SIMATIC. ET 200S distributed I/O 2AI U ST analog electronic module (6ES7134-4FB01-0AB0) Preface. Properties 1. Parameters 2.



Similar documents
SIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2.

SIMATIC. ET 200S distributed I/O Digital electronic module 8DI DC24V (6ES7131-4BF00-0AA0) Preface. Properties 1. Diagnostics 2.

SIMATIC. ET 200S distributed I/O Digital electronic module 8DO DC24V/0.5 A (6ES7132-4BF00-0AA0) Preface. Properties 1. Diagnostics 2.

CPU PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU PN/DP: Configuring an ET 200S as PROFINET IO device

SIMATIC NET. CP AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

SIMATIC. SM 335 High-Speed Analog Input/Output Module for the SIMATIC S7-300

Modular I/O System Analog and Digital Interface Modules

SIMATIC S Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E

SIMATIC HMI. WinCC flexible 2008 Getting Started - First-Time Users Getting Started. Printout of the Online Help 06/2008 A5E

Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3 SIMATIC. Readme. Programming and Operating Manual

Fieldbus slave modules with I/Os, DIO

Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date:

DI 16x24VDC HF Digital Input Module (6ES7521-1BH00-0AB0) SIMATIC. S7-1500/ET 200MP DI 16x24VDC HF Digital Input Module (6ES7521-1BH00-0AB0) Preface

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

SIMATIC. S7 300 PLC CPU 317T-2 DP: Controlling a virtual axis. Introduction. Preparation. Learning units 3. Further information 4.

2 Counter Module SIMATIC. S7-300 FM Counter module. Preface. Product Overview. How the FM Counts 2. Installing and Removing the FM 350-

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

SIMATIC. WinCC V7.0. Getting started. Getting started. Welcome 2. Icons 3. Creating a project 4. Configure communication 5

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

SIMATIC. ET 200S distributed I/O IM151-1 STANDARD interface module (6ES7151-1AA05-0AB0) Preface. Properties 1. Parameters 2.

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library. Deleting program block Main [OB1] Copying program blocks

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

6ES7314-6CG03-0AB0. Supply voltages Rated value 24 V DC Yes permissible range, upper limit (DC) circuit breaker type B, min. 4 A

6ES7313-5BF03-0AB0. Supply voltages Rated value 24 V DC Yes permissible range, upper limit (DC) circuit breaker type B, min. 4 A

ABB Drives. User s Manual HTL Encoder Interface FEN-31

SIMATIC. S7-300 and M7-300 Programmable Controllers Module Specifications. Preface, Contents. General Technical Specifications. Power Supply Modules

Allen-Bradley/Rockwell

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

SINAMICS drives SINAMICS DCM. DC converters from 6 kw to 2500 kw for variable-speed direct-current drives. Load-balanced control application

MINI MCR-SL-R-UI(-SP)

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

Digital input modules

Validity 1. Installation 2 SIMATIC. WinCC flexible Tag simulator Update 1. Readme

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

Contents. Document information

Product Information. Gateway For Connecting EnDat Encoders to PROFIBUS-DP

Specifications for EM VDC 4 In/4 Out and EM VDC 4 In/4 Relay Out

SIMATIC. SIMATIC Logon. User management and electronic signatures. Hardware and Software Requirements. Scope of delivery 3.

JUMPFLEX 857 Series ma V ma. Transducers / Relay and Optocoupler Modules


SIMATIC NET. Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs. Preface. Overview and general information on working with FCs and FBs

What ensures easy and fast wiring?

Technical data. General specifications. Signal voltage V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.

PCS0100en Persy Control Services B.V. Netherlands

SIMATIC HMI. WinCC flexible Getting Started First Time User. Order number 6ZB5370-1CL02-0BA2. Edition 04/2006 A5E

Automation Unit TM 1703 ACP Flexible automation and telecontrol

Permissible ambient temperature Operation Storage, transport

SIMATIC. Open TCP/IP Communication via Industrial Ethernet. Contents Open TCP/IP Communication via Industrial Ethernet 1. Index.

