Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior



Similar documents
Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

Research on the Air Conditioning Water Heater System

Testing methods applicable to refrigeration components and systems

Experimental Analysis of an Automotive Air Conditioning System With Two-Phase Flow Measurements

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July Prepared by

Experimental Evaluation Of The Frost Formation

Development and testing of a multi-type air conditioner without using AC inverters

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Cooling kw Heating kw

Chapter 3.4: HVAC & Refrigeration System

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

Natural geothermal energy.

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

Inverter and programmable controls in heat pump applications

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

High Pressure Ammonia Systems New Opportunities

UNIT 2 REFRIGERATION CYCLE

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

Mohan Chandrasekharan #1

Aspects of Household Cooling Technology

Scroll compressors for Low GWP Heat Pumps using R290 natural refrigerant. Pierre Ginies, Next Heat Pump Generation 2015

Isentropic and Volumetric Efficiencies for Compressors with Economizer Port

Why and How we Use Capacity Control

Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange

Capacity Control of Residential Heat Pump Heating Systems

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

Refrigerant Charge and Ambient Temperature Effects on the Refrigeration Cycle of a Small Capacity Food Freezer

Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

HVAC Efficiency Definitions

FEASIBILITY OF A BRAYTON CYCLE AUTOMOTIVE AIR CONDITIONING SYSTEM

Cylinder Head Gasket Contact Pressure Simulation for a Hermetic Compressor

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System

Energy savings in commercial refrigeration. Low pressure control

Analytical Study on the Performance Characteristics of a Liquid Injection Refrigeration Cycle.

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL

Thermodynamics - Example Problems Problems and Solutions

How To Calculate The Performance Of A Refrigerator And Heat Pump

Design of a Heat Pump Assisted Solar Thermal System

The Second Law of Thermodynamics

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

HP switch LP switch Discharge thermo Comp. Surface thermo

MICRO-COGENERATION AND DESALINATION USING ROTARY STEAM ENGINE (RSE) TECHNOLOGY

HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE

How To Know If A Refrigeration System Is Efficient

How Ground/Water Source Heat Pumps Work

Simulation of a small size solar assisted adsorption air conditioning system for residential applications

Ambient Energy Fraction of a Heat Pump

Model-Based Approach for Optimizing a Data Center Centralized Cooling System

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

In Situ Performance Evaluation of Industrial Reciprocating Air Compressors

UR...3 URX CF...7 URHE CF Heat recovery unit. Heat recovery unit with refrigerant circuit( cfm)

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

AIR-COOLED CHILLERS APPLIED SYSTEMS. EUWA*5-24KAZW - EUWY*5-24KAZW -

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES

ADVANCES IN SUPERMARKET REFRIGERATION SYSTEMS

The natural ombination

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy

CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors

New Trends in the Field of Automobile Air Conditioning

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

Impact of Control System Technologies on Industrial Energy Savings

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

Daikin Altherma hybrid heat pump. The natural combination

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Analysis of Heat Pump Condenser's Performance using the Mathematical Model and a Numerical Method

york air-conditioning products Residential & VRF News 2015

SOLAR COOLING WITH ICE STORAGE

APPLIED THERMODYNAMICS. TUTORIAL No.3 GAS TURBINE POWER CYCLES. Revise gas expansions in turbines. Study the Joule cycle with friction.

Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30,

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING. Campus du Sart Tilman, B49, B-4000 Liège, Belgium

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

A Balanced View of Reciprocating and Screw Compressor Efficiencies

Field test of a novel combined solar thermal and heat pump system with an ice store

Combination Ductless Heat Pump & Heat Pump Water Heater Lab and Field Tests

How To Save Energy With High Pressure Control

Commercial Hot Water. Make a difference...

8. Heat pumps, heat pipes, cold thermal energy storage

Over 30% 2-40 TR. Air Conditioning Danfoss compressors For comfort and precise cooling. energy savings

