Technical Note. Configuring an Omron PLC with Omron FINS Ethernet Driver. 1. Introduction



Similar documents
Kepware Technologies OPC Quick Client Connectivity Guide

Kepware Technologies KEPServerEX Client Connectivity Guide for GE's Proficy ifix

Allen Bradley ControlLogix Ethernet Driver for KEPServerEX

FINS Gateway For OMRON PLCs

Kepware Technologies KEPServerEX OPC Tunnel

Recommended KEPServerEX Settings for groov

Cisco - Configure the 1721 Router for VLANs Using a Switch Module (WIC-4ESW)

Configuring Omron CJ2H PLC s with Ethernet/IP for use with Acromag Ethernet/IP Remote I/O

Configuration of Kepware OPC Server in PanelMate Configuration Editor

C-more Remote Access with Apple ipad or iphone Tutorial

Flexi Soft Ethernet IP: Implicit Messaging with a Omron PLC

Custom Solutions Center. Users Guide. Low Cost OEM PackML Templates L02 Release. Version LC-1.0

Using Ladder Logic Instructions to Communicate with an Ethernet IP Nexus Unit

Configuring the WT-4 for Upload to a Computer (Ad-hoc Mode)

CMP-102U. Quick Installation Guide

Chapter7 Setting the Receiving PC for Direct Upload. Setting the Receiving PC for Direct Upload For Windows For Macintosh...

Kepware Technologies KEPServerEX Client Connectivity Guide for Wonderware InTouch

CONVI. User and Service Manual. Viscolone uk_1.doc. 10. august 2010

EZ-ZONE RMA & EtherNet/IP Configuration & Startup Using an Allen-Bradley CompactLogix PLC EtherNet/IP Fundamentals

IntraVUE Plug Scanner/Recorder Installation and Start-Up

IGSS. Interactive Graphical SCADA System. Quick Start Guide

Kepware Technologies Optimizing KEPServerEX V5 Projects

Using KEPServerEX OPC Server (Kepware)with the iologik E2210

TechNote. Contents. Introduction. System Requirements. SRA Two-factor Authentication with Quest Defender. Secure Remote Access.

Network/Floating License Installation Instructions

Windows 98 and Windows Me

USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: Rev 6

WSNetServer User Manual. Date: July

PCLinq2 Hi-Speed USB Bridge-Network Cable. Quick Network Setup Guide

DataWorX32 Professional Getting Started with Redundancy

Follow these steps to prepare the module and evaluation board for testing.

Deployment Guide: Transparent Mode

Deploying Windows Streaming Media Servers NLB Cluster and metasan

Interfacing Basler GigE Cameras With Cognex VisionPro 7.2

Use this guide if you are no longer able to scan to Sharpdesk. Begin with section 1 (easiest) and complete all sections only if necessary.

KEPServerEX Client Connectivity Guide

A L ERT. Quick Start With

EDGE FX Network configuration

KEPServerEX Client Connectivity Guide

Configuring the WT-4 for Upload to a Computer (Infrastructure Mode)

IIS, FTP Server and Windows

Adding a Modbus TCP Device to the Network. Setting Up Your Network

Ethernet Module Manual

Configuring the WT-4 for Upload to a Computer (Ad-hoc Mode)

DCOM Configuration for KEPServerEX

Configuring the SST DeviceNet OPC Server

Enabling Internet Connection Sharing on Windows Enabling ICS On Windows XP As The Host 4 Enabling ICS On Windows XP As The Client 11

Network Load Balancing

Configuring the WT-4 for Upload to a Computer (Infrastructure Mode)

Monitoring Traffic. Traffic Monitoring. This chapter includes the following sections:

1.0 Basic Principles of TCP/IP Network Communications

Recommended Network Setup

Adding Traffic Sources to a Monitoring Session, page 7 Activating a Traffic Monitoring Session, page 8 Deleting a Traffic Monitoring Session, page 9

Packet Tracer 3 Lab VLSM 2 Solution

ERserver. iseries. Networking TCP/IP Setup

Installation Guide Installing / Licensing / Unlocking Kepware Products

Configuring Network Load Balancing with Cerberus FTP Server

Configuring the WT-4 for Upload to a Computer (Infrastructure Mode)

1. Installing The Monitoring Software

Configuring a customer owned router to function as a switch with Ultra TV

ENPS-MF1. 1 USB Port. Multifunctional Print Server. Quick Installation Guide V1.0

Volume. Instruction Manual

Kepware Technologies Remote OPC DA Quick Start Guide (DCOM)

C-more Remote Access, Data Log, FTP File Transfer, and Tutorial

KEPServerEX Client Connectivity Guide

OPC Unified Architecture - Connectivity Guide

Beckhoff TwinCAT. Assigning IP Addresses to Beckhoff Ethernet Devices

Windows 2000/XP Network

64-Bit Compatibility with Micromeritics Applications

(1) Network Camera

Technical Note. Setting ACS drive IP address automatically with Rockwell BOOTP/DHCP Server. Contents

Setting the Management IP Address

Setting up your laptop to print to the student lounge printer

E-Blocks Easy Internet Bundle

E-Map Application CHAPTER. The E-Map Editor

Preparing the Computers for TCP/IP Networking

Siemens S7 TCP/IP Master with TIA S7 Tag Import Communications Driver

Setting up DCOM for Windows XP. Research

Important Notes for WinConnect Server VS Software Installation:

Remote Connection to a WAGO using a High-Speed Internet connection Application note

SIP Domain/Proxy, Ring Detect Extension or/and Page Audio Extension, (The 8180 needs its own phone extension) Authentication ID, Password,

