ACTATOR FOR DAMPERS Quick running actuator Actuator with rotation drive. 4 Nm 8 Nm For the application with Laboratory ventilation techniques Room ventilation techniques VAV Valves Page: Content: 3 4-5 6-7 8-9 0-7 8-9 0 General overview quick running actuator,.,, 8 Nm + Actuator with digital drive Technical Data, quick running actuator,. Technical Data, quick running actuator, 8 Nm Technical Data, quick running actuator, Technical Data, quick running actuator, Technical Data, quick running actuator, 4 Nm Specific characteristics of continuous control Notes our way to Gruner G R N E R t h e f r i e n d l y a l t e r n a t i v e
GENERAL OVERVIEW: QICK RNNING ACTATORS = Standard = Optional Type Torque Running time (90 ) Control Tri-state On/Off Continuous control (0)...0 VDC or (0) 4...0 ma Power supply 4 VAC/DC 30 VAC Options Digital Drive Feedback signal GAC Connection Page 7CS-04-0 7CS-04-08. s 4 8 Nm 4 s 6 5 s 8 7CS-04-5 = Standard = Optional Type Torque Running time (90 ) Control Tri-state On/Off Continuous control (0)...0 VDC or (0) 4...0 ma w/ 500Ω Power supply 4 VAC/DC 30 VAC Options Digital Drive Potentiometer Feedback signal Auxiliary switch GAC Connection Page 0...35s 0 7S-04-05 0...35s 0 7S-04-05-S 0...35s 0 0...35s 7S-30-05 7S-04-05-P5 0...35s 7S-30-05-S 0...35s Standard version with universal locking clamp and anti torsion bow. Also available with concentric form locking for shaft ( 8 mm) and flange fixing. All actuators dispose of manual override button, a mechanical limitation of the angle of rotation and setting button for the rotation direction (cw/ccw). Actuators according to S-standards available upon demand. 7S-30-05-P5 0...35s 4 7S-3-30-05 0...35s 4 7S-3-30-05-S 0...35s 4 7S-3-30-05-P5 0...35s 6 7CS-04-05 4 Nm 5 s 8 7CS-04-04
ACTATOR WITH DIGITAL DRIVE 3 The actuators with digital drive have no dip switches for setting the functions. All settings are done by the GIV (Windows PC or Handheld device) via PP-Bus: Available options: direction of rotation increasing of running time up to 0 s control signal = (0)...0 VDC control signal = (0) 4...0 ma @ 500Ω feedback signal = (0)...0 VDC limitation of angle of rotation 0...00% of 95 - α Min correspond (0) VDC - α Max correspond 0 VDC digital control via α Const as variable for angular control Connection scheme BBNBKG /PP Angular control Windows software 00% 0% 0 /VDC GIV Connection PP-Bus LED's / PP FNCTION DATA CONNECT POWER LED RD E GN 3 / PP GIV-S B BN BK G - + AC 4V DC 4V 3 5 5 / PP GIV-S 3 3 PC
4 7CS-04-0 Applications To regulate dampers, valves or other regulatory functions: sturdy drive torque. running time s position indication angle of rotation changeable from outside load independent speed regulated direction of rotation changeable from inside electromagnetic compatibility controlled maintenance-free Technical data 7CS-04-0 Connnection scheme (continuous control) Control Control signal (Continuous control) Control signal (On/Off) Feedback signal Connecting voltage Power consumption Transformer sizing Angle of rotation Direction of rotation Running time (90 ) Torque Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight Continuous control / On/Off 0...0 VDC or...0 VDC (Standard) or 0...0 ma or 4...0 ma 0 VDC (Off) 4 VAC / DC (On) 0...0 VDC or...0 VDC (Standard) 4 VAC (50/60 Hz) / DC±0% 8.0 W.0 VA max. 95 (adjustable from outside) changeable from inside s. cable 900 mm / 0.75 mm III IP 54 (cable downwards) 5 x 65 x 89 mm -0...+50 C maintenance-free 73/3/EWG, 89/336/EWG 750 g BBNBKG
