SAFETY MANUAL. Ultima OPIR-5 Infrared Open Path Gas Detector



Similar documents
ALTAIR 5 with WirelessUSB module ALTAIR 5X with WirelessUSB module

Application Requirement

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

RGC-IR Remote Gas Calibrator for IR400

Ultima X Series Gas Monitors

TABLE OF CONTENT

SAFETY MANUAL SIL SMART Transmitter Power Supply

Engineering Specifications XNX Universal Transmitter

SAFETY MANUAL SIL RELAY MODULE

RAEGuard EC FGM-13XX

Quick Start Guide , Rev DA March Rosemount 8714D (Calibration Standard) Magnetic Flowtube Simulator

SAFETY MANUAL SIL Switch Amplifier

S-series Mass Connection Solutions

TYPE 65UV CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output

CARING FOR YOUR WATER HEATER

ABSTRACT INTRODUCTION

ramon 2.2 Radon Monitor manual

MSA Fixed Gas & Flame Detection for the Oil, Gas & Petrochemical Industries

PART 1 - INTRODUCTION...

SAFETY MANUAL SIL SWITCH AMPLIFIER

How to Select a Flame Detector

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

Manual Ranging MultiMeter

Basic Fundamentals Of Safety Instrumented Systems

Lockout Specification BW Clip Maintenance-free single gas detector

Selecting Sensors for Safety Instrumented Systems per IEC (ISA )

Original instructions Tina 3A/Aps Adaptor unit

Online Infrared Flue Gas Analyzer Gasboard 3000

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

FLARE MONITORS FLARE MONITOR (FM) PILOT MONITOR (PM) FLAME INTENSITY (FI)

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

Fire detection equipment

Data Sheet PS1B Pressure Switch

FIRERAY 2000 Installation Guide

Rosemount 333 HART Tri-Loop

MXa SIL Guidance and Certification

Accuracy counts! SENSORS WITH ANALOG OUTPUT

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

EzFlex Combustible Gas Leak Detector Model EZ40

Failure Modes, Effects and Diagnostic Analysis

Agilent 87421A/87422A Power Supply

FEMA ELECTRÓNICA. Serie ISC SIGNAL CONVERTERS WITH GALVANIC ISOLATION. MODEL ISC-IAC for AC Currents ISC-IDC for DC Currents USER S MANUAL

Congratulations! Thank you!

Certified according to DIN EN ISO 9001 Technical Datasheet KVO Series Vortex Flow Meter

Safety Manual BT50(T) Safety relay / Expansion relay

ALTAIR 5X Multigas Detector Bid Specification

Overview of Standards for CO Detection Products

S4000TH HART. HART Communication Manual

Combustible Gas Safety Monitoring: Infrared vs. Catalytic Gas Detectors

Isolating Barriers for our sensors A5S1 in Ex-areas Series D461

Rosemount 333 HART Tri-Loop

Digital multimeters DMG

Chlorine Gas Detection System Operation & Maintenance

ALTAIR Family Gas Detectors A Tough Bunch

Buckeye Detection Systems Fixed Detection Systems Application Survey

MSA Fixed Gas & Flame Detection for the Water & Wastewater Industries

CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter

3500/62 Process Variable Monitor

Sieger Searchpoint Optima Plus

Smoke Detectors Ordering Information DS230 DS230 Series Heat Detectors DS230F DS233F Peripheral Accessories EOL200 TP280 Bases Features

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

High Availability and Safety solutions for Critical Processes

PolyGard Carbon Monoxide CO Transmitter ADTX3 1110

Safety Relay Units. G9SR family. Diagnosis with LEDs Selectable operating modes and times Increased extension possibilities. industrial.omron.

Instruction Manual. T3111 T3111L T3111P T3111Ex

E-PDD Duct Smoke Detector Installation Sheet

EX-5175-EC Sensor/Transmitter Manual

Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC)

Technical data sheet TDS0070

Tele Radio Panther SAFETY instructions

Hardware safety integrity Guideline

AutoRanging Digital MultiMeter

Safety manual for Fisherr ED,ES,ET,EZ, HP, or HPA Valves with 657 / 667 Actuator

Electrical Safety Tester Verification

EVOLUTION Thermal Imaging Camera Remote Wireless Video Receiver System

THE DETECTION OF GREENHOUSE GASES

HARDWARE MANUAL. Ixx24-A 1/20. Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel vc@valcontrols.com

EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL

Tina 2A/B Adaptor unit

IS3016A Passive Infrared Motion Sensor with Anti-Mask - Installation Instructions

