Development of 22-kV XLPE Cable and Joint with Reduced Insulation Thickness Having Water-Impervious Aluminum Layer



Similar documents
Development of a 500-kV DC XLPE Cable System

A Study of a MV Cable Joint

UGVCL/SP/591/11KV HT AB CABLE

CABLE ACCESSORIES kv

Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

KNOW YOUR OPTIONS: 230 KV POWER CABLES

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

EHV Cable Installation Technology for Tunnels and Ducts in Japan. S. TSUCHIYA T. IIDA Y. MORISHITA Tokyo Electric Power Company

Section kv Power Cables

Terminal Cleaning and Protection

No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint

FLEXIBLE COPPER & ALUMINIUM CONNECTIONS. Product Range 1 VGL - ALLIED CONNECTORS

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

Draka Industrial Cable GmbH

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

INTERNATIONAL STANDARD

)454, !,5-).)5- #!",% 3(%!4(3 #/.3425#4)/. ).34!,,!4)/.!.$ 02/4%#4)/. /& #!",%3!.$ /4(%2 %,%-%.43 /& /543)$% 0,!.43. )454 Recommendation,

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION

Transformer Bushings for GIS

1 FOSC cover 1 piece Protecting fiber cable splices in whole 2 FOSC bottom 1 piece Fixing reinforced core, fiber cable

Catalog May Cable Accessories < 1 kv

COATING & WRAPPING OF UNDERGROUND PIPING

R=Required by Lab S=May be subcontracted IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT COMMITTEE OF TESTING LABORATORIES

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

High Voltage Systems. Today. The history of cables

6-36kV Medium Voltage Underground Power Cables. XLPE insulated cables

EDS KV TRIPLEX CABLE

WIRE AND CABLE ENGINEERING GUIDE

PTFE Teflon Glass Fabric Grades & Material Data Sheets

CLAMPS CONNECTORS & EQUIPOTENTIAL RING

Athena is the name given to our assortment of electronic tapes. products of the very highest quality. These tapes both conduct and

WIRE AND CABLE ENGINEERING GUIDE

WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors

WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS

Cables. Accessories. For Force, Torque and Strain Sensors

Pulse Withstanding Thick Film Chip Resistor-SMDP Series. official distributor of

Discussion Group C32D: Support of transmission cables in manholes

GK Packing System Welding Instructions

1ZSC AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

08. SEK IDC CONNECTORS

WATERPROOFING OF WET ROOMS

EDITION 2012 CABLE SYSTEMS

Zero peel strength of acrylic pressure sensitive adhesive is at about 45 C (-50 F).

ADHESIVES TAPES FOR CAR S INDUSTRY All tapes can be supplied in die cuts form and more tapes available

Session Five: Modern XLPE Materials for Extruded Energy Cable Systems

SECTION HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section

Operating Instructions

Medium Voltage Terminations, 5 kv 46 kv

FAQs-Main switchboard design criteria

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

APPLICATION ORIENTED DESIGN OF CABLES

Plastic Injection Molds

KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR

White Paper. Recommendations for Installing Flash LEDs on Flex Circuits. By Shereen Lim. Abstract. What is a Flex Circuit?

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

Portable digital microprocessor thermometers with interchangeable probes

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

Cable Accessories. for Extruded Dielectric Cable 69kV - 230kV Rated. Catalog Python13

a Nexans company Catalogue 2013

EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES

Flexible Circuit Simple Design Guide

Waterproof Connectors for Outdoor Use

The original heating cable just got better

Fault location on power cables. Fault location on power cables

Premolded cable termination, indoors SOT 7.2 kv

Development of High-Speed High-Precision Cooling Plate

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C Date of issue , Updated July 1, 2011

TC50 High Precision Power Thin Film chip resistors (RoHS compliant Halogen Free) Size 1206, 0805, 0603

B EHV XLPE CABLE SYSTEMS UP TO 400 kv - MORE THAN 10 YEARS FIELD EXPERIENCE

C A B L E P R O T E C T I O N

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Test Report No. C829QPEN

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES

WR12, WR08, WR06, WR04 ±1%, ±5% Thick Film General Purpose Chip Resistors Size 1206, 0805, 0603, 0402

