Operating and installation manual
|
|
|
- Stanley Richard
- 9 years ago
- Views:
Transcription
1 Operating and installation manual Functional module LON-WA1/FT3 For the monitoring and control of fire dampers and smoke control dampers with an electric actuator Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014)
2 Contents 1 General information 3 Trademarks 3 Other applicable documentation 3 Symbols used in this manual 3 2 Safety and correct use 4 General information regarding safety 4 General safety measures 4 Correct use 4 Incorrect use 4 Residual risks 4 3 Product description 5 Functional description 5 4 Technical data 6 5 Transport, storage, and packaging 7 Delivery check 7 Transport on site 7 Storage 7 Packaging 7 6 Installation 8 7 Wiring 9 Connecting the data lines 9 Connecting the spring return actuator 9 Capturing of the end positions 9 8 Commissioning and maintenance 10 Connecting the supply voltage 10 Setting the supply voltage 10 9 Description of functional object Installing the plug-in 14 System requirements Description of the plug-in 15 Starting the plug-in 15 Description of the tabs 16 Main tab 16 Dampe1 to Damper4 tabs 17 Config1/2 and Config3/4 tabs 19 TROX GmbH Heinrich-Trox-Platz Neukirchen-Vluyn, Germany Phone +49 (0) Fax +49 (0) [email protected] Part No. A Subject to change / All rights reserved TROX GmbH 2 Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014)
3 1 General information This manual describes the TROXNETCOM module LON-WA1/FT3 and the plug-in software for configuring the module. To ensure complete functioning of the module it is essential to read the provided operating and installation manual before starting any work, and to comply with it. The manual must be given to the facilities manager when handing over the system. The facilities manager must include the manual with the system documentation. The manufacturer does not accept any liability for any malfunction or damage resulting from noncompliance with this manual or non-compliance with relevant statutory regulations. Trademarks Echelon, LON, LonWorks, and LonMark are trademarks of Echelon Corporation, registered in the US and other countries. Lonmaker and LNS are trademarks of Echelon Corporation. Microsoft and Windows are trademarks of Microsoft Corporation. These and other trademarks are used in this manual but are not marked so as to make this manual easier to read. Other applicable documentation In addition to this manual, the following documents apply: Project-specific wiring documents Symbols used in this manual Warning! Designates danger to life and limb. Danger! Designates danger to life and limb due to electrical voltage. Important! Designates danger that can cause minor personal injury or damage to property. Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014) 3
4 2 Safety and correct use General information regarding safety Only skilled qualified personnel are allowed to perform the described work on the module. Only skilled qualified electricians are allowed to work on the electrical system. General safety measures Large temperature differences Condensation can damage the electronics beyond repair. If the module has been kept in an unheated area, wait at least two hours before switching on the supply voltage for commissioning. Electrostatic charge Electrostatic charge can damage the electronics. For this reason, first touch an equipotentially bonded metal surface, e.g. a water pipe, for electrical earthing before you remove the expansion module from its protective wrapping. Avoid skin contact with any components or printed circuits. Correct use Functional module LON-WA1/FT3 is used for the monitoring and control of fire dampers and smoke control dampers with an electric actuator. The module can be used to control up to four motorised fire dampers or smoke control dampers. All fire dampers or smoke control dampers to be controlled must have a 24 V or 230 V power supply. Incorrect use Do not use the module outdoors, in wet areas, or in potentially explosive atmospheres. Residual risks Failure of the LON interface does not affect the safety function of the fire damper but does affect data exchange with the central BMS. Smoke control dampers maintain the position that was last transmitted from the LON interface. Additional safety related applications require further precautions. Foreign matter and liquids If liquid gets onto the PCB or inside the expansion module, let the expansion module completely dry before commissioning. Remove foreign matter, if any. If the device emits a smell or smoke, have it checked by the manufacturer. 4 Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014)
5 3 Product description Functional description LON-WA1/FT3 can be used to control up to four fire dampers or smoke control dampers. If less than four dampers are connected, the 4-pole terminal blocks must have a wire link between the respective 'OPEN position' terminals (E1, E3, E5, E7). This is to prevent an alarm for non-existing dampers. Input variable ActuDrive is used to control the fire damper or smoke control damper. Output variable ActuPosn is used to signal the current damper blade position. The following applies: Normal = Fire damper is OPEN Fire = Fire damper is CLOSED Normal = Smoke control damper is CLOSED Fire = Smoke control damper is OPEN When LON-WA1/FT3 is supplied with voltage, the connected dampers move into their respective normal position. Safe positions In case of an error, VDMA sheet (Automated fire protection and smoke extract systems) applies: Fire damper = CLOSED Smoke control damper = Last position is maintained Monitoring function If LON-WA1/FT3 is used, the heartbeat function should be activated (for safety reasons). Setting parameter MaxRcvTime for variable ActuDrive, and parameter MaxSendTime for variable ActuPosn, ensures that the LON-WA1/FT3 module regularly sends and receives information. This ensures that the transmission path is being monitored. In case of an error, the damper