Q U A D S C A N I I GENERAL User Interface Enclosure Display QUADSCAN II Temperature Range RECEIVER DISPLAY Sensor Weight Optional Relay Enclosure

Motion Detector 360 Degrees 5420/360. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

CL90i Please read these instructions before operating the product. 3 - Beam Self-Leveling Cross Line Laser

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

Multi Tube Rotator. Model No. 4632Q CE CECN /05/11

EuroFID Total Hydrocarbon Analyzer. Precise Determination of Total Hydrocarbons in Air for Corrosive as well as Condensing Gases

Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

How To Use A Ds340 (Dsp)

Triple Waveband Infra-Red Flame Detection

Make the invisible visible! SENSORS WITH EXCELLENT BACKGROUND SUPPRESSION

Fire & Security DETECTORS

Infrarot-Bewegungsmelder IP44

NI Channel, 60 V, High-Speed, Sourcing Digital Output Module

Final Element Architecture Comparison

Title: Standard Operating Procedure for Thermo-Miran SapphIRe portable gas analyzer

Vroom Hardware manual ver Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features:

Transcription:

SAFETY MANUAL Ultima OPIR-5 Infrared Open Path Gas Detector The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by MSA. Safety Manual MSA reserves the right to change published specifications and designs without prior notice. Part No. MANOPIR5SAFETY Revision 01

This manual describes the safety related information for the installation, operation, configuration, and maintenance of the. For complete information regarding performance, installation, operation, maintenance, and specifications of the Ultima OPIR-5 Gas Detector, please refer to the associated product manual. MSA s mission is to benefit society by providing safety solutions through industry-leading products, services, and systems that save lives and protect capital resources from the dangers of hazardous flames, gases, and vapors. The safety product you have purchased should be handled carefully, and installed and maintained in accordance with the Ultima OPIR-5 Gas Detector instruction manual. Remember, this product is for your safety. WARNING: TOXIC, COMBUSTIBLE, AND FLAMMABLE GASES AND VAPORS ARE VERY DANGEROUS. USE EXTREME CAUTION WHEN THESE HAZARDS ARE PRESENT. 2

INTRODUCTION General Description The MSA Ultima OPIR-5 Gas Detector continuously monitors hydrocarbon gases and provides a 4-20 ma analog signal proportional to the LEL gas concentration and optional LEL relay output. The gas detector has Heavy Hydrocarbon (propane) version monitor gases in the 0 to 1 LEL meter range. This safety manual applies to all versions. The Ultima OPIR-5 Gas Detector uses a single beam source and detector to monitor gas concentrations, improving accuracy, reducing drift and improving immunity to false alarms. The Ultima OPIR-5 Gas Detector is regarded as a Type B field device per IEC 61508. The safety function of the Ultima OPIR-5 Gas Detector does not include: HART communication RS-485 Modbus communication 3

INSTALLATION WARNING: Under NO circumstances should equipment be connected or disconnected when under power. This is contrary to hazardous area regulations and may also lead to serious damage to the equipment. Equipment damaged in this manner is not covered under warranty. For complete information on the installation of the Ultima OPIR-5 Gas Detector, refer to the respective product instruction manual. Be sure to closely follow alignment instructions. Location Considerations There are no standard rules for placement, since the optimum location varies with each application. Some factors to consider when selecting locations: The system should be accessible for occasional response checks. The line of sight between the Source and Receiver units should be free from objects that may block the beam and interruptions caused by frequent human or animal crossings. The Receiver unit should be mounted so that the display is visible to aid in alignment and so that direct sunlight does not enter the front window. Do not mount near strong magnetic fields or degradation of performance may result. Although the Ultima OPIR-5 Gas Detector is Radio Frequency Interference (RFI) resistant, it should not be mounted too close to radio transmitters or similar equipment. The units should be reasonably protected (i.e. covered by a hood if temperatures exceed the environmental specifications in the product instruction manual). Mount away from sources of excessive vibration and away from high voltage/high current power lines and from concentrated sources of heat. An aperture plate is required if the open path length is less than 20 meters (Ultima OPIR- 5 Gas Detector standard range). It is important to obtain the highest alignment number possible within the allowed range. NOTE: Frequent inspection, cleaning, and sensitivity checking is suggested for gas detectors mounted in dirty environments. No special or additional detector mounting, wiring, power, or tool requirements exist beyond the standard installation practices documented in the Ultima OPIR-5 Gas Detector instruction manual. 4

