Description / Application RAVV is a self-acting thermostatic element which can be combined with 2-way valve bodies RAV-/8, VMT-/8 or VMA 15. RAVV is used to control temperatures in small hot water cylinders and to control flow temperatures in central heating systems. There is a special version with a section of the capillary tube coiled up to function as minimum temperature sensor. This version can be used to control air heating coils. RAVV-RAV and RAVV-VMT - closes on rising sensor temperature - must be installed in the flow pipe - is dimensioned for pressure stage (PN) 10, max.120 C RAVV-VMA - closes on rising sensor temperature - must be installed in the flow pipe - is dimensioned for pressure stage (PN) 16, max.130 C Principles Hot water cylinder Air heating coil Ordering Setting Capillary tube Max. Type range lenght sensor temperature Code No. C m C 10-38 1.5 120 013U1255 1) RAVV 10-38 5.0 2) 120 013U1256 27-57 1.5 120 013U1252 1) 40-70 1.5 120 013U1251 1) 1) Incl. R 1 p / 2 capillary tube gland 2) Effektive lenght including minimum temperature sensor Accessories Material Code No. Brass 993N3568 Sensor pocket Stainless steel 993N3615 SIBC VD.52.O2.02 Danfoss 05/02 1
Valve bodies Type Connection 1) k v Inlet Outlet m 3 /h Code No. RAV 10/8 R 3 p /8 3) R 3 /8 3) 1.1 013U0012 RAV 15/8 R 1 p / 3) 2 R 1 / 3) 2 1.2 013U0017 RAV 20/8 R 3 p / 3) 4 R 3 / 3) 4 1.5 013U0022 RAV 25/8 R p 1 3) R 1 3) 1.6 013U0027 VMT 15/8 2) G 3 / 4 A 4) G 3 / 4 A 4) 1.2 065F0115 VMT 20/8 2) G 1 A 4) G 1 A 4) 1.5 065F0120 VMT 25/8 2) G 1 1 / 4 A 4) G 1 1 / 4 A 4) 1.6 065F0125 VMA 15 0.4 065F2031 VMA 15 0.6 065F2032 VMA 15 G 3 / 4 A 4) G 3 / 4 A 4) 0.8 065F2033 VMA 15 1.1 065F2034 VMA 15 1.7 065F2035 1) The capacity (k v ) iapplies to a P-band of 6 C. Other P-band, see "Data". 2) Ordering cooper fittings, see "Accessories" 3) According to ISO 7/1 4) According to ISO 228/1 Accessories VMT Type Copper fittings (delivered in boxes of 10) Code No. 15 1 013G4125 VMT 15 16 1 013G4126 18 1 013G4128 VMT 20 18 1 013U0134 22 1 013U0135 VMT 25 28 1 013U0140 Accessories VMA Typ Nipple sets Code No. VMA 15 Set of weld-on nipples 003N5090 VMA 15 Set of nipples with external threads 003N5070 Data k v (m 3 /h) Max. Max. Max. Max. Type for a P-band in C of working differential test flow pressure pressure pressure temperature RAVV- 2 4 6 8 10 12 bar bar bar C RAV 10/8 0.6 0.8 1.1 1.2 1.3 1.4 RAV or VMT 15/8 0.6 0.9 1.2 1.3 1.5 1.6 RAV or VMT 20/8 0.7 1.2 1.5 1.8 2.1 2.3 10 0.8 16 120 RAV or VMT 25/8 0.7 1.2 1.6 2.0 2.3 2.6 VMA 15 (k vs = 0.4) 0.2 0.3 0.4 5 1) VMA 15 (k vs = 0.63) 0.3 0.5 0.6 VMA 15 (k vs = 1.0) 0.4 0.7 0.8 16 2 1) 25 130 VMA 15 (k vs = 1.6) 0.4 0.8 1.1 VMA 15 (k vs = 2.5) 0.7 1.2 1.7 1 1) 1) In installations requiring a low-noise function the differential pressure is not to exceed 1 bar. 2 VD.52.O2.02 Danfoss 05/02 SIBC
Design Materials, parts in contact with water Valve body: Ms 58, nickel plated Valve cone: NBR-rubber Pressure pin: Stainless steel 18/8 O-ring: EPDM-rubber Sensor: Cu, nickel plated Sensor pocket: Brass or stainless steel 1. Setting knob 2. Setting spring 3. Bellows element 4. Gland 5. Bottom screw 6. Valve body 7. Valve cone 8. Remote sensor 9. Capillary tube gland Setting Relation between scale figures and closing temperature. The values given are approximate. Installation The valve body must be fitted in the flow pipe with the flow in direction of the cast-in arrow. The flow temperature must be min. 15 C higher than the set closing temperature. The sensor must be fitted in position from horizontal to vercally down. The sensor must always be placed in a pocket when the temperature is to be measured directly in a medium. SIBC VD.52.O2.02 Danfoss 05/02 3
Sizing Example: Temperature control for hot water service Given Load: Cooling (flow - return): 20 C 14 kw (12000 kcal/h) Flow volume: 12 20 = 0.6 m 3 /h Differential pressure p across the valve: 0.12 bar Required Correct valve size Method From the flow volume (0.6 m 3 /h) and the differential pressure (0.12 bar) read off the necessary k v -value in the diagram = 1.75. In this example, a P-band of 6 C is required. From the k v -columns in the table, under 6 C, find the appropriate valve body. Here, the most suitable valve body is RAV 25/8 or VMT 25/8 with a k v -value of 1.6. 4 VD.52.O2.02 Danfoss 05/02 SIBC
Dimensions RAVV-RAV/8 RAVV-RAV/8 d d Widths 2 across flats L L 2 L 3 L 4 L 5 H 1 H 2 S 1 S 2 DN ISO 7/1 mm mm mm mm mm mm mm mm mm 10 R 3 p /8 R 3 /8 59 85 26 52 22 45 93 22 27 15 R 1 p / 2 R 1 / 2 66 95 29 58 26 45 93 27 30 20 R 3 p / 4 R 3 / 4 74 106 34 66 29 45 93 32 37 25 R p 1 R 1 90 125 40 75 34 58 106 41 46 RAVV-VMT 15/8 Widths a b L 1 L 2 H 1 across flats DN mm ISO 228/1 mm mm mm S mm 15 15/ 16/ 18 G 3 / 4 A 66 90 93 30 20 18/ 22 G 1 A 74 101 93 37 25 28 G 1 1 / 4 A 90 120 106 45 RAVV-VMT RAVV-VMA a L L 1 L 2 S DN ISO 228/1 mm mm mm mm 15 G 3 / 4 A 65 131 139 27 RAVV-VMA Pocket sensor SIBC VD.52.O2.02 Danfoss 05/02 5