moves to a safe position, and an alarm is emitted. Pulse The Pulse variable is used to check a LON network. If the input variable is set, the LON-WA1/FT3 module will change the output variable after 1 second. If there is a chain of modules, a trigger pulse is generated which can be read out at the end of the chain after N 1 seconds (N = number of LON- WA1/FT3 modules). Damper blade functional test Input variable FT_Test or the test push button of the module can be used to initiate a functional test of the damper. This moves the dampers to the Fire position (fire damper = CLOSED / smoke control damper = OPEN) and back to the Normal position (fire damper = OPEN / smoke control damper = CLOSED). The output variable FT_Test indicates whether a test is being carried out. The module remains in the text condition for the entire TestHoldTime. If ActuDrive switches to Fire during a test, the test is automatically aborted. Fire Chain If there is a chain of modules (and hence fire dampers), the FireChain variables can transmit a signal from the first to the last but will not release a damper. The FireChain relay in the LON-WA1/FT3 module receives a signal and can be used for consolidated alarms or to switch off systems. This function is only available for fire dampers. Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014) 5
6 14 1 Technical PageHeaderToc data Supply voltage Technical data 230 V AC ±10%, 50/60 Hz, 24 V AC or 24 V DC ± 10% as an option; double terminals for looping through Power consumption approx. 12 VA (without actuators 4.8 VA or W) Inputs Outputs Communication interfaces Acceptable temperature range Acceptable humidity 8 digital inputs for volt-free switches 5 digital outputs, each with changeover relay LON interface LON-WA1/FT3: 4-pole spring-loaded terminals for 0.08 mm 2 to 2.5 mm 2 FT5000 free topology for storage -10 C to +70 C for operation +10 C to +60 C 20 to 95 %, non-condensing (for storage and operation) Protection level IP 20 Connection terminals All terminals are suitable for a cable cross section of 0.08 to 2.5 mm² Displays Software application Actuator control 4-pole spring-loaded terminals Actuator end positions 4-pole spring-loaded terminals 90 Supply voltage LON-WA1/FT3 Terminals 2 3-pole FireChain signal 3-pole spring-loaded terminals 5 output LEDs, 1 consolidated alarm LED, 2 LON communication Software applications for LON-WA1/FT3 (xif/apb-file) Download from Dimensions ~ ~ Keep clear to provide access 6 Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014)
7 5 Transport, storage and packaging Delivery check Check delivered items immediately after arrival for transport damage and completeness. In case of any damage or an incomplete shipment, inform the shipping company and your TROX contact person immediately. A complete shipment includes: LON-WA1/FT3 module Operating and installation manual Transport on site If possible, take the module in its transport packaging up to the installation location. Do not remove the protective wrapping until just before installation. Storage If you need to store the module temporarily, make sure that the following conditions apply: Leave the unit in its packaging and do not expose it to the effects of weather. Store the module in a dry place and away from direct sunlight. Temperature -10 C to +70 C, humidity maximum 90% (non-condensing) Packaging Properly dispose of packaging material. Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014) 7
8 16 1 Installation PageHeaderToc Wall installation with mounting bracket (part of the supply package). 4 mm Click Click 8 Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014)
9 27 1 Wiring PageHeaderToc For installation, wiring, and commissioning observe the code of good practice and especially safety and accident prevention regulations. For any wiring work follow the national and local regulations and guidelines for electrical installation. 5 Danger! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. Only skilled qualified electricians are allowed to work on the electrical system. Switch off the power supply before working on any electrical equipment Connecting the data lines LON-WA1/FT3 has terminals 5 for two bus cables of a LonWorks network. Strip the insulation from at least two wires of the bus cable, insert the bare wires into the terminals. Fix the data cables to the casing using the wire clamping bracket. Within a bus segment connect the shield only at one point with the earth. Earthing the shield at every module will lead to interferential voltages. A maximum of 64 units can be operated in one network segment. To avoid cable reflections, network segments with a bus topology must be terminated at both ends with 120Ω bus terminators. In case of a free topology, a terminator is only required on one end. For wiring the LON bus we recommend cable type UTB-flex 4PR AWG 26/7 Cat5. Alternatively, one of the following cable types, which are recommended by LONMARK, may be used: Max. length with free topology: 500 m (after router) J-Y(ST)Y 2x2x0,8 (use only twisted pair for B+ and A-) 8471 or 85102, manufactured by Belden Level IV cable Max. length with free topology: 250 m (after router) TIA 568A Category 5 1 Supply voltage 2 Fire Chain 3 Actuators for fire dampers and smoke protection dampers 4 Capturing of the end positions 5 LON bus 6 Wire links for changing the voltage 7 Wire links Connecting the spring return actuator 3 Actuator 1: U Actuator 2: U Actuator 3: U Actuator 4: U If no wire links 7 are set, the outputs are volt-free Common contact (21, 31, 41, 51) = U+ For setting the supply voltage see page 10. Capturing of the end positions 4 Actuator 1: E1 > OPEN (S4 + S6) E2 > CLOSED (S1 + S2) Actuator 2: E3 > OPEN (S4 + S6) E4 > CLOSED (S1 + S2) Actuator 3: E5 > OPEN (S4 + S6) E6 > CLOSED (S1 + S2) Actuator 4: E7 > OPEN (S4 + S6) E8 > CLOSED (S1 + S2) Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014) 9
