Estimation of electrical losses in Network Rail Electrification Systems



Similar documents
Network Rail. Consultation on Traction Electricity Consumption Rates for Train Operating Companies. August 2008

Power transformers. Special transformers Railway

Kinetic energy recovery on railway systems with feedback to the grid

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

High Performance Railway Power

Modeling of Transmission Lines

DC Traction Power Supply. Powerful, efficient and safe. siemens.com/mobility

The electrical energy produced at the gen

Current Cost TREC Current Cost ENVI Current Cost EnviR SmartNow Solar Monitoring Kit

Appendix 7. Conceptual Design of Electrification System. December 2010

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Bussmann series Third rail fuse links application guide. Leadership in fusible circuit protection solutions

Qualitative Analysis of Power Distribution Configurations for Data Centers

PR13: ORR consultation on electricity for traction charges for CP5

reduction ore = metal oxides metal oxidation

Multi-conductor Train Simulations for Electrification Systems

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Hyperlinks are Inactive

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe

EFFICIENT ELECTRICAL ENERGY TRANSMISSION AND DISTRIBUTION INTERNATIONAL ELECTROTECHNICAL COMMISSION

SHE Transmission. 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015

Hybrid shunter locomotive

Background Information

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS

Joint Con Edison LIPA Offshore Wind Power Integration Project Feasibility Assessment

KINETIC ENERGY RECOVERY SYSTEM BY MEANS OF FLYWHEEL ENERGY STORAGE

Inverter / Charger Installation General Operations and AC and DC Connections

ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1

TECHNICAL MEMORANDUM

Screened cable and data cable segregation

FIXED CHARGE: This is a cost that goes towards making the service available, including

RAILWAY CATENARY SYSTEMS. Components and Systems for the Electrification of Railway Lines. ibemo

UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS

Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS)

Report on structure and functionalities of the new online energy efficiency screening tool for railways

Power Feeding Equipment for Optical Submarine Cable Systems

AMSC s Superconductor Cable Technologies for Electric Utilities

Analysis of fuel cell

3-phase, bidirectional energy meter

Conservation Voltage Reduction (CVR)

Summary of Electric Transmission Assessment Report

Your Power. Traction energy

Earthing Guidance Notes

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

Knowing the FACTS. FACTS that enhance power quality in rail feeder systems

SSE s criteria used for GHG emissions reporting

DESIGN STANDARDS STRAY CURRENT MANAGEMENT

We appreciate your feedback

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

Fundamentals of Power

HIGH-CAPACITY HIGH TEMPERATURE SUPERCONDUCTING POWER CABLES

Brochure Introducing HVDC

6. The estimated costs here do not include any applicable ITCC tax

Efficient recovery of braking energy through a reversible dc substation

Inverter technology. bulletin

Coupling Effect in Substation Ground Measurements

Linear DC Motors Magnetic Flux Permanent Bar Magnets

How To Monitor Water Penetration In A Cable Screen

Carbon Footprint Report

Electron S.R.L. A29 ELECTRICAL POWER SYSTEM TRAINERS. Production Transmission Distribution

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

Resistors in Series and Parallel

Project description. Power Electronics for Reliable and Energy efficient Renewable Energy Systems

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

Modeling of electric railway vehicle for harmonic analysis of traction power-supply system using spline interpolation in frequency domain

Electric Power Distribution

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

415V DISTRIBUTION FOR GREEN DATA CENTERS

Good EMC Design Principles: cable routing

Power factor correction. An introduction to technology and techniques

Unit 4: Electricity (Part 2)

Hendrix Spacer Cable

WIND TURBINE TECHNOLOGY

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

Respecting the environment

Offshore Platform Powered With New Electrical Motor Drive System

Volvo Cars, Plug-In Hybrid Concept Development

2012 San Francisco Colloquium

Product brochure Multi Functional Switchgear PASS M kv Flexible and compact switchgear solutions for windfarms

Integration Capacity Analysis Workshop 11/10/15 California IOU s Approach

HIGH VOLTAGE SHORE CONNECTION

The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system.

Power System review W I L L I A M V. T O R R E A P R I L 1 0,

Three-Phase Electric Power Distribution for Computer Data Centers

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

HySTAT HYDROGEN GENERATORS

SURGE PROTECTIVE DEVICES

415V DISTRIBUTION FOR GREEN DATA CENTERS

Engine Optimization Concepts for CVT-Hybrid Systems to Obtain the Best Performance and Fuel Efficiency. Professor Andrew A. Frank Univ.

