Tracer Controls. Tracer VV550/551 VAV Controllers CNT-PRC003-EN. October 2005



Similar documents
Functional Profile: Heat Pump with Temperature Control

Product Catalog BAS-PRC010-E4. Tracker Version 12 Building Automation System. August 2010

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

Tracer Summit Web Server

STAT-RT Series.

Tracker. Tracker Version 12 Building Automation System BAS-PRC010-EN. March 2008

Controller Operator Guide. VariTrac TM Central Control Panel VAV-SVU01A-EN

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

Installation Owner Diagnostics

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Product Catalog. Tracer SC System Controller For Tracer Building Automated Systems BAS-PRC031-EN. July 2010

Workshop 7 PC Software - Tracker

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007

Variable Air Volume - VAV

HVAC and Lighting Control Products for Open Building Automation Systems

T7560A,B,C Digital Wall Module

Building Management Systems


Room Controllers. SER8300 Line Voltage Fan Coil Room Controller with SC3000 Relay Pack

FX07 Field Controller

T5000 T000 LCD Digital Fan Coil Thermostat

Protects against unwanted thermostat controller tampering. Increases occupancy comfort by providing dehumidification.

Using Time-of-Day Scheduling To Save Energy

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

Guest Room Controls & Monitoring System. Integrated Solution for Hotels Southern Countries.

3466 Building Energy Management Training Systems

Actuator Plug-In

Daily Operations TRACER SUMMIT

Y-200 Multi-Stage Sequencer

Aurora UPC ZS Zone Sensors User Guide

FX07 Field Controller

Personna PC web-based software. Q-AdminTM client. Lighting management hub (floor 1)

English plain text messages with constant backlight that brightens during user interaction. On/Off, Floating, or Proportional 0 to 10 VDC Control

TR21, TR22, TR23, and TR24 Wall Modules

Integrated Building Management and Security System. Building Automation & Security.

PC Personal 120V 600VA 375W Standby UPS with Pure Sine Wave Output, Tower, 6 Outlets

ABB i-bus KNX Fan Coil Controller FC/S 1.1

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out

Overview. Alarm console supports simultaneous viewing of both live and recorded video when alarm events are selected

Multi-Range Programmable DC Power Supplies 9115 Series

Comm5 Wiring Installation

Siemens BACnet Programmable TEC Terminal Box (VAV) Controller Owner's Manual

HVAC Processes. Lecture 7

CATALYST Frequently Asked Questions

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

The ABB i-bus KNX Room Master Concept Your first step into the KNX world

Technical requirements

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ

Tracer Summit. Critical Control System BAS-PRC017-EN. May 2004

Integrated Controls & Monitoring System for Apartments. Solution for southern countries.

Fundamentals of HVAC Control Systems

Amplifier: AMP Feature Summary

Programmable Logic Controllers

Wireless Thermostats 230v and Battery Operated Instruction Manual

Hotel System Management The Hotel Smartest Solution

The THERMOSTAT THE EVOLUTION OF CAPABILITIES INTO A PLATFORM FOR ENERGY MANAGEMENT

HMI display Installation Guide

Application Sheet Fan coil unit with staged fan, heating/cooling coil (2 pipe) on analog output

CE6500 Energy Recovery Ventilator

SECTION DETECTION AND ALARM

SECTION LOW VOLTAGE LIGHTING CONTROLS

IntesisBox Modbus Server SAMSUNG Air Conditioners

Integrated Building Management and Security System. Building Automation & Security.

Powerline 1200 User Manual

3500/62 Process Variable Monitor

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

Introduction. Functional Description. Features. DSL Protocol Analyzer. Network Side ADSL CPE. Transparent ADSL Data Recording.

SmartOnline V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire

Operating and installation manual

ADDENDUM TO THE CONTRACT. for the. Bartlett Regional Hospital Server Room Cooling System Replacement. Contract No. E12-149

CompactLogix Power Supplies Specifications

MP-4000 Alarm List (Software version or later)

It s all open from here.

NETWORK ENABLED EQUIPMENT MONITOR

MCS-BMS-GATEWAY STARTUP GUIDE

How To Learn To Use A Trane Building Control System

Water-Source Heat Pump

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS

IntesisBox. KNX SAMSUNG Air Conditioning. Gateway for integration of Samsung air conditioners into KNX control systems. RS485.

Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P

Controls for fan coil units and cassettes

Temperature controller for heated/chilled ceiling systems

A-307. Mobile Data Terminal. Android OS Platform Datasheet

Air Conditioning Clinic

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

Back-UPS Pro 1300/1500 Installation and Operation

Healthcare Solutions Room Pressure Monitors and Controls

Communicating Thermostats. Add More Flexibility to Building Automation with New. Communicating Thermostats

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

IntesisBox DK-RC-ENO-1iC. EnOcean Interface for DAIKIN Air Conditioners Compatible with SKY and VRV lines

Cisco Redundant Power System 2300

AIS 3000 APC AIS kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass

Duct Humidity Transmitter

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

Transcription:

Tracer Controls Tracer VV550/551 VAV Controllers October 2005 CNT-PRC003-EN

Introduction Tracer VV550 and Tracer VV551 variable air volume (VAV) controllers provide single-duct digital control for VAV boxes. They support the following VAV control sequences: Space temperature control Flow tracking Ventilation flow control The Tracer VV550 VAV controller is available factory-installed on Trane VariTrane VAV boxes (Figure 1). The Tracer VV551 VAV controller is available for field installation for a variety of VAV applications (Figure 2). Figure 1. Tracer VV550 controller Figure 2. Tracer VV551 controller (uses same board as Tracer VV550) Because the Tracer VV550 and Tracer VV551 VAV controllers use the same logic controller, both offer the same wide range of application and control flexibility. The Tracer VV551 VAV controller includes additional laborsaving packaging features for fieldinstalled applications. Tracer VV550/551 VAV controllers can operate as part of a Trane Integrated Comfort system (ICS), as part of a building management system from another manufacturer, or as a standalone device. When it is part of a Trane ICS, a Tracer VV550/551 VAV controller enables the building automation system (BAS) to perform functions such as scheduling, trending, alarming, remote communications, and VAV air system (VAS) coordination. The controller communicates with a Tracer Summit BAS over the LonTalk communications link. The controller can also communicate with other building control systems that are compliant with the LonMark Space Comfort Controller (SCC) profile. Tracer VV550/551 VAV controllers can be configured using the Rover service tool. They have the following inputs and outputs (Figure 3 on page 6): Analog inputs: Space temperature (10 kω thermistor) Space setpoint (1 kω potentiometer) Primary/discharge air temperature (10 kω thermistor) Primary air flow Binary inputs: Occupancy or generic Binary outputs: Air valve close Air valve open Heat 1 Heat 2 Heat 3 or fan On/Off The following are trademarks or registered trademarks of their respective companies: ICS, Rover, Tracer, Tracer Summit, and Trane of American Standard Inc.; LonMark, LonTalk, and LonWorks of the Echelon Corporation. 2 2005 American Standard All rights reserved CNT-PRC003-EN

Contents Introduction........................ 2 Features and benefits................ 4 Automatic calibration......................... 4 Ventilation flexibility......................... 4 Flow tracking............................... 4 Ventilation flow control with tempering......... 4 Local versus remote reheat flexibility........... 4 Occupied and unoccupied operation............ 4 Timed override.............................. 4 Service pin from the Trane zone sensor......... 4 Auto-commissioning sequence................ 5 Manual test function......................... 5 Drive minimum and maximum from zone sensor. 5 Trane controller compatibility.................. 5 Interoperability.............................. 5 Wiring diagram.............................. 5 Wiring diagram for Tracer VV550/551 VAV controllers.......................... 6 Network architecture................. 7 Zone sensor options................. 8 Dimensions and specifications......... 9 Power requirements.......................... 9 Operating environment....................... 9 Storage environment......................... 9 Dimensions................................. 9 Weight with enclosure (Tracer VV551)........... 9 Analog inputs............................... 9 Binary input................................ 9 Binary outputs.............................. 9 Agency listings/compliance.................... 9 Data lists.......................... 11 CNT-PRC003-EN 3

