ECM. Service Guide. www.thedealertoolbox.com



Similar documents
ECM SERVICE GUIDE. A Regal Brand Regal-Beloit Corporation

ECM Blower Motor Replacement Controls Programming Process

Digi-Motor Installation Guide

Fan Coil EC Motor Control

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY

, User s Manual

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS


Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

E2 Series Electric Furnaces

MODEL 2202IQ (1991-MSRP $549.00)

Fossil fuel heating equipment

12-Volt Negative Ground Installation Instructions

G670 Intermittent Pilot Ignition Controls

Operating Precautions: User configuration options:

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

FUEL-16, Troubleshooting Fuel Supply Problems

A4 Air Conditioning Control Circuit Troubleshooting Rev 7, 6/18/2009

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Manual Ranging MultiMeter

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

INSTALLATION & SERVICE MANUAL. Display Panel

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

TROUBLESHOOTING GUIDE

STEALTH I DC MANUAL TECH SUPPORT WEB BLACK UNIT IS 24/36 ONLY

Portable Air Conditioner

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

Installation Instructions

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty Safety notes Policy Warranty.

Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU

Quickie Rhapsody Service Manual

Troubleshooting Guide for Dispenser Model #900172

PRODUCT: WASHER / WASHER-DRYER COMBO MODEL: AW 120 / AW 122 / AW 125 AWD 120 / AWD 121 / AWD 129

HEAT PUMP PROGRAMMABLE THERMOSTAT

ATS Overhead Table Shelf System INSTRUCTION MANUAL

SL280UHV SERIES GAS FURNACE WARNING

FOXAIR 60/50 ALL MODELS

MCR1900 Media Converter 19-Slot Chassis

INSTALLER S & OWNER S MANUAL

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

2. Remove rear cover of head lamp if bulbs are covered/sealed within the housings, and remove halogen bulb carefully.

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Inch PowerVent LED Indicator Explanations & Troubleshooting Table

Evaluate, Clean, and Tune Guidance

ILISC515-A Shift Interlock (Manual Lift Door) 2015 Ford Transit, 3.7L and 3.5L

GLOLAB Universal Telephone Hold

MIGRATION HEIGHT-ADJUSTABLE DESKS. Troubleshooting Guide

Troubleshooting and Diagnostics

AIR CONDITIONER & HEAT PUMP DIGITAL CONTROL FOR DUCTED SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

CARING FOR YOUR WATER HEATER

OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12)

Ultraviolet Germicidal Lamps Owner s Manual MODELS 1910 & 1930

Your safety and the safety of others are very important.

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Inspiron 15. Service Manual Series

Power Supplies. Overview. Measuring Electricity. Understanding Electricity. Two Types of Current. Powering the PC

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

LUCCI AIRFUSION QUEST II CEILING FAN

Dehumidifier Users manual. For Models: DH45S DH65S

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

T7560A,B,C Digital Wall Module

SX460. Generator Automatic Voltage Regulator Operation Manual

Rain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English RAIN BIRD ( ) or visit

BATTERY BOX INSTALLATION WARNING WARNING CAUTION ATTENTION AVERTISSEMENT ADVERTENCIA PRECAUCIÓN SOLBBOX12V CARTON INVENTORY COMPLETED OVERVIEW

Owners & Installation Manual for the Sheridan, Mountainair, Pine Valley and Old Forge Ceiling Fan Family

AutoRanging Digital MultiMeter

Retrofit Instructions Installing a Sport Heated Steering Wheel - Leather, Multifunction BMW X5, E53,

INSTALLATION INSTRUCTIONS

Analog Control Wiring & Adjustment Manual for Gyro Tech Swing Door Operators

Oil and Coolant Circulating Heating System. Model - OCSM

Triac Printed Circuit Board Replacement

This slide is hidden. It will not show up during presentation.

DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

430 Power/Electronics Replacement


Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Companion Service Guide

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Tankless Electric (RTE) Troubleshooting

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

Installation Instructions

Portable Evaporative Air Cooler. OWNER S MANUAL Read and save these instructions before use. Model: CL30XC

Thermo Top - Troubleshooting Tree

Air Conditioning Sign-Off Sheet

IMPORTANT SAFETY RULES TO FOLLOW

Advantium 2 Plus Alarm

Installation and maintenance instructions. Danfoss Vent

Transcription:

ECM Service Guide www.thedealertoolbox.com

ECM Table of Contents Service Guide Working on the motor with power connected may result in electrical shock or other conditions that may cause personal injury, death or property damage. On models 2.0/ 2.3/ 2.5 always disconnect the power from the HVAC system and wait at least 5 minutes before opening the motor, i.e. removing the two bolts from the motor control (end bell) and disconnecting the 3-pin plug to the motor. This is to allow the capacitors to dissipate for safety. Always disconnect the power from the HVAC system before removing or replacing connectors, servicing the motor, removing the high voltage plug, and before reconnecting. Disconnect AC power from the system and make sure the blower wheel has come to a complete stop. Do not operate motor without blower wheel attached. Such operation will cause the motor to oscillate up and down. You must have the correct replacement module from the manufacturer that is a direct replacement for the failed module. USING THE WRONG MODULE VOIDS ALL PRODUCT WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS. Using the ECM Service Guide Start Here: Using the ECM Service Guide HVAC System Troubleshooting Basics Tech Tips 4 Motor Identification Chart 6 Motor Diagnostics & Replacement MODELS 2.0 / 2.3 / 2.5 Premium ECM Motor Diagnostics MODEL X13 Standard ECM Motor Diagnostics TECMATE TECMate Usage Chart Troubleshooting with the TECMate MODULE REPLACEMENT ECM Control Module ECM Motor Module 1 2 9 13 19 20 23 28 X13 MOTOR REPLACEMENT 29 Final Installation Checks 30

Using the ECM Service Guide Read this section before using Motor Diagnostics & Replacement Start Here: Using the ECM Service Guide The purpose of this guide is to help you accurately and efficiently troubleshoot GE ECM-driven systems. For ease of troubleshooting and to avoid misdiagnosis, it is strongly recommended that each step of this guide be used in the following order: 1. 2. 3. 4. page 8 Begin with the HVAC System Troubleshooting Basics section on the opposite page. If the answer to the problem is not solved there, read all of the Tech Tips on pages 4-5. After reading all of the Tech Tips, go to the Motor ID section of this guide on page 6 to be sure you use the procedures for the correct motor. After determining which motor you are working on from the Motor ID chart on page 6, go to the section in this guide for the motor model you are working on and follow the instructions listed there. HVAC System Troubleshooting Basics Before troubleshooting the ECM motor, check these system basics: 1. 2. 3. Confirm that the correct thermostat input and ONLY the correct input voltage is present at the interface or main control board on the furnace/ air handler. Loose or broken lowvoltage wires are also potential problem areas and can cause intermittent problems. For the heating and/or cooling systems, use the manufacturers guide to confirm proper demands (heat or cool), especially on multistage systems. Use the Sequence of Operation charts and the Thermostat Wiring Diagrams, found in these guides to confirm proper wiring and operation. When checking low-voltage connections, always use the C terminal on the board, never ground. Check the setting of the jumper pins or DIP switches on the manufacturer s control board. Do not assume they are correct; use the manufacturer s guide to select the proper airflow, delays, and profiles. Always disconnect the main power to the unit when making these adjustments. START HERE 1 2