Smart Grid - Big Data visualized in GIS

Business Area Power Supply

AP1 Electricity. 1. A student wearing shoes stands on a tile floor. The students shoes do not fall into the tile floor due to

(3 )Three Phase Alternating Voltage and Current

Underground vs. Overhead Transmission and Distribution

Transcription:

Estimation of electrical losses in Network Rail Electrification Systems Page 1 of 16

Contents 1. BACKGROUND...3 2. PURPOSE...3 3. SCOPE...3 4. DEFINITIONS & ABBREVIATIONS...4 5. NETWORK RAIL INFRASTRUCTURE BACKGROUND...5 5.1. ac Electrification...5 5.2. dc Electrification...7 6. FUNDAMENTALS OF ENERGY LOSS...10 6.1. Train Current (Load)...11 6.2. Loop Impedance...12 7. AC 25 KV ELECTRIFICATION...13 8. DC 750V ELECTRIFICATION...15 9. REGENERATION...16 10. CONCLUSION...16 Page 2 of 16

1. BACKGROUND Rail is responsible for less than 1% of UK carbon emissions. Electric traction powers around 60% of rail journeys but accounts for around 43% of rail carbon emissions. The Climate Change Act 2008 creates a legally binding target to reduce the UK s emissions of greenhouse gasses to at least 80% below 1990 levels by 2050 To enable the industry to account for energy usage with more accuracy, the ORR periodic review 2008 contained the provision for on train metering, and the track access arrangement to allow for EC4T settlement via meter readings. The ORR provision includes the acknowledgement that metered consumption would need to be uplifted to ensure that infrastructure transmission losses are accounted. 2. PURPOSE The purpose of this report is to provide a guide to the magnitude of loss occurring in the electrification systems operating modern trainsets. 3. SCOPE Electrical losses incurred in the electricity supply industry or on board trains are excluded from this report. This report only considers losses incurring on railway infrastructure. Page 3 of 16

4. DEFINITIONS & ABBREVIATIONS Ac alternating current AT Autotransformer BT Booster Transformer CP4 Control Period 4 dc direct current EC4T Electric Current for Traction ESI Electricity Supply Industry ESTA Electricity Supply Tariff Area NR Network Rail OLE Overhead Line Equipment ORR The Office of Rail Regulator RR Rail Return TPH Traction Paralleling Hut (DC) TSC Traction Section Cabin (AC) Page 4 of 16

5. NETWORK RAIL INFRASTRUCTURE BACKGROUND Network Rail has around 8000km of ac OLE electrified routes and 4800km of dc electrified tracks. Last year, a higher proportion of energy per route km was consumed on the dc than ac systems. (a) Track Length (km) (b) Power Consumption (MWh) 8,000 track km 25 kv AC 64% 4,481 track km 650/750V DC 36% 1,744,946 MWh 25 kv AC 55% 1,433,052 MWh 650/750V DC 45% Figure 1 - NR Electrified Track and Power Consumptions in (Apr 08 Mar 09) 5.1. ac Electrification The NR ac traction system is based on 25kV OLE and is installed on WCML, ECML and the suburban areas of Glasgow, Leeds, Birmingham & Anglia. The system consists of HV Transformer substation (nominal 132/25kV or 400/25.0.25kV) Feeder station and along track distribution buildings Mid Point distribution buildings with neutral sections OLE contact wire and catenary OLE structures, associated track bonds The ECR and SCADA system which control the status of ac and dc circuit breakers, and other remote operated devices. Originally, the railway was electrified using the rail return system. However as the load increased, so did the voltage induced into telecoms circuits. Booster transformers were installed to boost the return current into the return conductor which due to its closer proximity to the OLE provides an electric field cancellation effect. Booster transformers are installed in over 85% of the ac network. Unfortunately, booster transformers add impedance to the electrical system, which limits system capacity. Network Rail has developed autotransformer technology to retro fit on existing infrastructure. This successfully lowers the system impendence. The addition of an anti phase conductor, also doubles the transmission voltage, further improving the efficiency. Page 5 of 16

