CB29M Bulletin #490071 February 1996



Similar documents
C26 Bulletin # November 1997 Supersedes January 1997 (Coil/Furnace Match Up Charts)

Commercial Gas Furnace Upflow

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF (10/2011) LF24 Standard

INDOOR COILS. RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

AIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

Cased/Uncased Coils For Gas And Oil Furnaces

INDOOR COILS. RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INDOOR COILS. RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INDOOR COILS. RCFM- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

Low Profile Unit Cooler

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Cooling/Heat Pump Convertible Air Handlers

ELITE SERIES Up Flow / Horizontal Precision Speed Blower

Local Dealer:

Installation Manual CLIFC Fan & Coil Variable Speed

GCS16 GCS20 WARNING CAUTION

Cooling Capacity CFM in. w.c. (125 Pa)

DESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System

WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin / March 2013

G26 Corp L11 Revised LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

ARMSTRONG AIR HEAT PUMPS

Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO

SECTION HEAT PUMPS

ECOCIAT. Domestic hot water heat recovery unit

SPLIT-SYSTEM CONDENSING UNITS SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION FEATURES

INSTALLATION INSTRUCTIONS

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

INSTALLATION INSTRUCTIONS

Fan Dia. Motor Amps Connections Approx. 115 V 10 O TD 15 O TD H W D CFM (Quantity) 115 V 230 V Inlet Suction Drain Ship. Wt. Lbs.

TWE+TTA TWE+TWA T.R.

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

GCS

LH and GH/GL Series UNIT COOLERS. Technical Bulletin: LHGH_001_ Products that provide lasting solutions.

catalog Single Package Vertical Air Conditioners and Heat Pumps

MAC-120HE-01 Air-Cooled Chiller

Split System Heat Pump Product Data

PRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS

SECTION AIR CONDITIONING UNIT

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES

Installer s Guide 18-AH39D1-13

F9MXE. Product Specifications

Glossary of Heating, Ventilation and Air Conditioning Terms

E2 Series Electric Furnaces

Split System Cooling Product Data

XV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE

Greensource iseries HY Model Unitary Air Handler/Fan Coil

Chilled Water Fan Coil Unit. Model:HFCA Size 03~14

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Elegant ECM. ELEGANT ECM air conditioners allow. The range is made up of 12 models: Ceiling Air Conditioner

The prevailing force in the field. AIR CONDITIONING SOLUTIONS FOR THE PULP AND PAPER INDUSTRY

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

HP switch LP switch Discharge thermo Comp. Surface thermo

A. Section includes air conditioning units, controls and control panels.

Split System Heat Pump Product Data

Cooling Capacity CFM in. w.c. (125 Pa)

LSA LSE, LSR & LST LPA LPE, LPG & LPH LAA LAE, LAG & LAH COMMERCIAL WALK-IN COOLERS AND FREEZERS

Defining Quality. Building Comfort. Heating and Cooling Coils

Element D Services Heating, Ventilating, and Air Conditioning


1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None

G9MXE. Product Specifications

How To Install An Evaporator Coil

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

Cooling Capacity CFM in. w.c. (125 Pa)

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water

Technical data. Danfoss DHP-A

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

Contents and Nomenclature

Installation Instructions

SPACE COOLERS. P.O. Box 956 Paoli, PA (800) FAX (610) The leader in packaged Space Cooling.

MODEL IX -WAC/HP AIR CONDITIONERS & HEAT PUMPS FOR HIGHLY CORROSIVE & HAZARDOUS AREAS

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

Test Code: 8297 / Version 1

Split System Cooling Product Data

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

HEAVY DUTY STORAGE GAS

CA SERIES. Available in sizes from 3/4 through 1-1/4 tons the CA Series offers a wide range of features such as:

WINDOW ROOM AIR CONDITIONER

Commercial Electric Water Heater

"EC" Series Electric Humidifier

XV 95. Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace PUB. NO.