Creating the project and hardware. TIA Portal. SIMATIC Creating the project and hardware. Introduction to the TIA Portal 1. Creating a project

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

Information Server Documentation SIMATIC. Information Server V8.0 Update 1 Information Server Documentation. Introduction 1. Web application basics 2

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

CQM1-SF200/CS1W-SF200

Visualization SIMATIC. Visualization. Present sample project. HMI configuration. Insert HMI device from libraries 3. Configuring HMI connection 4

ABB i-bus EIB Logic Module LM/S 1.1

EE-SPY801/802. Photomicrosensors for detecting wafer-carrier mounting. Wafer-carrier Mounting Photomicrosensors. Ordering Information.

Disturbance Recoder SPCR 8C27. Product Guide

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

Installation guide H A. HSI hardwired system interface

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

LOGO! LOGO! App V.10. LOGO! app 1. Making basic settings and establishing a connection to LOGO! Using the device overview 3. Creating controls 4

Short-circuit current rating (SCCR) of. industrial control panels. NEC Article 409 and UL 508A

SIMATIC. PC Adapter USB. Preface, Contents Properties of the PC Adapter USB 1. Package Components

Part 1: User information SIMATIC ET 200B Distributed I/O Station Manual Part 2: Reference information Appendices EWA 4NEB c Edition 04

Getting Started - SINAMICS Startdrive. Startdrive. SINAMICS Getting Started - SINAMICS Startdrive. Introduction 1

CompactLogix Power Supplies Specifications

Duct Humidity Transmitter

Non-Isolated Analog Voltage/Current Output module IC695ALG704 provides four configurable voltage or current output channels. Isolated +24 VDC Power

SIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M

Switch Actuator, 8-fold, 10 A, MDRC AT/S , GH Q R0111

Current Monitoring Kit

SIMATIC NET. AS-Interface - Introduction and Basics A B. Preface, Contents

Configuration limits for products of the SIMATIC NET PC Software V12 SIMATIC NET. Configuration limits for products of the SIMATIC NET PC Software V12

S7-400H SIMATIC. Fault-tolerant systems S7-400H. Preface 1 Fault-tolerant automation systems. S7-400H setup options 3.

SIMADYN D Digital Control System. Interface module SE21.2. User Manual. Edition DK-Nr

Operating Manual UMB Analogue/Digital Converter ANACON Order Number: 8160.UANA

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

TEA1024/ TEA1124. Zero Voltage Switch with Fixed Ramp. Description. Features. Block Diagram

L5354 ControlNet Communications Interface

IO-DIM6 6-Channel, Digital to Analogue Converters

EXTERNAL DIMENSIONS AND PARTS

IRT Eurocard. Types DAX-3200

Product Information Sheet UH36 Hi Pot Tester

Original instructions Tina 3A/Aps Adaptor unit

Speed sensor MiniCoder GEL 247

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODUL E04

Siemens AG 2011 SINAMICS V60. The perfect solution for basic servo applications. Brochure May 2011 SINAMICS. Answers for industry.

IBS IP KIS A. Data Sheet INTERBUS-S. Digital I/O Module

Operating instructions Diffuse reflection sensor. OJ50xx / / 2004

Safety technique. Emergency stop module BO 5988 safemaster

T-SERIES INDUSTRIAL INCLINOMETER ANALOG INTERFACE

NTE2053 Integrated Circuit 8 Bit MPU Compatible A/D Converter

Inductive Proximity Sensors

Patch management and security. updates SIMATIC. Process Control System PCS 7 Patch management and security updates. Preface 1

3M Wrist Strap and Footwear Tester 740. User s Guide

IRT Eurocard. Type DAX Audio Extractor for 270 Mb/s SDI

Preset Counter signo 721

Transcription:

SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O 2AI U ST analog electronic module (6ES7134-4FB01-0AB0) Manual Preface Properties 1 Parameters 2 Diagnostics 3 Analog value representation 4 Connecting 5 04/2007 A5E01076000-01

Safety Guidelines Safety Guidelines This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. CAUTION without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. NOTICE Qualified Personnel Prescribed Usage Trademarks indicates that an unintended result or situation can occur if the corresponding information is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes in this documentation qualified persons are defined as persons who are authorized to commission, ground and label devices, systems and circuits in accordance with established safety practices and standards. Note the following Disclaimer of Liability WARNING This device may only be used for the applications described in the catalog or the technical description and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as well as careful operation and maintenance. All names identified by are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Automation and Drives Postfach 48 48 90327 NÜRNBERG GERMANY Ordernumber A5E01076000-01 P 09/2007 Copyright Siemens AG 2007. Technical data subject to change

