Supplementary Protectors/Miniature Circuit Breakers



Similar documents
Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Bulletin 1489 Circuit Breakers. Selection Guide

Bimetallic Overload Relay Specifications

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

CompactLogix Power Supplies Specifications

Circuit Breakers. Next Generation of Protection Capabilities

Electronic overload relay EF65, EF96 and EF146

Product Guide. Cable-in / cable-out miniature circuit breakers and supplementary protectors

Electronic overload relay EF19 and EF45

R.C.C.B. s two-pole LEXIC

Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P

Circuit Breakers Supplementary Protectors Manual Motor Controllers

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

System pro M compact Miniature Circuit Breaker S 200/S 200 M

Thermal-Magnetic Circuit Breaker M1-..

Manual motor starter MS116

Micro800 Programmable Controllers. Bulletin 2080 Selection Guide

Rotary Disconnect Switch Specifications

AF / AF09Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

RM4TG20 three-phase network control relay RM4-T - range V

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Application Switchgear for industrial and commercial applications. U e V AC 230/ (per pole)

Three-phase monitoring relay CM-PFE

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

SMC -3 Specifications

Type: DILM32 10(24V50HZ) Article No.:

Catalog. Modular DIN rail components Installation contactors

Technical catalogue. Modular DIN rail components Installation contactors

Bulletin 150 SMC Flex Smart Motor Controller Specifications

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

1756 ControlLogix Chassis Specifications

Circuit Breaker. Description

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

Safety technique. Emergency stop module BO 5988 safemaster

ControlNet Standard and High-flex Coax Cable

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

Type: DILM50(230V50HZ,240V60HZ) Article No.:

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

USB-to-Data Highway Plus Cable

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

The complete range of consumer switchboards and switchgear

Type: DILM9 10(24VDC) Article No.:

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

D-Line Contactors, Overload Relays and Accessories

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1

Tmax MCCBs. Molded case circuit breakers. Tmax

5SV Residual Current Protective Devices

Circuit Breakers. NRC Series. NRC Series

Molded Case Circuit Breakers, Motor Protection Circuit Breakers, and Motor Circuit Protectors. Technical Data

Relés e Contatores de Estado Sólido SIRIUS

ADM1TE 5/30A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Installation Instructions. Before Installation. Read these installation instructions carefully before commissioning the pressure transmitter.

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade

49 Series - Relay interface modules A. Features

48 SERIES Relay interface modules 10 A

MicroLogix 1100 Embedded Web Server

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

AP/UP, AP/MIL Series. Magnetic Circuit Protectors

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Sentron Series Circuit Breakers

Safety automation solutions

PowerFlex Dynamic Braking Resistor Calculator

Manual Motor Starter MS 116 up to 16 A Technical Data

Redundancy Module QUINT-DIODE/40

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Power Supplies 3. SDN-P DIN Rail Series

VEO. V4PF480Y/277VSYTK02 Art.Nr.: V4PF480Y/277VSYTK02P Art.Nr.: TECHNICAL DATA

SURGE PROTECTIVE DEVICES

Short-circuit current rating (SCCR) of. industrial control panels. NEC Article 409 and UL 508A

PSR The compact range Description

Technicaldata General

MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA

E-STOP relays, safety gate monitors

Universal Serial Bus (USB) to DH-485 Interface Converter

BRITISH STYLE SEMICONDUCTOR PROTECTION FUSES

38 Series - Relay interface modules A

8146/5 Series Breaker Panelboards

IEC style contactors - long electrical and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide

Stratix 5700 Network Address Translation. Quick Start

How To Protect A Motor From Overcurrent

Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date:

38 Series - Relay interface modules A

Cross-beam scanning system to detect slim objects. 100 mm in

Transcription:

Technical Data Supplementary Protectors/Miniature Circuit Breakers Catalog Numbers 1492-SP Series C

Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Introduction Supplementary Protectors & Accessories Figure 1-1492-SP* Devices & Accessory Overview Accessories Supplementary Protector/Miniature Circuit Breaker 1 Auxiliary/Signal Alarm 1492-ASPHS3 or 142-ASPHSC3 7 Shunt Trip 1492-ASPA1 3 Single-Pole 1492-SP1 Two-Pole 1492-SP2 Dual Auxiliary Contact 1492-ASPHH3 6 Undervoltage Release 1492-ASPU115 4 Three Pole 1492-SP3 Switched Pole Neutral Protector 2 Auxilliary Contact 1492-ASPH3 5 ➀ Supplementary Protector/Miniature Circuit Breaker Available in single-, two-, three-pole, one-pole neutral, and four-pole neutral Specifications & Certifications: Meets UL 1077/CSA 22.2 No. 235 In conformity with IEC/EN 60 898 CE Marked Trip Characteristics B-Trip for resistive or slightly inductive loads C-Trip for inductive loads D- Trip for highly inductive loads ➁ Switched Pole Protector (not field-mountable) Switched neutral pole closes before the adjacent protected pole (i.e., early make) Instantaneous/magnetic release provided, but no overload thermal release Rockwell Automation Publication 1492-TC010D-EN-P April 2011 3

➂ Shunt Trip Field installable Mounts to side Module width is equal to that of a single-pole ➃ Undervoltage Release Field installable Mounts to side Module width is equal to that of a single-pole ➄ Auxiliary Contact Field installable Changeover contact Switches when protective device is operated manually or is tripped electrically 1 Form C ➅ Dual Auxiliary Contact Field installable Two auxiliary contacts Changeover contact Switches when protective device is operated manually or is tripped electrically 2 Form C Version with convertible contact ➆ Auxiliary/Signal Alarm Field installable Auxiliary contacts Auxiliary contact switches when protective device is operated manually or is tripped electrically Signal alarm Signal alarm contact switches only when protective device is tripped electrically Changeover contact 2 Form C Front indicator indicates when device is tripped electrically 4 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Description Bulletin 1492-SP Supplementary Protector/Miniature Circuit Breakers are energy limiting, thermal-magnetic type, overcurrent-protective devices meeting UL 1077/CSA 22.2 No. 235, IEC/EN 60898 and IEC 60947-2. These devices are designed for the protection of a wide variety of products including: Solenoids Test Equipment Controller I/O Points Relay and Contractor Coils Computers Transformers Automotive Systems Power Supplies Medical Equipment Control Instrumentation Bulletin 1492-SP Supplementary Protectors/Miniature Circuit Breakers are available in one-, two-, three-, and four-pole units as well as one- and three-pole plus neutral units. One- and two-pole AC units also have limited DC ratings. Two and three-pole units are connected at the handle for simultaneous operation. Screw termination is standard on all Bulletin1492-SP units. Both line and load side terminals accept #16 4 AWG (1.5 25 mm 2 ) copper wire. IMPORTANT UL 1077, CSA C22.2 No. 235 In North America, miniature circuit breakers are recognized as supplementary protectors and are intended for use as overcurrent protection within an appliance or other electrical equipment where branch circuit protection is already provided or not required. Internationally, these products are rated to IEC standards as miniature circuit breakers for equipment. Rockwell Automation Publication 1492-TD010D-EN-P April 2011 5