AIR-COOLED CONDENSERS Technical Guide

CAB LCAB HACAB RMP/AMP CC CY/YY RVP CUSTOM CU

RHF High Efficiency Remote Heat Pumps and Matching Blower Coils

A. Air-Conditioning and Refrigeration Institute: 1. ARI Commercial and Industrial Air Filter Equipment.

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

Product Data. FV4C Performancet Series Fan Coil Sizes 002 Thru 006 PREMIUM ENVIRONMENTALLY SOUND FAN COIL

Light Duty Commercial Electric Water Heater

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

RPV - RP - RA air handling units

26 AND 27 SLEEVES. IDEAL for NEW CONSTRUCTION, RETROFITS and REMODELS.

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA

SECTION MORTUARY REFRIGERATORS

Single Package Vertical Air Conditioners. Vert-I-Pak

Transcription:

ENGINEERING DT MTCHED REMOTE SYSTEMS 50hz S LOWER UNITS 50hz ELITE 10 MULTI POSITION LOWER UNITS 20 100 to 49 00 tuh (5.9 to 14.4 kw) Cooling Capacity 19 700 to 49 100 tuh (5.8 to 14.4 kw) Heat Pump Heating Capacity 2.5 to 0.0 kw Optional Electric Heat pplications Multi-position (up-flow, down-flow or horizontal) applications. pplicable to expansion valve systems in cooling applications and check and expansion valve systems in heat pump applications. Wide range check and expansion valve factory installed. See Condensing Unit bulletins in section Cooling Units Condensing Units for cooling capacities. See Heat Pump Outdoor Unit ulletins in section Heat Pumps Matched Remote Systems for cooling and heating capacities. Optional field installed electric heaters available in several sizes for additive heating capacity. Filter furnished. Optional additive base available for models with electric heat installed in down-flow position on combustible floors. Completely Tested Tested with matching condensing and heat pump units in the Lennox Research Laboratory environmental test room which meets merican Society of Heating, Refrigeration and ir-conditioning Engineers (SHRE) Standard 7 requirements. Rating test conditions are those included in ir Conditioning and Refrigeration Institute (RI) Standard 210/240 test conditions while operating at rated voltages and air volumes. lower performance data according to unit tests conducted in Lennox air test chamber. lower-coil units components within are bonded for grounding to meet safety standards for servicing required by the International Electrotechnical Commission (I.E.C.). Units developed in accordance with ISO 9002 quality standards. Cabinet Constructed of heavy gauge galvanized steel. Completely insulated with thick fiberglass insulation. Pre-painted steel cabinets have mildly textured enamel finish with primer coat on unpainted side of all panels. No external screw heads on sides of cabinet for tight installations without damage to walls or woodwork. Removable panels provide complete service access. Electrical inlets provided in sides and top of cabinet. See dimension drawings for locations. Typical pplications C29M ulletin #490071 February 1996 C29M Up-flow Position (With Optional Electric Heat) C29M Horizontal Left Hand Position (With Optional Electric Heat) Horizontal Installation Up-Flow Installation With Optional Electronic ir Cleaner Down-Flow Installation NOTE Due to Lennox ongoing committent to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. 1996 Lennox Industries Inc.