Tech Tips 4. Check all terminal/plug connections both at the furnace/air-handler control board and at the motor. Always disconnect power to the system before disconnecting and reconnecting plugs. Look for: Loose plugs and/ or loose pin connections in the plug. Burnt, bent or loose pins or seats. Tech Tip #1 Do not automatically assume the ECM motor has failed. Follow this guide completely before replacing it. Working on the motor with power connected may result in electrical shock or other conditions that may cause personal injury, death or property damage. TECH TIPS 5. 6. Confirm there are no limits, rollouts or safeties tripped. Also check for any fault codes present on the furnace/air-handler control boards. If fault codes are present, follow the manufacturer s recommendations to resolve the problem. If these checks do not solve the problem, or if a fault code reveals a motor problem, read the Tech Tips on pages 4-5, and go to the Motor ID section on page 6 to identify the motor. Then go to the corresponding motor section in this guide for additional diagnostics. Always disconnect the power from the HVAC system before removing or replacing connectors or servicing the motor Tech Tip #2 On models 2.0/ 2.3/ 2.5 always disconnect the power from the HVAC system and wait at least 5 minutes before opening the motor, i.e. removing the two bolts from the motor control (end bell) and disconnecting the 3-pin plug to the motor. This is to allow the capacitors to dissipate for safety. When it is necessary to disconnect the power from the HVAC system, it is always good practice to verify that voltage has been disconnected with a voltmeter. Tech Tip #3 A True- RMS meter is not needed to check high voltage or low voltage (communication voltage) to the motor. 3 4

Tech Tip #4 If you must replace the 2.0, 2.3, or 2.5 control module, then be sure to use a direct replacement from the manufacturer. ECM control modules are factory programmed for specific manufacturer applications. Use of the wrong control module voids all product warranties and may result in improper or no blower operation. Tech Tip #5 ECM X13 ECM 2.3 / 2.5 Motor Identification Chart g Identification Sticker g Heat sink g Speed taps 2.3 10 wires MOTOR ID If a check of the 2.0, 2.3, or 2.5 control module indicates replacement is required, then also check the motor module. Installing a new control on a failed motor will result in the new control also failing. Tech Tip #6 g Identification Sticker NOTE: Early models do not have identification stickers. g Painted, steel motor control 2.5 5 wires g 2.3-10 or more wires in the 16-pin connector g 2.5-5 or less wires in the 16-pin connector Always pull on the connector and not the wires. Most connectors are also keyed. Reconnecting a connector the wrong way could damage the motor. Tech Tip #7 When checking any plug connector, the meter leads are most likely larger than the terminals or socket. Using thin leads will prevent the terminals from being damaged by voltage checks. Thinner leads are also available in a 90º angle as needed. Go to thedealertoolbox.com for part numbers and ordering information if needed. ECM 2.0 ECM 1.0 g Unpainted, cast aluminum motor control g Square motor control NOTE: ECM 1.0 & 2.0 motors are no longer in production. NOTE: See manufacturer s service guide for 1.0 motor diagnostics. 5 6

motor diagnostics & replacement Working on the motor with power connected may result in electrical shock or other conditions that may cause personal injury, death or property damage. On models 2.0/ 2.3/ 2.5 always disconnect the power from the HVAC system and wait at least 5 minutes before opening the motor, i.e. removing the two bolts from the motor control (end bell) and disconnecting the 3-pin plug to the motor. This is to allow the capacitors to dissipate for safety. Always disconnect the power from the HVAC system before removing or replacing connectors, servicing the motor, removing the high voltage plug, and before reconnecting. Disconnect AC power from the system and make sure the blower wheel has come to a complete stop. Do not operate motor without blower wheel attached. Such operation will cause the motor to oscillate up and down. Read Using the ECM Service Guide before using this section. Motor Diagnostics & Replacement Table of Contents MODELS 2.0 / 2.3 / 2.5 Premium ECM Motor Diagnostics MODEL X13 Standard ECM Motor Diagnostics TECMATE TECMate Usage Chart Troubleshooting with the TECMate MODULE REPLACEMENT ECM Control Module ECM Motor Module 9 13 19 20 23 28 X13 MOTOR REPLACEMENT 29 Final Installation Checks 30 You must have the correct replacement module from the manufacturer that is a direct replacement for the failed module. USING THE WRONG MODULE VOIDS ALL PRODUCT WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS. 7 8

