MUNICIPAL WASTEWATER PUMP STATION DESIGN PROBLEMS AND SOLUTIONS



Similar documents
Wastewater Collection System Supplemental Design Standards for Capital Improvement Program Projects

HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS

Terry Biederman, PE- Director of Public Works Greg Gucwa, PE- Principal Johnson and Anderson Engineering

Sewer Rehabilitation Design Requirements

Before H 2 Town of South Windsor, CT Evaluates Large Diameter Concrete Pipe

DIVISION OF WATER QUALITY CONSTRUCTION GRANTS & LOANS SECTION FAST TRACK AUDIT CHECKLIST

Module 9: Basics of Pumps and Hydraulics Instructor Guide

Flygt Ball Check Valves

Design of Sewage Pumping Stations by John Zoeller, PE, CEO/President

Appendix S Pump Station Evaluation

Practice Problems on Pumps. Answer(s): Q 2 = 1850 gpm H 2 = 41.7 ft W = 24.1 hp. C. Wassgren, Purdue University Page 1 of 16 Last Updated: 2010 Oct 29

Specifications for Residential Property Owners Connection to New Public Sewer

Emerging Technologies in Wastewater Collection Systems

SECTION GROUND WATER STORAGE TANKS

Chapter 4 - Preferred Alternative...25

Waste Collection Systems

CCU Engineering Specifications. Section PRECAST CONCRETE PRODUCTS

SECTION XXXXXX TECHNICAL SPECIFICATIONS FOR INSTALLATION OF PROTECTIVE COATINGS FOR MANHOLES, WETWELLS, AND OTHER SANITARY SEWER STRUCTURES

Module 7: Hydraulic Design of Sewers and Storm Water Drains. Lecture 7 : Hydraulic Design of Sewers and Storm Water Drains

SEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

Outline. Objective. Overview Sanitary Drainage System. Design. Materials

SECTION STORM DRAINAGE TABLE OF CONTENTS

Module 3: Sewer Material Lecture 3: Sewer Material

Rehabilitation or Replacement? That Is The Question

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

Wastewater Collection Practice Test #3 Page 1 of 15

Town House Center Highway North Huntingdon, PA 15642

BSM MOTOR DRIVEN CENTRIFUGAL PUMPS

Rehabilitation Alternatives. MWEA Collection System Seminar October 1, 2009

CONFIRMING WET WEATHER TREATMENT FACILITY HYDRAULIC DESIGN WITH PHYSICAL MODEL STUDY

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

MODEL INSTALLATION INSTRUCTIONS

Module 3 : Sewer Material. Lecture 3 : Sewer Material

Theory, Application, and Sizing of Air Valves

SECTION POINT REPAIRS TO SANITARY SEWERS. A. Repairs to existing sewer lines by replacing short lengths of failed pipe.

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

SANITARY SEWER BACKUP. Causes & Prevention

SPECIFICATIONS FOR SEWER PIPE AND LINING INSERTION - TRENCHLESS; GENERAL GUIDELINES (As Provided by NASSCO)

Repairs Made With Under Pressure Installations Can Offer Reduced Risks And Expenses

SANITARY SEWER SPECIFICATIONS

SANITARY SEWER SYSTEM ASSESSMENT

Wastewater Capital Projects Management Standard Construction Specification

PART 6 - STANDARD DESIGN AND CALCULATION FORMS 6.1 SANITARY SEWER DATA SHEET

PACKAGE TERTIARY FILTER SYSTEM SPECIFICATIONS MODELS TF-2-6-C THROUGH TF-2-35-C

Jay R. Smith Mfg. Co.

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

FY08 SEWER POINT REPAIRS BID TABULATION

CITY OF DAYTON DEPARTMENT OF WATER 42-INCH SANITARY SEWER REHABILITATION

Fire Pump Plan Review March 2010

The checklist utilized by the Authority will be similar to that which is shown below. Project Name: Location: Consulting Engineering Firm:

Storm Sewer Trenchless Upgrade Alternatives and Recommendations

Coast Trunk Sewer Rehabilitation Project for the Orange County Sanitation District

SRA-125/SRAX-125 Double-Rail Lift-Out Rail System Installation & Service Manual with Parts List

SEPTIC SYSTEMS. 1. Building sewer connects the building plumbing to the septic tank.