7CS-04-0 5 Adjustment of the angle of rotation (fig. ) 0 Both end stops are adjusted to 0 and 90. For smaller rotation angles, loosen the screws at the metal end stop, adjust the end stops as requested, and fasten the screws again. Ø6 Fixing of the shaft (fig. ) by the locking clamp to the damper shaft: 8... mm 8...6 mm Adjustment of the functional switches (fig. ) Direction of rotation clockwise (0...90 ) counter clockwise (90...0 ) OFF ON 3 - - 3 ON OFF 3 4 Control signal...0 VDC (Standard) 0...0 VDC 4...0 ma 0...0 ma, - -, Switches actually unused must be at position OFF. All switches are set to OFF by factory default. Technical drawing 7CS-04-0
6 7CS-04-08 Application To regulate dampers, valves or other regulatory functions: sturdy drive torque 84 Nm running time 4 s position indication angle of rotation changeable from outside load independent speed regulated direction of rotation changeable from inside electromagnetic compatibility controlled maintenance-free Technical data 7CS-04-08 Connnection scheme (continuous control) Control Control signal (Continuous control) Control signal (On/Off) Feedback signal Connecting voltage Power consumption Transformer sizing Angle of rotation Direction of rotation Running time (90 ) Torque Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight Continuous control / On/Off 0...0 VDC or...0 VDC (Standard) or 0...0 ma or 4...0 ma 0 VDC (Off) 4 VAC / DC (On) 0...0 VDC or...0 VDC (Standard) 4 VAC (50/60 Hz) / DC±0%.0 W 5.0 VA max. 95 (adjustable from outside) changeable from inside 4 s 8 Nm cable 900 mm / 0.75 mm III IP 54 (cable downwards) 5 x 65 x 89 mm -0...+50 C maintenance-free 73/3/EWG, 89/336/EWG 750 g BBNBKG
7CS-04-08 7 Adjustment of the angle of rotation (fig. ) 0 Both end stops are adjusted to 0 and 90. For smaller rotation angles, loosen the screws at the metal end stop, adjust the end stops as requested, and fasten the screws again. Ø6 Fixing of the shaft (fig. ) by the locking clamp to the damper shaft: 8... mm 8...6 mm Adjustment of the functional switches (fig. ) Direction of rotation clockwise (0...90 ) counter clockwise (90...0 ) OFF ON 3 - - 3 ON OFF 3 4 Control signal...0 VDC (Standard) 0...0 VDC 4...0 ma 0...0 ma, - -, Switches actually unused must be at position OFF. All switches are set to OFF by factory default. Technical drawing 7CS-04-08
8 7CS-04-5 Application To regulate dampers, valves or other regulatory functions: Lifetime under full load 8 Nm more than 60,000 cycles at least 0,000 cycles running time 5 s angle of rotation changeable from outside load independent speed regulated direction of rotation changeable from inside electromagnetic compatibility controlled maintenance-free Technical data 7CS-04-5 Connnection scheme (continuous control) Control Control signal (Continuous control) Control signal (On/Off) Feedback signal Connecting voltage Power consumption Transformer sizing Max. allowable running time per 00 s Angle of rotation Direction of rotation Running time (90 ) Torque Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight Conntinuous control / On/Off 0...0 VDC or...0 VDC (Standard) or 0...0 ma or 4...0 ma 0 VDC (Off) 4 VAC / DC (On) 0...0 VDC or...0 VDC (Standard) 4 VAC (50/60 Hz) / DC±0% 0.0 W 6.0 VA 50% ED max. 95 (adjustable from outside) changeable from inside 5 s cable 900 mm / 0.75 mm III IP 54 (cable downwards) 5 x 65 x 89 mm -0...+50 C maintenance-free 73/3/EWG, 89/336/EWG 750 g BBNBKG
7CS-04-5 9 Adjustment of the angle of rotation (fig. ) 0 Both end stops are adjusted to 0 and 90. For smaller rotation angles, loosen the screws at the metal end stop, adjust the end stops as requested, and fasten the screws again. Ø6 Fixing of the shaft (fig. ) by the locking clamp to the damper shaft: 8... mm 8...6 mm Adjustment of the functional switches (fig. ) Direction of rotation clockwise (0...90 ) counter clockwise (90...0 ) OFF ON 3 - - 3 ON OFF 3 4 Control signal...0 VDC (Standard) 0...0 VDC 4...0 ma 0...0 ma, - -, Switches actually unused must be at position OFF. All switches are set to OFF by factory default. Technical drawing 7CS-04-5