Features and benefits Automatic calibration Tracer VV550/551 VAV controllers automatically calibrate the flow transducer each time the box transitions to the unoccupied state. This eliminates the need to initiate/schedule calibration for most installations. The exception is 24/7 sites, in which case the Tracer Summit building automation system can be used to initiate/schedule calibration. Ventilation flexibility Tracer VV550/551 VAV controllers can manage ventilation in the following ways: Fixed occupancy ventilation setpoint Scheduled (or otherwise calculated) ventilation setpoint Occupancy sensor to switch between normal and reduced ventilation CO 2 sensor for demand-controlled ventilation This flexibility gives owners and facility managers an option to simply select one of several effective solutions for managing ventilation. Flow tracking Tracer VV550/551 VAV controllers can easily be applied in flow tracking applications. In a flow tracking application, supply and exhaust boxes are paired together for the purpose of maintaining either positive or negative space static pressure. This feature allows the installer to quickly define the relationship of the supply and exhaust air boxes without the need for custom programming. Ventilation flow control with tempering Tracer VV550/551 VAV controllers have been designed for ventilation flow control applications. These applications pair a fresh air unit or self-contained unit with ventilation boxes to provide fresh (tempered) air to a floor/area. With this feature, the installer can quickly configure the flow control boxes and set up the system without the need for custom programming. Local versus remote reheat flexibility Tracer VV550/551 VAV controllers can be configured to have local and/or remote heat. This configuration flexibility enables the controllers to be applied across a broad range of VAV applications. Occupied and unoccupied operation The occupancy input on a Tracer VV550/ 551 VAV controller works with a motion (occupancy) sensor or a time clock to determine the occupancy mode. An occupancy request can also be communicated from a building automation system to determine the mode of the controller. Whether standalone or combined with a communicated occupancy request, a Tracer VV550/551 controller can be used with an occupancy sensor to save energy whenever a space is vacant. Timed override The timed override function for afterhours operation allows users to request unit operation by the touch of a button on the unit zone sensor. Additionally, users can press the CANCEL button at any time to place the unit back into unoccupied mode. This occupancy feature minimizes energy use by running the system only as scheduled or as demanded after hours. Service pin from the Trane zone sensor Certain installation scenarios require access to the SERVICE button on the controller. Access to this button typically requires a ladder or a lift. The Tracer VV550/551 VAV controller allows a technician to replicate pressing the SERVICE button by pressing the zone sensor ON button. This feature eliminates the need for accessing the SERVICE button, saving the technician time and energy. 4 CNT-PRC003-EN

Auto-commissioning sequence Tracer VV550/551 VAV controllers provide an automatic commissioning sequence. With a discharge air temperature sensor installed, this feature exercises the air valve, fan, and heat in the box and records the discharge air temperature before and after the action. This allows the installer to easily checkout the operation of the box and commission by exception. The data from this test is retained in the controller for immediate reports or retrieval at a later date (for comparison purposes). Manual test function A Tracer VV550/551 VAV controller includes a manual test button, which enables a technician to easily exercise the outputs of the controller. On consecutive button presses, the controller steps through a predefined sequence that exercises all of the controller outputs. Drive minimum and maximum from zone sensor When applied with a Trane zone sensor module that includes a thumbwheel setpoint, a Tracer VAV VV550/551 controller can easily be overridden to minimum and maximum flow. By simply turning the thumbwheel to, the controller drives the air valve to the minimum cooling flow setpoint. Similarly, turning the thumbwheel to drives the air valve to the maximum cooling flow setpoint. This simple override feature is most useful during the checkout and balancing phases of a project. Trane controller compatibility Tracer VV550/551 VAV controllers are compatible with the latest generation of Trane control products. The controllers communicate over a LonTalk communications link. This allows Tracer VV550/551 VAV controllers to exist on the same communication wire as other Trane controllers and to share data with them as required. Interoperability Tracer VV550/551 VAV controllers are designed with LonWorks technology and are LonMark certified. They follow the guidelines of the LonMark Space Comfort Controller (SCC) profile. As such, the Tracer VV550/551 controllers enable control system integration flexibility. Wiring diagram See Figure 3 on page 6. Wiring diagram 2 CNT-PRC003-EN 5

{ On Cancel Wiring diagram for Tracer VV550/551 VAV controllers Figure 3. Tracer VV550/551 wiring diagram 24V GND Binary outputs { { { Binary input Rover service tool Analog inputs In Out 1 2 3 LonTalk communication link Trane zone sensor 6 CNT-PRC003-EN