What Does A Sump Pump Do?

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Force Main Condition Assessment: New Technologies & Case Studies

Septic System Design Manual

Vertical selfpriming Side-Channel Pumps Type WPV

SECTION STORM DRAINAGE SYSTEM

Appendix A: Acceptable pipe and fitting materials

SECTION 812 SEWER LINE, MANHOLE AND WET WELL CLEANING

Pure Performance. Steady 1300 Series

Texas Commission on Environmental Quality Page 1 Chapter Design Criteria for Domestic Wastewater Systems

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6

Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries

Stainless Steel Perimeter Recirculation Systems Engineered supply and return systems for swimming pools, water features and aquatic facilities.

pvc well casing & drop pipe

812-3 LIMITATIONS: b. No fire hydrant shall be obstructed or used when there is a fire in the area.

Rehabilitation of an Aging Concrete Reservoir Adit Tower

FY11 Sanitary Sewer Main Rehab and Point Repair Bid Tabulation

OAR52 A-1 (September, 1981)

Installation of Large Diameter Buried Pipes

Standards for Water, Sewer, and Sewage Lift Station Design

Most agencies think about cleaning because of debris in the line.

ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING

SECTION 3 SANITARY SEWER DESIGN

STANDARD SPECIFICATIONS SECTION CLEANING AND LINING WATER MAINS

53.03 MATERIALS FOR SEWER LINER PIPE AND FITTINGS: The following materials are approved for installation in sanitary sewer lines:

Pumps SELECTION OF A PUMP

STRUCTURES Excavation and backfill for structures should conform to the topic EXCAVATION AND BACKFILL.

Section 2100-Trenching and Tunneling

FAIRBANKS NIJHUIS FIRE PUMPS.

UNDERGROUND INFRASTRUCTURE SPECIALISTS TABLE OF CONTENTS

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.

LOWER NORTH OUTFALL SEWER AND NORTH OUTFALL SEWER REHABILITATION USING AMERON S T HAB METHOD

DIVISION 4300 STORM DRAINAGE

HYDROVEX. CSO, SSO and Stormwater Management Specialist Products and Services for North America

2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

N-PUMP SERIES FOR MAXIMUM RELIABILITY AND EFFICIENCY IN WASTEWATER HANDLING. Flygt

A Guide to Trouble-Free Cooling Towers

Installation Manual. Solar Pool Heating System. Read the complete manual before beginning the installation

STANDARD SPECIFICATIONS SECTION CLOSED CIRCUIT TELEVISION INSPECTION OF SEWER MAINS, MANHOLES AND LATERALS

Collection Systems Technology Fact Sheet Sewers, Conventional Gravity

ARTICLE II (2) ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH Purpose and Application.

DEPARTMENT OF ENVIRONMENTAL QUALITY

Transcription:

MUNICIPAL WASTEWATER PUMP STATION DESIGN PROBLEMS AND SOLUTIONS Presented at: WEFTEC 2006 Dallas, TX October 24, 2006 New England Water Environment Association Meeting Westford, MA September 12, 2006 Virginia Water Environment Association Annual Meeting Roanoke, VA May 2, 2006