BioWin Network Installation

LOAD BALANCING 2X APPLICATIONSERVER XG SECURE CLIENT GATEWAYS THROUGH MICROSOFT NETWORK LOAD BALANCING

About This Guide SolarEdge Configuration Tool Software Guide. About This Guide

Basic ViPNet VPN Deployment Schemes. Supplement to ViPNet Documentation

Self Help Guide IMPORTANT! F5D Setting Up An Ad Hoc Connection. Please read the following carefully;

Omni 56K USB Lite Quick Start Guide

1. Hardware Installation

Routing and Remote Access Service

Enabling NAT and Routing in DGW v2.0 June 6, 2012

Pre-lab and In-class Laboratory Exercise 10 (L10)

Networking Basics for Automation Engineers

How To Manage A Network With Kepware

Cluster to Cluster Failover Using Double-Take

Technical Note. Monitoring Ethernet Traffic with Tolomatic ACS & Managed Switch. Contents

1-Port Wireless USB 2.0 Print Server Model # APSUSB201W. Quick Installation Guide. Ver. 2A

Technical Information Sheet Page 1 of 8

Service & Support. How can you establish a connection between an S PLC and SIMATIC NET OPC? S PLC, SIMATIC NET OPC.

Configuring RSLinx as an OPC Server for PanelMate epro

Administration Guide. . All right reserved. For more information about Specops Gpupdate and other Specops products, visit

Transcription:

Technical Note Configuring an Omron PLC with Omron FINS Ethernet Driver 1. Introduction This document describes how to configure an Omron PLC with a FINS-enabled Ethernet module and the Omron FINS Ethernet driver. For simplicity, these instructions assume the driver is in direct communication with a PLC on the local Ethernet network, though this driver may also be used to communicate with remote PLCs on interconnected FINS networks. The main issue with FINS Ethernet communications is that PLCs need a way to map FINS node numbers to IP addresses. IP address information is not conveyed in FINS messages and must be inferred from the FINS network parameters contained in the messages. Configure the PLCs to accomplish this via one of three methods: automatic conversion, IP address table, or combination. The automatic conversion method is usually easiest and is used in this example. The PLC calculates the IP address of the destination node from its own IP and the FINS node number of the destination. It is assumed that the host number of the IP, generally the last octet, is the same as the FINS node number. Note: The FINS limits the range of node numbers from 1 to 127, limiting the range of IP addresses that can be used with this method. The IP address table explicitly maps nodes to IP addresses in a delimited table format, allowing customization for most implementations. The combination method uses both. When the PLC sends a message to a given FINS node, it checks the IP address table for that node. If the node is listed, the PLC sends the message to the IP address in that table entry. If an entry is not found, the PLC constructs an IP address with the automatic conversion method. www.kepware.com 1 2015 Kepware, Inc.

2. Settings The relevant settings for an Omron CJ2 PLC and an Omron FINS Ethernet driver. PC (KEPServerEX host): IP: 10.10.112.118 Subnet Mask: 255.255.0.0 PLC (EtherNet IP): IP: 10.10.110.58 Unit: 0 Node Number: 58 Note: This is same as last octet of IP using auto conversion. Set IP with rotary switches on the EtherNet IP module: IP setting 10.10.110.58 (decimal) = 0A.0A.6E.3A (hex) The switches are oriented as shown below. Check the Ethernet module documentation for correct information. 3 A 6 E (socket) 0 A 0 A Set Unit Number with rotary switch on top of ETN01 module: Unit: 0 Set Node Number with rotary switch on top of ETN01 module: Unit: 58 (decimal) = 3A (hex) Node: 3 x161 A x 160 www.kepware.com 2 2015 Kepware, Inc.

3. Driver Setup 1. Set the UDP port number on the Channel Properties dialog box, Communications Parameters tab. FINS requires that all nodes on a FINS Ethernet network use the same port number. The default value is 9600. 2. Set the PLC model number and IP on the General tab. Tip: In this example, this is the model and IP of a single PLC. To communicate with a remote device, the model would be that of the remote device and the IP would be that of the go-between PLC. 3. Set the FINS network parameters on the FINS Network Configuration tab. Note: The source node number is the same as the last Octet of PC s IP address because the PLC is configured to use using automatic conversion. The network number is zero since because the ultimate destination is on a local Ethernet network. To communicate with a remote PLC, the destination network number would be non-zero and be configured in the go-between PLC s routing table. www.kepware.com 3 2015 Kepware, Inc.

4. PLC Setup 1. Verify the PLC is correctly configured to use the Ethernet and FINS network parameters specified in the driver configuration. 2. Run CX-Programmer. 3. Create a PLC object to communicate with the PLC or load a project that has been previously created for the PLC. 4. Select Work Online. 5. Select PLC Transfer From PLC to get current PLC configuration. 6. Verify that IO table is checked in the Upload Options dialog. 7. Click OK. 8. Double-click on IO table. 9. Expand the Built-in Port/Inner Board node. 10. Right-click on [1500] CJ2B- EIP21(Built In EtherNet/IP Port for CJ2) and select Unit Setup. www.kepware.com 4 2015 Kepware, Inc.

11. Select Auto in the Ethernet tab. 12. Select Default in the FINS UDP tab. 13. Select Transfer [PC to Unit]. 14. Click OK. 15. Select Yes 5. Summary Verify the PLC, the Omron FINS Ethernet driver, and the server are all correctly configured by launching OPC Quick Client and confirming the tags show Good quality. Congratulations! www.kepware.com 5 2015 Kepware, Inc.