75 80 70 85 * 65 60 ON 55 Cancel 50 ** 75 80 70 85 * 65 60 ON 55 Cancel 50 ** 75 80 70 85 * 65 60 ON 55 Cancel 50 ** Network architecture Tracer VV550/551 VAV controllers can operate on a Tracer Summit BAS, on a building management system from another manufacturer, on a peer-to-peer network, or as stand-alone devices. The Rover service tool can configure the controllers at any accessible location on the LonTalk communication link (Figure 4). Figure 4. Network architecture with Tracer VV551 VAV controllers Tracer Summit PC Workstation LAN (Ethernet or ARCNET) Building control unit (BCU) Building control unit (BCU) with operator display o o o ROVER TM Rover service tool LonTalk link Zone sensor LonTalk link Zone sensor Zone sensor Tracer VV551 Tracer VV551 Tracer VV551 VAV box VAV box VAV box CNT-PRC003-EN 7

Zone sensor options Zone sensors are available in a variety of configurations. Table 1 describes the features of the five Trane zone sensors that are available for use with Tracer VV550/551 VAV controllers. The same five sensors are shown in Figure 5. Contact your Trane sales office about other compatible zone sensors. Table 1. Zone sensors for use with Tracer VV550/551 GCC order number Setpoint thumbwheel Zone Temperature sensor Timed override buttons ON CANCEL LCD Comm jack 4190 1087 x x 4190 1088 x x x x 4190 1090 x x x x x 4190 1094 x x x 4190 1120 x x x x x x Figure 5. Zone sensors for use with Tracer VV550/551 4190 1090 4190 1094 4190 1088 4190 1087 4190 1120 8 CNT-PRC003-EN

Dimensions and specifications Power requirements Supply: 18 32 Vac (24 Vac nominal) at 50/60 Hz Operating environment Temperature: 32 to 140 F (0 to 60 C) Relative humidity: From 5 to 95% non-condensing Storage environment Temperature: -40 to 185 F (-40 to 85 C) Relative humidity: From 5 to 95% non-condensing Dimensions (See Figure 6 on page 10.) Board only Height: 4.5 in. (11.4 cm) Width: 5.5 in. (13.8 cm) Depth: 2 in. (5.1 cm) With enclosure (VV551) Height: 7.5 in. (13.7 cm) Width: 6.5 in. (16.7 cm) Depth: 5.5 in. (14.0 cm) Weight with enclosure (Tracer VV551) With no actuator: 3.9 lb (1.77 kg) With Belimo actuator: 5.0 lb (2.27 kg) With Trane actuator: 5.2 lb (2.36 kg) Analog inputs Space temperature; thermistor: 10 kω@ 77 F (25 C) From 14 to 122 F (-10 to 50 C) Space setpoint; potentiometer: 1 kω From 50 to 90 F (-10 to 32.2 C) Primary/discharge air temperature; thermistor: 10 kω@ 77 F (25 C) From -40 to 212 F (-40 to 100 C) Primary air flow; pressure transducer: From 0 to 2 in. water (0 to 498 Pa) Binary input Occupancy or generic (dry contact) Binary outputs Air valve close: maximum output rating: 12 VA Air valve open: maximum output rating: 12 VA Heat stage 1: maximum output rating: 12 VA Heat stage 2: maximum output rating: 12 VA Heat stage 3/Fan on/off: maximum output rating: 12 VA Agency listings/compliance Tracer VV550: UL 873 and CSA C22.2 No. 24-93: Temperature Indicating and Regulating Equipment Tracer VV551: UL-916-PAZX energy management CUL-C22.2 signal devices Canada UL 94-5V (UL flammability rating for plenum use) FCC Part 15, Class A CE marked CNT-PRC003-EN 9

Figure 6. Tracer VV551 dimensions Cover off 7.5 in. (19.2 cm) Cover on 6.5 in. (16.7 cm) 7.5 in. (19.2 cm) 5.5 in. (14.0 cm) 6.5 in. (16.7 cm) 10 CNT-PRC003-EN