MUNICIPAL WASTEWATER PUMP STATION DESIGN PROBLEMS AND SOLUTIONS INTRODUCTION In the Northern Virginia suburbs of Washington DC rapid residential growth has resulted in the need for construction of numerous municipal wastewater pumping stations. Municipal pump stations in Northern Virginia typically are submersible type pump stations with a design capacity between from 100 gpm to 1 MGD. The design requirements for submersible type pump stations continue to evolve to address construction and operation problems. This paper identifies several of these problems and the solutions that have been implemented in the design of several recently constructed wastewater pump stations in Northern Virginia. The author has prepared this paper based on his 32 years of experience in wastewater pump station design in the Northern Virginia Area. Contact: Jeff Chapin, P.E. 8401 Arlington Boulevard Fairfax, VA 22031 Phone: (703) 849-0555 Fax: (703) 849-0623 METHODOLOGY Each of the identified pump station design problems is listed below by number with the corresponding design solution indicated under the problem. PROBLEMS AND SOLUTIONS 1. Concrete Corrosion Protection Problem: Until recently, most pump stations in Northern Virginia were constructed of concrete. Typically the wet well interior and exterior concrete surfaces received two coats of a coal tar epoxy coating to protect the concrete from the corrosion due to hydrogen sulfide in the influent sewage. Experience has indicated that concrete corrosion will result if either the coal tar epoxy is not properly applied, or is not reapplied when it deteriorates over time. It is very difficult to reapply coal tar epoxy, because usually the pump station wet well can not be taken out of service. Solution: New pump stations include a high density polyethylene (HDPE) liner on the interior of the concrete surfaces exposed to wastewater for corrosion protection. This liner is provided as an option by the precast concrete suppliers and the concrete is formed around the outside of the liner. Following installation of the lined precast concrete structure a certified welder field welds the seams and welds around pipe penetrations to assure that the HDPE liner prevents sewer gas from attacking the concrete. Another alternative is to utilize precast polymer concrete structures. Polymer concrete utilizes epoxy to bind the aggregate instead of cement. Thus the polymer concrete is not susceptible to corrosion due to sewer gas.

2. Corrosion Resistant Materials: Problem: Previous pump station designs included the use of galvanized steel and coated metal components in areas susceptible to hydrogen sulfide in influent sewage. After several years the metal components corroded and had to be replaced. These items included piping, pump guide rails, supports, grating, hand rails, stairs, bar screens, bolts, weirs, ladders, slide gates and other items. Solution: Type 316 stainless steel is specified for guide rails, brackets, bolts, nuts, structural steel, supports, and stairs. Fiberglass grating and ladders are specified. Aluminum hatch covers and slide gates are still specified because they are light way and durable, but they are susceptible to corrosion over time. The exterior of ductile iron piping is epoxy coated. Corrosion resistant materials should also be specified for electrical components. 3. Pump Protection from Influent Sewage Debris Problem: Most of the older pump stations had the influent sewer entering directly into the wet well and relied on the ability of the submersible pumps to pump a 3 inch diameter solid. Some pump stations had a basket screen attached to the influent sewer inside the wet well to try to protect the pumps from damage. However, the screens have to be manually lifted out of the wet well and cleaned by hand often to be effective. Solution: In order to assure that the pumps are adequately protected, new submersible pump stations in Northern Virginia often include a comminutor vault preceding the wet well. Raw wastewater entering the pump station flows through the comminutor vault influent channel which is equipped with a grinder. The grinder is a hydraulically driven horizontal screen and cutter assembly. The rotating screen directs solids toward and into the cutters where the influent solids are ground into fine particles to protect the downstream pumps. The grinder 5hp hydraulic power pack is located in a fiberglass enclosure mounted on top of the comminutor vault. In the event the grinder must be taken out of service, slide gates are provided to direct comminutor vault influent flow to a bypass bar screen. Also, in the event flow backs up upstream of the grinder the influent channel wall has an overflow notch just upstream of the bar screen. The bar screen is constructed of stainless steel bars and must be manually cleaned with a rake. The comminutor vault is a 12 ft. diameter precast concrete manhole with an HDPE liner. Stainless steel alternating tread stairs are used for access to the bottom of the vault. All lighting and electrical equipment is explosion proof inside the vault. A ventilation fan is provided on top of the comminutor vault. 4. Pump Selection Based on Total Dynamic Head Calculations Pumps are selected based on total dynamic head (TDH) calculations which can lead to improper sizing unless the Engineer carefully considers the exact pipe inside diameter, the Williams Hazen flow coefficient (C), and the location of high points in the force main. Each of these factors is discussed as follows:

Inside Pipe Diameter: Typically in Northern Virginia force main piping is either double cement lined ductile iron pipe or PWC pipe per AWWA C-900. The inside pipe diameter may vary considerably depending on the type of pipe selected. For long force mains extending two or more miles in length this can result in a significant difference in friction head component of the TDH. Solution: Determine the type of force main to be constructed and the exact inside pipe diameter in preparing TDH calculations. If the force main could be either ductile iron pipe, PVC or some other material, the TDH calculations should be prepared for each possible pipe material to make sure that the selected pump is adequate for all pipe materials. Williams Hazen flow coefficient (C): For new ductile iron pipe a C factor of 140 is often used in TDH calculations to estimate friction head in the force main when it is first placed in service. A C factor of 120 is often used to estimate the friction head in the force main after several years of operation. Pump selection based on a C factor of 140 alone will result in a pump that may be undersized when the force main pipe C factor decreases due to increased roughness of pipe internal surfaces over time. If the pump selection is based on a C factor of 120, the pump may pump too high a flow rate at startup because the new smooth pipe C factor is actually 140. This can result in overloading the pump motor. Also, it is important to note that field measurements of the actual C factors for old force mains which have been in continuous service for over 25 years has indicated that the C factor has decreased to approximately 100. Solution: For new pump stations, prepare TDH calculations based on the initial new pipe C factor and the anticipated C factor after the force main has been in service for several years. When expanding the capacity of existing pump stations which have been in service for many years, the actual C factor of the force main should be determined by field measurements. Problem involves a Force Main High Point near the pump station: Typically the TDH calculations are based on the entire length of force main pipe from the pump station to the discharge point. However, when pumping from one valley over a hill to a gravity sewer on the other side of the hill it is important to consider whether or not there is free fall in the down hill segment of the force main such that the downhill length of pipe does not need to be considered in the TDH calculations. If the static head from the high point to the discharge point exceeds the full flow headloss in the downhill segment of force main, sewage should flow by gravity through the force main similar to a gravity sewer instead of as a full pipe under pressure. Failure to recognize this condition in long force mains with a high point near the pump station can result in the selection of much higher capacity pumping equipment than actually required, and in significantly higher pumping rates than anticipated.

5. Energy Efficient Operation Problem: Common pump station design practice over the past 50 years has been to provide two pumps sized for the peak design flow rate, one of which is a standby pump. For pump stations with long force mains, the friction loss when operating at the design peak flow rate is excessive, resulting in high energy costs. Energy efficiency is becoming a very important consideration in pump station design. The Town of Purcellville East End Pump Station in Loudoun County, VA was equipped with two 75 hp submersible pumps which cycled on and off at the peak design flow rate of 600 gpm at 127 feet TDH. Sewage is pumped through an 8-inch force main, 4,572 feet long with friction headloss of 39 feet and excessive energy costs from frequent pump cycling on and off due to sewer infiltration/inflow. Solution: A small 10 hp submersible jockey pump was installed in the wet well to operate almost continuously through the day at a flow rate of approximately 100 gpm. This lower flow rate significantly reduced the friction loss and energy requirements while providing reliable service. The friction headloss was reduced from 39 feet to 2 feet. The larger pumps only operate a few times a day during peak flow periods in the morning and evening which is sufficient to flush out solids in the force main. Power costs were significantly reduced based on three years of operation. 6. Pump Station Appearance Problem: For many years pump stations were designed to be functional with little attention given to the exterior appearance and the impact on the surrounding community. Many of the new pump stations in Northern Virginia are located next to new homes costing over $700,000 or next to attractive commercial development. Standard utility buildings with barbed wire exterior fencing are often unacceptable to the developers in Northern Virginia. Solution: The pump station control building exteriors include stone faced block walls or other features to match the surrounding development architecture. Ten foot high black galvanized steel picket fence is used with an extended top slanted for security. 7. Surge Protection Problem: When the pumps cycle off or there is a power failure, high surge pressures can damage piping. Solution: Soft start/stop electrical control equipment significantly reduces surge pressures. As backup protection a surge relief valve is often installed at each pump station in the event of a power failure or a failure of the soft start/stop equipment.