Application Engineering

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 21 Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior Hatef Madani Royal Institute of Technology Navid Ahmadi Royal Institute of Technology Joachim Claesson Royal Institute of Technology Per Lundqvist Royal Institute of Technology Follow this and additional works at: http://docs.lib.purdue.edu/iracc Madani, Hatef; Ahmadi, Navid; Claesson, Joachim; and Lundqvist, Per, "Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior" (21). International Refrigeration and Air Conditioning Conference. Paper 163. http://docs.lib.purdue.edu/iracc/163 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2241, Page 1 Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior Hatef MADANI*, Navid AHMADI, Joachim CLAESSON, Per LUNDQVIST Department of Energy Technology, Division of Applied Thermodynamics and Refrigeration Royal Institute of Technology, SE-1 44 Stockholm, Sweden * Email: hatef.madani@energy.kth.se, Tel: +46 ()8 79 86 53 ABSTRACT Capacity control with variable speed compressors in heat pump systems is one of the techniques having a potential for efficiency improvement in heat pump systems. It is anticipated that the compressor and inverter efficiency are influenced by changes of the compressor speed. The present experimental study evaluates these losses in a variable speed heat pump system. The experimental results show that increasing the compressor speed reduces the heat pump COP up to 3%. The inverter loss increases as the compressor speed is increased, although the inverter loss as the percentage of the total compressor power decreases. Increasing the compressor speed increases the pressure ratio from 2.7 to 5.8, increasing the loss due to the pressure ratio mismatch drastically. Finally, the highest total isentropic efficiency of the compressor is obtained when the compressor frequency is close to 5Hz. 1. INTRODUCTION Brine to water heat pump systems like Ground Source Heat Pumps (GSHPs) are one of the common and fast growing systems for heating the buildings in USA and European countries. As of 25, there are over a million units installed worldwide providing about 15 GW of thermal capacity (Rybach 25) and the annual global increase has been more than 1% over the last ten years (Lund et al. 24). Therefore, any improvement in the efficiency of these systems can save a considerable amount of energy and decrease the greenhouse emissions to a large extent. Capacity control by introducing variable speed compressors in heat pump systems is found by some researchers as one of the techniques having a potential for efficiency improvement in GSHPs. The speed of the inverter-driven compressor is modulated by the aid of a control algorithm so that the heat output from the heat pump unit offsets the load of the building; consequently, the discrepancy between the heat supply and the heat demand (in the building) can be reduced. Zhao et al.(23) made a comparison among variable speed capacity controls and three other control methods for GSHPs and concluded that changing the compressor speed is the preferred method; Furthermore, Madani et al. (21) conducted a comparative analysis between on/off controlled and variable capacity heat pump system and they found that variable speed compressors heat pump systems yields a better performance compared to constant speed on/off control when the ambient temperature is below the balance point and the auxiliary heater operates. The annual modeling of both on/off and variable speed systems done by Madani et al.(21) showed that when the on/off controlled HP system is designed to cover about 9% of the annual energy need and the auxiliary heater takes care of the rest, the seasonal performance factor of the system may be improved about 1% by switching to a variable speed HP system. However, Karlsson and Fahlen (27) concluded from their research that despite improved performance at part load (also shown by Qureshi and Tassou,1996), the variable-speed controlled heat pump did not improve the annual efficiency compared to the intermittently operated heat pump. Karlsson (27) suggested that it is mainly due to the inefficiencies of the inverter, the electrical motor of the compressor, and the need for control of pumps used in the heating and ground collector systems (Karlsson 27). The experimental study done by Cuevas and Lebrun (29) showed that in the variable speed scroll compressor, the inverter efficiency varies between 95% and 98% when the

2241, Page 2 compressor electrical power varies between 1.5 and 6.5 kw. It is also found that the additional electrical motor losses induced by the presence of the inverter are negligible (Cuevas and Lebrun 29). The present study aims at making an experimental analysis about the loss behavior in the variable speed compressor and frequency inverter when the compressor speed varies. The present paper provides an understanding how changing the compressor speed influences the frequency inverter losses and the total isentropic efficiency of the compressor; It would then be possible to evaluate the impact of the inverter and compressor loss on the annual performance of the heap pump system. 2. Methodology The experimental setup built for the measurements consists of a variable speed heat pump unit, liquid pumps, a storage tank, two plate heat exchangers, valves, and a data acquisition system (see fig.1). In the variable speed heat pump unit, two brazed plate heat exchangers are used as the evaporator and condenser. The scroll compressor is equipped with a frequency inverter in order to facilitate various compressor speeds. An electronic expansion valve maintains the superheat temperature of the heat pump unit at 5ºC. When the speed of the compressor is changed, the following parameters are maintained constant: Approach heat sink temperature to condenser called load side temperature Approach heat source temperature to evaporator called source side temperature Fig. 1. The schematic of the experimental setup Parameters which are measured and used in the present study are: The compressor power before and after the frequency inverter The compressor speed The heating and cooling capacity of the heat pump unit The condensation and evaporation pressure Superheat and sub-cooling temperature Furthermore, the built-in volume ratio of the compressor together with the constant and variable parts of the electromechanical losses, are estimated by a compressor model (section 3.4). The built-in volume ratio found from the modeling is used to calculate the compression power in the compressor and to evaluate the loss due to the mismatch between the actual and the built-in pressure ratio.