FETURES Multi-Position Capability Shipped for up-flow and horizontal right hand discharge. Quickly converted to down-flow or horizontal left hand air discharge. Dual Position Drain Pans Drain pans designed for up-flow, down-flow or horizontal applications. Deep, corrosion resistant plastic drain pans have dual pipe drains. See dimension drawings. Direct Drive lower Lennox designed and built direct drive blower. Statically and dynamically balanced before installation in unit. Resiliently mounted multi-speed leadless motor with plug-in connections. Choice of blower speeds. See blower performance tables. Speed changes easily accomplished by a simple wiring change. lower slides out of cabinet for servicing. Refrigerant Line Connections Suction (vapor) and liquid lines have sweat connections. Extended outside of the cabinet for ease of connection. See dimension drawings for locations. Check and Expansion Valve Furnished Wide range valve. Chatleff style fitting. Factory installed on all models internal to cabinet. Copper Tube/Enhanced Fin Evaporator Coil Lennox designed and fabricated twin coils. ssembled in configuration. Provides extra large surface and contact area, excellent heat transfer and low air resistance for maximum efficiency. Precise circuiting for uniform refrigerant distribution. Precisely spaced ripple-edged aluminum fins fitted to durable seamless copper tubes. Fins are strengthened to resist bending and are equipped with collars that grip tubing for maximum contact area. Lanced fins provide maximum exposure of fin surface to air stream. Long life copper tubing easy to service. Rifled tubing provides superior refrigerant flow with maximum heat transfer. Flared shoulder tubing joints and silver soldering provide tight, leakproof joints. Coil thoroughly factory tested under high pressure to insure leakproof construction. Transformer and lower Cooling Relay 24 volt transformer with circuit breaker and blower cooling relay furnished as standard. Factory installed in the unit control box. Terminal strip furnished. ir Filter Tool-less access to filter area for quick and easy servicing. Disposable frame type filter furnished and factory installed in rails in cabinet. See Specifications tables for sizes. OPTIONL CCESSORIES (Must e Ordered Extra) Down-Flow dditive ase (Optional) dditive base required for models with electric heat installed in down-flow position on combustible floors. See Specifications table and dimension drawing. Side Return Unit Stand (Optional for Up-Flow Only) Raises unit 16 in. (406mm) above floor for side return air duct connection. Eliminates need for wooden platform construction. ll aluminum construction. Two adjustable frames fit all sizes. Order (45K1) for C29M-21/26 models and (45K2) for C29M-1/41 thru -65 models. C29M / Page 2 Wall Hanging racket Kit (45K0) (Optional for Up-Flow Only) llows unit to be hung on wall at any height. Consists of heavy gauge steel support brackets (one for blower coil unit, one for wall mount). Screws furnished for fastening one bracket to unit. olts for fastening one bracket to wall are field provided. dditive Electric Heat (Optional) Field install internal to unit cabinet. vailable in several kw sizes. See Electric Heat tables. Helix wound nichrome heating elements exposed directly in air stream resulting in instant heat transfer, low element temperatures and long service life. Each element equipped with accurately located limit control with fixed temperature off setting and automatic reset. Supplemental thermal cutoff limit control, provides positive protection in case of excessive temperatures. Thermal sequencer relay brings elements on and off line, in sequence and equal increments, with time delay between each. Initiates and terminates blower operation. Heating control relay(s) furnished as standard. Control box and access cover constructed of heavy gauge galvanized steel. Factory assembled with controls installed and wired. Electric heat low voltage controls plug-in to blower coil unit. Circuit reaker Models EC29-5C, -8C, -10C, -12.5C, -15C, -20C, -25C and -0C (220/240v-1ph) heaters are equipped with circuit breakers for overload and short circuit protection. Factory wired and mounted on electric heat unit. Current sensitive and temperature actuated. Manual reset. Circuit breakers qualify as disconnect means at unit in many areas, eliminate the need for field provided disconnect. Consult local electrical code in your area. Single-Point Power Source Control ox (Optional) Control ox (21H9) may be used with optional electric heat when two or three circuits (if required by code) are specified. Field installs external to the unit cabinet on either side or top. Constructed of heavy gauge steel, baked enamel finish, prepunched mounting holes, electrical inlet knockouts, and terminal strip. Removeable cover provides easy access. 7 x 7 x 4 in. deep (178 x 178 x 102mm), shipping weight is 5 lbs. (2 kg.). CC1 EfficiencyPlus Humidity Control (Optional) Electronic control (5H00) installs next to room thermostat, allows selection of desired indoor humidity level during cooling mode. During heating season control is inoperable. CC1 controls indoor humidity by changing indoor blower speed and compressor speed (two speed outdoor units) Humidity level is adjusted with vertical set point slide on scale of 40% thru 60%, 50% recommended setting. Five indicator LED s in a bar graph configuration (MIN MX) indicate difference in actual relative humidity and set point, indicates demand imposed on system equipment, more lights on, the longer equipment will operate to obtain desired humidity level. No lights on, humidity is at or below set point. Requires ER1 lower Relay Kit. ER1 lower Relay Kit (75H90) (Optional) llows CC1 to be used with C29M blower coil units.