Models 2.0 / 2.3 / 2.5 Premium ECM Motor Diagnostics IF THE MOTOR IS RUNNING 1. 2. It is normal for the motor to rock back and forth on start up. Do not replace the motor if this is the only symptom identified. If the system is excessively noisy, does not appear to change speeds in response to a demand (Heat or Cool), or is having symptoms during the cycle such as a tripping limit or freezing coil, check the following: Wait for programmed delays to time out. If delays are too long, then reset them using the manufacturer s charts. Ensure the airflow settings are correct for the installed system using the manufacturer s charts. Remember that the change in airflow between continuous-fan speed and low stages of operation may be very slight depending on the size of the system. If the system is operating normally in each stage, then there is no problem. Remove the filter and check that all of the dampers, registers, and grills are open and free flowing. If removing the filter corrects the problem, clean or replace with a less restrictive filter. Also check and clean as needed the blower wheel, secondary heat exchanger (if applicable) and evaporator coil (if applicable). If this does not correct the problem then: 3. 4. Check the external static pressure. If it is higher than the manufacturer s recommendations, correct the airflow restriction. If the motor does not shut off at the end of the cycle, check the delay times and wait for the delays to time out. Also, make sure that there is no call for Continuous fan on the G terminal. This motor may take a while to come to a complete stop with selected delays and the normal ramp down. If the 2.0 / 2.3 motor has proper high voltage and ground at the 5-pin connector, go to the Troubleshooting with the TECMate section on page 20. If the 2.5 motor has proper high voltage and ground at the 5-pin connector, the equipment manufacturer s checks, located in their service manuals, must be referenced. This guide cannot troubleshoot the communication to the 2.5 motor. The TECMate is not designed for use on the 2.5 motor. Checking the high voltage on the 5-pin connector is outlined in step 1 on page 11. 2.0 / 2.3 2.5 MOTORS 9 10

11 IF THE MOTOR IS NOT RUNNING 1. 2. 3. Check for proper high voltage and ground at the 5-pin connector at the motor. Correct any voltage issues before proceeding to the next step. These are dual voltage motors capable of operating in 120 or 240VAC systems. On 120VAC systems there should be a jumper between terminals 1 and 2 (see Figure 1). On 240VAC systems the jumper should be removed (see Figure 2). If a motor is operating at 240VAC with the jumper in place, the motor will be permanently damaged. Input voltage within plus or minus 10% of the nominal 120VAC or 240VAC is acceptable. If the 2.0 / 2.3 motor has proper high voltage and ground at the 5-pin connector, go to the Troubleshooting with the TECMate section on page 20. If the 2.5 motor has proper high voltage and ground at the 5-pin connector, the equipment manufacturer s checks, located in their service manuals, must be referenced. This guide cannot troubleshoot the communication to the 2.5 motor. The TECMate is not designed for use on the 2.5 motor. If further troubleshooting identifies a failed control module, go to Replacing the ECM Control Module section on page 23 of this guide for replacement steps. Figure 1 1 2 3 4 1 2 3 4 5 Models 2.0 / 2.3 / 2.5 ground 120vaC 5 line 1 ground 120vaC line 1 neutral Always disconnect power from the system before removing the high voltage plug and before reconnecting. Figure 2 120VAC SYSTEM Models 2.0 / 2.3 / 2.5 240VAC SYSTEM 120vaC line 2 12

