DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION



Similar documents
CT Application Guide for the 489 Generator Management Relay

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Power Quality Paper #3

SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS. Sethuraman Ganesan ABB Inc. Allentown, PA

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Instrument Transformers Application Guide

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

Transformer circuit calculations

13 ELECTRIC MOTORS Basic Relations

PI734D - Technical Data Sheet

Chapter 11. Inductors ISU EE. C.Y. Lee

PI734B - Technical Data Sheet

SYNCHRONOUS MACHINES

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

6. Synchronous machine dynamics

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Enhanced Quality with a Touch of Style

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

UCI274C - Technical Data Sheet

UCI274H - Technical Data Sheet

6 ELECTRICAL PARAMETERS

Using Current Transformers with the 78M661x

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Induced voltages and Inductance Faraday s Law

Eðlisfræði 2, vor 2007

Current and voltage measuring relays

Line Reactors and AC Drives

Inductors in AC Circuits

RM4TG20 three-phase network control relay RM4-T - range V

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance

PM734F - Technical Data Sheet Winding 28

Transformer protection

Calculation of the Current Transformer Accuracy Limit Factor Application Note

Chapter 35 Alternating Current Circuits

45. The peak value of an alternating current in a 1500-W device is 5.4 A. What is the rms voltage across?

Edmund Li. Where is defined as the mutual inductance between and and has the SI units of Henries (H).

Type SA-1 Generator Differential Relay

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

7CURRENT TRANSFORMERS

ε: Voltage output of Signal Generator (also called the Source voltage or Applied

Physical Address: City: State: Zip Code:

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Current transformer selection guide

The following table shows approximate percentage wise the

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Chapter 9 Balanced Faults

Product Data Bulletin

EARTHING SYSTEM CALCULATION

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

Application Note. So You Need to Measure Some Inductors?

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

T Substation Maintenance and Commissioning Test Equipment

High Efficiency Motor Protection. Industry White Paper

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

Safety technique. Emergency stop module BO 5988 safemaster

Short Circuit Current Calculations

ACCURACY OF POTENTIALTRANSFORMERS

Magnetic Field of a Circular Coil Lab 12

8 Speed control of Induction Machines

VOLTAGE REGULATOR AND PARALLEL OPERATION

Short-circuit, Protective Device Coordination & Arc Flash Analysis. By Albert Marroquin Operation Technology, Inc.

Current and Temperature Ratings

Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters )

Introduction to Short Circuit Analysis

DS 600. A contact free flux gate based current measurement sensor 600A rms

SECTION VARIABLE FREQUENCY DRIVES

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

Three phase circuits

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

Circulating Current Relay. Type IRXm

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

Solution Derivations for Capa #11

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21,

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

Three-phase AC circuits

AC Generators. Basic Generator

Chapter 14: Inductor design

CONDUCTOR SHORT-CIRCUIT PROTECTION

Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB

12. The current in an inductor is changing at the rate of 100 A/s, and the inductor emf is 40 V. What is its self-inductance?

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Alternating-Current Circuits

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line

Chapter 12 Driven RLC Circuits

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

WHITE PAPER GROUND FAULT. Lowering the Limits for Ground Fault Detection

Inductance. Motors. Generators

= (0.400 A) (4.80 V) = 1.92 W = (0.400 A) (7.20 V) = 2.88 W

Medium voltage circuit breaker

Transcription:

ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1

CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note

ÿþ üûúùø öõöôùóùõò CT Dimensioning CONTENTS 1. TRANSIENTS ON CURRENT TRANSFORMERS -FUNDAMENTALS... 4. RESULTANT VOLTAGES ON CT SECONDARIES DURING FAULTS... 6 3. TIME TO MAXIMUM FLUX TIME TO SATURATION... 8 4. TRIPPING TIMES OF PROTECTION DEVICES... 11 5. RESULTANT FAULT VOLTAGES AND CT DIMENSIONING... 1 6. TERMS AND DEFINITIONS... 13 6.1 Rated Primary Short-circuit Current (I Primarysc )... 13 6. Instantaneous Error Current (I ε )... 13 6.3 Peak Instantaneous Error (ξ i )... 13 6.4 Peak Instantaneous Alternating Current Component Error (ξ ac )... 13 6.5 Accuracy Class... 13 6.6 Class Index... 13 6.7 Limit Factor... 13 6.8 Class P Current Transformer... 14 6.9 Class TPS Current Transformer... 14 6.10 Class TPX Current transformer... 14 6.11 Class TPY Current Transformer... 14 6.1 Class TPZ Current Transformer... 14 6.13 Primary Time Constant (T 1 )... 14 6.14 Secondary Loop Time Constant (T )... 14 6.15 Time to Maximum Flux (t ϕ max )... 14 6.16 Secondary Winding Resistance (R CT )... 15 6.17 Secondary Loop or Burden Resistance (R B )... 15 6.18 Low Leakage Flux Current Transformer... 15 6.19 Saturation Flux(Ψ S )... 15 6.0 Remanent Flux (Ψ R)... 15 Application note GER3973 3

CT Dimensioning ÿþ üûúùø öõöôùóùõò 1. TRANSIENTS ON CURRENT TRANSFORMERS - FUNDAMENTALS More than the steady state under load conditions of the CT s, the main concern is about the fault conditions when the protections installed in their secondaries must respond correctly to the short-circuit transient, specially during the first cycles. Because of this, it is necessary to define how much a CT must be oversized in order to avoid the saturation due to the asymmetrical component of the fault current (the dc offset or exponential component). The initial value of this dc offset depending on the voltage incidence angle (the voltage value when the fault occurs), and the line parameters may be between 0 and *I sc, being I sc the rms value of the short-circuit symmetrical current. Considering this maximum value, the transient short-circuit current is defined by the following equation: Where: I = Peak value of current ω = * π *f α= angle on voltage wave at which fault occurs θ = arctan (ω*x/r) T 1 = X/R (of power system) i(t) t ( t + ) I * Sin ( )* e ÿ1 = I*Sin (1) Assuming that the secondary load is essentially resistive, the necessary flux in the CT to avoid saturation is defined by the following expression: ϕ T = ϕ A [ T1T T1 T ts ts T1 T e e Sin t ] () Where: T 1 = T = ϕ A = t s = Line time constant or primary time constant = L/R CT time constant or secondary time constant Peak value of symmetrical ac flux Any given time during which maximum transient flux will remain without CT saturation, or the time after which saturation is permitted. For T >> T1 (the case of TPY and TPX class CT s with and without air gaps), Equation () turns to: ϕ T = ϕ A [ ts 1 T 1 T e 1 Sin t ] (3) As the load and wiring are mainly resistive, we can consider Sin ωt = -1; and then equation (3) is reduced to: ts e 1 ϕ T = ϕ A [ T1 1 T + 1] 4 GER-3973 Application note

ÿþ üûúùø öõöôùóùõò CT Dimensioning Finally because T s (relay response time + Circuit Breaker operating time) is normally much higher than T1, the expression can be reduced as follows: ϕ T = ϕ A (ωt 1 +1) (4) During faults the CT s will be forced to develop a flux necessary to feed fault current to the secondary with two components: the exponential (dc offset asymmetrical component) and the ac component (symmetrical component). The resultant voltage must be higher than that necessary to feed the load connected in the secondary side of CT s without distortions caused by saturation. Hence, the necessary oversize factor Ks is defined by: where the overdimensioning or transient factor is: ϕ transient = ϕ dc + ϕ ac =*K s ϕ ac K s = ts 1 T 1 T e 1 Sin t (5) Application note GER3973 5