10 18 1 Commissioning PageHeaderToc and maintenance Connecting the supply voltage The connection is made on terminal block 1 (see illustration on page 9). 230 V AC or 24 V AC U+ = L U- = N PE = PEPE = PE 24 V DC U+ = +24 V U- = 0 V Setting the supply voltage Depending on the voltage range of the spring return actuator it may be necessary to use wire links to set the supply voltage. The voltage is set on terminal block 6 (see illustration on page 9). Refer to the pictures on this page for setting the voltage. Fig. 1 Inner wire links for setting 230 V AC Fig. 2 Outer wire links for setting 24 V AC or 24 V DC 10 Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014)
11 29 1 Description PageHeaderToc of functional objects nvirequest SNVT_obj_request nvipulse SNVT_switch nviactudrive SNVT_hvac_emerg Node Object FSDA Object (viermal vorhanden) nvofiledirectory SNVT_address nvopulsefb SNVT_switch nvostatus SNVT_obj_status nvoactudrivefb SNVT_hvac_emerg nvoactuposn SNVT_hvac_emerg The specification of the node is based on LonMark profile 11001, Fire Smoke Damper Actuator (FSDA), and has been extended to cover the special functions of the LON-WA1/FT3. The LON node consists of the node object and four FSDA objects. The FSDA objects consist of network variables and configuration parameters. All variables and parameters are based on standard network variables (SNVT) to facilitate the integration of LON-WA1/FT3 with a LonWorks network. nvoalarm2 SNVT_alarm_2 nvifirechain SNVT_hvac_emerg nvift_test SNVT_hvac_emerg nvofirechain SNVT_hvac_emerg nvoft_test SNVT_hvac_emerg Configuration SCPTmaxSendTime (nvoactuposn) SCPToffDely SCPTdirection SCPTdriveTime SCPTactuatorType SCPTinstallDate SCPTlocation SCPTmaintDate SCPTzoneNum Network variables Node object nvipulse SNVT type: SNVT_switch Function: Used to check a LON network. If input variable nvipulse = 1, the LON-WA1/FT3 module will after 1 second change output variable nvopulse from 0 to 1. If output variable nvopulse and input variable nvipulse of the next module form a chain, a trigger pulse is generated which can be read out at the end of the chain after N x 1 seconds. Valid values: Switch.state Function 1 Pulse signal High 0 Pulse signal Low SCPTdevMajVer SCPTdevMinVer SCPTmaxRcvTime (nviactudrive) SCPTholdTime SCPTmanfDate SCPToemType Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014) 11
12 19 1 Description PageHeaderToc of functional objects nvirequest SNVT type: SNVT_obj_request Function: Used to request information and execute actions in the node. The following parameters can be received: Parameter RQ_Normal RQ_Disabled RQ_Update_Status RQ_Update_Alarm RQ_Report_Mask RQ_Enable RQ_Clear_Alarm RQ_Self_Test Function Initialise node, reset status Disabled Request status, respond via nvostatus Disabled List of all status bits Disabled Disabled Self test of the node nvofiledirectory SNVT type: SNVT_address Function: Start address to access the file system, e.g. with the configuration variables. nvopulsefb SNVT type: SNVT_switch Function: see nvipulse. nvostatus SNVT type: SNVT_obj_status Function: Output variable, contains the reply to a previous request by nvirequest with the requested status bits: Status bits invalid_id invalid_request disabled comm_failure fail_self_test self_test_in_progress Function Invalid object ID requested or ID not available Invalid parameter Node without a function (not active) Communication failure Self test has failed Self test in progress FSDA object nviactudrive SNVT type: SNVT_hvac_emerg Function: Input used to control the damper blade position. The input variable can be addressed in intervals; the number of repeats must be defined with SCPTmaxRcvTime. Valid values: Value EMERG_NORMAL EMERG_FIRE Function Normal position Fire position nvifirechain SNVT type: SNVT_hvac_emerg Function: If there is a chain of modules (and hence fire dampers), the nvifirechain and nvofirechain variables can transmit a signal from the first to the last but will not release a damper. In the event of a fire, i.e. when nvifirechain or nviactuposn changes to FIRE, the fire chain relay contact opens. This effect can be used, for example, to switch off a ventilation system. Value EMERG_NORMAL EMERG_FIRE Function Normal Fire nvift_test SNVT type: SNVT_hvac_emerg Function: Input variable used to trigger a damper blade test. This moves the dampers to the Fire position (fire damper = CLOSED / smoke control damper = OPEN) and back to the Normal position (fire damper = OPEN / smoke control damper = CLOSED). The test mode is maintained for the time set with configuration parameter SCPTholdTime. The damper can then be moved back to its Normal position using variable nviactudrive. Valid values: Value EMERG_NORMAL EMERG_FIRE Function No test Test 12 Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014)
13 29 1 Description PageHeaderToc of functional objects nvoactudrivefb SNVT type: SNVT_hvac_emerg Function: Output variable that reflects the status of nviactudrive. Valid values: Same as for nviactudrive. nvoactuposn SNVT type: SNVT_hvac_emerg Function: Output variable that reflects the current damper blade position; if the position changes, the change is immediately reflected. Changes can also be transmitted in intervals; in this case the repeat intervals must be set using the SCPTmaxSendTime parameter. Valid values: Value EMERG_NORMAL EMERG_FIRE EMERG_NUL Function Normal position Fire position Zero position (between Normal and Fire) nvofirechain SNVT type: SNVT_hvac_emerg Function: see nvifirechain nvoft_test SNVT type: SNVT_hvac_emerg Function: Output variable used to check whether a damper blade test is required Valid values: same as for nvift_test. nvoalarm2 SNVT type: SNVT_alarm2 Function: Alarm output used to signal an incorrect function of the LON node to a monitoring system. The message includes detailed information on the incorrect function. A message is issued as soon as an error occurs. For possible messages see the table below: Table: nvoalarm2 AlarmType Description Priority Level Explanation AL_NO_COND Normal 16 Damper is in Normal position AL_FIR_TRBL AL_FIR_MONI- TOR_COND AL_ERROR Fire 4 Damper blade is in Fire position; parameter is also read out during a test run. TimeToNormal Position TimeToFire Position ReceiveUpdate Error 6 The damper blade requires more time than the DriveTime set in the Config tab in order to move from the Fire position to the Normal position. 6 The damper blade requires more time than the OffTime set in the Config tab in order to move from the Normal position back to the Fire position. 6 The input variable nviactudrive has not been updated within the MaxRcvTime set in the Config tab. LimitSwitchFault 6 The damper blade signals that it is in Normal position and in Fire position at the same time. Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014) 13