International Approvals The Bulletin 1492-SP, Supplementary Protectors/Miniature Circuit Breakers, are designed to comply with standards for worldwide customer acceptance. The Bulletin 1492-SPs meet the following standards:. Table 1 - Bulletin 1492-SP Standards Certifying Agency Certification Marks Country Standard Underwriters Laboratory USA UL 1077 Canadian Standards Association Canada CSA 22.2 No. 235 Verband Deutscher Electrotechniker Germany IEC/EN 60 898 Germanischer Lloyd Germany IEC/EN 60 947-2 per Conformite European European Union IVD Directives per International Electrotechnical Commission Global IEC 60 898 IEC 60 947-2 China Quality Certification Center Global GB 10963 6 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Features The following features provide superior performance. Table 2 - Features of Bulletin 1492-SP Feature Energy limiting design Field mountable options True IP2X finger safe design (front) International approvals Ratings to 480Y/277V AC @ 240/415V AC AC and DC voltage ratings A positively trip-free mechanism Three trip curves Time delay (D characteristic) Superior shock and vibration resistance capabilities Mounts on DIN Rail Reversible line and load connections Description protects downstream components better than conventional breakers during short circuits for selective applications CE Marked and meets UL, CSA, and IEC (VDE, GL) standards for worldwide acceptance 10,000 A Interrupt Rating in one convenient device where the breaker operation cannot be defeated by holding the handle in the ON position B, C, and D for high inrush currents during inductive startups, such as transformers and power supplies helps to prevent nuisance tripping Rockwell Automation Publication 1492-TD010D-EN-P April 2011 7

Construction Figure 2 - Construction Screw Termination accepts #16...#4 (1.5... 25 mm 2 ) wire as standard Front View Convenient Terminals for commoning links and bus bars (both line and load side) Positively Trip-Free Mechanism Nylon Body provides toughness and durability required by the environment Ease of Installation & Replacement easily snaps on and off of DIN rail Flag Indicator is clearly marked for position in both international and domestic indication green OFF and red ON Amperage Rating is clearly marked on the front of the device for easy identification Finger Safe to IEC 947-1 Front Variety of Pole Options available in one-, two-, or three-pole and one- or three-pole neutral Side View Catalog Number Prefix Current & Voltage Ratings Approval Symbols Switched Neutral Module (not field-mountable) The switched neutral module opens the neutral line of the circuit when the protected poles are tripped. This module should be used as a safety measure (required by some standards) when protecting networks with a grounded neutral system. The switched neutral pole closes before the adjacent protected pole (i.e., early make). The switched neutral module also provides instantaneous/magnetic trip, manual actuation is through the linked handles, and should always be mounted on the right side of the protected poles. These modules are not field installable. 8 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Ordering Information To order the proper device, you need to know the: maximum rated current of equipment to be protected, system phase of one, two, or three, maximum startup (inrush) current, and accessories that are required. Catalog Number Determine the catalog number by following the steps below and referencing the Selection Tables on page 12. 1. Select a one-, two-, or three-pole device. 2. If needed, select the Switched Neutral Module. The Switched Neutral Module is mounted on the right side of the breaker. This module must be mounted at the factory. It cannot be installed in the field. 3. If applicable, consider the derating factors listed in the Rating Determination on page 9. 4. Order accessory contacts or modules as separate items. Accessory modules are always mounted on the left side of the supplemental protector/ miniature circuit breaker. A maximum of two accessory modules can be mounted on a single device. Refer to the Accessories on page 18 for possible combinations. Rating Determination The standard tripping characteristic for Bulletin 1492-SP is Type C. Type C has a magnetic trip activated at 5 10 times the rated current of the circuit breaker. The reference temperature for the thermal tripping characteristics is 30 C. The Type C characteristic will suit most applications. Use the following steps to determine the current rating for the breaker. 1. Take the rated current of the equipment. For example, 10 A. 2. Take the ambient temperature of the 1492-SP location (e.g., 50 C (122 F)). 3. Refer to the table below, which rerates the 1492-SP current for the given ambient temperature. Influence of the ambient temperature on the thermal tripping characteristic. Rockwell Automation Publication 1492-TD010D-EN-P April 2011 9

Table 3 - Ambient Temperature Derating Calibration temperature = 30 C; application below 0 C is for non-condensing atmosphere* Product Nameplate Continuous Current Rating Ambient Temperature in C -25-20 -10 0 10 20 30 35 40 45 50 55 60 0.5 0.61 0.60 0.58 0.56 0.54 0.52 0.50 0.49 0.48 0.47 0.46 0.45 0.44 1 1.2 1.1 1.0 0.99 0.97 0.95 0.93 0.90 0.89 2 2.4 2.3 2.2 2.1 2.0 1.9 1.8 3 3.7 3.6 3.5 3.4 3.3 3.1 3.0 2.9 2.8 2.7 4 4.9 4.8 4.7 4.5 4.3 4.2 4.0 3.9 3.8 3.7 3.6 3.5 5 6.1 6.0 5.8 5.6 5.4 5.2 5.0 4.9 4.8 4.7 4.6 4.5 4.4 6 7.3 7.2 7.0 6.7 6.5 6.3 6.0 5.9 5.8 5.7 5.6 5.4 5.3 8 9.8 9.6 9.3 9.0 8.7 8.4 8.0 7.9 7.7 7.6 7.4 7.2 7.1 10 12 11 10 9.9 9.7 9.5 9.3 9.0 8.9 13 16 15 14 13 12 15 18 17 16 15 14 13 16 20 19 18 17 16 15 14 20 24 23 22 21 20 19 18 25 31 30 29 28 27 26 25 24 23 22 32 39 38 37 36 35 33 32 31 30 29 28 40 49 48 47 45 43 42 40 39 38 37 36 35 50 61 60 58 56 54 52 50 49 48 47 46 45 44 63 77 76 73 71 68 66 63 62 61 60 58 57 56 *Care should be taken for application below 0 C. These devices are not certified to operate correctly in the presence of ice. 4. All other specifications for standard Bulletin1492-SP products remain unchanged. The ambient temperature derating applies to applications of the device as an IEC Miniature Circuit Breaker (MCB) following 60 947-2 and as a supplementary protector to UL1077/CSA 22.2 No 235. Ambient temperature refers to the free air temperature in contact with the 1492-SP. Contact Rockwell Automation for ambient temperatures beyond those shown above. 5. Select the 1492-SP with the next available rating at the given ambient temperature. In this example, it would be 13 A. With this selection, adequate overload protection is provided and nuisance tripping by thermal influences is avoided. 6. Check that transients of the system do not exceed the must hold value of the trip characteristic. This will eliminate nuisance tripping by magnetic influences. The Type C characteristic will be adequate for most applications. Refer to the Selection Tables on page 12. 10 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