Tremco Fire Protection Systems Group Technical Bulletin

EH-20 20m antenna. By VE3RGW

SECTION DRY-TYPE TRANSFORMERS

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

Section 21. Telecommunication Hardware. BuyLog Catalog 21-1

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application

Long-term experiences with XLPE cable systems up to 550 kv

Completion of Submarine Cable Lines Combining Low Environmental Impact with Low Cost

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

a Nexans company Catalogue 2014

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM

Multijacketed Tubing, Single-Jacketed Tubing, and Insulated Tubing

5800 Temperature Sensor Cable Assembly

High-ohmic/high-voltage resistors

MYTHBUSTING Takes on Shielded Cabling

AORC Technical meeting 2014

MEDIUM VOLTAGE CABLES Up to and including 36 KV

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

e-mobility Special cables for electric vehicles Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies

Product Data Sheet 3M Mini-Clamp II Plug and Socket Wiremount Connectors

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

Transcription:

Development of 22-kV XLPE Cable and Joint with Reduced Insulation Thickness Having Water-Impervious Aluminum Layer by Hiroyuki Mabuchi *, Satoru Koizumi *, Haruki Nozawa *, Yoshihiro Maeda * 2, Hideo Kawahara * 3, Junji Hirano * 3 and Shigeru Fujii * 3 Electric power supply using 22-kV systems is expanding aiming at reduction of ABSTRACT electric power distribution costs through upgrading the efficiency of facilities. It was thus required to develop a cable with joint that enabled maintaining the reliability as well as suppressing the cost of electric power supply. In response to this requirement, the authors have developed a new cable having a water-impervious layer of aluminum laminated tape together with its joint, whereby the thickness of the insulating layer was reduced to 4.5 mm --including the inner semiconductive layer-- by devising a novel method of terminating the end of the outer semiconductive layer. Moreover, a cold shrinkable straight joint has been developed thus improving the working efficiency at the site. This paper reports on the structure, performance, and working efficiency of this cable and the joint.. INTRODUCTION Electric power supply using 22-kV systems is expanding aiming at reduction of electric power distribution costs through upgrading the efficiency of facilities. In response to the requirement of developing a cable with joint that enables suppressing the cost while maintaining the reliability of electric power supply, we have developed a new cable with reduced insulation thickness having a waterimpervious layer together with its joint. By using an aluminum laminated tape for the cable and joint, we have been successful in maintaining the reliability while reducing the insulation thickness. This paper reports on the structure, characteristics, and working efficiency of this cable and the joint. 2. DESIGN OF 22-KV CV CABLE WITH REDUCED INSULATION THICKNESS HAVING WATER-IMPERVIOUS LAYER * Tokyo Electric Power Co. * 2 Engineering & Development Dept., Insulated Conductors & Components Div. * 3 Distribution Cable Accessories Sec., Engineering Dept., Power Cables Div. 2. Target Characteristics and Structure Table shows target characteristics. Whereas the electric characteristics are in compliance with JEC-3408-997 ), the lightning impulse test voltage is ±35 kv since lightning impulse withstand voltage (LIWV) is given as 95 kv. As for the water-imperviousness of the cable, it was fixed at a value equivalent to that of water-impervious lead layer (WILL) having an established track record in the 66- kv CV cables currently in use. 2.2 Design Details 2.2. Investigation of insulation thickness The cable insulation thickness was determined by adopting the greatest among those obtained by the electric field intensity of cable design (E L ) as well as the characteristics at the rise-up portion of the stress cone for joint and partial discharge characteristics. Required insulation thicknesses based the design factors mentioned above are described below. () Insulation thickness based on the cable design The insulation thickness based on the required AC withstand voltage is 2.3 mm including inner semiconductive layer (ISCL), given the AC design voltage of 35 kv/mm 2). Table Item Partial discharge AC withstand voltage Lightning impulse voltage Long-term loading (in air) Water imperviousness Target characteristics of cable Target characteristics 5 pc or less at 30 kv.0 min 45 kv. hr ±35 kv.3 repetitions (LIWV = 95 kv) 20 kv loading; Conductor temperature: 90 C 8 hr ON / 6 hr OFF, 80 repetitions Averaged water permeation: x 0-7 g.(cm/cm 2 ).day.mmhg or less 59

