Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V



Similar documents
Installation. Smart-UPS VT and MGE Galaxy Maintenance Bypass Panel with Power Distribution (wall-mount) kva 208 V

Unpacking, Installation, and Customization

Installation Guide Smart-UPS X External Battery Pack SMX120BP

Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U

LIEBERT VNSA Installation Sheet

Contractors Guide Central Inverter System Installation

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

Installation Guide Smart-UPS X Tower/Rack-Mount 2U 2000/2200/3000 VA

INSTALLATION INSTRUCTIONS

Triple Expansion Chassis

Uninterruptible Power Supply. 500 kva kva

RAY-MAX Integrated Solar Power Strip

Solar Inverter Sunny Boy 5000US, 6000US, 7000US

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

Smart-UPS VT kVA 400V. Site Preparation and Installation Manual

MGE TM Galaxy TM 7000

Power Management Module 2. Installation

DCF Optimized Rack System

HP UPS R1500 Generation 3

Express5800/120Ed. Rack Mount Kit Installation Procedures PN:

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

HotSwap MBP Maintenance Bypass

MEDIUM FLAT PANEL DISPLAY STATIC MOUNT MSR Series

42U/45U 28" Wide Rack Installation & Service Guide

Installation. Basic Rack Power Distribution Unit AP9559

About the BitStorm 6051 POTS Splitter

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

PowerFlex 700H and 700S AC Drives Frame 11 Main Fan Capacitor Replacement Kit

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

INSTALLATION INSTRUCTIONS for Bifold Doors (JII103)

Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

MCR1900 Media Converter 19-Slot Chassis

Upgrading a GainMaker Line Extender from a Line-Powered Source to a 120 V AC-Powered Source Installation Instructions

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

Wall-Mounting your HP computer. User Guide

PV-Inverter SunPower SPR-5000m / SPR-6000m / SPR-7000m / SPR-8000m

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

Owner s Manual Gantry Cranes

P System Cubicles. Certified for more safety

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.

APC Step-Down Transformer. User s Manual

INSTALLATION INSTRUCTIONS MULTI-MOUNT KIT Part Number: Application: Warn HP PowerPlant P/N 71800

ATS Overhead Table Shelf System INSTRUCTION MANUAL

Packaged Terminal Air Conditioner Wall Sleeve Installation

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions

Replacing the Gateway M320 Keyboard

GPS AutoSteer System Installation Manual

Owner's/Installation Manual

CoolWave r 2 Phase Control Board and Cable Replacement Kits

Lighting Controls ! WARNING RISK OF ELECTRIC SHOCK. Installation Instructions DESCRIPTION

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

AM/FM ANTENNA RELOCATION KIT

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

TOYOTA Tundra BACK-UP CAMERA SYSTEM Preparation

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

Premier & Deluxe 3-Season Room Sliding Glass Door

SB-C-CTS/10TW3 SKU# & Up Cadillac CTS/CTS-V

PS6500 Storage Arrays Rack Mount Instructions

Co-location Interconnect Power Panel (CIPP) Installation Guide

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

SERVICE GUIDE For WARN PULLZALL 120v AC &100v AC P/N &

GENUINE PARTS INSTALLATION INSTRUCTIONS

Operation Manual. Smart-UPS C. Uninterruptible Power Supply. Tower 1000/1500 VA. 120/230 Vac. su0813a

OPL BASIC. Dosing System for Professional Laundry machines. Contents

1000-LB. TRAILER JACK OWNER S MANUAL

T7079A,B Solid State Remote Temperature Controllers

Applied Electronics. Commercial Dimming System UPDATE NOTICE

UPS system for emergency lighting and smoke extraction

Parallel Redundant Uninterruptible Power Supply

HG600/HG800. Hydro-Power Unit. Installation and Operation Guide

Installation Instructions

AM/FM ANTENNA KIT (TOUR-PAK MOUNT)

SMART Board 8070i-SMP and 8070i

=============================== WARNING

INSTALLATION INSTRUCTIONS

Small Flat Panel Lift Arm FSA-1004 and KSA-1004

WINEGARD MOTORIZED SENSAR ANTENNA Models MA1055W & MA1055G MADE IN U.S.A. U.S. Patents D500,496 and 7,358,909 INSTALLATION MANUAL