7. In rare occurrences when the Type C characteristic does not fully meet the application, the following additional magnetic trip characteristics are available: 8. Type D allows for transients approximately twice as high as the standard Type C. Refer to the Selection Tables on page 12. 9. Type B achieves instantaneous tripping at current levels approximately half as high as Type D. Refer to the Selection Tables on page 12. 10. If multiple supplementary protectors are mounted side-by-side, they must be derated to determine the load carrying capacity. Use the derating equation below. Adjusted Current Rating = Rated Current multiplied by α The figure below shows the rated diversity factor, where miniature circuit breakers influence one another thermally at rated load. Figure 3 - Rated Diversity Factor 1.00 Rated Diversity Factor 0.90 0.80 0.70 1 2 3 4 5 6 7 8 Number of Circuit Breakers Rockwell Automation Publication 1492-TD010D-EN-P April 2011 11

Selection Tables B-Trip Characteristics Resistive/Slightly Inductive Loads, 3 5 I n Table 4 - One Pole & One-Pole Neutral One-Pole One-Pole plus Neutral Continuous Current Catalog 3rd Party Continuous Current Catalog 3rd Party Rating (In) Number Certification Rating (In) Number Certification 1 1492-SP1B010 ➊ 1 1492-SP1B010-N ➊ 2 1492-SP1B020 ➊ 2 1492-SP1B020-N ➊ 3 1492-SP1B030 ➊ 3 1492-SP1B030-N ➊ 4 1492-SP1B040 ➊ 4 1492-SP1B040-N ➊ 5 ➋ 1492-SP1B050 ➊ 6 1492-SP1B060 ➊ 6 1492-SP1B060-N ➊ 7 ➋ 1492-SP1B070 ➊ 8 1492-SP1B080 ➊ 8 1492-SP1B080-N ➊ 10 1492-SP1B100 ➊ 10 1492-SP1B100-N ➊ 13 1492-SP1B130 ➊ 13 1492-SP1B130-N ➊ 15 ➋ 1492-SP1B150 ➊ 16 1492-SP1B160 ➊ 16 1492-SP1B160-N ➊ 20 1492-SP1B200 ➊ 20 1492-SP1B200-N ➊ 25 1492-SP1B250 ➊ 25 1492-SP1B250-N ➊ 30 ➋ 1492-SP1B300 ➊ 32 1492-SP1B320 ➊ 32 1492-SP1B320-N ➊ 40 1492-SP1B400 ➊ 40 1492-SP1B400-N ➊ 50 1492-SP1B500 ➊ 50 1492-SP1B500-N ➊ 63 1492-SP1B630 ➊ 63 1492-SP1B630-N ➊ Operational Voltage IEC 240/415V AC/48V DC IEC 240V AC UL/CSA 277V AC/48V DC UL/CSA 277V AC Pieces Per Package 2 1 Diagram 1 2 1 2 N N ➊ ➋ Current rating used only in North America. 12 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Table 5 - Two-Pole, Three-Pole, & Three-Pole Neutral Two-Pole Three-Pole Three-Pole plus Neutral Continuous Current Rating (In) Catalog Number 3rd Party Certification Continuous Current Rating (In) Catalog Number 3rd Party Certification Continuous Current Rating (In) Catalog Number 1 1492-SP2B010 ➊ 1 1492-SP3B010 ➊ 1 1492-SP3B010-N ➊ 2 1492-SP2B020 ➊ 2 1492-SP3B020 ➊ 2 1492-SP3B020-N ➊ 3 1492-SP2B030 ➊ 3 1492-SP3B030 ➊ 3 1492-SP3B030-N ➊ 4 1492-SP2B040 ➊ 4 1492-SP3B040 ➊ 4 1492-SP3B040-N ➊ 5 ➋ 1492-SP2B050 ➊ 5 ➋ 1492-SP3B050 ➊ 6 1492-SP2B060 ➊ 6 1492-SP3B060 ➊ 6 1492-SP3B060-N ➊ 7 ➋ 1492-SP2B070 ➊ 7 ➋ 1492-SP3B070 ➊ 8 1492-SP2B080 ➊ 8 1492-SP3B080 ➊ 8 1492-SP3B080-N ➊ 10 1492-SP2B100 ➊ 10 1492-SP3B100 ➊ 10 1492-SP3B100-N ➊ 13 1492-SP2B130 ➊ 13 1492-SP3B130 ➊ 13 1492-SP3B130-N ➊ 15 ➋ 1492-SP2B150 ➊ 15 ➋ 1492-SP3B150 ➊ 16 1492-SP2B160 ➊ 16 1492-SP3B160 ➊ 16 1492-SP3B160-N ➊ 20 1492-SP2B200 ➊ 20 1492-SP3B200 ➊ 20 1492-SP3B200-N ➊ 25 1492-SP2B250 ➊ 25 1492-SP3B250 ➊ 25 1492-SP3B250-N ➊ 30 ➋ 1492-SP2B300 ➊ 30 ➋ 1492-SP3B300 ➊ 32 1492-SP2B320 ➊ 32 1492-SP3B320 ➊ 32 1492-SP3B320-N ➊ 40 1492-SP2B400 ➊ 40 1492-SP3B400 ➊ 40 1492-SP3B400-N ➊ 50 1492-SP2B500 ➊ 50 1492-SP3B500 ➊ 50 1492-SP3B500-N ➊ 63 1492-SP2B630 ➊ 63 1492-SP3B630 ➊ 63 1492-SP3B630-N ➊ 3rd Party Certification Operational Voltage Pieces per Package IEC 415V AC IEC 415V AC IEC 415V AC UL/CSA 480Y/277V AC, 96V DC UL/CSA 480Y/277V AC UL/CSA 480Y/277V AC 1 1 1 Diagram + 1 3 DC 1 3 5 1 3 5 N 2 4 2 4 6 2 4 6 N ➊ ➋ Current rating used only in North America. Rockwell Automation Publication 1492-TD010D-EN-P April 2011 13