OPERATION AND MAINTENANCE For complete operation, configuration, and maintenance information for the Ultima OPIR- 5 Gas Detector, refer to the product instruction manual. Before applying power to the system for the first time, all wiring connections should be checked for correctness and the Receivers housing cover should be securely fastened. Upon initial power-up, the Receiver will enter a two-minute set-up mode; the display will indicate SU. The Ultima OPIR-5 Gas Detector contains a heater circuit to remove condensation from the windows. The unit should be allowed to stabilize for approximately two hours before continuing with the setup mode. The Ultima OPIR-5 Gas Detector is an intelligent sensor that performs internal diagnostics on critical faults every second and responds with 0 ma for an internal fault and 1.5 ma for a beam block fault (see Table 2). User selectable delays and current levels allow for system flexibility. WARNING: The Ultima OPIR-5 Gas Detector does not respond to gas leaks upon complete IR beam blockage. Interruptions of the IR beam will delay the response time of this unit, and thus lead to a potentially unsafe situation. The optical path should be checked for blockage and the windows cleaned periodically. The Ultima OPIR-5 Gas Detector performs accurately and reliably for propane gas detection applications in extreme industrial environments. Under the following two situations: 1) a rapid and massive liquid propane release and 2) a rapid and massive buildup of a high concentration propane gas cloud, the Ultima OPIR-5 Gas Detector recognizes both situations and forces the analog output, and optional relay output, to over-range. Refer to the Troubleshooting Section in the Ultima OPIR-5 Gas Detector instruction manual in the event of a fault condition. In addition, spare parts should be on-hand to maintain the four hour repair time. Refer to the Spare Parts Section of the instruction manual for more information. After the Ultima OPIR-5 Gas Detector has been initially aligned and calibrated, very little must be done to maintain the unit. Although calibration is not required, response should be tested from time to time using the Test Gas Filters designed for the detectors. MSA recommends that a maintenance schedule be established and followed. If the detector is operated under dusty or dirty conditions, the windows should be cleaned periodically. This is accomplished by gently wiping them with a soft, clean cloth, which has had a commercial window cleaning solution applied. The cleaning should be done in test mode to prevent false alarms. 5

SPECIFICATIONS Table 1 and Table 2 list specifications for the Ultima OPIR-5 Gas Detector. For a complete list of specifications refer to the product instruction manual. Instruction Manual P/N Operating Temperature Range: Humidity Range: Input Voltage: Supply Power Source: Supply Power Receiver: Ultima OPIR 5 Detector MANOPIR5-67 F to 149 F (-55 C to 65 C) 10 to 95% RH, non-condensing 20 to 36 VDC With Heater 12 Watts No Heater 10 Watts With Relays and Heater: 10 W Relays, No Heater: 6 W No Relays, with Heater: 8.5 W No Relays, No Heater: 5 W Table 1 Environmental/Electrical Specifications Mode Ultima OPIR 5 Detector (non-hart) Ultima OPIR 5 Detector (HART) Fault 0 ma 1.25 or 3.5 ma Startup 0 ma 1.25 or 3.5 ma Set up 1.5 ma 1.5 or 3.5 ma Gas Check 0 or 1.5 ma 1.5 or 3.5 ma Beam Block 2 ma 2 or 3.5 ma Standard Unit 0 to 5 LEL m Heavy Hydrocarbon Unit 0 to 1 LEL m Split Range 4-20 ma 4-20 ma 4-20 ma 4-20 ma 4-12 ma for 0-5000ppm m (methane) or 0-2000 ppm m (propane) 12-20 ma for 0-5 LEL m (methane) or 0-1 LEL m (propane) 4-12 ma for 0-5000ppm m (methane) or 0-2000 ppm m (propane) 12-20 ma for 0-5 LEL m (methane) or 0-1 LEL m (propane) Over range 21.7 ma 21.7 ma Table 2 Analog Output Specifications (600 ohms max.) 6

CERTIFICATIONS AND FAILURE RATE DATA The Ultima OPIR-5 Gas Detector has gone through rigorous reliability and functional safety assessments, which have resulted in the gas detectors as certified to IEC 61508 Parts 1, 2, and 3, by FM Approvals. The reliability assessment is a failure rate prediction that assumes an average temperature of 40ºC and an environmental factor equivalent to Ground Fixed. It is assumed that the Ultima OPIR-5 Gas Detector will be installed in a Safety Instrumented System (SIS) operating in a Low Demand environment per IEC 61508. Table 3 lists the Safety Integrity Level (SIL) parameters for both systems. Field Device Ultima OPIR-5 Ultima OPIR-5 Analog Output Relay Output FM Certificate 3042476 3042476 Product Life (Years) 10-12* 10-12* λ DD (FIT)** 14.6E3 14.6E3 λ DU (FIT) 102 407 Safe Failure Fraction >99% 97% (SFF) Safety Integrity Level (SIL)*** Diagnostic Test Interval Response Time (when exposed to fullscale gas concentration in ppm range) Average Probability of Failure on Demand PFD avg 1oo1**** 3 2 30 minutes for memory faults, 1-30 seconds for all other faults 1.7E-4 T90 10 seconds 5.04E-4 Table 3 SIL Parameters for Ultima OPIR-5 Detector * Ultima OPIR-5 Transmitter flash lamp typical life of 3 4 years ** FIT = Failures in 1E9 Hours *** Hardware Fault Tolerance (HFT) = 0 **** PFD avg 1oo1 assumes a 4 hour repair time and 90 day proof test interval. Ultima OPIR-5 Detector ATEX CSA CE IEC 61508 per FM Approvals FM IECEx HART Communication Foundation Table 4 Agency Approvals 7