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

AMERBRITE UNDERWATER WHITE LED POOL LAMP

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

5800 Temperature Sensor Cable Assembly

AC-115 Compact Networked Single Door Controller. Installation and User Manual

Step 1. Item 6. Item 1

Anthro Tablet Charging Cabinets

Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1

HMI display Installation Guide

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Installation and Assembly: Desktop Mount with Desk Clamp and Grommet for 19" - 30" LCD Screens

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions

GreenWay Solar LED Path and Trail Lighting System. Installation and Owner s Manual

TOYOTA TACOMA HANDS FREE BLU LOGIC Preparation

SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT

T7560A,B,C Digital Wall Module

2013 Wireless Video Intercom INSTALLATION GUIDE

Transcription:

Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V

Contents Safety.................................................. 1 Save these instructions................................... 1 Safety warnings.......................................... 1 Maintenance performed while the MBP is receiving input power.. 2 Introduction............................................. 3 Receiving the MBP....................................... 3 Initial inspection......................................... 3 Maintenance Bypass Panel Components..................... 4 Front view (exterior)...................................... 4 Front view (interior)....................................... 5 Site Planning............................................ 6 Environmental considerations.............................. 6 Space considerations..................................... 6 Installation Procedure.................................... 7 Overview................................................ 7 Tools required........................................... 7 Access the internal components............................ 7 Create knockouts for cable access.......................... 7 Mount the MBP to the wall................................. 9 Internal cable connections................................. 9 External cable connections............................... 10 Specifications.......................................... 13 Maintenance Bypass Panel Schematic...................... 14 i

Safety Save these instructions This manual contains important instructions that must be followed during installation, operation, and maintenance of the wall-mount version of the Smart-UPS VT, MGE Galaxy 3500 Maintenance Bypass Panel (MBP). Safety warnings Caution: All wiring must be performed by a certified electrician or an APC-trained individual who is familiar with the construction and operation of this equipment. Installation must comply with local and national codes. Warning: This product receives power from more than one AC source. Disconnect all AC sources to completely de-energize the unit before servicing. Warning: This product receives power from more than one AC source. Disconnect all AC sources to completely de-energize the unit before servicing. Warning: Ensure that the Maintenance Bypass Panel is not connected to electrical power and that all switches are in the OFF position before installing or servicing the unit. Warning: Follow all wiring instructions exactly. Failure to do so may result in permanent damage to the equipment. Warning: Avoid contact with previously installed electrical wires and other potential hazards that might be embedded in the wall chosen for installation. 1

Maintenance performed while the MBP is receiving input power APC does not recommend performing maintenance on the MBP while it is receiving input power. However, due to the critical nature of data center loads, there may be times when live maintenance must occur. If you must perform maintenance while the MBP is receiving input power, observe the following precautions to reduce the risk of electric shock: Never work alone. Perform the maintenance only if you are a certified electrician who is trained in the hazards of live electrical installation. Know the procedure for disconnecting electricity to the MBP and to the data center in the event of an emergency. Wear appropriate protective personal clothing and other body equipment. Use double-insulated tools. If double-insulated tools are not available, insulate all tools with electrical tape. Always follow local codes and site regulations when working on the MBP. 2

Introduction This manual is intended for certified electricians or APC-trained personnel installing the wall-mount version of the Smart-UPS VT, MGE Galaxy 3500 Maintenance Bypass Panel (MBP). It provides detailed electrical installation instructions and physical specifications. For additional information regarding the Smart-UPS VT, MGE Galaxy 3500 see the manuals supplied with your UPS. You can find updates to this manual by clicking on the User Manuals link on the Support page of the APC Web site (www.apc.com/support). In the list of UPS manuals, look for the latest letter revision (A, B, etc.) of the part number on the back cover of this manual. Receiving the MBP Initial inspection Follow these steps upon receipt of the Maintenance Bypass Panel: Inspect the box for any obvious signs of rough handling or external damage. Transport the box to the installation site using a dolly or a hand truck. At the installation site, open the box and remove the MBP enclosure. Use the enclosed key to open the front door and inspect the unit for any signs of internal damage. Note: The key is shipped in a plastic bag inside of the box Note any damages that you observed during the external or internal inspection and immediately report the damages to the shipping carrier. Allow their personnel to conduct an equipment inspection, if necessary. Make your damage claim as specific as possible. If the carrier conducts an inspection, be sure to obtain a copy of the inspection report for your records. Contact APC using a phone number listed on the back cover of this manual. Inform the representative of the condition of the shipment and of your damage claim with the carrier. Note: Be sure to contact the shipping carrier before contacting APC. 3