C-Trip Characteristics Inductive Loads, 5 10 I n Table 6 - One Pole & One-Pole Neutral One-Pole One-Pole plus Neutral Continuous Current Rating (In) Catalog Number 3rd Party Certification Continuous Current Rating (In) Catalog Number 0.5 1492-SP1C005 ➊ 0.5 1492-SP1C005-N 1 1492-SP1C010 ➊ 1 1492-SP1C010-N ➊ 2 1492-SP1C020 ➊ 2 1492-SP1C020-N ➊ 3 1492-SP1C030 ➊ 3 1492-SP1C030-N ➊ 4 1492-SP1C040 ➊ 4 1492-SP1C040-N ➊ 5 ➋ 1492-SP1C050 ➊ 6 1492-SP1C060 ➊ 6 1492-SP1C060-N ➊ 7 ➋ 1492-SP1C070 ➊ 8 1492-SP1C080 ➊ 8 1492-SP1C080-N ➊ 10 1492-SP1C100 ➊ 10 1492-SP1C100-N ➊ 13 1492-SP1C130 ➊ 13 1492-SP1C130-N ➊ 15 ➋ 1492-SP1C150 ➊ 16 1492-SP1C160 ➊ 16 1492-SP1C160-N ➊ 20 1492-SP1C200 ➊ 20 1492-SP1C200-N ➊ 25 1492-SP1C250 ➊ 25 1492-SP1C250-N ➊ 30 ➋ 1492-SP1C300 ➊ 32 1492-SP1C320 ➊ 32 1492-SP1C320-N ➊ 40 1492-SP1C400 ➊ 40 1492-SP1C400-N ➊ 50 1492-SP1C500 ➊ 50 1492-SP1C500-N ➊ 63 1492-SP1C630 ➊ 63 1492-SP1C630-N ➊ Operational Voltage IEC 240/415V AC/48V DC IEC 240V AC UL/CSA 277V AC/48V DC UL/CSA 277V AC Pieces Per Package 2 1 3rd Party Certification Diagram 1 2 1 2 N N ➊ ➋ Current rating used only in North America. 14 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Table 7 - Two-Pole, Three-Pole, & Three-Pole Neutral Two-Pole Three-Pole Three-Pole plus Neutral Continuous Current Rating (In) Catalog Number 3rd Party Certification Continuous Current Rating (In) Catalog Number 3rd Party Certification Continuous Current Rating (In) Catalog Number 0.5 1492-SP2C005 ➊ 0.5 1492-SP3C005 ➊ 0.5 1492-SP3C005-N ➊ 1 1492-SP2C010 ➊ 1 1492-SP3C010 ➊ 1 1492-SP3C010-N ➊ 2 1492-SP2C020 ➊ 2 1492-SP3C020 ➊ 2 1492-SP3C020-N ➊ 3 1492-SP2C030 ➊ 3 1492-SP3C030 ➊ 3 1492-SP3C030-N ➊ 4 1492-SP2C040 ➊ 4 1492-SP3C040 ➊ 4 1492-SP3C040-N ➊ 5 ➋ 1492-SP2C050 ➊ 5 ➋ 1492-SP3C050 ➊ 6 1492-SP2C060 ➊ 6 1492-SP3C060 ➊ 6 1492-SP3C060-N ➊ 7 ➋ 1492-SP2C070 ➊ 7 ➋ 1492-SP3C070 ➊ 8 1492-SP2C080 ➊ 8 1492-SP3C080 ➊ 8 1492-SP3C080-N ➊ 10 1492-SP2C100 ➊ 10 1492-SP3C100 ➊ 10 1492-SP3C100-N ➊ 13 1492-SP2C130 ➊ 13 1492-SP3C130 ➊ 13 1492-SP3C130-N ➊ 15 ➋ 1492-SP2C150 ➊ 15 ➋ 1492-SP3C150 ➊ 16 1492-SP2C160 ➊ 16 1492-SP3C160 ➊ 16 1492-SP3C160-N ➊ 20 1492-SP2C200 ➊ 20 1492-SP3C200 ➊ 20 1492-SP3C200-N ➊ 25 1492-SP2C250 ➊ 25 1492-SP3C250 ➊ 25 1492-SP3C250-N ➊ 30 ➋ 1492-SP2C300 ➊ 30 ➋ 1492-SP3C300 ➊ 32 1492-SP2C320 ➊ 32 1492-SP3C320 ➊ 32 1492-SP3C320-N ➊ 40 1492-SP2C400 ➊ 40 1492-SP3C400 ➊ 40 1492-SP3C400-N ➊ 50 1492-SP2C500 ➊ 50 1492-SP3C500 ➊ 50 1492-SP3C500-N ➊ 63 1492-SP2C630 ➊ 63 1492-SP3C630 ➊ 63 1492-SP3C630-N ➊ 3rd Party Certification Operational Voltage Pieces per Package Diagram IEC 415V AC IEC 415V AC IEC 415V AC UL/CSA 480Y/277V AC, 96V DC UL/CSA 480Y/277V AC UL/CSA 480Y/277V AC 1 1 1 1 3 + 1 3 5 1 3 5 DC N 2 4 2 4 6 2 4 6 N ➊ ➋ Current rating used only in North America. Rockwell Automation Publication 1492-TD010D-EN-P April 2011 15