Preface Purpose of the manual This manual supplements the ET 200S Distributed I/O System Operating Instructions. General functions for the ET 200S are described in the ET 200S Distributed I/O System Operating Instructions. The information in this document along with the operating instructions enables you to commission the ET 200S. Basic knowledge requirements To understand these operating instructions you should have general knowledge of automation engineering. Scope of the manual This manual applies to this ET 200S module. It describes the components that are valid at the time of publication. Recycling and disposal Thanks to the fact that it is low in contaminants, this ET 200S module is recyclable. For environmentally compliant recycling and disposal of your electronic waste, please contact a company certified for the disposal of electronic waste. Additional support If you have any questions relating to the products described in these operating instructions, and do not find the answers in this document, please contact your local Siemens representative. http//www.siemens.com/automation/partner The portal to our technical documentation for the various SIMATIC products and systems is available at http//www.siemens.com/automation/simatic/portal The online catalog and ordering system are available at http//www.siemens.com/automation/mall Manual, 04/2007, A5E01076000-01 3

Preface Training center We offer courses to help you get started with the ET 200S and the SIMATIC S7 automation system. Please contact your regional training center or the central training center in D - 90327, Nuremberg, Germany. Phone +49 (911) 895-3200. http//www.siemens.com/sitrain Technical Support You can reach technical support for all A&D projects using the support request web form http//www.siemens.com/automation/support-request Phone + 49 180 5050 222 Fax + 49 180 5050 223 For more information about our technical support, refer to our Web site at http//www.siemens.de/automation/service Service & Support on the Internet In addition to our documentation services, you can also make use of our comprehensive online knowledge base on the Internet. http//www.siemens.com/automation/service&support There you will find Our Newsletter, which constantly provides you with the latest information about your products. The right documentation for you using our Service & Support search engine. The bulletin board, a worldwide knowledge exchange for users and experts. Your local contact for Automation & Drives in our contact database. Information about on-site services, repairs, spare parts. Lots more can be found on our "Services" pages. 4 Manual, 04/2007, A5E01076000-01

Table of contents Preface... 3 1 Properties... 7 1.1...7 2 Parameters... 11 2.1 Parameters...11 2.2 Parameter description...12 3 Diagnostics... 13 3.1 Diagnostics using LED display...13 3.2 Error types...14 4 Analog value representation... 15 4.1 Introduction...15 4.2 Analog value representation for measuring range with SIMATIC S7...15 4.3 Measuring ranges...16 4.4 Effect on analog value representation...18 4.4.1 Effect of the supply voltage and the operating state on analog input values...18 4.4.2 Effect of the value range on the 2AI U ST analog input...18 5 Connecting... 19 5.1 Connecting measuring sensors...19 5.2 Wiring unused channels of the analog input modules...22 5.3 Using the shield connection...22 Index... 23 Manual, 04/2007, A5E01076000-01 5

Table of contents 6 Manual, 04/2007, A5E01076000-01

Properties 1 1.1 Properties 2 inputs for measuring voltage Input ranges ± 10 V, resolution 13 bits + sign ± 5 V, resolution 13 bits + sign 1 V to 5 V, resolution 13 bits Isolated from the load voltage L+ Permissible common mode voltage 2 VACSS Extended temperature range from 0 to 50 C with vertical installation General terminal assignment Note Terminals 4, 8, A4, A8, A3 and A7 are only available at specified terminal modules. Terminal assignment for 2AI U ST (6ES7134-4FB01-0AB0) Terminal Assignment Terminal Assignment Notes 1 M0+ 5 M1+ Mn+ Input signal "+", channel n 2 M0-6 M1- Mn- Input signal "-", channel n 3 Mana 7 Mana Mana Ground of the module 4 n.c. 8 n.c. n.c. Not connected (max. 30 V DC can be connected) A4 AUX1 A8 AUX1 AUX1 Protective-conductor terminal or potential bus (freely usable up to 230 VAC) A3 AUX1 A7 AUX1 Manual, 04/2007, A5E01076000-01 7

