manufacturer: Emerson Flow Controls Description: ACK-8 Part No.: 064987 Multiple Compressor Application To ensure smooth and continuous modulation, selection of the digital and nondigital compressor capacities can be made according to the following rule. Rule: for optimum suction pressure control, the following guideline is recommended in the selection of digital scroll and fixed compressors, per suction header: - D > F1 - F2 < D + F1 - F3 < D + F1 + F2 - - FN < D + F1 + F2 +.+ FN-1 In the above equations, D is digital scroll capacity or horse power F1, FN are fixed speed compressor capacity or horse power Digital is recommended to be the lead compressor See Table 2 for a selection example by Btu/hr. Scroll Reference Material For general scroll compressor guidelines, refer to the following Application Engineering Bulletins: AE4-1317 AE4-1318 ZBKC/ZBKCE Refrigeration Scroll ZBKC/ZBKCE Refrigeration Scroll 7-15HP AE17-1320 Oil Management in Scroll Compressors in Parallel Applications AE4-1327 Economized Vapor Injection (EVI) Compressors Thermistor The discharge thermistor must be connected to the Copeland Digital Compressor Controller, see AE8-1328. The thermistor kit number is 998-0166-00. 6

Kit Number Identification Details 998-0073-00 Tubing kit with solenoid Sweat 998-0066-00 Table 1 Digital Solenoid Valve and Coil Kits Tubing kit with solenoid / ZBD30, ZBD45,ZBD57, ZFD13, ZFD18, ZFD25 Rotalock 998-0066-09 Tubing kit with solenoid / ZBD21, ZBD29 Rotalock 923-0058-08 Solenoid coil 110 volts 923-0058-09 Solenoid coil 220 volts 923-0058-00 Solenoid coil 24 volts Table 2 Example of Digital Compressor Selection Digital Fixed Fixed Fixed Fixed Cooling Demand ZBD45 ZB30 ZB30 ZB30 ZB30 System Output Capacity @ +10/120 3630 to 36300 24100 24100 24100 24100 Load 0 OFF OFF OFF OFF OFF 0 Load 3,630 to 36,300 ON OFF OFF OFF OFF 3,630 to 36,300 Load 36,301 to 60,400 ON ON OFF OFF OFF 36,301 to 60,400 Load 60,401 to 84,500 ON ON ON OFF OFF 60,401 to 84,500 Load 84,501 to 108,600 ON ON ON ON OFF 84,501 to 108,600 Load 108,601 to 132,700 ON ON ON ON ON 108,601 to 132,700 7

150 ZBD R-404A MED TEMP. 150 ZFD R-404A MED/ LOW TEMP. w/ economizer 140 130 120 110 100 60 49 140 60 130 120 49 110 100 90 32 90 32 80 80 70 60 21 70 21 60 50 C -23-9 0 13 50 C -23-9 0 13-40 -30-20 -10 0 10 20 30 40 50 60-40 -30-20 -10 0 10 20 30 40 50 60 Figure 1 ZBD R-404A Medium Temp. Figure 2 ZFD R-404A Med/Low Temp. w/economizer 20 Second Operating Cycle 90% Load 85% load 80% load 75% load 70% load 65% Load 60% Load 55% Load 50% Load 45% Load Scrolls Loaded Scrolls Unloaded 40% Load 35% Load 30% Load 25% Load 20% Load 15% Load 10% load 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Seconds Figure 3 20 Second Operating Cycle 8

Figure 4 Injection Assembly Diagram with Sweat Connections 9

6 SHIPPING PLUG MUST BE REMOVED WITH 3MM ALLEN WRENCH PRIOR TO ASSEMBLY Figure 5 Injection Assembly Diagram with Rotalock Connections 10

Gas Flow Axial Separation Figure 6 Unloaded Operation Solenoid Valve Energized (open) Gas Flow to System Figure 7 Loaded Operation Solenoid Valve De-energized (closed) 11

100% 90% 80% 70% Percentage of Full Power 60% 50% 40% 30% 20% 10% 0% 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% Percentage of Full Capacity 100% Figure 8 Typical Modulated Power Reduction The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies, Inc. and/or its affiliates (collectively "Emerson"), as applicable, reserve the right to modify the design or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson product remains solely with the purchaser or end user. 12