D-Trip Characteristics Highly Inductive Loads 10 20 I n Table 8 - One Pole & One-Pole Neutral One-Pole One-Pole plus Neutral Continuous Current Rating (In) Catalog Number 3rd Party Certification Continuous Current Rating (In) Catalog Number 0.5 1492-SP1D005 ➊ 0.5 1492-SP1D005-N 1 1492-SP1D010 ➊ 1 1492-SP1D010-N ➊ 2 1492-SP1D020 ➊ 2 1492-SP1D020-N ➊ 3 1492-SP1D030 ➊ 3 1492-SP1D030-N ➊ 4 1492-SP1D040 ➊ 4 1492-SP1D040-N ➊ 5 ➋ 1492-SP1D050 ➊ 6 1492-SP1D060 ➊ 6 1492-SP1D060-N ➊ 7 ➋ 1492-SP1D070 ➊ 8 1492-SP1D080 ➊ 8 1492-SP1D080-N ➊ 10 1492-SP1D100 ➊ 10 1492-SP1D100-N ➊ 13 1492-SP1D130 ➊ 13 1492-SP1D130-N ➊ 15 ➋ 1492-SP1D150 ➊ 16 1492-SP1D160 ➊ 16 1492-SP1D160-N ➊ 20 1492-SP1D200 ➊ 20 1492-SP1D200-N ➊ 25 1492-SP1D250 ➊ 25 1492-SP1D250-N ➊ 30 ➋ 1492-SP1D300 ➊ 32 1492-SP1D320 ➊ 32 1492-SP1D320-N ➊ 40 1492-SP1D400 ➊ 40 1492-SP1D400-N ➊ 50 1492-SP1D500 ➌ 50 1492-SP1D500-N ➌ 63 1492-SP1D630 ➌ 63 1492-SP1D630-N ➌ Operational Voltage IEC 240/415V AC/48V DC IEC 240V AC UL/CSA 277V AC/48V DC UL/CSA 277V AC Pieces Per Package 2 1 3rd Party Certification Diagram 1 2 1 2 N N ➊ ➋ Current rating used only in North America. ➌ 16 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Table 9 - Two-Pole, Three-Pole, & Three-Pole Neutral Two-Pole Three-Pole Three-Pole plus Neutral Operational Voltage Pieces per Package Continuous Current Rating (In) Catalog Number 3rd Party Certification Continuous Current Rating (In) Catalog Number 3rd Party Certification Continuous Current Rating (In) Catalog Number 0.5 1492-SP2D005 ➊ 0.5 1492-SP3D005 ➊ 0.5 1492-SP3D005-N ➊ 1 1492-SP2D010 ➊ 1 1492-SP3D010 ➊ 1 1492-SP3D010-N ➊ 2 1492-SP2D020 ➊ 2 1492-SP3D020 ➊ 2 1492-SP3D020-N ➊ 3 1492-SP2D030 ➊ 3 1492-SP3D030 ➊ 3 1492-SP3D030-N ➊ 4 1492-SP2D040 ➊ 4 1492-SP3D040 ➊ 4 1492-SP3D040-N ➊ 5 ➋ 1492-SP2D050 ➊ 5 ➋ 1492-SP3D050 ➊ 6 1492-SP2D060 ➊ 6 1492-SP3D060 ➊ 6 1492-SP3D060-N ➊ 7 ➋ 1492-SP2D070 ➊ 7 ➋ 1492-SP3D070 ➊ 8 1492-SP2D080 ➊ 8 1492-SP3D080 ➊ 8 1492-SP3D080-N ➊ 10 1492-SP2D100 ➊ 10 1492-SP3D100 ➊ 10 1492-SP3D100-N ➊ 13 1492-SP2D130 ➊ 13 1492-SP3D130 ➊ 13 1492-SP3D130-N ➊ 15 ➋ 1492-SP2D150 ➊ 15 ➋ 1492-SP3D150 ➊ 16 1492-SP2D160 ➊ 16 1492-SP3D160 ➊ 16 1492-SP3D160-N ➊ 20 1492-SP2D200 ➊ 20 1492-SP3D200 ➊ 20 1492-SP3D200-N ➊ 25 1492-SP2D250 ➊ 25 1492-SP3D250 ➊ 25 1492-SP3D250-N ➊ 30 ➋ 1492-SP2D300 ➊ 30 ➋ 1492-SP3D300 ➊ 32 1492-SP2D320 ➊ 32 1492-SP3D320 ➊ 32 1492-SP3D320-N ➊ 40 1492-SP2D400 ➊ 40 1492-SP3D400 ➊ 40 1492-SP3D400-N ➊ 50 1492-SP2D500 ➌ 50 1492-SP3D500 ➌ 50 1492-SP3D500-N ➌ 63 1492-SP2D630 ➌ 63 1492-SP3D630 ➌ 63 1492-SP3D630-N ➌ IEC 415V AC IEC 415V AC IEC 415V AC UL/CSA 480Y/277V AC, 96V DC UL/CSA 480Y/277V AC UL/CSA 480Y/277V AC 1 1 1 Diagram + 1 3 DC 1 3 5 1 3 5 N 3rd Party Certification 2 4 2 4 6 2 4 6 N ➊ ➋ Current rating used only in North America. ➌ Rockwell Automation Publication 1492-TD010D-EN-P April 2011 17

Accessories Table 10 - Auxiliary Contacts Auxiliary Contact Description Approvals Diagram Auxiliary Contact Module Changeover 1 Form C Switches when protective device is operated manually or tripped electrically 12 14 11 Catalog Number 1492-ASPH3 Dual Auxiliary Contact Module Two auxiliary contacts Changeover contact 2 Form C Switches when the protective device is operated manually or tripped electrically 12 14 22 24 11 21 1492-ASPHH3 Auxiliary/Signal Alarm Module Auxiliary Contact switches when the protective device is operated manually or tripped electrically Signal Alarm Contact trip indicating contact switches only when the protective device is tripped electrically Changeover Contact 2 Form C Front Indicator signals when device is tripped electronically Convertible Contact Module Customer selectable Contact sets similar to 1492-ASPHH3 or 1492- ASPHS3 Customer may field select one configuration or the other 96 98 12 14 95 11 96 98 12 14 95 11 1492-ASPHS3 1492-ASPHSC3 18 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Table 11 - Voltage Trips Voltage Trip Description Approvals Diagram Voltage Undervoltage Release Module Use to trip the adjacent breaker poles when the applied voltage is less than the nominal voltage Undervoltage trip is often used when loss of power and eventual restoration of power creates an unsafe or unknown set of conditions U < D1 D2 50 115V AC 110 240V AC Catalog Number 1492-ASPU115 1492-ASPU230 Shunt Trip Module Use to trip the adjacent breaker poles from a remote location. The module is actuated by applying a voltage (pickup voltage) to the trip terminals Use in emergency shutdown circuits where multiple power circuits must be switched off from a single location 110 415V AC 110 230V DC 12 110V AC 12 60V DC 1492-ASPA1 1492-ASPA2 Rockwell Automation Publication 1492-TD010D-EN-P April 2011 19