14 10 1 Installing PageHeaderToc the plug-in System requirements The TROX LON-WA1/FT3 plug-in is an LNS-enabled plug-in; it is based on the standard of the network management tool Lonmaker 3, service pack 8 and higher. Make sure that your personal computer meets the requirements before attempting to install the plugin. PC Operating system RAM Hard disk Screen LNS Recommended: Pentium III 1 GHz or faster Microsoft Windows 2000; Microsoft Windows XP; Microsoft Windows 7 at least 256 MB at least 30 MB Super VGA (1024x768) Version 3 with service pack 8 or higher Check the Device Resource Files before you attempt to install the plug-in. Device Resource Files (DRF) The Device Resource Files contain the definitions of the SNVTs. The application for LON-WA1/FT3 uses only standard network variables (SNVTs); this means that no manufacturer-specific definitions are required. However, the latest version of the Device Resource Files (Data Version 13.0 or higher) from LONMARK should have been installed on the computer. Installation Start Setup.exe. Follow the installation steps to install the setup program and install the files on your computer; a new TROX LNS PlugIn group of applications will be installed under Windows-Start/Programs. Do not change the standard directory. Registration You need to register the plug-in on your computer (just once). The plug-in can be registered during the installation procedure or later. To register the plug-in, go to Windows Start/Programs/TROX LNS PlugIn`s/WA1FT3 and select LON WA1/FT3.exe; follow the registration steps as prompted. Registration makes the plug-in available in the Windows system. You also need to register the plug-in for each project. 14 Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014)
15 211 1 Description PageHeaderToc of the plug-in Starting the plug-in Use the LonMaker network management tool to start the plug-in for a unit. To do so, select the node, then click right and select Configure. The plug-in is started for each new LON node, i.e. the plug-in is used to access each node. Do not open more than one plug-in at a time. The TROX LON-WA1/FT3 plug-in includes seven tabs. For a detailed description of each tab see the following pages. Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014) 15
16 11 1 Description PageHeaderToc of the plug-in Description of the tabs The following chapters describe the tabs and their functions. Main tab The Main tab is used to define whether the damper is a fire damper or a smoke control damper. It is also used to display the OEM type, the manufacturing date, the version number and the current pulse state. Damper Type: BSK / EK Used to define whether the damper is a fire damper (BSK) or a smoke control damper (EK). OEM type: Displays the OEM type. Manuf date: Displays the manufacturing date of the LON-WA1/FT3 software. Format: YYYY, MM, DD, HH, MM, SS Pulse in/out: Used to check a LON network. LOW = 0 HIGH = 1 Locked out: Used to activate or deactivate the error memory in LON-WA1/FT3. 16 Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014)
17 211 1 Description PageHeaderToc of the plug-in Damper1 to Damper4 tabs Used to display different states of the fire damper or smoke control damper. Inputs ActuDrive (red/green/yellow/grey): The colour indicates whether a command to close the damper has been signalled to the input. Display values: Colour Red Green Grey Meaning Damper will be moved to the Fire position. Damper will be moved to the Normal position LON-WA1/FT3 is offline FireChain (active/inactive): If there is a chain of modules, the FireChain input/output can transmit a signal from the first to the last but will not release a damper. In the event of a fire, i.e. when the FireChain input or the ActuPosn output changes to FIRE, the fire chain relay contact is opened. This effect can be used, for example, to switch off a ventilation system. FT-Test (active/inactive): Used to initiate a functional test of the damper. The dampers are then moved to the Fire position. Indicates if a test is running (active) or not (inactive). If a test is performed by pressing the test push button on the LON-WA1/FT3, the display will continue to show 'inactive'. Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014) 17
18 11 1 Description PageHeaderToc of the plug-in Outputs ActuDriveFb (red/green/yellow/grey): Used to display the state of input variable ActuDrive. The signal can be forwarded in this way. For the meaning of each colour see Inputs, ActuDrive. ActuPosn (red/yellow/green/grey): Indicates the state of the damper. Display values: Colour Red Green Yellow Grey Meaning Fire position Normal position Zero position (between Normal and Fire) LON-WA1/FT3 is offline FireChain (active/inactive): See FireChain input. FT-Test (active/inactive): Output variable used check whether a damper blade functional test is active. It does not matter whether the test has been initiated using the FT-Test input or using the test push button on the LON-WA1/FT3. Value Active Inactive Alarm Meaning Damper blade functional test is running No damper blade functional test is running AlarmType: Used to emit standard alarm messages (see p. 13, nvoalarm2). PriorityLevel: Used to display the priority of the alarm. SequenceNr.: Total number of alarm messages emitted since start/reset. This serves as an alarm history to check whether alarms have been signalled correctly. Description: Description of the alarm. 18 Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014)