Table 2 Breakdown test data of joint Joint type Slip-on straight joint Prefabricated joint Notes Minimum breakdown voltage (kv) AC 30 Imp 380 * AC 67 Imp 380 * G min (kv/mm) 7.4 5.0 9.8 45. Insulation thickness including ISCL (mm) 4. 4.2 3.7 4.5 () The * mark corresponds to the data outside the rise-up portion of stress relief cone. (2) Insulation thickness is calculated assuming that the required withstand voltage equals to the standard value multiplied by a sufficient margin --because of small numbers of measured data-- of.3. AC: 45 kv x.3 = 58.5 kv Imp: 35 kv x.3 = 75.5 kv Cross-section of water-impervious aluminum layer WIAL Screening copper tape Conductive binder tape Conductor Insulator ISCL OSCL Figure Aluminum foil Adhesive layer Plastic layer Conductive plastic layer 22-kV CVT cable with WIAL Sheath Meanwhile, the thickness based on the required lightning withstand voltage is 2.8 mm including ISCL, given the lightning withstand design voltage of 75 kv/mm 2). Thus, the insulation thickness based on the cable design was determined as 3.0 mm. (2) Insulation thickness based on the characteristics at the rise-up portion of the stress cone for joint Since reduction of the cable insulator thickness increases the electric field intensity on the cable insulator, withstand voltage characteristics of the rise-up portion of the stress relief cone must be considered. We calculated these characteristics based on the minimum breakdown voltage denoted by G min that was derived from breakdown test data of joints. Table 2 shows typical breakdown test data of 22-kV joints together with the calculated results, indicating that the cable insulation thickness can be reduced down to 4.0~4.5 mm including ISCL. (3) Insulation thickness based on partial discharge characteristics at the edge of outer semiconductive layer Since reduction of the cable insulator thickness has an influence on partial discharge characteristics at the edge of the outer semiconductive layer (OSCL), various termination methods were studied for their partial discharge characteristics. As a result, an insulation thickness of 4.0 mm including ISCL was identified to result in a partial discharge start voltage of 8.2 kv even for the greatest conductor size of 500 mm 2, thus meeting the specification for the joints of 7 kv 0 pc or less. Taking into consideration, however, such variations as data spread and possible degradation due to working environment at the site, the insulation thickness should be 4.5 mm or more. Based on the results of the foregoing investigation it was decided to adopt the greatest value of 4.5 mm including ISCL for the cable insulation thickness. 2.2.2 Water-Impervious Layer The water-impervious layer uses aluminum and employs a double laminated structure considering mechanical strength and corrosion resistance. The layer is placed underneath the cable sheath lengthwise and they are bonded together so as to improve the mechanical characteristics of the cable allowing them to integrally follow bending, expansion, and contraction of the cable. 2.2.3 Detailed Structure of the Cable Figure shows the structure of the CVT cable with waterimpervious aluminum layer (WIAL) developed at this time. 3. CABLE EVALUATION 3. Initial and Long-Term Characteristics Table 3 shows the results of the initial and long-term electrical characteristics tests of the developed cable. All test items are seen to meet the target characteristics. Long-term loading tests of 80-day duration were carried out to confirm the long-term performance of the cable. As for the test conditions, not only in-air test conditions but also in-water test conditions were investigated simulating submerged conditions to be encountered in practical Table 3 Electrical test results of 325-sq cable Partial discharge test No occurrence (30 kv. 0 min) Lightning impulse withstand voltage ±35 kv. 3 repetitions: Lightning impulse breakdown -650 kv. repetition AC long-term withstand voltage 45 kv. hr: AC breakdown 325 kv. 6 min Long-term loading test No abnormalities (in air and in hot water) Partial discharge No occurrence test (more than 30 kv) Residual performance after long-term AC breakdown * In hot water: 35~45 kv * 2 In air: 5~65 kv * 2 loading test Lightning impulse In air: -345 kv * 2 breakdown * In hot water: -345 kv * 2 Notes *: 60 C hot water long-term tests were carried out at the Central Research Institute of Electric Power Industry. *2: All breakdowns occurred at joints. 60 Furukawa Review, 20 200