0 7S-04-05, 7S-04-05-S, 7S-04-05-P5 Application To regulate dampers, valves or other regulatory functions: sturdy drive torque load dependent running time position indication angle of rotation changeable from outside direction of rotation changeable from outside Auxiliary switch adjustable from outside electromagnetic compatibility controlled maintenance-free Technical data Control Connecting voltage Power consumption Transformer sizing Angle of rotation Direction of rotation Running time (90 ) Torque max. auxiliary switch Schaltleistung Zusatzschalter Rückführpoti Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight On/Off + Tristate 4 VAC (50/60 HZ) / DC ±0% 3.5 W 6.5 VA max. 95 (adjustable from outside) changeable from outside 0...35 s changeable from outside 50 VAC / 5 A, change-over switch 4.7 kω cable 900 mm / 0.75 mm III IP 54 (cable downwards) 5 x 65 x 6 mm -0...+50 C maintenance-free 73/3/EWG, 89/336/EWG 530 g 7S-04-05 7S-04-05-S 7S-04-05-P5 Connection scheme Connection scheme Connection scheme B BNBK On/Off B BNBK B BNBK B BNBK B BNBK B BNBK 3 S Tristate Potentiometer 3 Auxiliary switch
7S-04-05, 7S-04-05-S, 7S-04-05-P5 M5 Adjustment of the angle of rotation (fig. ) Both end stops are adjusted to 0 and 90. For smaller rotation angles, loosen the screws at the metal end stop, adjust the end stops as requested, and fasten the screws again. 0 Fixing of the shaft (fig. ) Ø6 by the locking clamp to the damper shaft: 8... mm 8...6 mm Adjustment of the direction of rotation (fig. ) S S3 S 0,,4,6,8 S S3 S 50 VAC 5 (,5) A S S S3 7S-04-05-S 4VAC/ DC B BN BK 50/60Hz 3,5 W 0...35 s IP 54 The actuator is adjusted to clockwise direction by the factory => R. For changing the direction of rotation, turn the adjusting knob to L. Adjustment of the auxiliary switch (fig. ) The scale at the adjusting know corresponds to a percentage graduation, related to 0-90. ) End stop is set to 0 : Switch off the motor and choose the requested switching position by turning the knob to the right, i.e.. = 0%. ) End stop is set to : Switch off the motor rand choose the requested switching position by turning the knob to the left, i.e..8 = 0%. Technical drawing 7S-04-05
7S-30-05, 7S-30-05-S, 7S-30-05-P5 Application To regulate dampers, valves or other regulatory functions: sturdy drive torque load dependent running time position indication angle of rotation changeable from outside direction of rotation changeable from outside Auxiliary switch adjustable from outside electromagnetic compatibility controlled maintenance-free Technical data Control Connecting voltage Power consumption Transformer sizing Angle of rotation Direction of rotation Running time (90 ) Torque max. auxiliary switch Schaltleistung Zusatzschalter Rückführpoti Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight On/Off 30 VAC (50/60 HZ) ±5%. W 8.0 VA max. 95 (adjustable from outside) changeable from outside 0...35 s changeable from outside 50 VAC / 5 A, change-over switch 4.7 kω cable 900 mm / 0.75 mm II IP 54 (cable downwards) 5 x 65 x 6 mm -0...+50 C maintenance-free 73/3/EWG, 89/336/EWG 530 g 7S-30-05 7S-30-05-S 7S-30-05-P5 Connection scheme (On/Off) Connection scheme (On/Off) Connection scheme (On/Off) S 3 Auxiliary switch B BNBK B BNBK 3 B BNBK N L N L Potentiometer N L