SPECIFICTIONS Model Number C29M-21/26 C29M-1/41 C29M-51 C29M-65 Net face area ft. 2 (m 2 ).11 (0.29) 4.44 (0.41) 5.0 (0.46) 5.0 (0.46) Tube outside diameter in. (mm) /8 (9.5) /8 (9.5) /8 (9.5) /8 (9.5) Evaporator Number of rows 2 2 Coil Fins per inch (fins per m) 14 (551) 14 (551) 12 (472) 12 (472) Suction line connection in. (mm) sweat 7/8 (22.2) 1-1/8 (28) Liquid line connection in. (mm) sweat /8 (9.5) /8 (9.5) /8 (9.5) /8 (9.5) Condensate drain connection (female pipe thread) in. (mm) (2) (2) (2) (2) Nominal cooling capacity tons (kw) Refrigerant lower wheel nominal diameter x width in. (mm) 1.5 2 (5. 7.0) 10 x 7 (254 x 178) 2.5 (8.8 10.6) 10 x 8 (254 x 20) HCFC-22 4 (14.1) 5 (17.6) 11-1/2 x 9 (292 x 229) 11-1/2 x 9 (292 x 229) Nominal blower motor output hp (W) 1/ (249) 1/ (249) 1/2 (7) 1 (746) Number and size of filters Electrical characteristics in. (1) 15 x 20 x 1 (1) 20 x 20 x 1 mm (1) 81 x 508 x 25 (1) 508 x 508 x 25 220/240 50 hertz 1 phase Shipping weight lbs. (kg) 1 package 121 (55) 156 (71) 181 (8) 182 (8) Optional ccessories (Must e Ordered Extra) Side Return Unit Stand Catalog number 45K1 45K2 (Up-Flow Only) Shipping weight lbs. (kg) 5 (2) 6 () Wall Hanging racket Kit Shipping weight lbs. (kg) 45K0 (1) (Up-Flow Only) Down-Flow Combustible ase Shipping weight lbs. (kg) 4J72 8 (4) 4J7 8 (4) Disposable frame type filter. LOWER DT C29M-21/26 LOWER PERFORMNCE External Static ir Volume and Motor Watts at Specific lower Taps Pressure High Medium Low in. w.g. E t l St ti Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts.00 0 1175 555 425 970 460 5 715 40 260.05 10 1160 545 420 960 455 5 710 5 255.10 25 1140 540 415 945 445 0 695 0 250.15 5 1105 520 400 910 40 20 675 15 245.20 50 1090 515 95 895 420 15 660 10 240.25 60 1070 505 90 865 405 10 65 00 20.0 75 1040 490 75 850 400 05 625 295 225.40 100 970 455 50 785 70 285 580 275 210.50 125 910 40 0 70 45 265 55 255 190 NOTE ll air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. C29M-1/41 LOWER PERFORMNCE External Static ir Volume and Motor Watts at Specific lower Taps Pressure High Medium Low in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts.00 0 1460 690 50 1245 585 450 950 450 45.05 10 1440 680 520 1220 575 440 90 440 5.10 25 1410 665 510 1190 560 425 905 40 25.15 5 175 650 495 1155 545 415 880 415 15.20 50 140 60 485 1120 50 405 850 400 05.25 60 1295 610 470 1075 510 90 815 85 295.0 75 1245 585 455 100 485 80 780 70 285.40 100 1125 50 40 925 45 55 700 0 265.50 125 985 465 400 805 80 25 605 285 245.60 150 825 90 70 665 15 00 500 25 225 NOTE ll air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. C29M / Page