19 211 1 Description PageHeaderToc of the plug-in Config1/2 and Config3/4 tabs Damper 1-4 MaxRcvTime (sec): Period of time within which a signal must be forwarded to the nviactudrive input. If the input is not updated accordingly, the damper moves to the Fire position and output variable nvoalarm2 emits alarm type AL_ER- ROR. If you enter 0 seconds, no check will be carried out. MaxSendTime (sec): Used to define the interval for forwarding output variable nvoactuposn. 0 seconds means that the function is switched off. TestHoldTime (sec): Used to define for how long a test run that has been initiated using variable nvift_test shall remain active before the damper is moved back to the Normal position by variable nviactudrive. DriveTime (sec): Used to indicate the maximum time that a damper requires to move from the Fire position to the Normal position. If the damper requires longer than the set time, it is moved back to the Fire position and output variable nvo- Alarm2 emits alarm type AL_FIR_MONITOR_COND. If you enter 0 seconds, no check will be carried out. Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014) 19
20 11 1 Description PageHeaderToc of the plug-in OffTime (sec): Used to indicate the maximum time that a damper requires to move from the Normal position to the Fire position. If the damper requires longer than the set time, output variable nvoalarm2 emits alarm type AL_FIR_ MONITOR_COND. If you enter 0 seconds, no check will be carried out. ActuatorType: Description of the damper actuator (up to 30 ASCII characters). ZoneNr: Used to enter a zone number that may help to indicate the location of the LON module. Location: Description of the location of the LON module (up to 30 ASCII characters). InstallDate: Used to enter the installation time of the node in the LON network. MaintDate: Used to enter the date and time of the last maintenance or inspection of the damper and/or actuator. 20 Operating manual LON-WA1/FT3 / Technical leaflet no. A (11/2014)
Automation and Systems Technology. LABCONTROL TFM/TPM User Manual TroxMConnect Operating Software. 1. Introduction 1. 2. Software Installation 2
1. Introduction 1 2. Software Installation 2 2.1 System Requirements 2 2.2 TroxMConnect Installation 2 2.3 Connection to the PC 3 3. TroxMConnect Description 4 3.1 Starting the Software 4 3.2 Layout 4
Modular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
EMBEDDED ACCESS CONTROL Hardware Installation Guide
EMBEDDED ACCESS CONTROL Hardware Installation Guide Lenel goentry Hardware Installation Guide, product version 1.00. This guide is item number DOC- ENHW-ENU, revision 1.003, April 2009 Copyright 2009 Lenel
SmartRouters Optionally with Bus Diagnostics RTRS RTRSD
SmartRouters Optionally with Bus Diagnostics RTRS RTRSD Data Sheet The present instruction is intended to support you concerning installation and use of the device. The information has been composed with
RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
DMX2PWM 9 Channel Dimmer Setup Manual
DMX2PWM 9 Channel Dimmer Setup Manual www.ecue.de DMX2PWM 9ch Dimmer - Setup Manual e:cue control GmbH An OSRAM Company Rev. 1.3_01/2010 DMX2PWM 9ch Dimmer - Setup Manual Table of Contents 1. Device Overview....................................4
MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS
MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.
Technical Information
Technical Information Interface with DDC 6 720 642 841-00.1RS Logamatic LON-Gateway For heating contractors during project planning 6 720 643 554 (11/2010) US/CA Contents Contents 1 Explanation of symbols
Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811
Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The
Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868
Instruction Sheet 10-2004 Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868 PowerCommand is a registered trademark of Cummins Inc. InPower
LonManager PCC-10 and ISA Protocol Analyzers Models 33100-00 and 33100-10
LonManager and Protocol Analyzers Models 33100-00 and 33100-10 Description The LonManager Protocol Analyzer provides LONWORKS manufacturers, system integrators, and end-users with a rich set of Windows
Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases
Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases
Operating instructions Diffuse reflection sensor with background suppression O1D101 O1D104 706114 / 00 01 / 2012
Operating instructions Diffuse reflection sensor with background suppression O1D101 O1D104 706114 / 00 01 / 2012 Contents 1 Preliminary note 3 1.1 Symbols used 3 1.2 Warning signs used 3 2 Safety instructions
INTELLIGENT CONTROL MODULE SA-2000-II HARDWARE MANUAL. Access Technologies International, Inc.
SA-2000-II HARDWARE MANUAL Access Technologies International, Inc. 1 Table of Contents 1. Introduction 3 2. Features 3 3. Specification 4 4. Identifying Supplied Parts 4 5. Panel Description 5 6. Connection
Safety Precautions WARNINGS
Safety Precautions This guide contains a variety of safety markings related to the safe and correct operation of the USB Data Transfer Cable. Be sure to read this guide and any related manuals carefully
User s manual FLIR VP50/VP52 Non-contact AC voltage detector
User s manual FLIR VP50/VP52 Non-contact AC voltage detector User s manual FLIR VP50/VP52 #T559851; r. AD/ 9134/9134; en-us Table of contents 1 Disclaimers... 1 1.1 Copyright... 1 1.2 Quality assurance...
Data sheet GIOD.1 Input/output module with CAN bus. ERP no.: 5204183. www.guentner.de. Data sheet GIOD.1 V_3.0
Data sheet GIOD.1 Input/output module with CAN bus ERP no.: 5204183 www.guentner.de Page 2 / 10 Contents 1 GIOD.1... 3 1.1 Functional description...3 1.2 Connections... 5 1.3 Electrical properties of...