Properties 1.1 Usable terminal modules TM-E15C26-A1 (6ES7193-4CA50-0AA0) TM-E15S26-A1 (6ES7193-4CA40-0AA0) TM-E15N26-A1 (6ES7193-4CA80-0AA0) TM-E15C24-A1 (6ES7193-4CA30-0AA0) TM-E15S24-A1 (6ES7193-4CA20-0AA0) TM-E15N24-A1 (6ES7193-4CA70-0AA0) Usable terminal modules for 2AI U ST (6ES7134-4FB01-0AB0) TM-E15C24-01 (6ES7193-4CB30-0AA0) TM-E15S24-01 (6ES7193-4CB20-0AA0) TM-E15N24-01 (6ES7193-4CB70-0AA0) TM-E15C23-01 (6ES7193-4CB10-0AA0) TM-E15S23-01 (6ES7193-4CB00-0AA0) TM-E15N23-01 (6ES7193-4CB60-0AA0) Spring terminal Screw-type terminal Fast Connect Block diagram Figure 1-1 Block diagram of the 2AI U ST 8 Manual, 04/2007, A5E01076000-01

Properties 1.1 2AI U ST technical specifications (6ES7134-4FB01-0AB0) Dimensions and weight Width (mm) 15 Weight Supports isochronous operation Approx. 40 g Module-specific data Number of inputs 2 Cable length Shielded Max. 200 m Parameter length Address space Rated load voltage L+ (from the power module) No 4 bytes 4 bytes Voltages, currents, potentials Reverse polarity protection Yes Electrical isolation Between the channels and backplane bus Yes Between the channels and load voltage L+ Yes Between the channels No Permissible potential difference 24 VDC Between the inputs and MANA (UCM) 2 VACSS Between MANA and the central grounding point (UISO) Insulation tested Current consumption 75 VDC / 60 VAC 500 VDC From load voltage L+ Max. 30 ma Power dissipation of the module Diagnostics function Typically 0.6 W Status, interrupts, diagnostics Group error Red "SF" LED Diagnostic functions readable Yes Measuring principle Integration and cycle time/resolution per channel Analog value generation Integration time can be assigned parameters Yes Integrative Interference frequency suppression in Hz 60 50 Integration time in ms 16,7 20 Conversion time in ms 55 65 Cycle time in ms Number of active channels per module x conversion time Resolution (including overshoot range) ± 10 V/13 bits + sign ± 5 V/13 bits + sign 1 V to 5 V/13 bits Manual, 04/2007, A5E01076000-01 9

Properties 1.1 Suppression of interference, limits of error Interference voltage suppression for f = n x (f1 ± 1 %), (f1 = interference frequency) Common-mode interference (USS) Series-mode interference (peak interference value < rated value of input range) Crosstalk between the inputs Operational limit (in the entire temperature range, with reference to the input range) Basic error limit (operational limit at 25 C with reference to input range) Temperature error (with reference to the input range) Min. 90 db min. 70 db min. -50 db ± 0,6 % ± 0,4 % ±0.01 %/K Linearity error (with reference to the input range) ± 0,01 % Repeatability (in steady state at 25 C with ± 0,05 % reference to input range) Data for selecting a sensor Input range (rated value)/input resistance Voltage ± 5 V/min. 100 kω 1 V to 5 V/min.100 kω ± 10 V/min. 100 kω Permitted input voltage (destruction limit) 35 V continuous, 75 V at max. duration of 1 ms (sampling ratio 120) Smoothing of the measured values Yes, can be assigned parameters in 4 steps by means of digital filtering Step None Weak Medium Strong Time constant 1 x cycle time 4 x cycle time 32 x cycle time 64 x cycle time 10 Manual, 04/2007, A5E01076000-01

Parameters 2 2.1 Parameters Table 2-1 Parameters for analog input module 2 AI U ST Range of values Default setting Applicability Group diagnostics (parameter Disable assignment error, internal error) Enable Diagnostics Overflow/underflow Disable Enable Diagnostics Wire break* Disable Enable Smoothing None Weak Medium Strong Type/range of measurement Deactivated ±5 V ±10 V 1 to 5 V * Only in the measuring range of 1 to 5 V Disable Module Disable Module Disable Channel None Channel ±10 V Channel Manual, 04/2007, A5E01076000-01 11