Data lists Table 2 provides an input/output listing for Tracer VV550/551 VAV controllers. Table 3 provides the configuration properties for the controller. The content of the lists conforms to both the LonMark SCC functional profile 8500 and the LonMark node object. Table 2. Input/output listing Input description Input SNVT type Output description Output SNVT type Space temperature nvispacetemp SNVT_temp_p Space temperature nvospacetemp SNVT_temp_p Setpoint nvisetpoint SNVT_temp_p Unit status, mode nvounitstatus SNVT_hvac_status Occupancy, schedule nvioccschedule SNVT_tod_event Effective setpoint nvoeffectsetpt SNVT_temp_p Occupancy, manual nvioccmancmd SNVT_occupancy Effective occupancy nvoeffectoccup SNVT_occupancy command Occupancy sensor nvioccsensor SNVT_occupancy Heat cool mode nvoheatcool SNVT_hvac_mode Application mode nviapplicmode SNVT_hvac_mode Setpoint nvosetpoint SNVT_temp_p Heat/cool mode input nviheatcool SNVT_hvac_mode Discharge air nvodischairtemp SNVT_temp_p temperature Fan speed command nvifanspeedcmd SNVT_switch Terminal load nvoterminalload SNVT_lev_percent Auxiliary heat enable nviauxheatenable SNVT_switch Space CO 2 nvospaceco2 SNVT_ppm Valve override nvivalveoverride SNVT_hvac_overid Effective air flow nvoeffectflowsp SNVT_flow setpoint Flow override nviflowoverride SNVT_hvac_overid Air flow nvoairflow SNVT_flow Emergency override nviemergoverride SNVT_hvac_emerg File table address nvofiledirectory* SNVT_address Source temperature nvisourcetemp SNVT_temp_p Object status nvostatus* SNVT_obj_status Space CO 2 nvispaceco2 SNVT_ppm Alarm message nvoalarmmessage SNVT_str_asc Clear alarms/ nvirequest* SNVT_obj_request * Part of the node object. diagnostics Air flow setpoint input nviairflowsetpt SNVT_flow Ventilation ratio limit nviventratiolim SNVT_lev_percent Ventilation for the zone nviventsetpt SNVT_flow input * Part of the node object. Table 3. Configuration properties Configuration property description Configuration property SNVT type SCPT reference Send heartbeat ncisndhrtbt SNVT_time_sec SCPTmaxSendTime (49) Occ temperature setpoints ncisetpoints SNVT_temp_setpt SCPTsetPnts (60) Minimum send time nciminouttm SNVT_time_sec SCPTminSendTime (52) Receive heartbeat ncirechrtbt SNVT_time_sec SCPTmaxRcvTime (48) Location label ncilocation SNVT_str_asc SCPTlocation (17) Local bypass time ncibypasstime SNVT_time_min SCPTbypassTime (34) Manual override time ncimanualtime SNVT_time_min SCPTmanOverTime (35) Space CO 2 limit ncispaceco2lim SNVT_ppm SCPTlimitCO2 (42) Nominal air flow ncinomflow SNVT_flow SCPTnomAirFlow (57) Air flow measurement gain nciflowgain SNVT_multiplier SCPTsensConstVAV (67) Minimum air flow nciminflow SNVT_flow SCPTminFlow (54) Maximum air flow ncimaxflow SNVT_flow SCPTmaxFlow (51) Minimum air flow for heat nciminflowheat SNVT_flow SCPTminFlowHeat (55) Maximum air flow for heat ncimaxflowheat SNVT_flow SCPTmaxFlowHeat (37) Minimum flow for standby nciminflowstdby SNVT_flow SCPTminFlowStby (56) Firmware major version ncidevmajver* n/a SCPTdevMajVer (165) Firmware minor version ncidevminver* n/a SCPTdevMinVer (166) Flow offset for tracking applications nciflowoffset SNVT_flow_f SCPToffsetFlow (265) Local heating minimum air flow nciminflowunitht SNVT_flow SCPTminFlowUnitHeat (270) * Part of the node object. CNT-PRC003-EN 11

Trane A business of American Standard Inc. www.trane.com For more information, contact your local Trane office or e-mail us at comfort@trane.com Literature Order Number CNT-PRC003-EN File Number PL-ES-CNT-PRC003-1005 Supersedes CNT PRC003-EN April 2004 Stocking Location Inland Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.