Operating instructions Diffuse reflection sensor. OJ50xx 701396 / 01 07 / 2004
Operating instructions Diffuse reflection sensor OJ50xx 7096 / 0 07 / 004 Contents Preliminary note. Symbols used Function and features Installation. Installation of the supplied mounting fixture 4 4 Electrical
KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184
EN KNX TH65-AP Thermo-Hygrometer Technical specifications and installation instructions Item number 70184 Elsner Elektronik GmbH Control and Automation Engineering Herdweg 7 D 75391 Gechingen Phone +49
Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date: 2013-03-20
Documentation for KL2602 and KL2622 Two-channel Relay Output Terminals for 230 V AC / 30 V DC Version: 1.4 Date: 2013-03-20 Table of contents Table of contents 1 Foreword 1 1.1 Notes on the documentation
Combi B Alarm box. Mounting instructions
Combi B Alarm box Mounting instructions EN Mounting instructions Alarm box Combi B VdS, G113064, G113065, G113066 Table of Contents 1 Description... 3 2 System overview... 3 3 Structure... 3 3.1 Power
CelluLine CGW-TS GSM Cellular Gateway. Installation and Programming Manual
CelluLine CGW-TS GSM Cellular Gateway Installation and Programming Manual CelluLine CGW-TS GSM Cellular Gateway Installation and Programming Manual CGWTS-M001A Version 1, Release 1, December 2004 NOTICE
Shunt lock function 3066
Version: January 2004 Contents Alarm System Activation unit Deactivation unit Digital locking cylinder or Smart Relay 1.0 Method of Operation 4 1.1 General 4 1.2 Turning the Alarm System On 4 1.3 Turning
Functional Profile: Heat Pump with Temperature Control
Heat Pump with Temperature Control: 8051 LONMARK Functional Profile: Heat Pump with Temperature Control LONMARK Functional Profile: Heat Pump with Temperature Control 1 8051-10 1996, LONMARK Interoperability
Digital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
Secure Keypads for access control
torm Secure Keypads for access control Strike Master Read this manual carefully before attempting to install, program or operate the STORM AXS Strike Master Keypad. After installation the Command Summary
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
ADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
IntesisBox KNX - LON
IntesisBox KNX - Gateway for integration of devices into KNX systems. Integrate Air Conditioning from the main manufacturers (DAIKIN, Mitsubishi Electric, Mitsubishi Heavy Industries, Toshiba, Fujitsu,
Drayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
Inwall 4 Input / 4 Output Module
Inwall 4 Input / 4 Output Module IO44C02KNX Product Handbook Product: Inwall 4 Input / 4 Output Module Order Code: IO44C02KNX 1/27 INDEX 1. General Introduction... 3 2. Technical data... 3 2.1 Wiring Diagram...
IntesisBox ASCII Server - LON
IntesisBox ASCII Server - LON Gateway for integration of LON devices into ASCII enabled control systems. Integrate Air Conditioning from the main manufacturers (DAIKIN, Mitsubishi Electric, Mitsubishi
Product and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE
Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE TABLE OF CONTENTS INTRODUCTION...1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.1.1 Apple Mac Requirements 1.1.2 PC Requirements 1.1.3 Supported PCIe Cards 1.2 PACKAGE
3x cinch/s-video socket Order no.: 33 1532 xx. USB/3.5 mm audio socket Order no.: 33 1539 xx. VGA socket Order no.: 33 1540 xx
3x cinch/s-video socket Order no.: 33 1532 xx USB/3.5 mm audio socket Order no.: 33 1539 xx VGA socket Order no.: 33 1540 xx VGA socket with screw-in lift terminals Order no.: 33 1541 xx High definition
Operation and Installation Manual
Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control
Radiant Temperature Sensor TY7321
AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional
Application/Connection Examples
This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.
User Guide. HDMI Active Cable Extender. DVI-7370c
User Guide HDMI Active Cable Extender DVI-7370c TABLE OF CONTENTS SECTION PAGE PRODUCT SAFETY...1 PRODUCT LIABILITY...1 1.0 INTRODUCTION...2 2.0 SPECIFICATIONS...3 3.0 PACKAGE CONTENTS...4 4.0 CONNECTING
R60 USB to CAN interface Manual (1.5 EN)
R60 USB to CAN interface Manual (1.5 EN) General information R60 USB to CAN interface Manual Version 1.5 EN, 02/2010, DOC01586 Copyright 2010 by ; all rights reserved. Eugen-Adolff-Strasse 134, D-71522
Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A
COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850
PCS0100en 02.2008. Persy Control Services B.V. Netherlands
P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for
CMC III Temperatur-/ Feuchtesensor CMC III Temperature/ Humidity Sensor
CMC III Temperatur-/ Feuchtesensor CMC III Temperature/ Humidity Sensor 7030.111 Montage-, Installations- und Bedienungsanleitung Assembly and operating instructions Foreword Foreword Dear Customer, Thank
When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only
Taurus Super-S3 LCM. Dual-Bay RAID Storage Enclosure for two 3.5-inch Serial ATA Hard Drives. User Manual March 31, 2014 v1.2 www.akitio.
Dual-Bay RAID Storage Enclosure for two 3.5-inch Serial ATA Hard Drives User Manual March 31, 2014 v1.2 www.akitio.com EN Table of Contents Table of Contents 1 Introduction... 1 1.1 Technical Specifications...
2. + 4. + 6. Actuator Plug-In
2. + 4. + 6. Actuator Plug-In Description / Documentation # Tools-007-E-1 nvivalue SNVT_xxx nvovalue SNVT_xxx LONWORKS LONWORKS MP-BUS Data communication / Tools / Kem / 07.01.02 1 / 10 Contents Page 1.