2241, Page 3 3. Result 3.1 The heat pump heat capacity and Coefficient Of Performance (COP) Fig. 2-a and 2-b shows the heat pump heat capacity and COP (defined as the ratio of heat capacity to compressor power) when changing the compressor frequency. R134a and R47C is used as the refrigerant in fig. 2-a and2-b, respectively. The source/load side temperatures are held constant at 4.5ºC/26ºC in all the operating points presented in both figures. As may be seen from fig. 2-a, varying compressor speed from 3 Hz to 1 Hz increases the heat capacity from 5 kw to 12 kw and decreases the COP from 4.4 to 2.9. Furthermore(fig. 2-b) when the R134a is replaced by R47C, the heat pump yields higher heat capacity and lower COP. When the compressor speed increases from 3 Hz to 9 Hz, the heat capacity of the system with R47C increases from 6.5kW to 14kW and system COP decreases from 3.9 to 2.7 (see fig.2-b). R134a R47C 14. 4.5 14. 4.5 Heat pump heat capacity (kw) 12. 1. 8. 6. 4. 2. Heat capacity (kw) COP 4 3.5 3 2.5 2 1.5 1.5 Heat Pump COP Heat Pump heat capacity (kw) 12. 1. 8. 6. 4. 2. heat capacity (kw) COP 4. 3.5 3. 2.5 2. 1.5 1..5 Heat Pump COP. 2 4 6 8 1 12.. 2 4 6 8 1 a) b) Fig. 2. The heat pump heat capacity (kw) and COP versus compressor frequency when R134a (a) and R47C (b) is used as the refrigerant 3.2 The compressor power before and after inverter Fig. 3-a and 3-b present the compressor power measured before and after the inverter when R134a or R47C is used as the refrigerant, respectively. The source/load side temperatures for both cases are held constant at 4.5ºC/26ºC. As may be seen from fig. 3-a, for the system with R134a, changing the compressor speed from 3Hz to 1Hz increases the compressor power from 1 kw to 4.2 kw. For the system with R47C, the compressor power increases from 1.7kW to 5.1kW by increasing the compressor frequency from 3Hz to 9 Hz (see fig. 3-b). Compressor Power (kw) 5 4 3 2 1 R134a Power before the inverter power after the inverter Compressor power (Kw) R47C Power before the inverter (kw) 5. 4. 3. 2. 1. power after the inverter 2 4 6 8 1 12. 2 4 6 8 1 a) b) Fig. 3. Compressor power (kw) measured before and after inverter when R134a (a) or R47C (b) is used as the refrigerant. The source/load side temperatures are 4.5ºC/26ºC for all the operating points.

2241, Page 4 3.3 The inverter loss versus compressor frequency Fig. 4 and fig.5 shows how the inverter loss changes when the compressor frequency increases from 3Hz to 1 Hz for two different set of source/load side temperatures (square and triangle dots). As it may be observed from fig. 4- a, with R134a the inverter loss varies between 1 W and 2 W with a peak at about 85 Hz. Fig. 4-b shows that the ratio of the inverter loss to the total compressor power (the power measured before the inverter) decreases from 11% to 3% when the frequency changes from 3 to 1 Hz. The trend for the system with R47C is very similar, as it can be seen from fig.5. The inverter loss varies between 13 W and 25 W. Furthermore, as it is presented in fig. 5- b, the higher the compressor speed, the lower the ratio of inverter loss to the total compressor power. Inverter loss(kw).25.2.15.1.5 4.5 ºC/26 ºC as the source/load side temps 1.5 ºC/21.5 ºC as the source/load side temps 2 4 6 8 1 12 2 4 6 8 1 12 a) b) Fig. 4. The measured inverter loss in kw (a) and in % of the total compressor power (b) when the frequency varies between 3Hz and 1Hz: the heat pump with R134a Inverter loss (kw).3.25.2.15.1.5 2 4 6 8 1 a) b) Fig. 5. The measured inverter loss in kw (a) and in % of the total compressor power (b) when the frequency varies between 3Hz and 9Hz: the heat pump with R47C Inverter loss(% of total compressor power) Inverter loss (% of total compressor power) 12 1 8 6 4 2 1 9 8 7 6 5 4 3 2 1 4.5 ºC/26 ºC as the source/load side temps 1.5 ºC/21.5 ºC as the source/load side temps 2 4 6 8 1 3. Compressor modeling A semi-empirical of the compressor is made in order to estimate the built-in volume ratio, the compression power of the compressor (at every operating point), and the variable and constant part of the electromechanical losses in the compressor. Winandy (1999) obtained equation (1) to calculate the compression work, assuming an ideal gas: - - - (1)