Model X13 Standard ECM Motor Diagnostics IF THE MOTOR IS RUNNING 1. 2. It is normal for the motor to rock back and forth on start up. Do not replace the motor if this is the only problem identified. If the system is excessively noisy, does not appear to change speeds in response to a demand (Heat or Cool), or is having symptoms during the cycle such as a tripping limit or freezing coil, check the following: Wait for programmed delays to time out. If delays are too long, reset them using the manufacturer s charts. Ensure the airflow settings are correct for the installed system using the manufacturer s charts. If the system is operating normally in each mode, there is no problem. Remove the filter and check that all of the dampers, registers, and grills are open and free flowing. If removing the filter corrects the problem, clean or replace with a less restrictive filter. Also check and clean as needed the blower wheel, secondary heat exchanger (if applicable) and evaporator coil (if applicable). If this does not correct the problem then: 3. 4. Check the external static pressure. If it is higher than the manufacturer s recommendations, correct the airflow restriction. If the motor does not shut off at the end of the cycle, check the delay times and wait for the delays to time out. Also make sure that there is no call for Continuous fan on the G terminal. This motor may take a while to come to a complete stop with selected delays. If the above diagnostics do not solve the problem, confirm the voltage checks in the next section below, then continue diagnostics in the section, Model X13 Standard ECM Motor Communication Diagnostics. The TECMate is not designed for use on this motor. Always disconnect power from the system before removing the high voltage connection(s) and before reconnecting. IF THE MOTOR IS NOT RUNNING 1. Check for proper high voltage and ground at the (L)(G)(N) connections at the motor (see Figure 3 on the next page). Correct any voltage issues before proceeding to the next step. The X13 motor is voltage specific. Only the correct voltage should be applied to the proper motor. Input X13 MOTOR 13 14

2. Figure 3 15 voltage within plus or minus 10% of the nominal 115VAC or 230VAC is acceptable. The TECMate is not designed for use on this motor. If the motor has proper high voltage and ground at the (L)(G)(N) connections, continue diagnostics in the next section, Model X13 Standard ECM Motor Communication Diagnostics. 115vaC line 1 115vaC line 1 ground neutral C l g n 1 2 3 4 5 115vaC MoToR ground 115vaC line 2 C l g n 1 2 3 4 5 230vaC MoToR Model X13 Standard ECM Motor Communication Diagnostics The X13 motor can be communicated through AC or DC low voltage. AC voltage is typically 24VAC and DC voltage can be between 9-23VDC (see Figures 4 and 5 on the next page). 1. 2. Start with the manufacturer s literature to confirm proper set-up, connections and voltage. It is not required that all terminals on the motor have a program. If the lowvoltage communication is applied to an unprogrammed terminal, the motor will not operate, which is normal. Initiate a demand from the thermostat and check the voltage between the common and the appropriate motor terminal 1-5. Confirm the meter is set to the voltage identified from the manufacturer s literature (see Figures 4 and 5 on the next page). If the low voltage communication is not present, check the demand from the thermostat. Also check the output terminal and wire(s) from the manufacturer s control board or relays to the motor. If the motor has proper high voltage as identified in the previous section, and proper low voltage to a programmed terminal, and is not operating, the motor is failed. Go to Replacing the X13 Motor section on page 29 of this guide. 16

Figure 4 24vaC ac volts C l g n v CoM ac voltage ConTRol inputs 1 2 3 4 5 Figure 5 9-23 vdc dc volts C l g n v CoM dc voltage ConTRol inputs 1 2 3 4 5 17 18

TeCMate Xl 4 button TeCMate Pro 1 button 19 TECMate USAGE CHART ge ecm Troubleshooter * 4 button w/three position TeCMate Xl 4 button TeCMate Pro 1 button ** (G) switch indoor blower motors All manufacturers 1.0 / 2.5 / X13 n/a n/a n/a All manufacturers 2.0 / 2.3 y y*** y ge ecm Troubleshooter This tool will accurately diagnose this motor This tool is not applicable to this motor 4 button w/three position (G) switch N/A TeCMate Xl 4 button Y * The TECMate XL is no longer available. It has been replaced with the TECMate Pro. ** The GE ECM Troubleshooter contains its own instructions for use and is available *** The TECMate XL may not accurately troubleshoot Carrier/Bryant 2.0 / 2.3 motors. only from Carrier/Bryant distributors. part number (P/N HK50EA001) Note: These tools are not for ge use ecm on GE ECM condensing fan or draft inducer motors. Troubleshooter 4 button w/three position (G) switch Troubleshooting with the TECMate (Models 2.0 / 2.3 only) See Motor ID Chart on page 6, if needed. See the Usage Chart on the opposite page for motors applicable to the TECMate. The TECMate is capable of identifying a motor control failure versus another HVAC system controller or wiring failures. 1. 2. Disconnect AC power from the system and make sure the blower wheel has come to a complete stop. Do not operate motor without blower wheel attached. Such operation will cause the motor to oscillate up and down. Remove the 16-pin connector from the motor, and connect the 16-pin connector from the TECMate. Remove the 5-pin AC power connector first to make accessing the 16-pin locking tab easier. Reconnect the 5-pin AC power connector. Connect the two alligator clips from the TECMate to a constant 24VAC (24VAC terminal and Common terminal) source such as the transformer low- voltage terminals or terminal strip on the manufacturer s control board 20 TECMATE