Allowable Combinations of Field Added Modules IMPORTANT All field added modules must be added to left side of supplementary protector/miniature circuit breaker. Table 12 - Allowable Combinations of Field Added Modules + Catalog Number 1492- Catalog Number 1492- ASPHSC3 ASPH3 ASPHH3 ASPHS3 ASPA ASPU SP* X X X X X X X X X X X X X X X X X X X X X X X X (1) Auxiliary Contact Module (1) Dual Auxiliary Contact Module (1) Auxiliary/Signal Alarm Contact Module (1) Convertible Contact Module (1) Shunt Trip Module (1) Undervoltage Release Module (1) Auxiliary Contact Module + (1) Shunt Trip Module (1) Dual Auxiliary Contact Module + (1) Shunt Trip Module (1) Auxiliary/Signal Alarm Module + (1) Shunt Trip Module (1) Convertible Contact Module + (1) Shunt Trip Module 20 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Additional Accessories The following table lists additional accessories used with all 1492-SP* Miniature Circuit Breakers. Table 13 - Additional Accessories Accessory Mounting Rails Catalog Number Pieces per Package 1 m Symmetrical DIN 199-DR1 10 1 m Hi-Rise Symmetrical DIN 1492-DR6 2 1 m Angled Hi-Rise Symmetrical DIN 1492-DR7 2 End Anchor 1492-EAH35 50 Lockout Attachment 1492-ASPLOA 10 Product Selection Cuttable Copper Bus Bar NOTE: The copper bus bar is 1 meter in length and may be cut to a length suitable for your application. Figure 4 - Bus Bar Specifications Bus Bar Description Devices per Meter Amperage Approvals Catalog Number 1492- Single-Phase 57 80 UL 508 A1B8 1 100 UL E56639 Category A1B1 36 with 80 NMTR2 A1B8H Auxiliary ULus listed Module 100 CE A1B1H Two-Phase 29 80 A2B8 22 with Auxiliary Module 100 A2B1 80 A12B8H 100 A12B1H Three-Phase 19 80 A3B8 16 with Auxiliary Module 100 A3B1 80 A3B8H 100 A3B1H Package Quantity Rockwell Automation Publication 1492-TD010D-EN-P April 2011 21

Table 14 - Bus Bar Accessory Specifications Accessory Description Amperage Approvals Figure 5 - Bus Bar Installation Catalog Number 1492- End Caps for Single-Phase Bus Bar UL 508 A1E 10 use with: UL E56639 Two- & Three-Phase Bus Bar Category AME Protective Shroud NMTR2 AAP Terminal Lug 80/100 ULus Listed CE AAT1 Package Quantity * Ampacity of Devices Z2 AWG lb-in Nm 18...4 21 2.4 6...4 27 3.1 1492-SP... or 1492-FB... 1489-AAP 4 mm AWG lb-in Nm 10...2 50 5.5 1492-AAT1 22 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Table 15 - Bus Bar Installation Specifications Type Number of 1492-SP* Rated Operational I e : End Feed per Phase Center Feed per Phase (I e < 63 A) Approvals Catalog Number 1492- Fork Style Commoning Links may be cut to length, not for use with accessories One-Pole 1 m 63 100 ASPCL1 1 (56 devices/m) Three-Pole 1 m 63 100 ASPCL3 1 (19 devices/m) End Cap for Three-Pole ASPEC1 10 Fork Style Commoning Links may NOT be cut to length, not for use with accessories One-Pole 2 63 100 ASPCL102 6 ASPCL106 20 12 ASPCL112 20 Two-Pole 2 63 100 ASPCL204 10 (One-Pole plus Neutral) 3 ASPCL206 10 6 ASPCL212 10 Three-Pole 2 63 100 ASPCL306 10 4 ASPCL312 10 Four-Pole 2 63 100 ASPCL408 5 3 ASPCL412 5 Fork-Style Commoning Links (for use with accessories) One-Pole 2 63 100 ASPCL1A02 20 Two-Pole (One-Pole plus Neutral) 6 ASPCL1A06 9 ASPCL1A09 2 63 100 ASPCL1A04 10 3 ASPCL1A06 5 ASPCL1A10 Three-Pole 2 63 100 ASPCL3A06 10 4 ASPCL3A12 Three-Phase Bus Bar for Multiple One-Pole (each with one auxiliary contact) 2x3 (1p) 63 100 ASPCL3AP06 10 2x3 (1p)+2 (1p) 63 100 ASPCL3AP08 10 3x3 (1p) 63 100 ASPCL3AP09 10 Incoming Terminals for Fork Style (not for use in North America) Pieces per Package For Max 25 mm 2 Wire For Max 25 mm 2 Wire 100 ASPCT25 50 100 ASPCLT35 10 Protective Covers for Unused Forks ASPCLPS 10 sets (5 per set) Rockwell Automation Publication 1492-TD010D-EN-P April 2011 23

Technical Information Limiting Let-Through Energy Bulletin 1492-SP versus Conventional Breakers The 1492-SP line features the unique ability to achieve short-circuit interruptions far more effectively than conventional breakers. In conventional circuit breakers, the short-circuit interruption time required is approximately one or two half cycles of an AC sine wave. When the contacts open, the resulting arc continues to burn until the current level passes through zero. The arc may reignite because of the insufficient width of the contact gap. The current that flows until the arc is extinguished produces a heating effect proportional to the I 2 t value (let-through-energy) of the fault current. The 1492-SP device is designed to substantially reduce the amount of letthrough-current and the resulting let-through-energy that can damage protected components. The 1492-SP has the ability to interrupt short-circuit current within the first half cycle of the fault. Limiting let-through-energy will protect against the harmful effects of overcurrent and is focused primarily on avoiding: excessive heat and mechanical damage. Both of these factors are proportional to the square of the current. Thermal energy is proportional to the square of the RMS value and magnetic forces are proportional to the square of the peak value. The most effective way to provide protection is to substantially limit let-through-energy. This provides the following advantages: Far less damage at the location of the short circuit. Fast electric separation of a faulty unit from the system; in particular, power supplies connected in parallel that are switched off when the voltage of the power bus drops below a certain level. Far less wear on the miniature circuit breaker itself, which means more safe interruptions. Better protection of all components in the short circuit path. Far wider range of selective action when used with an upstream protective device; there are no nuisance shut downs from feeder line interruptions, causing a blackout in all connected branches. 24 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Short-Circuit Interruption The following graphic shows the short circuit interruption from 10 ka 120V AC with an instant of initiation of 15 after a voltage of zero. Figure 6 - Short-Circuit Interruption Conventional Breakers 10 ka 120V AC Instant of Initiation: 15 After Voltage Zero Current Voltage Across Breaker A B C Time A B C Maximum Arc Voltage Recovery Voltage A = instant when the short is initiated B = instant when the contacts open and the arc is initiated C = instant when the arc extinguishes and the current ceases to flow 79,000 A 2 s Let-Though I 2 t 3,500 A 2 s Rockwell Automation Publication 1492-TD010D-EN-P April 2011 25