The OLE is sectioned so only one supply transformer can feed an electrical section. Neutral sections provide electrical insulation between two sections. Figure 2 Rail Return system Figure 3 Booster Transformer system Figure 4 Autotransformer system Page 6 of 16

5.2. dc Electrification The Network Rail dc traction system is based on a nominal 750 V, top contact, third rail system. This system is installed on over 4800 km of railway tracks south of London, plus North London Line, Northern City Lines, Euston to Watford and Merseyrail. The third rail system consists of the following major components: The 3-phase high voltage ac Grid supply points The 3-phase high voltage ac distribution cables and switching stations The dc distribution track paralleling huts and substations including the transformer rectifiers The ETE and associated return current equipment, ie impedance bonds. The ECR and SCADA system which control the status of ac and dc circuit breakers, and other remote operated devices. Substations / track paralleling huts are provided every 2 5 km along the electrified route. Originally these alternated (Figure 8). However, as the power requirements have increased a significant number of TPHs have been converted to SS resulting in double end fed sections (Figure 7). Some simple, stub end feed electrical sections also exist, though these tend to be located at terminal stations and depots. There are about 370 DC SS and more than 260 TPH which are used to section and protect the ETE by means of circuit breakers. These allow most roads to be independently controlled. The significant factor in the overall system capability is the loop impedance of the electrical sections. Initially, 100 lb/yd and 106 lb/yd steel conductor rail was used. However, since the 1960 s, it has been railway policy to install 150 lb/yd steel rail. Low impedance aluminium conductor rail has been trialled in some locations, but it lacked durability. This has limited its suitability. Likewise, the running rails have also increased in size from 95 lb/yd and 109 lb/yd, to 113 lb/yd and now UIC 60. The current return system utilises all available running rails, which are cross-bonded around every 800m, to allow for current sharing and reduce the impedance of the system. Impedance bonds are used to provide continuity of the dc traction return current whilst maintaining segregation of the ac track circuits. Therefore, with varying lengths, and varying conductors / running rails, plus the number of running rails, the loop impedances of electrical sections vary significantly as Figure 5 shows. Page 7 of 16

1000 100% 900 90% 800 80% Quantity 700 600 500 400 300 70% 60% 50% 40% 30% Cumulative Percentage 200 20% 100 10% 0 0 - <10 10 - <20 20 - <30 30 - <40 40 - <50 50 - <60 60 - <70 70 - <80 80 - <90 90-100 - 110-120 - 130-140 - 150-160 - 170-180 - 190 - <100 <110 <120 <130 <140 <150 <160 <170 <180 <190 <200 Circuit Breaker Impedance Setting [m Ω] Figure 5 Southern Circuit Breaker Impedance Settings 0% Figure 6 Simple Stub End fed section Figure 7 Double end fed section (SS-SS) Page 8 of 16

Figure 8 Conventional fed section (SS-TPH-SS) Page 9 of 16

6. FUNDAMENTALS OF ENERGY LOSS Power losses will occur during the cycle of generating electricity, transmission, distribution and use of appliances, machines or other consumers of electricity. In terms of elementary physics, the energy loss in real power of an electric circuit is determined by the current and resistances of the circuit. This is expressed in the following equation: 2 P = I * R (1) An illustrative diagram of the electric traction system is shown in Figure 3. Figure 9 - Electric traction system circuit In the diagram, the power source is represented by an ideal voltage source (V ss ) with inner impedance (R ss ), the train is represented by an ideal current (I train ) taking power from the system, the voltage drop of the train is represented by ( V t ) and the impedance from the train to the power source is represented by loop resistance ( R Loop ). The train s inner impedance is not considered in this example. From the electric circuit in Figure 3, the power supplied by the power source is: P source = Vss * I The power demand of the train is, The power loss is: train train train P = I * V 2 2 P = I * R + R ) = I * R loss train ( ss loop train Σ t (2) (3) (4) The energy loss in percentage terms is thus expressed as: Loss (%) = P P loss source (5) Page 10 of 16

Two key factors are therefore the impedance (or resistance) of the transmission system and the current drawn by the train. The calculation results are shown visually in Figure 10. The impedance from the train to the power source is represented by loop the impedance. The energy losses of the DC system are shown in the 3D diagram on the right hand side of Figure 10. Figure 10-3 dimension chart showing the resultant energy loss 6.1. Train Current (Load) The maximum current drawn by a trainset is well understood as this is used to dimension the capacity of electrical circuits. The average current a trainset draws during an average day is less well understood. There will be significant periods of time when the train will draw minimal current. However, minimal current attracts minimal losses and the majority of losses will occur when the train is accelerating and drawing heavy current. For the purpose of this report the train current is assumed to be around 80% of the maximum current Page 11 of 16