installation environments. But if the water temperature was set to a normal temperature while raising the in-water cable conductor temperature to 90 C, the temperature of the in-air cable conductor --the test system is controlled based on this temperature-- would exceed the allowable temperature of the cable. Thus, the water temperature was set to 60 C enabling the test temperature of 90 C to be applied for both the in-air and in-water cables. No abnormalities such as breakdown were found during this test. Furthermore, residual performance tests including AC partial discharge test, AC breakdown test, and lightning impulse breakdown test were carried out after this test, and it was confirmed, as shown in Table 3, that the performance remained unchanged from the initial characteristics. 3.2 Water-Imperviousness The following tests were carried out to evaluate the performance of the water-impervious structure applied to the developed cable, ultimately confirming that the WIAL was equivalent to the WILL of established track record and that the cable would withstand 30-years of use. 3.2. Water Permeation Measurement Water permeation was measured simulating the permeation of water from the outside, in which a cable sheath alone was submerged into hot water followed by measuring the amount of permeated water to obtain water permeation. Figure 2 and Table 5 show the results of measurement together with the water permeation. 3.2.2 Thermo-Mechanical Characteristics Test The cable was tested to see whether cracks occur in the WIAL by expansion and contraction due to 30 years of heat cycle. The expansion of the cable caused by temperature rise due to current loading was measured, and it was investigated whether cracks occur when a strain corresponding to this expansion was applied to the WIAL, while the S-N characteristic of the WIAL was obtained in advance to support this investigation. Table 5 and Figure 3 show the results of the strain measurement and the S-N characteristic curve. 4. DESIGN OF JOINTS FOR 22-KV XLPE CABLE WITH REDUCED INSULATION THICKNESS HAVING WIAL 4. Target Characteristics and Structure Development objectives are straight joint, Y-branch joint, and terminating joint and their target characteristics are shown in Table 6. Whereas the electric characteristics are in compliance with JEC-3408-997 ), the lightning impulse test voltage is ±35 kv since the LIWV is given as 95 kv. As for the water-imperviousness of the joints, since there are no standards for joints, it was fixed at a value equivalent to that of heat shrinkable WILL which has an established track record in the water-impervious terminations for metal-sheathed cables of 66-kV rating or over. 4.2 Design Details Figure 4 shows the structure of the developed straight joint. 0 Table 5 Estimated strains of the sheath due to temperature change Water permeation (g) 0. 0.0 0.00 0 0 20 30 40 Category Diurnal temp. change (once a day) Short-duration temp. change (once a year) Annual temp. change (once a year) Accumulated strain cycle 0,950 30 30 Strain 0.38% 0.6%.05% Time (day) Without water-impervious layer With WIAL With WILL 0 Figure 2 Results of water permeation measurement of cable Table 4 Measured water permeation of cable Present 22-kV CV Developed cable Reference cable cable with no impervious layer with WIAL with WILL Averaged water permeation.32 0-6 8.73 0-9.93 0-9 Water permeation unit: g. (cm/cm 2 ). day. mmhg Strain (%) 0..0E+00.0E+0.0E+02.0E+03.0E+04.0E+05.0E+06.0E+07 Figure 3 Strain due to annual temperature change Strain due to short-duration temperature change Sheet sample of WIAL Strain due to diurnal temperature change Number of strain cycle until crack occurrence (count) Results of S-N characteristic test 6