2241, Page 5 is the built-in volume ratio, i.e. the ratio between the suction and discharge volume. The built-in volume ratio is a compressor characteristic based on the geometry and under idealized condition, it is related to built-in pressure ratio given by equation (2). (2) The difference between the built-in pressure ratio and the actual pressure ratio (the ratio of condensation pressure to evaporation pressure) can influence the compressor efficiency, as it will be discussed later in this section. Furthermore, the swept volume flow can be determined by the equation (3): n is the compressor speed in rpm. It is possible to estimate the compression power in the compressor by combining Equation (1) and (3). Moreover, as Winandy (1999) and Cuevas et al.(21) suggested, the total compressor power comprises of the internal compression power and the compressor electromechanical losses which also can be divided into two terms: constant part and variable part which varies by the internal compression power, as given in equation (4): (3) (4) where is the parameter representing the variable part of electromechanical losses, and is the constant part of electromechanical loss (kw). Consequently,,, and built-in volume ratio are the three parameters which are found by the semi-empirical parameter estimation model (see fig.6). Table 1 presents the results of the modeling for the analyzed heat pump system with two different refrigerants: R134a and R47C. The difference between the built-in volume ratios for the heat pump with R134a and R47C can be due to the uncertainties in the compressor model (about 6%). The measured compressor power The measured condensation pressure The measured evaporation pressure The measured compressor speed minimization of the error between the calculation and measurment using the generic method Fig. 6. The flowchart of compressor modeling Built-in volume ratio W loss Table 1. Results of the modeling for the analyzed heat pump system in two different cases: the heat pump uses either R134a or R47C as the refrigerant The estimated parameter The heat pump with R134a The heat pump with R47C Built-in volume ratio 2.17 2.4.72.86.245.44 Fig.7 shows the influence of the mismatch between the built-in and actual pressure ratio on the isentropic efficiency when the actual pressure ratio changes by varying the compressor speed. Fig. 7 is made based on equation (5) suggested by Granryd (25) in order to estimate the losses due to the fact that the actual pressure ratio for compression does not match the built-in pressure ratio. As fig.7 depicts, the compressor tested in the present study is designed in a way that the loss due to the pressure ratio mismatch is very low when the actual pressure ratio is close to 2.7 and it decreases when the pressure ratio increases from 2.7 to 5.8. It is predicted that the - - - - - - - - (5)

2241, Page 6 1 R134a R47C.95.9.85.8 built_in.75.7.65.6.55.5 1 2 3 4 5 6 7 Pressure ratio (condensation pressure/evaporation pressure) Fig. 7. The influence of built-in volume ratio on isentropic efficiency of compressor 3.5 The compressor total isentropic efficiency Fig. 8 present the total isentropic efficiency of the compressor versus the compressor frequency for two sets of source/load side temperatures, when R134a (fig.8-a) or R47C (fig.8-b) is used as the refrigerant. This efficiency, in equation (6), covers all kind of losses including both constant and variable parts of electromechanical losses, presented in equation (3), and also the losses due to the pressure ratio mismatch (shown in figure 7). (6) As it is shown in fig.8, the total isentropic efficiency of the compressor changes about 11% when the compressor frequency changes from 3Hz to 1Hz. Furthermore, fig. 8 shows that the highest total isentropic efficiency occurs when the compressor frequency is between 5Hz and 55Hz for all the presented cases. Total isentropic efficiency of compressor.62.61.6.59.58.57.56.55.54.53 4.5 ºC/26 ºC as the source/load side temps 1.5 ºC/21.5 ºC as the source/load side temps.52 2 4 6 8 1 12.57 2 4 6 8 1 Fig. 8. The variation in the total isentropic efficiency of the compressor based on the changes in the compressor frequency when R134a (a) or R47C (b) is used as the refrigerant Total isentropic efficiency of compressor.67.66.65.64.63.62.61.6.59.58 4.5 ºC/26 ºC as the source/load side temps 5 ºC/3 ºC as the source/load side temps