CT Dimensioning ÿþ üûúùø öõöôùóùõò. RESULTANT VOLTAGES ON CT SECONDARIES DURING FAULTS In general, testing and experience have shown that the performance of many relays will not be adversely affected by moderate degrees of CT saturation. However, since it is not economically feasible to test and determine the performance of all types of relays with different degrees of saturation, it is common practice to specify CT requirements for various protective schemes. The requirement generally specified is that the CTs should not saturate before the relays operate for some specified fault location. To meet this criterion, the required transient performance for a current transformer can be specified by calculating the minimum required saturation voltage. In general different standards as IEC 185, BS3938 or ANSI/IEEE C5713 fix this voltage by the general expression: V s = k 0 k s kr I R (6) where: V s = I = R = Saturation voltage as defined by the intersection point of the extensions of the straight line portions (the unsaturated and the saturated regions) of the excitation curve Symmetrical fault current in secondary Amperes Total secondary resistance burden including CT secondary, wiring loop resistance, lead resistance and load resistance. T1T T1 T s s e e k s = Saturation or transient factor = T1 T + 1 t t (as per Eq. ) where T = Secondary time constant T 1 = Time constant of the dc component of fault component. It is proportional to the X/R ratio of the system. ω = t s = K 0 = K R = System angular frequency Time to saturation. This is equal or greater than the relay operating time. Represents the effect of the offset present during the fault. This offset is a function of the time when the fault occurs, being maximum at zero voltage (0º or 180º). Experience states that the incidence angle of the faulted voltage is near 90º that produce a lower offset effect. Therefore this factor will apply in those cases where offset exceeds 0.5 p.u Remanent flux factor. The remanent flux can remain in the core due to the following: The excitation current leads the load current by 90º and thereby under normal control open commands, the load current is cut near or at zero crosses, but the excitation current in the CT has significant value. DC tests performed on the CT s The effect of the dc component on offset fault currents (exponential component) which is interrupted when tripping the circuit breaker. 6 GER-3973 Application note

ÿþ üûúùø öõöôùóùõò CT Dimensioning Equation () is valid for CTs with air-gapped cores because of their low magnetizing impedance and then with low secondary time constant T. The air-gaps used in CTs tends to reduce drastically the effect of the remanent flux left in the core due to its lower magnetizing impedance and therefore much lower secondary time constant. The effect of the remanent flux is also to reduce the time to saturation. This factor may vary from1.4to.6timestheratedfluxinthecore. For a closed-core CTs (normal CT s), the secondary time constant T is too high (L magnetizing before saturation), equation (5) does no include it, and then a conservative value for time to saturation will result. Application note GER3973 7

CT Dimensioning ÿþ üûúùø öõöôùóùõò 3. TIME TO MAXIMUM FLUX TIME TO SATURATION After the initiation of the short-circuit the flux β 0 and the corresponding magnetizing current I 0 will reach a maximum at a time defined by: T1 T T1 T ln T T 1 t ma x = (7) Finally the time to saturation is given by the following expression: t s = ÿ f ln K 1 s 1 ÿ (8) Where: K s =V Saturation /( I fault *R ) V Saturation = Saturation voltage as defined in page 5 I fault = Secondary fault current R = Total loop resistance as defined in page 5 X/R = Reactance to resistance ratio of any given circuit, generator, etc. See Tables 1 or and specific curves herein enclosed. The decrement or rate of decay of the d-c component is proportional to the ratio of reactance to resistance of the complete circuit from the generator (source) to the short-circuit. If the ratio of reactance to resistance is infinite (i.e zero resistance), the d-c component never decays. On the other hand, if the ratio is zero (all resistance, no reactance), it decays immediately. For any ratio of reactance to resistance in between these limits, the d-c component takes a definite time to decrease to zero. In generators the ratio of subtransient reactance to resistance may be as much as 70:1; so it takes several cycles for the d-c component to disappear. /*In circuits remote from generators, the ratio of reactance to resistance is lower, and the d-c component decays more rapidly. The higher the resistance in proportion to the reactance, the more I R loss from the d-c component, and the energy of the direct current is dissipated sooner. Often said that generators, motors, or circuits have a certain d-c time constant. This refers again to the rate of decay of the d-c component. The d-c time constant is the time, in seconds, required by the d-c component to reduce to about 37% of its original value at the instant of short circuit. It is the ratio of the inductance in Henrys [V * s/a] to the resistance in Ohms of the machine or circuit. This is merely a guide to show how fast the d-c component decays. Typical values of X/R ratios of distribution and transmission lines depending on their rated voltages and geometrical configuration are shown in Table 1. 8 GER-3973 Application note