Table 6 Target characteristics of joints Item Target characteristics 0 pc or less at 7 kv Partial discharge (in conformity to JEC-209) AC withstand voltage 45 kv. hr Lightning impulse voltage ±35 kv. 3 repetitions (LIWV = 95 kv) 20 kv loading; Conductor temperature: 90 C Long-term loading (in air) 8 hr ON / 6 hr OFF, 80 repetitions 26.2 ka. 2 sec, Current loading No abnormalities should be observed External pressure: 98 kpa. hr, No water Water-tightness permeation should be observed Water imperviousness Equivalent to heat shrinkable WILL Polyolefin layer Figure 6 Aluminum foil Aluminum foil Polyolefin layer Adhesive layer Cross-section of a shrinkable with aluminum waterimpervious layer 232 Approx. 750 025 approx. 290 Figure 4 4 3 2 Water-impervious shrinking tube Grounding terminal Cold shrinkable splice housing Conductor sleeve 7 6 5 Waterproofing tape ACP tape Semiconductive tape Straight joint for 22-kV XLPE cable with reduced insulation thickness having WIAL Figure 7 7 6 5 4 3 2 Insulating cover Splice housing (B) Spacer Splice housing (A) Terminal lug Metal housing Main body 4 3 2 0 9 8 Sealing tape ACP tape Conductive paint Self-bonding semiconductive tape Terminal lug Grounding wire Water-impervious shrink tube Y-branch joint for 22-kV XLPE cable with reduced insulation thickness having WIAL Semiconductive tape ACP tape Figure 5 OSCL of cable Conductive paint Heat-shrinkable tube is heated using a hair drier, smoothing the edge by the heat and the tube's contraction force New processing method for the edge of OSCL Considering cost reduction by eliminating spacer sleeve covers together with easy installation at the site, a coldshrinkable type was employed for insulation, in which a cold-shrinkable splicing housing was expanded at the factory in advance and was subsequently installed by on-site shrinking. As for the material of the splicing housing, silicone rubber was employed for its excellent electrical as well as permanent set characteristics. While permanent set is one of the most important key factors in the application of cold-shrinkable technology with factory expansion, the use of silicone rubber with excellent permanent set performance enables to suppress degradation of interfacial pressures satisfactorily during the entire service period of 30 years. Additionally, whereas the reduction of the insulation thickness increased the electric field intensity on the insulator surface, the conventional method for processing the OSCL of 22-kV class, i.e., ACP tape wrapping on the OSCL became unable to meet the target performance requirement in terms of partial discharge characteristics. Therefore, a new OSCL processing method of "conductive paint coating plus semiconductive tape wrapping" was developed as illustrated in Figure 5. In this method, semiconductive paint that had been successfully applied in the class of 66-kV rating or over was coated over the edge of the cable OSCL to eliminate triangular voids thereof, thus improving the partial discharge characteristics. Furthermore, semiconductive tape was wrapped for protection against possible peeling due to clamping wedge in the case of pre-molded type joint, followed by a smoothing process in which a heat-shrinkable tube --to be removed after the process-- and a hair drier were used to make the edge of the tape level with the surface of the cable insulator, thereby enabling suppression of the voids while making this structure applicable to all types of such joints. By applying this method, a partial discharge start voltage of 30 kv or more was realized even with the cable insulation thickness of 4.5 mm including ISCL. A shrinkable tube with aluminum water-impervious layer was employed for the water-impervious structure. The tube consists of polyolefin shrinkable tube and waterimpervious aluminum layer sandwiched therein, and the structure is such that each layer is firmly bonded together by an adhesive layer, enabling control of water permeation by adjusting the lapping width of the water-impervious layer. By shrinking the tube on its entire length, the straight joint can be made as impervious to water as the cable. Figure 6 shows the cross-section of a shrinkable tube with aluminum water-impervious layer. Figure 7 shows the structure of a Y-branch joint developed this time. The joint employed, attaching much impor- 62 Furukawa Review, 20 200