Smoke exhaust systems
1 Fire zone, e.g. hall 2 Smoke exhaust zone, separated by smoke curtains Natural and mechanical smoke extraction General information 3 Natural smoke and heat exhaust vent 4 Air inlet opening or wake max.
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Keysight N4877A Clock Data Recovery and Demultiplexer 1:2
Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 Getting Started Getting Started with the Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 You only need a few minutes to get started
Operating Instructions
Operating Instructions Kühn Controls AG, Gräfenhäuser Str. 14, D-75305 Neuenbürg, Germany Tel. +49 (0)7082-94 00 00 www.kuehn-controls.de [email protected] Fax +49 (0)7082-94 00 01 Content 1. SMS
Electronic Control Devices The European Product Catalogue 2007
FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,
PD 100A. Printing data system
PD 100A Printing data system Operating instructions ENGLISH IMPORTANT: Read these instructions carefully before installing and using the device; do not forget following all additional information. Keep
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
KNX L. Brightness Sensor. Technical specifications and installation instructions Item number 70119
EN KNX L Brightness Sensor Technical specifications and installation instructions Item number 70119 Elsner Elektronik GmbH Control and Automation Engineering Herdweg 7 D 75391 Gechingen Phone +49 (0) 70
ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user
For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
User Manual Software for DSL Digital Speed Switch
User Manual Software for DSL Digital Speed Switch Software version from 1.0.1 Baumer Hübner GmbH Max-Dohrn-Str. 2+4 D-10589 Berlin Phone +49 (0)30 690 03-0 Fax +49 (0)30 690 03-104 [email protected]
Processor. Installation Guide
Processor Installation Guide Land Instruments International Dronfield, S18 1DJ England Telephone: (01246) 417691 Facsimile: (01246) 410585 Email: [email protected] Internet: www.landinst.com
4-Port Pocket. USB KVM Switch with USB 2.0 Hub
4-Port Pocket USB KVM Switch with USB 2.0 Hub Manual - 1 - Index 1. INTRODUCTION... 3 1.1 FEATURES... 3 1.2 PHYSICAL DIAGRAM... 4 1.3 PACKAGE CONTENTS... 4 2. SPECIFICATIONS... 5 2.1 ERAL... 5 2.2 LED
F453. TiF453. User guide 10/11-01 PC
F453 TiF453 User guide 10/11-01 PC 2 TiF453 User guide Contents 1. Hardware and Software requirements 4 2. Installation 4 1.1 Minimum Hardware requirements 4 1.2 Minimum Software requirements 4 3. Fundamental
KNX R. Rain Sensor. Installation and Adjustment
EN KNX R Rain Sensor Installation and Adjustment 1 Content 1. Description... 3 1.1. Technical specifications... 3 2. Installation and commissioning... 4 2.1. Installation notes... 4 2.2. Location... 4
IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.
THERMAWAVE CERAMIC HEATER Model HZ-850 Series Model HZ-860 Series IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. Warning Failure to
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
REGULINE 600VA / 1000VA REGULATOR USER MANUAL
REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate
INSTALLATION GUIDE 1
INSTALLATION GUIDE 1 Setting information MAC-558IF-E address(mac) MAC-558IF-E serial number(id) MAC-558IF-E code(pin) Indoor unit model name Indoor unit serial number Outdoor unit model name Outdoor unit
Product Information. Gateway For Connecting EnDat Encoders to PROFIBUS-DP
Product Information Gateway For Connecting EnDat Encoders to PROFIBUS-DP April 2012 PROFIBUS Gateway For Connecting EnDat Encoders Encoders with EnDat interface for connection via gateway All absolute
ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01
ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions
Single Station Remote Alarm
ADI 5106G Certified ISO 9001:2000 Single Station Remote Alarm 529 5106-01-120 529 5106-01-220 INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Controls Corporation
The GV-I/O Box 8 Ports provides 8 inputs and 8 relay outputs, and supports both DC and AC output voltages.
GV-I/O Box 8 Ports The GV-I/O Box 8 Ports provides 8 inputs and 8 relay outputs, and supports both DC and AC output voltages. Key Features 8 inputs and 8 outputs are provided. Up to 9 pieces of GV-I/O
Point of view HDMI Smart TV dongle Mini RF Keyboard
Point of view HDMI Smart TV dongle Mini RF Keyboard English Contents Contents... 1 General notices for use... 2 Disclaimer... 2 Box Contents... 2 1. HDMI TV dongle... 3 1.1. Product display... 3 1.2. Instructions
Charge Controller CC611/CC612 Preliminary datasheet
Preliminary datasheet Preliminary datasheet CC61x_D00xxx_00_D_XXE_preliminary/04.2015 Product description The ender charge controller CC611 is the main component of a charging point and is designed for
PU-USBX. USB over Ethernet Extender OPERATION MANUAL
PU-USBX USB over Ethernet Extender OPERATION MANUAL Safety Precautions Please read all instructions before attempting to unpack or install or operate this equipment, and before connecting the power supply.