Energy-Limiting Characteristics Tripping Characteristics Figure 7 - Tripping Characteristics at 30º C 7200 3600 1200 600 300 1 2 120 60 3 30 Time in Seconds 10 5 2 1 0.5 3 0.2 0.1 0.05 0.02 0.01 0.005 0.002 0.001 0.0005 4 6 1 2 3 4 5 7 9 8 5 6 7 8 9 10 15 20 30 40 50 I / I N ➊ Conventional Non-Tripping Current: 1 nt =1.13I N : t >1h ➋ Conventional Tripping Current: 1t=1.45: t <1h ➌ 2.55I N : t=1-60 seconds (I N < 32a); t=1-120 seconds (I N < 32a) ➍ Type B: 31 N : t > 0.1 seconds ➎ Type B: 51 N : t < 0.1 seconds ➏ Type C: 51 N : t > 0.1 seconds ➐ Type C: 101 N : t < 0.1 seconds ➑ Type D: 101 N : t > 0.1 seconds ➒ Type D: 201 N : t < 0.1 seconds 26 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Specifications Table 16 - Basic Specifications Description B Curve C Curve D Curve Tripping Characteristic Poles (17 mm width per pole) Resistive or Slightly Inductive Loads, 3 5 I n 1, 2, 3, 1+ N, 3 + N Approvals See Selection Tables on page 12 Maximum Voltage Dielectric Strength Shock Vibration Operating Temperature Range Shipment & Short-Term Temperature Limits Wire Size (Cu Only) Housing Material #18 8 AWG (1.0 10 mm 2 ) #6 4 AWG (16 25 mm 2 ) Recommended Wire Strip Length Electromechanical Life Switched Neutral Rating Direction of Incoming Supply Contact Position Indicator Terminals Mounting Mounting Position 1960V AC Inductive Loads, Highly Inductive 5 10 I n Loads, 10 20 I n 25 G Half Sine Wave for 11 ms (3 axes) Frequency Range: 10 2000 Hz Max. Amplitude (p - p) = 0.030 in. Max. Acceleration = 5 G 2 hours each of 3 axes -22 +158 F (-30 +70 C) non-condensing -40 +185 F (-40 +85 C) Nylon Tightening Torque: 2.4 N m (21 lb-in.) Tightening Torque: 3.1 N m (27 lb-in.) 0.51 in. (13 mm) 6,000 operations (1 operation = 2 switching events) ON/OFF 277V AC As Required Red/Green M5 (with slotted screw PZ2) DIN Rail (IEC60715) As Required Rockwell Automation Publication 1492-TD010D-EN-P April 2011 27

Table 17 - Basic Specifications, Continued Description B Curve C Curve D Curve Current Range 1 63 A 0.5 63 A 0.5 40 A Certifications Use Group (UG) Terminals (FW) Overload Rating One-Pole, One-Pole plus Neutral UL 1077 Recognized Component QVNU2 - E65138 CSA 22.2 No. 235 Certified Components UG A General Industrial FW 3 Line and Load Evaluated for Field Wiring OL 0 (General Use) Maximum Voltage 277V AC 48V DC Tripping Current (TC) TC1, 40 C Short-Circuit Current Rating (SC) SC U2 SCU1 <35 A 10 ka @ 277V AC; B & C Curve 5 ka @ 277V AC; D Curve 40, 50, 63 A 5 ka @ 277V AC; B, C, & D Curve Two-Pole, Three-Pole, Three-Pole plus Neutral 10 ka @ 48V DC; B, C, & D Curve Maximum Volts 480Y/277V AC 96V DC (Two-Pole Series) Tripping Current (TC) TC2, 40 C Short-Circuit Current Rating SC U2 SC U1 Miniature Circuit Breakers <35 A 10 ka @ 480V AC; B & C Curve 5 ka @ 480V AC; D Curve 40, 50, 63 A 5 ka @ 277V AC; B, C, & D Curve 10 ka @ 48V DC; B, C, & D Curve Current Range 1 63 A 0.5 63 A 0.5 40 A Certifications Electrical Specifications IEC/EN 60 898 (VDE) IEC/EN 60 947-2 (GL) (not including D50 and D63) CQC (GB-10963) (not including D50 and D63) Rated Voltage Un 240/415 VAC 48 V DC (CE 60747-2) Rated Insulation Voltage Ui 440 V AC Rated Impulse Withstand Voltage U imp 4 kv (1.2/50) Conventional Non-Tripping Current Conventional Tripping Current int=1.13 In it=1/45 In Reference Temperature 30 C Temperature Factor Maximum Back-Up Fuse Selectivity Class 3 Rated Short-Circuit Capacity Service Short-Circuit Capacity Climatic Conditions 0.5% per K 125 A gl/gg Icn (IEC 60 898)=10 ka Icu (IEC 60 947-2)=15 ka Ics=7.5 ka Acc to IEC 68-2 (25 55 C/90 95% RH) 28 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Auxiliary Contacts Module Type Catalog Number 1492- Degree of Protection Auxiliary Contact, Dual Auxiliary Contact, Auxiliary /Signal Alarm Undervoltage Release Shunt Trip ASPH3, ASPHH3, ASPHS3, ASPHSE3 ASPU115, ASPU230 ASPA1, ASPA 2 IP 20 (IP 00) Dimensions See Dimensions on page 31. Weight in kg 0.045 0.355 0.155 Mechanical Lifespan in Operations Minimum Impulse Duration Minimum Command Time Operating Voltage 6,000 10,000 4,000 > 15 ms 200 ms ASPU115 U n - 115V AC U min - 50V AC ASPU230 U n - 230/240V AC U min - 110V AC ASPA1 ASPA2 Inrush Current 3.6/44 ma (AC/DC) 25/12 ma (AC) 15/2 ma (DC) Dropout 0.7 0.35 x U s 110 415V AC 110 230V DC 12 110V AC 12 60V DC Voltage Range 0.7 1.1 x U s IEC UL 1077, CSA 22.2 No. 235 Maximum Operating Current Terminal Capacity IEC Rigid, CU Tightening Torque Maximum Operating Current Terminal Capacity CU Tightening Torque AC13 @ 250V AC 3 A AC15 @ 250V AC 0.5 A DC12 @ 110V DC 0.5 A U min - 5V AC 0.5 2.5 mm 2 0.5 4.0 mm 2 1.0 25 mm 2 2 x 0.5 2 x 2.5 mm 2 2 x 0.5 2 x 2.5 mm 2 2 x 1.0 2 x 4.0 mm 2 0.8 Nm 1.1 Nm 2.4 Nm @ 230V AC 2 A @ 110V DC 0.5 A U min - 5 V DC #18 #14 AWG 2 x #18 2x #14 AWG #18 #14 AWG 2 x #18 2x #14 AWG 7 lb-in. 10 lb-in. 21 lb-in. #18 #8 AWG 2 x #18 2x #12 AWG Rockwell Automation Publication 1492-TD010D-EN-P April 2011 29