2241, Page 7 4. Conclusion The present study mainly aims at analyzing the loss behavior in the variable speed compressor and frequency inverter when the compressor speed varies. To make the analysis, an experimental setup is made and measurements are done for two different cases: The heat pump uses R134a as the refrigerant The heat pump uses R47C as the refrigerant When the compressor speed is changed, other boundary parameters such as source/load side temperatures are kept constant. The measurement results showed that increasing the compressor speed from 3 Hz to1hz lowers the heat pump COP up to 3% for both refrigerants used. Furthermore, the inverter loss increases quantitatively by increasing the compressor speed. For example, for the heat pump with R47C, increasing the compressor frequency from 3Hz to 9 Hz almost doubles the amount of inverter loss (the inverter loss increases from 13W to 25W) although the inverter loss as the percentage of the total compressor power decreases from 8% to 4%. The compressor loss due to the mismatch between the actual pressure ratio and the built-in pressure ratio is found based on the compressor built-in volume ratio of the compressor. A semi-empirical model of the compressor is made to obtain the built-in volume ratio for the compressor studied in the present paper. Then, the loss due to the pressure ratio mismatch is studied and it is found that this loss rises from 1% to 2% when the pressure ratio increases from 2.7 to 5.8. Finally, the total isentropic efficiency of the compressor which represents all kinds of losses in the compressor was analyzed at different compressor speeds. The results showed that the total isentropic efficiency of the compressor shows a maximum value when the compressor frequency is close to 5Hz. This efficiency changes about 11% when the compressor frequency varies between 3Hz and 1Hz. NOMENCLATURE n Speed (rpm) Subscripts P Pressure (kpa) cons constant V Volume ( ) comp compression Volume flow rate ( ) ex exhaust W Work (J) isen isentropic Power (kw) sup supply Polytropic exponent ( ) Efficiency ( ) Built-in volume ratio (-) Built-in pressure ratio (-) REFERENCES Cuevas, C., Lebrun, J., 29. Testing and modelling of a variable speed scroll compressor. Applied thermal engineering, vol. 29:p. 469 478. Cuevas, C., Lebrun, J., Lemort V., Winandy, E., 21. Characterization of a scroll compressor under extended operating conditions. Applied thermal engineering, vol. 3:p. 469 478. Granryd, E., Lundqvist, P., et al. 25, Refrigeration Engineering, Department of Energy technology, Stockholm, Sweden, p.7-31. Karlsson, F., Fahlen, P., 27. Capacity-controlled ground source heat pumps in hydronic heating systems. International Journal Of Refrigeration, vol. 3:p. 221-229. Karlsson, F., 27. Capacity control of residential heat pump heating system. Department of Energy and Environment. Göteborg, Chalmers University of Technology. Doctoral thesis.

2241, Page 8 Lund, J., Sanner, B. et al. 24. Geothermal (Ground Source) Heat Pumps, A World Overview. Geo-Heat Centre Quarterly Bulletin, Klmath Falls, Oregon: Oregon Institute of Technology, vol. 25, no. 3: p. 1 1. Madani, H., Claesson, J., Lundqvist, P., 21. Capacity control in ground source heat pump systems- Part I:modeling and simulation, International Journal Of Refrigeration xx, xx-xx. Madani, H., Claesson, J., Lundqvist, P., 21. Capacity control in ground source heat pump systems- Part II: Comparative analysis between on/off controlled and variable capacity systems, International Journal Of Refrigeration xx, xx-xx. Qureshi, T.Q., Tassou, S. A., 1996. Variable-speed capacity control in refrigeration systems. Applied thermal engineering, vol. 16, no.2:p. 13-113. Rybach, L., 25. The Advance of Geothermal Heat Pumps World-wide. Newsletter IEA Heat Pump Centre (23/4). Winandy, E., 1999, Contribution to the performance analysis of reciprocating and scroll refrigeration compressors, Mechanical Engineering department, University of Concepcion, Chile. Doctoral thesis. Zhao, L., Zhao, L. et al., 23. Theoretical and Basic experimental analysis on load adjustment of geothermal heat pump systems. Energy Conversion and Management, vol. 44:p. 1-9. ACKNOWLEDGEMENT This research is a part of a national research and development program in Sweden called Effsys2. It is a four year program for applied R&D in Refrigeration and Heat Pump Technology financed by Swedish Energy Agency and several national and international industrial partners. Special thanks to Kenneth Weber from the company called ETM Kylteknik and Klas Berglöf from Climacheck Sweden who provided the opportunity to carry out this experimental analysis.