Parameters 2.2 Parameter description 2.2 Parameter description Smoothing The individual measured values are smoothed by digital filtering. The smoothing can be adjusted in four steps, in which the smoothing factor k multiplied with cycle time of the electronic module equals the time constant of the smoothing filter. The greater the smoothing, the greater the time constant of the filter. The figure below shows the step response with the various smoothing factors in relation to the number of subassembly cycles. Figure 2-1 Smoothing with the 2AI U ST 12 Manual, 04/2007, A5E01076000-01

Diagnostics 3 3.1 Diagnostics using LED display LED display 1 1 Batch error (red) Status and error displays Event (LED) SF On Cause No configuration or incorrect module plugged in. No load voltage.present There is a diagnostic message. Remedy Check the parameter assignment. Check the load voltage. Evaluate the diagnostics. Manual, 04/2007, A5E01076000-01 13

Diagnostics 3.2 Error types 3.2 Error types Analog input module error types Table 3-1 Error types 16D Error type Meaning Remedy 10000 Parameter assignment error Module cannot use the parameter for the channel Inserted module does not match the one configured. Incorrect parameter assignment. 9D 01001 Error Internal module error (diagnostic message at channel 0 applies to the entire module) 7D 00111 Upper limit exceeded 8D 01000 Lower limit value undershot 6D 00110 Open circuit Value is above the overshoot range. Value is below the underrange. Line to the encoder interrupted. Correct the configuration (align actual and set configuration). Correct the parameter assignment (wire break diagnostics only parameterized for the permitted measuring ranges). Replace the module. Correct the module/final controlling element tuning. Correct the module/final controlling element tuning. Correct the process wiring. 14 Manual, 04/2007, A5E01076000-01

Analog value representation 4 4.1 Introduction Electronic modules with analog outputs With the electronic module with analog inputs, continuously variable signals, such as those occurring in temperature measurement and resistance measurement, can be acquired, evaluated, and converted to digital values for further processing. 4.2 Analog value representation for measuring range with SIMATIC S7 Analog value representation With the same nominal range, the digitized analog value is the same for input and output values. Analog values are represented in two's complement. The following table shows the analog value representation of the analog electronic modules. Table 4-1 Analog value representation (SIMATIC S7 format) Resolution Analog value Bit number 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Significance of the bits S 2 14 2 13 2 12 2 11 2 10 2 9 2 8 2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 0 Sign The sign (S) of the analog value is always in bit number 15 "0" + "1" Manual, 04/2007, A5E01076000-01 15

Analog value representation 4.3 Measuring ranges Output value The following table shows the representation of the binary analog values and the corresponding decimal and hexadecimal representation of the units of the analog values. The table below shows the resolutions 11, 12, 13, and 15 bit + sign. Each analog value is entered left aligned in the ACCU. The bits marked with "x" are set to "0". Table 4-2 Output values (SIMATIC S7 format) Resolution in bits Units Analog value Decimal Hexadecimal High byte Low byte 11+S 16 10H S 0 0 0 0 0 0 0 0 0 1 x x x x 12+S 8 8H S 0 0 0 0 0 0 0 0 0 0 1 x x x 13+S 4 4H S 0 0 0 0 0 0 0 0 0 0 0 1 x x 15 + sign 1 1H S 0 0 0 0 0 0 0 0 0 0 0 0 0 1 4.3 Measuring ranges Introduction The following tables contain the digitized analog values for the measuring ranges of the analog input modules. Since the binary representation of the analog values is always the same, these tables only compare the measuring ranges with the units. Voltage measuring ranges ±5 V, ±10 V Table 4-3 SIMATIC S7 format Measuring ranges ±5 V and ±10 V Measuring range ±5 V Measuring range Units ±10 V Decimal Hexadecimal Range > 5,8794 > 11,7589 32767 7FFFH Overflow 5,8794 11,7589 32511 7EFFH Overshoot range 5,0002 10,0004 27649 6C01H 5,00 3,75 10,00 7,50 27648 20736 6C00H 5100H Nominal range -3,75-5,00-7,50-10,00-20736 -27648 AF00H 9400H -5,0002-10,0004-27649 93FFH Underrange -5,8796-11,759-32512 8100H < -5,8796 < -11,759-32768 8000H Underflow 16 Manual, 04/2007, A5E01076000-01