MSA in Europe [ www.msasafety.com ] Northern Europe Southern Europe Eastern Europe Central Europe Netherlands MSA Nederland Kernweg 20 1627 LH Hoorn Phone +31 [229] 25 03 03 Fax +31 [229] 21 13 40 info.nl@msasafety.com France MSA GALLET Zone Industrielle Sud 01400 Châtillon sur Chalaronne Phone +33 [474] 55 01 55 Fax +33 [474] 55 47 99 info.fr@msasafety.com Poland MSA Safety Poland Sp. z o.o. Ul. Wschodnia 5A 05-090 Raszyn k/warszawy Phone +48 [22] 711 50 00 Fax +48 [22] 711 50 19 info.pl@msasafety.com Germany MSA AUER GmbH Thiemannstrasse 1 12059 Berlin Phone +49 [30] 68 86 0 Fax +49 [30] 68 86 15 17 info.de@msasafety.com Belgium MSA Belgium N.V. Duwijckstraat 17 2500 Lier Phone +32 [3] 491 91 50 Fax +32 [3] 491 91 51 info.be@msasafety.com Great Britain MSA (Britain) Limited Lochard House Linnet Way Strathclyde Business Park BELLSHILL ML4 3RA Scotland Phone +44 [16 98] 57 33 57 Fax +44 [16 98] 74 01 41 info.gb@msasafety.com Sweden MSA NORDIC Kopparbergsgatan 29 214 44 Malmö Phone +46 [40] 699 07 70 Fax +46 [40] 699 07 77 info.se@msasafety.com MSA SORDIN Rörläggarvägen 8 33153 Värnamo Phone +46 [370] 69 35 50 Fax +46 [370] 69 35 55 info.se@msasafety.com Italy MSA Italiana S.p.A. Via Po 13/17 20089 Rozzano [MI] Phone +39 [02] 89 217 1 Fax +39 [02] 82 59 228 info.it@msasafety.com Spain MSA Española, S.A.U. Narcís Monturiol, 7 Pol. Ind. del Sudoeste 08960 Sant-Just Desvern [Barcelona] Phone +34 [93] 372 51 62 Fax +34 [93] 372 66 57 info.es@msasafety.com Czech republic MSA Safety Czech s.r.o. Dolnojircanska 270/22b 142 00 Praha 4 - Kamyk Phone +420 241440 537 Fax +420 241440 537 info.cz@msasafety.com Hungary MSA Safety Hungaria Francia út 10 1143 Budapest Phone +36 [1] 251 34 88 Fax +36 [1] 251 46 51 info.hu@msasafety.com Romania MSA Safety Romania S.R.L. Str. Virgil Madgearu, Nr. 5 Ap. 2, Sector 1 014135 Bucuresti Phone +40 [21] 232 62 45 Fax +40 [21] 232 87 23 info.ro@msasafety.com Russia MSA Safety Russia Походный проезд д.14. 125373 Москва Phone +7 [495] 921 1370 Fax +7 [495] 921 1368 info.ru@msasafety.com Austria MSA AUER Austria Vertriebs GmbH Modecenterstrasse 22 MGC Office 4, Top 601 1030 Wien Phone +43 [0] 1 / 796 04 96 Fax +43 [0] 1 / 796 04 96-20 info.at@msasafety.com Switzerland MSA Schweiz Eichweg 6 8154 Oberglatt Phone +41 [43] 255 89 00 Fax +41 [43] 255 99 90 info.ch@msasafety.com European International Sales [Africa, Asia, Australia, Latin America, Middle East] MSA Europe Thiemannstrasse 1 12059 Berlin Phone +49 [30] 68 86 0 Fax +49 [30] 68 86 15 58 info.de@msasafety.com