Table 7 Results of the initial and breakdown characteristic tests of 325-sq joints 0 Partial discharge test Lightning impulse withstand voltage Lightning impulse breakdown (0 kv. 3 step-ups) No occurrence (Occurrence voltage of 30 kv or more was confirmed) ±35 kv. 3 repetitions: S-joint: -395~-425 kv Y-joint: -205~-25 kv Water permeation (g) 0. AC withstand voltage AC breakdown (0 kv. hr step-ups) Current loading Water-tightness 45 kv. hr: S-joint: 45~85 kv Y-joint: 75~95 kv (Residual performance was the same as for the initial) 0.0 0 0 20 30 40 50 Time (day) WILL Water-tight tube without water-impervious layer Power-rule calculation for WIAL Power-rule calculation for water-tight tube without water-impervious layer WIAL WILL with 0 test pinholes of φ2 Power-rule calculation for WILL Table 8 Results of long-term tests of 325-sq joints Figure 8 Results of water permeation measurement of joints Long-term loading test No abnormalities (in air and in hot water) Partial discharge No occurrence (Occurrence voltage test of 30 kv or more was confirmed) In air: 5~65 kv S-joint AC breakdown In air: 85~95 kv In hot water: 35~45 kv Residual characteristics after Y-joint In hot water: 85~95 kv long-term tests In air: -345 kv Lightning S-joint In hot water: -345 kv impulse breakdown In air: -335 kv Y-joint In hot water: -275 kv Note 60 C hot water long-term tests were carried out at the Central Research Institute of Electric Power Industry. tance to cost reduction, a three-layered rubber mold structure with outer casing of metal, terminal lug jointing for conductor joints, and the "splice housing plus spacer" structure for insulation. In terms of OSCL edge processing and the water-impervious structure, the same method and structure as for the straight joint were applied. 5. EVALUATION OF JOINTS 5. Initial Characteristics It was confirmed that the initial characteristics of the joint satisfactorily met every requirement of target characteristics. Table 7 shows the results of the initial characteristics tests together with the breakdown tests that were conducted to know the ultimate performance. 5.2 Long-Term Test Long-term test of 80-days duration was carried out to confirm the long-term performance of the developed joints, and Table 8 shows the results. In this test, no abnormalities such as breakdown were Table 9 Inner-pressure tightness Water permeation measurement Thermomechanical characteristics Results of water permeation measurement of joints Test conditions No air-leak should be observed at 49 kpa. 24 hr in 60 C water Water permeation after 0, 20, and 30 days of immersion in 60 C water to be measured and compared with WILL No crack should occur when following strains are applied Diurnal strain: 0,950 count Short-duration strain: 30 count Annual strain: 30 count found. Furthermore, the residual performance tests after the long-term test were conducted in terms of partial discharge, AC breakdown, and lightning impulse, verifying that the performance was the same as for the initial characteristics as shown in Figure 8. 5.3 Water-Imperviousness The following tests were carried out to evaluate the performance of the water-impervious structure applied to the developed joints, confirming that the water-imperviousness of the shrinkable tube with WIAL was equivalent to the WILL of established track record. Table 9 and Figure 8 show the results of the tests. 5.3. Inner-Pressure Air-Tightness Test The water-impervious structure was tested whether it could withstand the pressure increase within the joints. 5.3.2 Water Permeation Measurement The water permeation of WIAL and WILL was measured and compared in accordance with the water permeation measuring methods of CV cables with 66-kV rating or over. 63

[Straight joint] Table 0 Comparison of installation work Item Joint currently in use Joint developed Splice housing mounting Dedicated tool is used since manual insertion is difficult Neither skill nor tools required thanks to cold-shrinkable splice housing Shrinkable tube mounting Heat source required The same as for the waterproof tube in present use Finished dimensions φ 30 x 50 (mm) Downsized to about 60 % of current joint Photo Appearance of installed straight joint [Y-branch joint] Conductor splicing Dedicated tools required for wedge splicing within the Y-branch body Bolt connection using terminal lug outside the Y-branch body, ensuring secure connection without using dedicated tools Finished dimensions W50 x H292 x L260 (mm) Downsized to about 90 % of current joint except for the equivalent total length 5.3.3 Thermo-Mechanical Characteristics Test Thermo-mechanical characteristics were evaluated based on a method that is basically the same as that described in Clause 3.2.2. 5.4 Installation Work Ease of installation of the joints was evaluated and it was verified the developed joints could be installed in a shorter time than the conventional slip-on type straight joint or prefabricated type Y-branch joint. Table 0 shows the comparison, and Photos and 2 show the installed straight joint and Y-branch joint. 6. CONCLUSION We have developed a new cable with reduced insulation thickness having water-impervious layer in conjunction with its joints for 22-kV power supply systems in which future application is expected to expand. The development program was aimed at cost reduction through insulation thickness reduction while maintaining reliability and improved environment-friendliness. Last but not least, we would like to thank Mr. Takeda, Chief Researcher of the Central Research Institute of Electric Power Industry for his great help in carrying out the long-term loading test in hot water. Photo 2 Appearance of installed Y-branch joint REFERENCES ) JEC-3408, "High-Voltage Testing Method for Ultra-High Voltage -- kv to 275 kv-- Cross-Linked Polyethylene Cables and Joints", 997 (in Japanese) 2) "High-Voltage Testing Method for CV Cables and Joints", Electrical Cooperative Research, Vol. 5, (995) (in Japanese) Manuscript received on December 26, 2000. 64 Furukawa Review, 20 200