8. Rehabilitation of Existing Pump Stations Problem: Fairfax County has a program to rehabilitate four to eight pump stations every few years under one construction contract as necessary. After approximately 20 years of service they have found that parts are no longer available for electrical controls, and pumps and valves need to be replaced. Also, the building structures, roads and electrical service are often in need of replacement. The pump station must be maintained in continuous service through construction and thus constructability issues must be identified in the design process. Solution: Based on over 15 recent pump station rehabilitation projects, a typical scope of work can be identified for construction rehabilitation. Each pump station needs to be examined separately to determine what rehabilitation measures are needed. Pumps and valves and other mechanical equipment items are replaced. Typically, dry pit submersible pumps are used to replaced shaft pumps. New electrical controls are installed. Corrosion resistant materials are installed to replace corroded materials or epoxy coatings are applied to existing surfaces. Structural and architectural improvements are identified. The construction phasing and temporary pumping requirements are identified in the contract documents for construction. An existing 20 MGD wet well/dry well pump station with vertical shaft pumps was expanded to 40 MGD capacity with dry pit submersible pumps while maintaining continuous operation. This was achieved by first installing two of the submersible pumps in the wet well and providing a temporary force main. Once this temporary pumping system was operations, all of the equipment in the dry well was replaced with new equipment. Once two of the four dry pit submersibles were installed in the dry well, the two pumps in the wet well were removed and also installed in the dry well to complete the project. 9. Prevention of Leakage into the Pump Station Structures Problem: Cracks or joints in precast concrete manhole structures used to construct new pump stations can result in groundwater leakage into the pump station which must be pumped to the treatment facility resulting in unnecessary costs and reduced capacity. It is often difficult to permanently seal such cracks or joints after construction is completed and the pump station is in service creating a confined space. This is especially true for deep pump stations. Solution: All weather butyl joint sealant materials are available for effective sealing precast concrete joints exposed to high groundwater pressures. Butyl sealants are rubber based and exhibit physical properties such as rebound, compression, low temperature and high temperature flows that are all required for long term sealing performance. This joint material was effectively used at the 50 foot deep Morris Farm Pump Station in Prince William County to prevent leakage. Other methods of sealing the joints and concrete surfaces are also available including bentonite.

10. Odor Control Problem: Sewage piping designed for future ultimate design flows is often way oversized for initial flows resulting in long pipe retention times and septic odors. Solution: Chemical feed addition at pump stations can help minimize odor problems throughout the downstream sewer system. Bioxide chemical solution has been utilized at several new pump stations to minimize odors. The Bioxide material utilizes the inherent ability of the facultative bacteria normally present in wastewater to metabolize hydrogen sulfide and other odor-causing, reduced sulfur containing compounds. The material provides nitrate-oxygen to the wastewater to support this biochemical mechanism. This nitrate-oxygen is applied via nitrate salts. The material shall be chemically stable, allowing continuous removal of sulfide contributed by side streams downstream of the application point. The pump station design includes a pad mounted Bioxide chemical storage tank and automatic chemical feed equipment. 11. Provisions for Future Expansion Problem: The rapid growth experienced in Northern Virginia over the past few years can result in pump stations being undersized to convey projected flow rates. If provisions for future expansion are not included in the design, the entire pump station or major components of the pump station may have to be replaced. Solution: Provisions for future expansion include the selection of pumps with higher than required motor horsepower to allow the future installation of larger diameter impellers capable of pumping increased flows. The Morris Farm Pump Station in Prince William County was almost over capacity at start up because of the addition of unanticipated sewage flows from a new elementary school which was supposed to be served by an adjacent gravity sewer system. Fortunately, by adding a larger impeller the additional flow could be accommodated without any other changes. Other considerations include sizing the force main, generator set, wet well, electrical service and other components to allow some increase in capacity without causing problems during initial operation. 12. Grit Deposition in Wet Wells Sized for Future Flow Rates Problem: The design criteria for submersible pump wet well sizing can lead to excessive grit deposition in the wet well due to initial low flow conditions. The grit can result in serious odor problems and is difficult to remove. Solution: Provide temporary solid concrete block filler in the wet well areas subject to grit deposition or provide baffle walls to reduce the wet well area during initial low flow conditions. In the future when the flows approach the design flow rate, the blocks or baffle walls can be removed. CONCLUSION The planning and design of new municipal wastewater pump stations or rehabilitation/expansion of existing pump stations requires careful consideration of potential problems and possible solutions presented above.