Analog value representation 4.3 Measuring ranges Voltage measuring ranges 1 to 5 V Table 4-4 SIMATIC S7 format Measuring range 1 to 5 V Measuring range 1 to 5 V Decimal Units Hexadecimal > 5,704 32767 7FFFH Overflow 5,704 32511 7EFFH 5,000145 27649 6C01H 5,000 27648 6C00H 4,000 20736 5100H Nominal range 1,000 0 0H 0,999855-1 FFFFH Underrange 0,296-4864 ED00H < 0,296-32768 8000H Underflow Range Overshoot range Measured values in the event of a wire break in relation to enabled diagnostics The following additional information applies to the voltage measuring range 1 to 5 V Table 4-5 Measured values in the event of a wire break in relation to enabled diagnostics Format Parameter assignment 1 Measured values Description Decimal Hexadecimal S7 "Wire break" diagnostics enabled 32767 7FFFH "Open circuit" diagnostic message "Wire break" diagnostics disabled -32767 8000H Measured value after leaving the underrange "Overflow/underflow" diagnostics enabled "Wire break" diagnostics disabled "Overflow/underflow" diagnostics disabled 1 Measuring range limits for wire break and underflow detection At 0.296 V "Lower limit value undershot" diagnostic message -32767 8000H Measured value after leaving the underrange Manual, 04/2007, A5E01076000-01 17

Analog value representation 4.4 Effect on analog value representation 4.4 Effect on analog value representation 4.4.1 Effect of the supply voltage and the operating state on analog input values The input values of the analog modules are dependent on the supply voltage for electronics/encoders and on the operating state of the PLC (CPU of the DP master). This is illustrated by the table below. Table 4-6 Relationship between the analog input values for the operating state of the PLC (CPU of the DP master) and the supply voltage L+ Operating state of the PLC (CPU of the DP master) POWER ON RUN Supply voltage L+ on ET 200S (power module) L+ present Input value of the electronic module with analog inputs (evaluation possible on the CPU of the DP master) Process values 7FFFH until first conversion after startup, or after assignment of parameters for the module is completed. POWER ON STOP L+ missing 7FFFH L+ present Process value POWER OFF - L+ missing 7FFFH L+ present - L+ missing - 4.4.2 Effect of the value range on the 2AI U ST analog input The way electronic modules respond to analog inputs depends on where the input values fall within the value range. This is illustrated by the table below. Table 4-7 Response of the analog modules, depending on where the analog input value falls within the range of values Measured value within... Input value in SIMATIC S7 format Input value in SIMATIC S5 format Nominal range Measured value Measured value Over-/underrange Measured value Measured value Overflow 7FFFH End of the overshoot range +1 plus overflow bit Underflow 8000H End of the underrange -1 plus overflow bit Prior to parameter assignment, or with incorrect parameter assignment * 7FFFH 7FFFH * With product version 1 of the 2 AI U ST, the following applies If the parameter setting error diagnostic message is triggered because the parameters have been assigned incorrectly (e.g., wire break in measuring range ± 20 ma), the SF LED on the module lights up and the diagnostics can be evaluated. With this status, the correct input values are sent to the DP master. 18 Manual, 04/2007, A5E01076000-01