ÿþ üûúùø öõöôùóùõò CT Dimensioning TABLE 1 Sequence X/R Ratios for Distribution and Transmission Lines 69 kv (Avg.) 115 kv (Avg.) 138 kv (Avg.) 30 kv (Avg.) 380 kv (Line Type) 500 kv (Line Type) X 1 /R 1.30 3.40 3.98 7.36 9.80 (Hor.) 9.6 (Delta) X 0 /R 0 1.95 3.05 4.3 4.08 3. (Hor.) 3.3 (Delta) 4.3 (Hor.) 18.5 (Vert.l) 3.5 (Hor.) 5.0 (Vert.) Table shows X/R ratios for generators, transformers, etc. as a function of their rated power. TABLE X/R Ratios for Other Power System Elements Large Generators Power Transformers Reactors Utilities 40-10 Typical 80 See Curve 40-10 Typical 80 15-30 (near generating plant) Power Transformer X/R Ratios X/R Ratios 10 9 8 7 6 5 4 3 1 0 0 0.5 1 1.5.5 3 3.5 ONAN MVARating (0.03-3 MVA) Application note GER3973 9

CT Dimensioning ÿþ üûúùø öõöôùóùõò Power Transformer X/R Ratios X/R Ratio 50 40 30 0 10 0 0 50 100 150 00 50 ONAN MVA Rating (3-00 MVA) 10 GER-3973 Application note

ÿþ üûúùø öõöôùóùõò CT Dimensioning 4. TRIPPING TIMES OF PROTECTION DEVICES Instantaneous units of overcurrent (50) and distance protections normally operates in 15 to 30 ms, and therefore dimensioning factors must consider that the relay tripping times should be lower than time to saturation t s Therefore to guarantee the correct operation of protection devices the equation () must be applied choosing as parameter t the instantaneous operating times of the different relays. Table 3 shows typical tripping times for different GE relays and the necessary overdimensioning factor K s using CT class TPX with a secondary time constant T = 3 seconds. TABLE 3 Relay Instantaneous Operating Time (s) Primary Time Constant T 1 (after which saturation is permitted) Overdimensioning Factor K s MIC/MRC 5 ms 40 ms 6.81 60 ms 7.39 70 ms 7.57 80 ms 7.7 DLP 0 ms 70ms 6.45 ALPS 10 ms 70ms 3.9 DGP 5 ms 70ms 7.57 SR489 45 ms 70ms 11.34 SMOR 5ms 70ms 7.57 DTP 45ms 70ms 11.34 Application note GER3973 11

CT Dimensioning ÿþ üûúùø öõöôùóùõò 5. RESULTANT FAULT VOLTAGES AND CT DIMENSIONING With results shown in TABLE 3 and neglecting factors K 0 and K R for equation (6), the next lines describe the way to find the resultant Precision Limit and the necessary overdimensioning of the CT core (rated power dimensioning) to avoid saturation previous to the tripping time of relays under consideration. If assumes that the phase-to-phase short-circuit current is of the same order of magnitude than the phase-toground short-circuit current, then a single equation should be used. If not K s factor must be verified for both situations: the positive sequence component during three-phase faults as well as the zero sequence component for phase-to-ground faults. In the present case will use equation (6) for all: Example Being: K s =6.18 Relay Resistance: 0.04Ω CT Ratio: 600/1 V rated = 13.8 kv, 50 Hz P shortcircuit = 0.597 GVA (assumed) CT Class: 5P0 CT Secondary Winding Resistance: 1.5Ω (assumed) L wiring : * 10m (6 mm cross section cable) (assumed) R wiring = 0.059Ω K 0 not considered K R not considered P 3 V CT SC ( RCT+ RW RR) V s rated Ks + ratio V s = k 0 k s krir = = 4976/600 (1.5Ω + 0.059Ω +0.04Ω) = 411 V 411 Equivalent Power: 0 () 1A 15. Ω 1 = 19 VA 1 GER-3973 Application note