7S-30-05, 7S-30-05-S, 7S-30-05-P5 3 M5 Adjustment of the angle of rotation (fig. ) Both end stops are adjusted to 0 and 90. For smaller rotation angles, loosen the screws at the metal end stop, adjust the end stops as requested, and fasten the screws again. 0 Fixing of the shaft (fig. ) Ø6 by the locking clamp to the damper shaft: 8... mm 8...6 mm Adjustment of the direction of rotation (fig. ) S S3 S 0,,4,6,8 S S3 S 50 VAC 5 (,5) A S S S3 7S-04-05-S 4VAC/ DC B BN BK 50/60Hz 3,5 W 0...35 s IP 54 The actuator is adjusted to clockwise direction by the factory => R. For changing the direction of rotation, turn the adjusting knob to L. Adjustment of the auxiliary switch (fig. ) The scale at the adjusting know corresponds to a percentage graduation, related to 0-90. ) End stop is set to 0 : Switch off the motor and choose the requested switching position by turning the knob to the right, i.e.. = 0%. ) End stop is set to : Switch off the motor rand choose the requested switching position by turning the knob to the left, i.e..8 = 0%. Technical drawing 7S-30-05
4 7S-3-30-05, 7S-3-30-05-S, 7S-3-30-05-P5 Application To regulate dampers, valves or other regulatory functions: sturdy drive torque load dependent running time position indication angle of rotation changeable from outside direction of rotation changeable from outside Auxiliary switch adjustable from outside electromagnetic compatibility controlled maintenance-free Technische Daten Control Connecting voltage Power consumption Transformer sizing Angle of rotation Direction of rotation Running time (90 ) Torque max. auxiliary switch Schaltleistung Zusatzschalter Rückführpoti Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight Tristate 30 VAC (50/60 HZ) ±5%. W 8.0 VA max. 95 (adjustable from outside) changeable from outside 0...35 s changeable from outside 50 VAC / 5 A, change-over switch 4.7 kω cable 900 mm / 0.75 mm II IP 54 (cable downwards) 5 x 65 x 6 mm -0...+50 C wartungsfrei 73/3/EWG, 89/336/EWG 530 g 7S-3-30-05 7S-3-30-05-S 7S-3-30-05-P5 Connection scheme (Tri-state) Connection scheme (Tri-state) Connection scheme (Tri-state) S B BNBK B BNBK 3 B BNBK 3 N L N L Potentiometer N L Auxiliary switch
7S-3-30-05,7S-3-30-05-S,7S-3-30-05-P5 5 M5 Adjustment of the angle of rotation (fig. ) Both end stops are adjusted to 0 and 90. For smaller rotation angles, loosen the screws at the metal end stop, adjust the end stops as requested, and fasten the screws again. 0 Fixing of the shaft (fig. ) Ø6 by the locking clamp to the damper shaft: 8... mm 8...6 mm Adjustment of the direction of rotation (fig. ) S S3 S 0,,4,6,8 S S3 S 50 VAC 5 (,5) A S S S3 7S-04-05-S 4VAC/ DC B BN BK 50/60Hz 3,5 W 0...35 s IP 54 The actuator is adjusted to clockwise direction by the factory => R. For changing the direction of rotation, turn the adjusting knob to L. Adjustment of the auxiliary switch (fig. ) The scale at the adjusting know corresponds to a percentage graduation, related to 0-90. ) End stop is set to 0 : Switch off the motor and choose the requested switching position by turning the knob to the right, i.e.. = 0%. ) End stop is set to : Switch off the motor rand choose the requested switching position by turning the knob to the left, i.e..8 = 0%. Technical drawing 7S-3-30-05
6 7CS-04-05 Application To regulate dampers, valves or other regulatory functions: sturdy drive torque load dependent running time position indication angle of rotation changeable from outside direction of rotation changeable from outside electromagnetic compatibility controlled maintenance-free 7CS-04-05 Connection scheme (Continuous control) Control Control signal Feedback signal Connecting voltage Power consumption Transformer sizing Angle of rotation Direction of rotation Running time (90 ) Torque Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight Technical data Continuous control 0...0 VDC or...0 VDC (Standard) or 0...0 ma or 4...0 ma 0...0 VDC or...0 VDC (Standard) 4 VAC (50/60 Hz) / DC ±0% 3.5 W 5.5 VA max. 95 (adjustable from outside) changeable from outside 0...35 s cable 900 mm / 0.75 mm III IP 54 (cable downwards) 5 x 65 x 6 mm -0...+50 C maintenance-free 73/3/EWG, 89/336/EWG 530 g BBNBKG