Connecting 5 5.1 Connecting measuring sensors Introduction You can connect encoders with voltage signals to the 2AI U ST analog input module. In this chapter you will find out how to connect the measuring encoders and what to watch out for when doing so. Cables for analog signals You should use shielded and twisted-pair cables for the analog signals. This reduces the effect of interference. You should ground the shield of the analog cables at both ends. If there are differences in potential between the cable ends, an equipotential bonding current that may interfere with the analog signals will flow across the shield. If this is the case, you should only ground the shield at one end of the cable. Analog input modules The analog input modules are electrically isolated Between the logic and backplane bus Between the load voltage and the channels. Electrical isolation No link between MANA and the central grounding point (UISO) Note Ensure that this difference in potential UISO does not exceed the permitted value. If there is a possibility of exceeding the permitted value, establish a connection between terminal MANA and the central grounding point. Connecting measuring encoders to analog inputs There can be only a limited potential difference UCM (common mode) between the measuring lines M- of the input channels and the reference point of the measuring circuit MANA. To ensure that the permitted value is not exceeded, you must take different steps depending on the whether the encoders are isolated or non-isolated. The steps you have to take are described in this chapter. Manual, 04/2007, A5E01076000-01 19

Connecting 5.1 Connecting measuring sensors Abbreviations used The meanings of the abbreviations in the figures below are as follows M+ Measuring line (positive) M- Measuring line (negative) MANA Analog measuring circuit reference potential M Ground connection L+ Rated load voltage 24 V DC UCM Potential difference between inputs and reference potential of the measuring circuit MANA UISO Potential difference between MANA and central grounding point Isolated measuring encoders The isolated measuring encoders are not connected to the local ground potential. These can be potential-free. Depending on local conditions or interference, potential differences UCM (static or dynamic) can occur between the measuring lines M- of the input channels and the reference point of the measuring circuit MANA. To ensure that the permitted value for UCM is not exceeded in environments with strong EMC interference, the following applies For the 2 AI U analog input module Connect M- to MANA! The following schematic representation illustrates the connection of isolated measuring encoders to the optically isolated analog input modules. 5 1 2 3 4 1 2 3 4 5 Logic Backplane bus Ground bus Central grounding point Isolated measuring encoders 20 Manual, 04/2007, A5E01076000-01

Connecting 5.1 Connecting measuring sensors Non-isolated measuring encoders The non-isolated measuring encoders are connected to the local ground potential. You must connect MANA to the ground potential. Depending on local conditions or interference, potential differences UCM (static or dynamic) can occur between the locally distributed measuring points. If the permitted value for UCM is exceeded, there must be equipotential bonding conductors between the measuring points. The following schematic representation illustrates the connection of non-isolated measuring encoders to an optically isolated analog input module. 5 1 2 4 3 1 2 3 4 5 Logic Backplane bus Ground bus Equipotential bonding conductor Non-isolated measuring encoders Manual, 04/2007, A5E01076000-01 21

Connecting 5.2 Wiring unused channels of the analog input modules 5.2 Wiring unused channels of the analog input modules Rules Pay attention to the following instructions when wiring unused channels "Deactivate" unused input channels when assigning parameters. A deactivated channel always returns the value 7FFFH. The module cycle time is halved with the 2 AI U ST module. To adhere to the permissible potential differences (UCM), you must wire jumpers on the terminal module for the unused channels. 2 AI U ST Analog input module TM connecting terminal Channel 0 Channel 1 1 2 3 4 5 6 7 8 5.3 Using the shield connection Rules To prevent interference we recommend the following for analog electronic modules Use shielded wires to the sensors and actuators. Lay out the wire shields on the shield connection. Connect the shield connection to the ground bus with low impedance. 22 Manual, 04/2007, A5E01076000-01

Index 2 2A U ST analog electronic module Technical specifications, 9 2AI U ST analog electronic module Block diagram, 8 Properties, 7 Terminal assignment, 7 A Analog input modules Error types, 14 Analog value processing, 19 B Basic knowledge requirements, 3 C Cables for analog signals, 19 Connecting, 19 Connecting measuring encoders to analog inputs, 19 D Disposal, 3 I Internet Service & Support, 4 Isolated measuring encoders, 20 M Measured value resolution, 16 Measuring encoders, 19 Measuring ranges with SIMATIC S7, 15 N Non-isolated measuring encoders, 21 P Parameters For analog electronic modules, 11 R Recycling, 3 Response of the analog modules, 18 During operation, 18 When faults occur, 18 S Scope Manual, 3 Service & Support, 4 Shield connection, 22 Smoothing, 12 T Technical Support, 4 Training center, 4 L LED display, 13 Manual, 04/2007, A5E01076000-01 23

Index 24 Manual, 04/2007, A5E01076000-01