Figure 6 (see Figure 6 below). These connections are not polarity sensitive. ecm MoToR TeCMate PRo 24vaC NOTE: The high voltage 5-Pin connector must be connected to the motor for TECMate tests. 6. If using a TECMate XL or the GE ECM Troubleshooter, make sure to set the switches according to the instructions on the back for each demand test to eliminate misdiagnosing the problem. When testing is finished, place the TECMate switch(es) in the OFF position and wait for the motor to completely stop. (Based on the manufacturer s program, the motor may not shut off immediately after a test; this is normal). If the motor operates with the TECMate, the motor is ok. Confirm the proper demand call from the thermostat is present at the manufacturer s control board. Check the 16-pin harness for broken wires or bad pin connectors. Troubleshoot the communication with the manufacturer s troubleshooting guide. 3. 4. 5. Place the TECMate switch(es) in the OFF position. Reconnect the AC power to the system. The green LED light on the TECMate should be on when connected properly to 24VAC. Refer to the table on the back of the TECMate for operation guidelines. Observe the motor for a minimum of 15 seconds. If the motor does not operate with the TECMate, confirm high voltage (pages 11-12) is present before replacing the control module. Follow the next section on Replacing the ECM Control Module on page 23. 21 22

Replacing the ECM Control Module (Models 2.0 / 2.3 / 2.5 Only) Figure 7 MoToR ConneCToR (3-Pin) Push until latch seats over ramp Before replacing the electronic-control module, you must test the motor module to ensure it is not also damaged. Installing a new control on a failed motor will result in the new control failing as well. Procedures for testing the motor module are included below. HeX Head screws CiRCUiT board from MoToR 16-Pin & 5- Pin ConneCToRs Only remove Hex Head Bolts You must have the correct replacement module from the manufacturer that is a direct replacement for the failed module. USING THE WRONG MODULE VOIDS ALL PRODUCT WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS. Disconnect AC power from HVAC system and wait 5 minutes before opening the motor to avoid electrical shock from motor s capacitors 1. 2. 3. 4. After the system AC power has been off for 5 minutes, unplug the 16-pin connector and the 5-pin connector from the motor control. Remove the blower assembly from the HVAC system. Remove the two (2) hex-head screws from the back of the control. Unplug the 3-pin connector from the inside the control by squeezing the latch and gently pulling on the connector (see Figure 7 on the next page). Now you re ready to test the motor. Motor Module Tests A. The Winding Test (see Figure 8) Set ohm meter to the highest possible setting and measure resistance between each of the three motor leads to the unpainted part of the end shield. The motor passes the test if the meter indicates greater than 100k ohms. winding test Figure 8 MoToR ConneCToR (3-Pin) motor ok WHen r > 100k ohm MODULE REPLACEMENT 23 24