LOWER DT C29M-51 LOWER PERFORMNCE External Static ir Volume and Motor Watts at Specific lower Taps Pressure High Medium Low in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts.00 0 1920 905 770 1515 715 585 125 580 450.05 10 1905 900 760 1505 710 580 1215 575 445.10 25 1855 875 70 1460 690 560 1195 565 45.15 5 180 865 720 145 675 550 1170 555 425.20 50 1775 840 695 1410 665 545 1150 540 420.25 60 1725 815 675 165 645 525 1105 520 400.0 75 1675 790 655 140 65 515 1080 510 95.40 100 1570 740 625 1250 590 480 1015 480 70.50 125 1465 690 595 1155 545 445 880 415 20.60 150 110 615 550 1015 480 90 745 50 275.70 175 1125 50 485 825 90 20 565 265 205 NOTE ll air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. C29M-65 LOWER PERFORMNCE External Static ir Volume and Motor Watts at Specific lower Taps Pressure High Medium Low in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts.00 0 2295 1085 1405 2070 975 1200 185 865 975.05 10 2280 1075 1400 2050 970 1190 1820 860 975.10 25 2260 1065 190 200 960 1180 1800 850 970.15 5 2240 1055 185 2010 950 1170 1780 840 965.20 50 2215 1045 175 1990 940 1160 1760 80 960.25 60 2190 105 165 1965 925 1150 1745 825 955.0 75 2170 1025 160 195 915 1140 1725 815 950.40 100 2125 1005 145 1895 895 1125 1680 790 940.50 125 2075 980 10 1845 870 1105 1640 775 90.60 150 2025 955 115 1795 845 1090 1595 750 920.70 175 1980 95 100 1745 825 1080 1545 70 905 NOTE ll air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. ELECTRIC HET DT C29M-21/26 lower Coil Electric Heat kw, Model Number Model Number & Shipping Weight Number of Elements (Steps) Volts Heating Capacity Input (1 phase) kw tuh 2.5 kw EC29-2.5 (28K0) 220 2.1 7 200 1 20 2. 7 800 240 2.5 8 500 C29M-21/2621/26 5 kw 8 kw EC29-5 (28K1) 220 4.2 14 00 EC29-5C 1 20 4.6 15 700 (28K2) 240 5.0 17 100 EC29-8 220 6.7 22 900 (28K) EC29-8C 2 20 7. 25 100 (28K4) 5 lbs. (2 kg) 240 8.0 27 00 EC29-10 220 8.4 28 700 10 kw (28K5) EC29-10C 2 20 9.2 1 400 (28K6) 5 lbs. (2 kg) 240 10.0 4 100 *Refer to local codes to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167 F (75 C). C29M / Page 4