Municipal Sewage Pump Station Design Problems and Solutions presented by: Jeff Chapin, PE October 24, 2006 Session 28

Morris Farm Western Prince William County, Virginia

Prince William County Service Authority Morris Farm Pump Station 928 GPM Capacity

Prince William County Service Authority Morris Farm Pump Station

Corrosion Sewer Gas Corrodes Concrete and Metal Components

Prince William County Service Authority Morris Farm Pump Station Grinder Vault with HPDE Liner & Stainless Steel Stairs

Prince William County Service Authority Morris Farm Pump Station Grinder

Prince William County Service Authority Morris Farm Pump Station Grinder Hydraulic Power Drive

Prince William County Service Authority Morris Farm Pump Station Bypass Bar Screen

Prince William County Service Authority Morris Farm Pump Station Wet Well

Prince William County Service Authority Morris Farm Pump Station Valve Vault

Prince William County Service Authority Morris Farm Pump Station Control Building & Standby Generator

Prince William County Service Authority Morris Farm Pump Station Control Building Panels

Odor Control Prince William County Service Authority Morris Farm Pump Station Bioxide Tank

Construction Problems Commuter Vault Wet Well Valve Vault Meter Vault Potential for Differential Settlement Potential for Water Leakage Typical Submersible Pump Station Section View Prince William County, Virginia

Watertight Structures 250 gpm Camp Glenkirk Pump Station

Rock Excavation Prince William County Service Authority Broad Run Pump Station Rock Saw

Potential Problems & Solutions Lift Chain Enters Volute Short Chain Length Power Cable Excessive Flexing Short Cable Length Cavitation With 2 Pumps Running At Low Speed Pump Head Does Not Overcome System Head Air Entrainment From Concentric Reducer On Pump Suction Piping Check 2 Pump Curve Check Pump Curve At Low Speed Use Eccentric Reducer

Energy Efficiency Improvement at Purcellville East End Pump Station Original Pump System Two 75 hp Submersible Pumps 600 GPM Pumping Rate Significant Infiltration & Inflow 4,572 Feet of 8-inch Force Main Friction Headloss = 39 feet Excessive Surge With Frequent Pump Starts

Installation of Small Pump

Energy Efficiency Improvement at Purcellville East End Pump Station Improvements: Added a new 10 hp submersible pump Rated 120 gpm at 90 feet TDH Friction Headloss = 2 feet Cost of Pump and Controls Installed = $6,500 Benefits: Less Surge from Frequent Stop Starts Operation at Lower Head Reduces Energy Consumption Eliminates current surges when 75 hp pump starts

Design Calculation Pitfalls Force Main Profile

Grease Problems 2.9 MGD Pump Station Wet Well

Pipe Clogging Sonar Image 30 Pipe

Appearance Town of Leesburg Goose Creek Pump Station

20 MGD to 40 MGD Expansion Existing 20 MGD Pump Station Dry Well

Installation of Larger Pumps Expansion to 40 MGD Pump Station Dry Well

Grit in Wet Well 100 MGD Pump Station

Conclusion Corrosion Resistant Materials Watertight Structures Minimize Settlement Check Design Calculations Consider Grease & Grit Energy Efficiency Constructability