MoToR ConneCToR (3-Pin) B. The Phase-to-Phase Test (see Figure 9 below) Set ohm meter to lowest possible setting and measure the motor phase to phase resistance by checking these combinations of the 3-pin motor connector with an ohm meter: Lead 1 to lead 2 Lead 1 to lead 3 Lead 2 to lead 3 For the purpose of this test, either end of the 3-pin plug is lead 1. Resistance values should be less than 20 ohms and each of the three values should be the same (plus or minus 10%). If the measured resistance is outside of these parameters, the motor fails the test. PHase-To-PHase test Figure 9 25 motor ok WHen r < 20 ohm (lead to lead) 5. 6. C. If the motor passes both of these tests, then the motor is ok and only the control must be replaced. Continue with replacing the ECM control module in step 5. D. If the motor fails either of these tests, replace the motor module following the guidelines on page 28. When finished installing the motor module, continue with the replacement of the ECM control module, in step 5 below. Insert the 3-pin connector back into the new control module. A slight click will be heard when inserted properly. This connector is keyed for proper connection. Attach the new control module with connectors facing down: If replacing an ECM 2.0 control with an ECM 2.3 control, insert plastic tab into perimeter of replacement control and align tab with mating hole in the endshield. Use the new shorter bolts provided to ensure a secure attachment. Orient the control connectors to the endshield between 4 and 8 o clock (as seen similarly in Figure 10 on the next page), insert bolts and tighten. If replacing an ECM 2.3 with an ECM 2.3 control, orient the new control to the motor s endshield with connectors facing down, insert bolts and tighten. 26

8. 9. 10. ECM 2.5 control must be replaced with an ECM 2.5 control. Orient the new control to the motor s endshield with connectors facing down, insert bolts and tighten. Reinstall the blower/ motor assembly into the HVAC system by following the manufacturer s guidelines. Plug the 16-pin connector and the 5-pin connector back into the motor. The connectors are keyed. Observe proper orientation. Be certain to form a drip loop so that water cannot enter the motor by draining down the cables (see Figure 10 below). 11. Go to the Final Installation Checks on page 30. drip loop Figure 10 Replacing the ECM Motor Module (Models 2.0 / 2.3 / 2.5) Make sure the belly band is not covering any shell holes. The motor module does not have a specified orientation, however, the motor control does. Make sure the three-wire plug will reach the motor control when it is oriented properly before tightening down the belly band. Proper orientation is for the connectors to be facing down or at least between 4 and 8 o clock (as seen similarly in Figure 10 on the opposite page). After installing the new motor module, install the motor control starting at step 5 on page 26. drip loop connector Orientation Between 4 and 8 o clock 27 28

Replacing the X13 Motor The X13 is a one piece motor. Do not open motor to service. Motor must be a direct replacement from the manufacturer with respect to voltage and model unit. When replacing the X13 motor with a belly band for mounting, the band should not be located in the area identified in Figure 11. Final Installation Checks Check all wiring and connections, especially those removed while servicing. Ensure the system is set up as follows: Verify the condensate drain is not plugged or clogged. Reconnect the AC power to the HVAC system and verify that the motor is working properly. Reconnect high and low voltage wiring according to the manufacturer s guidelines. Proper orientation is for the connectors to be facing down or at least between 4 and 8 o clock (as seen similarly in Figure 10 on the previous page). DO not cover Vents 29 ECM X13 Figure 11 recommended BellYBAnD AreA 2.75 BellYBAnD KeeP out area Check and plug leaks in return ducts and equipment cabinet. Verify that the system is running quietly and smoothly, in all modes (heating, cooling, and continuous fan) and all stages (if applicable). Return all thermostat settings to the customer s preference. Note: If this is a repeat failure then it is important that you check the following: Any evidence of moisture correcting the issue. If the area is subject to high amounts of lightning strikes, then use of additional transient protection may be helpful. See good practices on next page: 30 FINAL CHECKS

Good Practices: Finish all service calls by checking all safeties, and perform a visual inspection of the overall job to prevent call-backs. Check the level of Carbon Monoxide (CO) in the vent(s) and living spaces of all homes with fossil-fuel appliances. Recommend annual maintenance. Visit www.thedealertoolbox.com to learn more. 2006 Regal-Beloit Corporation GE is a trademark of General Electric Company and is used under license to Regal-Beloit Corporation GEECM-1002 (5M 08/06) Version 1.0 TECMate PRO is a registered trademark of Regal-Beloit Corporation www.thedealertoolbox.com