POINTS POSITION INDICATOR PPI4
POINTS POSITION INDICATOR PPI4 Advanced PPI with Adjustable Brightness & Simplified Wiring Monitors the brief positive operating voltage across points motors when they are switched Lights a corresponding
ETS4 Diagnostics. KNX Association
ETS4 Diagnostics Table of Contents 1 Diagnostics and fault location... 3 2 Diagnostics: Individual addresses...... 4 2.1 Devices in Programming Mode... 4 2.2 Checking if an address exists and locating
ACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
SIMATIC S7-300. Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01
SIMATIC S7-300 Getting Started for First Time Users Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01 Safety Guidelines This manual contains notices you have to observe in order to ensure your personal
Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR
Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions
INDEX. Trademarks All name and product s trademarks mentioned below are the property of their respective companies.
USB2.0 EASY IDE ADAPTER INDEX Trademarks ---------------------------------------------------------------------------- Introduction ---------------------------------------------------------------------------
SOFTWARE EasyComm (Code 775 044) USER S MANUAL (Code M 981 357/00 - A) 1997-2000 CIRCUTOR, S.A. All rights reserved
SOFTWARE EasyComm (Code 775 044) USER S MANUAL (Code M 981 357/00 - A) 1997-2000 CIRCUTOR, S.A. All rights reserved EasyComm INDEX 1. Introduction... Page 2 2. EasyComm contents... Page 2 3. Main features...
COMPLETE MANUAL. Version: Optic. September 2015 (English), version 1.0. EnergyOT Optic Developed and Manufactured by Genoa Spark, lda Made in Portugal
Version: Optic COMPLETE MANUAL September 2015 (English), version 1.0. EnergyOT Optic Developed and Manufactured by Genoa Spark, lda Made in Portugal Specifications are subject to change without notice.
Introduction. Page 2 / 9
Installation Manual English, US, version 1.1, as of November 13th, 2015 2015 Smappee NV. All rights reserved. Specifications are subject to change without notice. All product names are trademarks of their
Short Range Wireless Switch System Handheld 8 Installation and Operations Guide
Phone: (866) 701-1146 Fax: (425) 216-7558 www.remotecontroltech.com Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Introduction... 2 Before Installation... 2 Receiver Installation...
KNX. Siemens Building Technologies HVAC Products. Synco Konnex bus. For devices of the Synco 700 / RXB ranges
7 7Z0 Synco Konnex bus For devices of the Synco 700 / RXB ranges KNX The Konnex bus (short KNX) unites the three existing bus technologies EIB (European Installation Bus also called Instabus), BatiBUS,
1. Overview. WPT Wireless Range Tester Kit User Manual Doc No. 910-00009-01 Rev 05. 1.1. Components. 1.2. Prerequisites for Site Survey
1. Overview The Cypress Envirosystems Wireless Pneumatic Thermostat (WPT) retrofits an existing pneumatic thermostat to provide Direct Digital Control (DDC) like zone control functionality at a fraction
AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T
Product Instruction Manual Accona AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T Panel heater v16.5/5 Version 3.2 Jan 2015 Contents 1. Important safety points 2. Installation 2.1. Wall mounting
Power supply unit Model: PAC-SC50KUA
Building Air Conditioning Control System Power supply unit Model: PAC-SC50KUA Installation Manual Contents 1. Safety precautions... 1 2. Product feature... 2 1. Specification... 2 2. Appearance... 2 3.
Network Camera. Quick Operation Guide V4.0.1
Network Camera Quick Operation Guide V4.0.1 Thank you for purchasing our product. If there are any questions, or requests, please do not hesitate to contact the dealer. This manual applies to DS-2CD8253F-EI(Z),
LN-Builder 3.4 Installation Instructions
LN-Builder 3.4 Installation Instructions Code No. LIT-12011532 Issued June 17, 2013 Supersedes January 30, 2013 Refer to the QuickLIT website for the most up-to-date version of this document. Document
IO-RM3 3-Stage Relay Module
Page 1 of 6 IO-RM3 3-Stage Relay Module Features: Benefits: Link selectable modes binary, heat/cool, staged or sequenced On/Off/Auto links for ease of commissioning DIN Rail mounting Fault finding LED
How To Use A Power Supply On A Powerline 2.2 (Ai)
KNX/EIB Product documentation Issue: 05.08.2010 629x1220 Push button sensor 3 comfort 1-gang Push button sensor 3 comfort 2-gang (1+1) Push button sensor 3 comfort 3-gang Push button sensor 3 comfort 4-gang
Sense Components. Sense monitor. Antenna assembly. External mounting kit Current sensors. Download the Sense app. Go to sense.com/app.
Sense Components Sense monitor Antenna assembly External mounting kit Current sensors Download the Sense app. Go to sense.com/app Power cable Technical Specifications Sense is a home energy monitoring
Repeaters and Mimics Data Sheet
Repeaters and Mimics Data Sheet IDR series repeaters and mimics allow vital information from a Notifier fire system to be communicated to points around a building remote from the fire alarm control panel.
BroadBand PowerShield. User Manual
BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains
Data logger. Installation and operating instructions. Read carefully before installation, commissioning and operation.
Data logger Installation and operating instructions SOREL Connect Read carefully before installation, commissioning and operation 1.1. - Specifications Description of data logger Electrical specifications:
Installation and Operating Instructions for ROBA -takt Control Unit Type 014.000.2
Manufacturer s Declaration This product is intended f installation in a machine system, based on the machine directive 006/4/EC. It is fbidden to start use of the product until the machine system into
SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program
Preface Contents SIMATIC NET CP 243-2 AS-Interface Master Manual Technical Description and Installation Instructions Interface to the User Program 2 in the S7-200 CPU Access to the Data of the AS-i Slaves