ELECTRIC HET DT C29M-1/41, C29M-51 ND C29M-65 lower Coil Model Number Electric Heat kw, Model Number & Shipping Weight Number of Elements (Steps) Volts Heating Capacity Input (1 phase) kw tuh 5 kw EC29-5 (28K1) 220 4.2 14 00 EC29-5C (28K2) 1 20 4.6 15 700 4lb lbs. (2k kg) 240 5.0 17 100 8 kw EC29-8 (28K) 220 6.7 22 900 EC29-8C (28K4) 2 20 7. 25 100 5 lbs. (2 kg) 240 8.0 27 00 C29M-1/41 EC29-10 (28K5) 220 8.4 28 700 10 kw EC29-10C (28K6) 2 20 9.2 1 400 5 lbs. (2 kg) 240 10.0 4 100 220 10.5 5 800 12.5 kw EC29-12.5C (28K7) 20 11.5 9 200 240 12.5 42 600 15 kw EC29-15C (28K8) 220 12.6 4 000 20 1.5 47 000 240 15.0 51 200 20 kw EC29-20C 20C (28K9) 14 lbs. (6 kg) 4 220 16.8 57 00 20 18.4 62 700 240 20.0 68 200 5 kw EC29-5 (28K1) 220 4.2 14 00 EC29-5C (28K2) 1 20 4.6 15 700 240 5.0 17 100 8 kw EC29-8 (28K) 220 6.7 22 900 EC29-8C (28K4) 2 20 7. 25 100 240 8.0 27 00 10 kw EC29-10 (28K5) 220 8.4 28 700 EC29-10C (28K6) 2 20 9.2 1 400 5 lbs. (2 kg) 240 10.0 4 100 C29M-51 12.5 kw EC29-12.5C (28K7) 220 10.5 5 800 20 11.5 9 200 240 12.5 42 600 15 kw EC29-15C (28K8) 220 12.6 4 000 20 1.5 47 000 240 15.0 51 200 20 kw EC29-20C 20C (28K9) 14 lbs. (6 kg) 4 220 16.8 57 00 20 18.4 62 700 240 20.0 68 200 25 kw EC29-25C 25C (28K40) 18 lbs. (8 kg) 5 220 21.0 71 700 20 2.0 78 00 240 25.0 85 00 5 kw EC29-5 (28K1) 220 4.2 14 00 EC29-5C (28K2) 1 20 4.6 15 700 240 5.0 17 100 8 kw EC29-8 (28K) 220 6.7 22 900 EC29-8C (28K4) 2 20 7. 25 100 240 8.0 27 00 10 kw EC29-10 (28K5) 220 8.4 28 700 EC29-10C (28K6) 2 20 9.2 1 400 5 lbs. (2 kg) 240 10.0 4 100 C29M-65 12.5 kw EC29-12.5C (28K7) 220 10.5 5 800 20 11.5 9 200 240 12.5 42 600 15 kw EC29-15C (28K8) 220 12.6 4 000 20 1.5 47 000 240 15.0 51 200 20 kw EC29-20C 20C (28K9) 14 lbs. (6 kg) 4 220 16.8 57 00 20 18.4 62 700 240 20.0 68 200 25 kw EC29-25C 25C (28K40) 18 lbs. (8 kg) 5 220 21.0 71 700 20 2.0 78 00 240 25.0 85 00 0 kw EC29-0C (28K41) 1 lbs. (9 kg) 5 220 25.2 86 000 20 27.5 94 000 240 0.0 102 400 *Refer to local codes to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167 F (75 C). C29M / Page 5

DIMENSIONS inches (mm) 11-1/16 (281) D VOLTGE INLETS (Top and Left Side) SUPPLY LOW VOLTGE INLETS (Top and Right Side) 1-1/8 (29) SUCTION 2 (51) 5-/8 (17) 2- (70) DETIL OF 1- (44) 4-/8 (111) C29M UP-FLOW POSITION -1/2 (89) C CONDENSTE DRINS (2) (Horizontal) CONDENSTE DRINS (2) (Up-Flow and Down-flow) Model Number C29M-21/26 C29M-1/41 C29M-51 C29M-65 inch mm inch mm inch mm 45-1/4 1149 49-1/4 1251 52-1/2 14 16-1/4 41 21-1/4 540 21-1/4 540 C 20-524 20-524 22-575 FLOW OPTIONL ELECTRIC HET (Field Installed) LOWER D 14-75 19-502 19-502 E 19 48 19 48 21 5 F 15 51 20 508 20 508 SUCTION CCESS Model Number Return ir F FRONT VIEW C29M-21/26 C29M-1/41 1 (25) C29M-51 C29M-65 Return ir E SIDE VIEW inch mm inch mm inch mm C29M DOWN-FLOW POSITION E 5.8 F RETURN 1 (25) CCESS 1-1/8 (29) SUCTION 2 (51) 5-/8 (17) 2- (70) DETIL OF 1- (44) 4-/8 (111) -1/2 (89) C CONDENSTE DRINS (2) (Horizontal) CONDENSTE DRINS (2) (Up-Flow and Down-flow) 45-1/4 1149 49-1/4 1251 52-1/2 14 16-1/4 41 21-1/4 540 21-1/4 540 C 20-524 20-524 22-575 SUCTION D 14-75 19-502 19-502 E 19 48 19 48 21 5 F 15 51 20 508 20 508 FLOW OPTIONL ELECTRIC HET (Field Installed) LOWER LOW VOLTGE (Right Side) VOLTGE (Left Side) C29M / Page 6 Supply ir D FRONT VIEW Supply ir 11-1/16 (281) SIDE VIEW