6.2. Loop Impedance The loop impedance is dominated by the distance between the train and the substation. For the purpose of calculation the cumulative losses will be calculated to simulate a moving train along a typical electric section. Various other factors influence the infrastructure impedance. These include:- Feeding Section length Number of tracks Single or Double traction return Configuration of electrical network Length of cables Wear on contact system and running rail Page 12 of 16

7. AC 25 KV ELECTRIFICATION A 250 amp train load was simulated along the entire section length for the three ac configurations for typical feeding lengths and the cumulative energy loss calculated. 5.0% 4.5% 4.0% 3.5% Energy Loss (%) 3.0% 2.5% 2.0% 1.5% 1.0% 0.5% 0.0% 0 10 20 30 40 50 60 Section Lenght (km) Rail Return Booster Transformer Autotransformer Figure 11 Single train load, cumulative energy loss comparison for 25 kv ac system configurations Due to the length of the ac feeding sections it is likely that more than one train will be present. Two or more trains present in the same electrical section will result in additional resultant losses To illustrate this effect, three simulations were run to demonstrate the effect of train density and load assumed. Simulation Headway [mins] Speed [mph] Distance between trains [km] Load [Amps] 1 10 125 36 125 2 5 125 18 125 3 5 125 18 250 Page 13 of 16

5.00% 4.50% 5.00% 4.50% 4.00% 3.50% 4.00% 3.50% 3.00% 2.50% 2.00% 3.00% 2.50% 2.00% 1.50% 1.00% 1.50% 1.00% 0.50% 0.00% Multiple Train Scenario 1 Multiple Train Scenario 2 Multiple Train Scenario 3 Rail Return (20 km) Booster Transformer (20km) Autotransformer (40km) Single Train (20km) Single Train (20km) Single Train (40km) 0.50% 0.00% Figure 12 Multiple train load, cumulative energy loss comparison for 25 kv ac system under different density of trains and single train load conditions Scenario 3 uses the same train load as with the single train simulation (results shown by horizontal line on Figure 12). This illustrates that the energy losses rise when more than one train is present. For example, BT 20km results, previous calculated as 2.3%, now increased to 3.2%. Page 14 of 16

8. DC 750V ELECTRIFICATION Trainsets operating on the dc network have comparable power to the ac train fleets. To provide this power at much lower voltages, the current in the system is far higher. dc trainsets configurations vary, but the maximum current is around 1500 Amps per 4 car EMU. These currents dominate the magnitude of energy losses. Incremental train loads were simulated to determine the electrical loss in the dc distribution and contact system. To take account of the variation in system loop impedance two values were chosen:- 40 mohm representing SS-SS configuration 80 mohm representing SS-TPH-SS configuration 45% 40% Loss Percentage (%) 35% 30% 25% 20% 15% 10% 5% 0% 1500 A 2000 A 2500 A 3000 A 3500 A 4000 A 4500 A 5000 A 5500 A 6000 A R = 40 mohms R = 80 mohms Figure 13 Single train load, cumulative energy loss for 750V dc system The effect of multiple trains will theoretically occur again with the dc system. However, the electrical sections are far shorter, so the likelihood of more than one train present is reduced. The dc system is fed from a HV (majority 33 kv) cable network. This takes electricity from around 40 ESI connections and distributes to the 370 substations. The losses associated with this are believed to be similar to 25 kv OLE system, and are additional to the losses incurred by the dc energy. Page 15 of 16

9. REGENERATION Regenerative braking reduces energy consumption by 15%-20% This saving only occurs on the dc system if a receptive load is also present. If no load is present then the opportunity to regenerate is missed. On the ac system, if no receptive load is present then the energy is transmitted back to the ESI via the supply transformers. This will incur similar losses as load conditions. 10. CONCLUSION Losses on 25 kv OLE system are expected to be below 5% Losses on the 750 V system could be up to 35% and vary greatly with respect to train current which in turn, is strongly correlated to train length. Page 16 of 16