7CS-04-05 7 M5 Adjustment of the angle of rotation (fig. ) Both end stops are adjusted to 0 and 90. For smaller rotation angles, loosen the screws at the metal end stop, adjust the end stops as requested, and fasten the screws again. 0 Fixing of the shaft (fig. ) Ø6 by the locking clamp to the damper shaft: 8... mm 8...6 mm Adjustments (fig. ) 0% 00% 7CS-04-05 4VAC/DC 50/60Hz 3,5 W 0...35 s IP 54 =...0VDC =...0VDC Angle of rotation: The actuator is adjusted to clockwise direction by the factory => R. For changing the direction of rotation, turn the adjusting knob to L. Regulation range: The actuators are supplied with the (0)...0 VDC for the regulation range 0 to 90. A smaller angle (proportional) can be chosen, where the regulation range (0)...0 VDC goes for. The actuator must be switched off for doing so. B BN BK G Technical drawing 7CS-04-05
8 7CS-04-04 Application To regulate dampers, valves or other regulatory functions: sturdy drive torque 4 Nm load dependent running time position indication angle of rotation changeable from outside direction of rotation changeable from outside electromagnetic compatibility controlled maintenance-free 7CS-04-04 Connection scheme (Continuous control) Control Control signal Feedback signal Connecting voltage Power consumption Transformer sizing Angle of rotation Direction of rotation Running time (90 ) Torque Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight Technical data Continuous control 0...0 VDC or...0 VDC (Standard) or 0...0 ma or 4...0 ma 0...0 VDC or...0 VDC (Standard) 4 VAC (50/60 Hz) / DC ±0%.0 W 5.0 VA max. 95 (adjustable from outside) changeable from outside 5 s 4 Nm cable 900 mm / 0.75 mm III IP 54 (cable downwards) 5 x 65 x 6 mm -0...+50 C maintenance-free 73/3/EWG, 89/336/EWG 530 g BBNBKG
7CS-04-04 9 M5 Adjustment of the angle of rotation (fig. ) Both end stops are adjusted to 0 and 90. For smaller rotation angles, loosen the screws at the metal end stop, adjust the end stops as requested, and fasten the screws again. 0 Fixing of the shaft (fig. ) Ø6 by the locking clamp to the damper shaft: 8... mm 8...6 mm Adjustment of the direction of rotation (fig. ) 7CS-04-04 4VAC/DC 50/60Hz W 4 Nm 5 s IP 54 =...0VDC =...0VDC The actuator is adjusted to clockwise direction by the factory => R. For changing the direction of rotation, turn the adjusting knob to L. B BN BK G Technical drawing 7CS-04-04
0 SPECIFIC CHARACTERISTICS OF CONTINOS CONTROL Wiring configuration and recommended cable length - + 7CS - + 7CS B BN BK G B BN BK G L L 4VAC transformer I G R L < 4VAC transformer - + - + - + - + DC 0()...0V by the controller DC 0()...0V by the actuator max. cable length ( I + I ) R A G L > L L DC 0()...0V by the controller DC 0()...0V by the actuator max. cable length current of set valve selector actuator current cable resistance cable length cable cross section cable cross section 0,75 mm mm,5 mm max. cable length 3 m 3 m 46 m,5 mm 76 m For several actuators switched in parallel the max. cable length must be divided by the number of actuators. Teach-in of range of angle > 30 BBNBKG. Actuator stand by. Adjusting mechanical endstops 3. 5 VDC at 4. Power on actuator 5. Actuator starts teach-in process of range of angle (0...30 s) 6. Remove 5 VDC at 5 VDC http://www..gruner.de
NOTES http://www..gruner.de
OR WA TO GRNER Stuttgart A8 München Balingen Strasbourg A5 Karlsruhe Freudenstadt Schramberg Offenburg B33 Freiburg B3 Schömberg A8 Wehingen B7 Gosheim Frittlingen Denkingen Tuttlingen Rottweil B4 34 B7 Donaueschingen Singen Spaichingen Aldingen Basel N3 Zürich N http://www..gruner.de