DIMENSIONS inches (mm) DETIL OF C29M HORIZONTL POSITION (RIGHT-HND DISCHRGE) 5-/8 (17) 2 (51) SUCTION 1-1/8 (29) LOWER C 5- (146) CONDENSTE DRINS (2) (Up-Flow and Down-flow) 1- (44) 1-1/2 (8) 4-/8 (111) CONDENSTE DRINS (2) (Horizontal) SUCTION OPTIONL ELECTRIC HET (Field Installed) VOLTGE INLETS (Top and Right Side) 11-1/16 (281) E F RETURN 1 (25) FLOW SUPPLY D END VIEW CCESS FRONT VIEW LOW VOLTGE INLETS (ottom and Right Side) END VIEW C29M HORIZONTL POSITION (LEFT-HND DISCHRGE) DETIL OF C LOWER 4-/8 (111) 1-1/8 (29) OPTIONL ELECTRIC HET (Field Installed) SUCTION SUCTION 2 (51) 5-/8 (17) 11-1/16 (281) LOW VOLTGE INLETS (Top and Left Side) D SUPPLY FLOW CCESS CONDENSTE DRINS (2) (Horizontal) 1 (25) E RETURN F END VIEW VOLTGE INLETS (ottom and Left Side) FRONT VIEW 1- (44) 5- (146) 1-1/2 (8) END VIEW Model C D E F Number inch mm inch mm inch mm inch mm inch mm inch mm C29M-21/26 45-1/4 1149 16-1/4 41 20-524 14-75 19 48 15 51 C29M-1/41 49-1/4 1251 21-1/4 540 20-524 19-502 19 48 20 508 C29M-51 C29M-65 52-1/2 14 21-1/4 540 22-575 19-502 21 5 20 508 C29M / Page 7

DIMENSIONS inches (mm) DOWN-FLOW COMUSTILE FLOOR SE 1- (41) LOWER UNIT 1- (41) 1- (41) 11-/8 (289) SUPPLY C29M-21/26 18-1/4 (464) C29M-1/41 thru -65 2-1/4 (591) C29M-21/26 15 (81) C29M-1/41 THRU 65 20 (508) 16 (406) 6 (152) SIDE RETURN UNIT STND (Up-Flow Only) DOWN-FLOW COMUSTILE FLOOR SE 22-1/8 (562) 1-/8 (40) Opening SIDE VIEW 2 (51) C29M-21/26 16-1/4 (41) C29M-1/41 thru -65 21-1/4 (540) DJUSTLE 20 (508) to 25 (65) LL UNITS FLOW FLOW FLOW RIGHT HND FLOW LEFT HND FLOW FLOW lower Coil Model Number in. mm in. mm C29M-21/26 45-1/4 1149 16-1/4 41 C29M-1/41 49-1/4 1251 21-1/4 540 C29M-51 C29M-65 52-1/2 14 21-1/4 540 FLOW UP-FLOW INSTLLTION CLERNCES LL MODELS DOWN-FLOW Cabinet 0 inch (0 mm) Plenum and Outlet duct on blower/coil units 1 inch (25 mm) Plenum and Warm air duct within feet (914mm) of cabinet 1 inch (25 mm) Floor *Combustible *When unit is installed in the down-flow position with electric heat on a combustible floor an optional down flow base is required. C29M / Page 8