Maintenance Bypass Panel Components Front view (exterior) 10 20kVA MBP 30 40kVA MBP Door lock(s) Q1 input switch Q3 bypass switch Q2 output switch 4

Front view (interior) Q1 input switch PE studs Busbar connections Q3 bypass switch Q2 output switch UPS control terminal block Ground studs MBP mounting holes (mounting holes are also located at the top of the enclosure) 5

Site Planning Environmental considerations Ensure that the wall area you selected to install the MBP is structurally sound and able to support the size and weight of the unit. Note: See Specifications on page 13 for the size and weight specifications for your particular unit. Store or operate the MBP in a climate-controlled environment. Ensure a temperature of 0 to 40 C (32 to 104 F) and a relative humidity of 0 to 95%, non-condensing. Protect the MBP at all times from excessive moisture, construction dirt, corrosive elements, or other contaminants. Space considerations Refer to the following figure to determine the space requirements for installing the MBP. Consult local codes for any additional requirements. Ideally, install the MBP in a location close to the UPS. Minimum front clearance 914mm (36 in) Minimum floor clearance 467mm (18 in) Note: When choosing a location to mount the MBP, consider the need for easy access to all of the switches and internal components. 6

Installation Procedure Overview Warning: Prior to beginning installation of the MBP, read and understand all safety instructions provided in Safety on page 1. Tools required All internal cable connections and the Q3 to Q2 busbar connections are made at the factory prior to shipment. All external cable connections with the UPS and mains must be made on-site. External cable is not supplied with the shipment. All control wire connections between the UPS and the MBP must be made on-site. Control wires are not supplied with the shipment. The installation procedures provided in this manual require the following tools and equipment: Standard screwdriver Phillips screwdriver M8 wrench Knockout punch Drill Level Tape measure Marker Four (4) 6-mm hex-head lag bolts Four (4) flat washers Access the internal components Access the internal components of the MBP by unlocking and opening the front door, using the key provided with the shipment. Create knockouts for cable access Note: You can create knockouts for cable access either before or after you have mounted the MBP to the wall. APC recommends creating all necessary knockouts prior to mounting the MBP to the wall. Using a knockout punch, create appropriate-sized holes for the grommet in either the top or bottom plates of the MBP (depending on your wiring preference). For easier access when creating knockouts, remove either plate by using a Phillips screwdriver to detach the eight screws that secure it to the enclosure. The following illustration shows removal of the top plate. 7

Note: APC recommends running mains utility wires through the top of the enclosure and running UPS input, output, and control wiring through the bottom of the enclosure. 8

Mount the MBP to the wall Note: APC strongly recommends mounting the MBP to a minimum 20-mm thick plywood board or similar solid backing that has approximate dimensions of 660mm (26in) L 600mm (24in) W. Mount the plywood (or other backing) to the wall using appropriate hardware for the type of wall used. See Site Planning on page 6 for guidelines on choosing where to mount the unit. Measure and mark the four (4) mounting hole locations on the backing. Refer to the following table for the correct horizontal and vertical spacing between each of the mounting holes. KVA Vertical Spacing Horizontal Spacing 10-20 240mm (9.45 in) between holes 240mm (9.45 in) between holes 30-40 380mm (14.96 in) between holes 330mm (13.00 in) between holes Drill starter holes in each of the four (4) marked locations. Lift the MBP and position it against the backing, lining up each of the four (4) mounting holes with each of the four (4) drilled starter holes. Note: APC recommends that two people mount the MBP to the wall one person to lift and hold the enclosure, and a second person to secure it to the wall. Using a metric wrench, screw four (4) 6-mm hex-head lag bolts (each 25-mm long), along with four flat washers, into the enclosure s mounting holes. Tighten until rigid. Internal cable connections The MBP ships from the factory with the internal wiring between the Q1 input switch and the Q3 bypass switch, as well as the Q3 to Q2 busbar connections, completed. Prior to beginning external wiring, verify these internal connections as shown in the following illustration. 9