ÿþ üûúùø öõöôùóùõò CT Dimensioning 6. TERMS AND DEFINITIONS 6.1 Rated Primary Short-circuit Current (IPrimarysc) RMS value of the primary symmetrical short-circuit current on which the rated accuracy performance of the current transformer is based. 6. Instantaneous Error Current (I ε ) Difference between instantaneous values of the primary current and the product of the turns ratio times the instantaneous values of the secondary current. When both alternating current and direct current components are present, I ε must be computed as the sum of both constituent components: I ε =I εac +I εdc = ( n * I Secondary ac - I Primary ac )+(n*i Secondary dc - I Primary dc ) 6.3 Peak Instantaneous Error (ξ i ) Maximum instantaneous error current for the specified duty cycle, expressed as a percentage of the peak instantaneous value of the rated primary short-circuit current 6.4 Peak Instantaneous Alternating Current Component Error (ξ ac ) Maximum instantaneous error of the alternating current component expressed as a percentage of the peak instantaneous value of the rated primary short-circuit current. ξ ac = 100 * I ε ac /( *I Primary Short-circuit ) (%) Defined by the Class Index followed by the letter P 6.5 Accuracy Class 6.6 Class Index Accuracy limit defined by composite error (ξ c ) with the steady state symmetrical primary current. This number indicates the upper limit of the composite error at the maximum accuracy current feeding the accuracy load. The standard class indexes are 5 and 10. No limit for remnant flux. 6.7 Limit Factor Is the ratio between the limit accuracy current and the rated primary current. For protection applications this factor normally is 10 or 0 Application note GER3973 13

CT Dimensioning ÿþ üûúùø öõöôùóùõò 6.8 Class P Current Transformer Indicates Protection current transformers destined to feed protection relays. Accuracy limit is defined by composite error ξ ac with steady state symmetrical primary current. There is no limit for remanent flux. 6.9 Class TPS Current Transformer Low leakage flux current transformer for which performance is defined by the secondary excitation characteristics and turns ratio error limits. There is no limit for remanent flux. 6.10 Class TPX Current transformer Accuracy limit defined by peak instantaneous error (ξ i ) during specified transient duty cycle. There is no limit for remanent flux. 6.11 Class TPY Current Transformer Accuracy limit defined by peak instantaneous error (ξ i ) during specified transient duty cycle. Remanent flux does not exceed 10% of the saturation flux. 6.1 Class TPZ Current Transformer Accuracy limit defined by peak instantaneous alternating current component error (ξ ac ) during single energization with maximum dc. offset at specified secondary loop time constant. No requirements for dc. component error limit. Remanent flux to be practically null. 6.13 Primary Time Constant (T 1 ) That specified value of the time constant of the dc. component of the primary current on which the performance of the current transformer is based. 6.14 Secondary Loop Time Constant (T ) Value of the time constant of the secondary loop of the current transformer obtained from the sum of the magnetizing and the leakage inductance (L s ) and the secondary loop resistance (R s ). Normally this value is higher as compared with T 1 in TPS class current transformers (about 10s). T will depend on the precision requirements but normally oscillates between 0.3 and 1 seconds for TPY class current transformers. Finally T is much more lower in TPZ class current transformers (about 0.07 seconds). 6.15 Time to Maximum Flux (t ϕ max ) Elapsed time during a prescribed energization period at which the transient flux in a current transformer core achieves maximum value, it being assumed that saturation of the core does not occur. 14 GER-3973 Application note

ÿþ üûúùø öõöôùóùõò CT Dimensioning 6.16 Secondary Winding Resistance (R CT ) Secondary winding dc. resistance in Ohms, corrected to 75º C, unless otherwise specified, and inclusive of all external burden connected. 6.17 Secondary Loop or Burden Resistance (R B ) Total resistance of the secondary circuit, unless otherwise specified, and inclusive of all external burden connected. 6.18 Low Leakage Flux Current Transformer Current transformer for which a knowledge of the secondary excitation characteristic and secondary winding resistance is sufficient for an assessment of its transient performance. This is true for any combination of burden and duty cycle at rated or lower value of primary symmetrical short-circuit current up to the theoretical limit of the current transformer determined from the secondary excitation characteristic. 6.19 Saturation Flux(Ψ S ) That peak value of the flux which would exist in a core in the transition from the non-saturated to the fully saturated condition. This regards to the point on the B-H characteristic of the core at which a 10% increase in B causes H to be increased by 50%. 6.0 Remanent Flux (Ψ R) That value of flux which would remain in the core three minutes after the interruption of an exciting current of sufficient magnitude as to induce the saturation flux (Ψ S ). Application note GER3973 15

CT Dimensioning ÿþ üûúùø öõöôùóùõò 16 GER-3973 Application note