Busbar N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 External cable connections Route the external cables to the MBP through the knockouts that you created in either the top or bottom plate of the unit. If you did not create knockouts prior to mounting the MBP to the wall, do so at this time. See Create knockouts for cable access on page 7 for instructions. Note: The cables are colored per local code. Utility connections. Caution: Connect all cables and wires according to the labels on the switches and studs. Connect the four inputs (N, L1, L2, L3) from the mains utility to the terminals on top of the Q1 switch. Use a Phillips screwdriver and torque to 7Nm (60 in-lbs). Connect the one PE input from the mains utility to one of the PE studs located above the Q3 switch using an M6 washer, lock washer, and nut. Use an M8 wrench and torque to 27Nm (240 in-lbs). 10

From mains utility PE PE N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 UPS connections. See your Smart-UPS VT, MGE Galaxy 3500 10 40 kva Installation manual for instructions on how to connect wiring at the UPS. Caution: Connect all cables and wires according to the labels on the switches or on the terminal block, as required. Connect the four UPS inputs (N, L1, L2, L3) to the Q1 switch in the MBP. Use a Phillips or standard screwdriver, and torque to 7Nm (60in-lbs). Connect the four UPS outputs (N, L1, L2, L3) to the Q2 switch in the MBP. Use a Phillips or standard screwdriver, and torque to 7Nm (60 in-lbs). Connect the two UPS control wires to Pins 1 and 2 at the MBP control terminal block. Use a small standard screwdriver, and hand-tighten the screws. 11

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 UPS Inputs N L1 L2 L3 N L1 L2 L3 UPS Outputs Pin 1 Pin 2 UPS Control Wires For information on how to use the UPS display interface to change operational modes, see your Smart-UPS VT, MGE Galaxy 3500 10 40 kva, 400V Operation manual. 12

Specifications Electrical 10-20 kva 30-40 kva Input Nominal voltage 380/400/415V 4W + GND 380/400/415V 4W + GND Output Nominal voltage 380/400/415V 4W + GND 380/400/415V 4W + GND Wiring (only use copper conductors suitable for at least 75 C) Maximum cable size 16mm² 35mm² System output/ UPS output cable 10mm² 25mm² System input/ups input cable 10mm² 25mm² Physical Dimensions (H W D) MBP Shipping 315 305 125mm (12.4 12.0 4.9in) 442 305 175mm 460 400 125mm (18.1 15.7 4.9in) 587 400 175mm (17.4 12.0 6.9in) (23.1 15.8 6.9in) Weight MBP 7.0kg (15.4lb) 11.0kg (24.3lb) Shipping 7.7kg (17.0lb) 12.3kg (27.0lb) Environmental Operating environment Indoor use only, protect from water and conductive contaminates Temperature (operating and storage) 0 to 40 C (32 to 104 F) Humidity (operating and storage) 0 to 95%, non-condensing Pollution degree 2 Protection class IP 30 Compliance Approvals CE 13

Maintenance Bypass Panel Schematic 14

APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. www.apc.com (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. www.apc.com/support/ Global support searching APC Knowledge Base and using e-support. Contact the APC Customer Support Center by telephone or e-mail. Local, country-specific centers: go to www.apc.com/support/contact for contact information. For information on how to obtain local customer support, contact the APC representative or other distributors from whom you purchased your APC product. 2009 APC by Schneider Electric. APC, the APC logo, and TRADEMARK NAMES are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners. 990-4204D-001 *990-4204D-001* 8/2009