Ampacity in Amps Ampacity in Amps Application Information A bus bar may be used for all 1492-SP Miniature Circuit Breakers. IMPORTANT Position high current drawing devices nearest to the Feed Terminal, 1492-AAT1. Figure 8 - For 1492-ANNN Bus Bars * Ampacity of Devices Z2 AWG lb-in Nm 18...4 21 2.4 6...4 27 3.1 1492-SP... or 1492-FB... 1489-AAP 4 mm AWG lb-in Nm 10...2 50 5.5 1492-AAT1 Figure 9 - Temperature Current Characteristic 100 Ampacity of 1492-A_B8_Bus Bar 95 90 85 80 75 70 65 60 15 20 25 30 35 40 45 50 55 Temperature in Celsius 100 Ampacity of 1492-A_B1_Bus Bar 95 90 85 80 75 70 65 60 15 20 25 30 35 40 45 50 55 Temperature in Celsius 1492-FB 1492-SP 30 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

LISTED 3HXJ For use with 1492-FB: 80A/600V AC, 100kA RMS Sym.Amps SCCR w/175a J Fuse, 600V AC, max. For use with 1492-SP: 80A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. LISTED 3HXJ LISTED 3HXJ Made in Germany LISTED 3HXJ LISTED 3HXJ For use with 1492-FB: 80A/600V AC, 100kA RMS Sym.Amps SCCR w/175a J Fuse, 600V AC, max. For use with 1492-SP: 80A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. LISTED 3HXJ Made in Germany Dimensions Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes. Figure 10-1492-SP Series C 80.0 45.0 17.5 35.0 52.5 70.0 5.5 44.0 61.5 8.0 Figure 11 - Bulletin 1492-A1B8 17.8 5.5 56.00 x 17.8 = 996.8 2.0 1009.0 +2-0 5.0 15.0 15.0 1492-A1B8 Ser. A 1492-A1E 1492-A1B8 Ser. A 1492-A1E Figure 12 - Bulletin 1492-A2B8 36.5 23.0 (23) 21.2 14.0 6.0 1492-AME 1492-A2B8 Ser. A For use with 1492-FB: 80A/600V AC, 100kA RMS Sym.Amps SCCR w/175a J Fuse, 600V AC, max. For use with 1492-SP: 80A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 17.8 55.00 x 17.8 = 979.0 1492-AME 1492-A2B8 Ser. A For use with 1492-FB: 80A/600V AC, 100kA RMS Sym.Amps SCCR w/175a J Fuse, 600V AC, max. For use with 1492-SP: 80A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 1.5 991.0 +2-0 Figure 13 - Bulletin 1492-A3B8 37.0 23.0 21.2 14.0 6.0 17.8 1492-AME 1492-A3B8 Ser. A For use with 1492-FB: 80A/600V AC, 100kA RMS Sym.Amps SCCR w/175a J Fuse, 600V AC, max. For use with 1492-SP: 80A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 56.0 x 17.8 = 996.8 1492-AME 1492-A3B8 Ser. A For use with 1492-FB: 80A/600V AC, 100kA RMS Sym.Amps SCCR w/175a J Fuse, 600V AC, max. For use with 1492-SP: 80A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 1.5 1009.0 +2-0 Rockwell Automation Publication 1492-TD010D-EN-P April 2011 31

LISTED 3HXJ For use with 1492-FB: 100A/600V AC, 100kA RMS Sym.Amps SCCR w/200a J Fuse, 600V AC, max. For use with 1492-SP: 100A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. LISTED 3HXJ LISTED 3HXJ For use with 1492-FB: 100A/600V AC, 100kA RMS Sym.Amps SCCR w/200a J Fuse, 600V AC, max. For use with 1492-SP: 100A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. LISTED 3HXJ For use with 1492-FB: 80A/600V AC, 100kA RMS Sym.Amps SCCR w/175a J Fuse, 600V AC, max. For use with 1492-SP: 80A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany Made in Germany Made in Germany LISTED 3HXJ LISTED 3HXJ For use with 1492-FB: 100A/600V AC, 100kA RMS Sym.Amps SCCR w/200a J Fuse, 600V AC, max. For use with 1492-SP: 100A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. LISTED 3HXJ For use with 1492-FB: 100A/600V AC, 100kA RMS Sym.Amps SCCR w/200a J Fuse, 600V AC, max. For use with 1492-SP: 100A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. LISTED 3HXJ For use with 1492-FB: 80A/600V AC, 100kA RMS Sym.Amps SCCR w/175a J Fuse, 600V AC, max. For use with 1492-SP: 80A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany Made in Germany Made in Germany Figure 14 - Bulletin 1492-A1B1 17.8 5.5 56.00 x 17.8 = 996.8 2.0 5.0 15.0 15.0 1492-A1B1 Ser. A 1492-A1E 1009.0 +2-0 1492-A1B1 Ser. A 1492-A1E Figure 15 - Bulletin 1492-A2B1 14.0 1492-AME 1492-A3B1 Ser. A For use with 1492-FB: 100A/600V AC, 100kA RMS Sym.Amps SCCR w/200a J Fuse, 600V AC, max. For use with 1492-SP: 100A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 1492-AME 1492-A3B1 Ser. A For use with 1492-FB: 100A/600V AC, 100kA RMS Sym.Amps SCCR w/200a J Fuse, 600V AC, max. For use with 1492-SP: 100A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 21.2 6.0 17.8 56.00 x 17.8 = 996.8 36.5 23.0 2.0 1009.0 +2-0 Figure 16 - Bulletin 1492-A1B1H 2.5 27.0 5.5 36.0 x 27.0 = 972.0 5.0 15.0 985.0 +2-0 15.0 1492-A1B1H Ser. A 1492-A1E 1492-A1B1H Ser. A 1492-A1E Figure 17 - Bulletin 1492-A1B8H 2.0 27.0 5.5 36.0 x 27.0 = 972.0 5.0 15.0 985.0 +2-0 15.0 1492-A1B8H Ser. A 1492-A1E 1492-A1B8H Ser. A 1492-A1E 32 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

LISTED 3HXJ LISTED 3HXJ LISTED 3HXJ LISTED 3HXJ LISTED 3HXJ LISTED 3HXJ Figure 18 - Bulletin 1492-A2B8H 36.5 23.0 21.2 1.5 14.0 1492-AME 1492-A2B8H Ser. A For use with 1492-FB: 80A/600V AC, 100kA RMS Sym.Amps SCCR w/175a J Fuse, 600V AC, max. For use with 1492-SP: 80A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. 6.0 17.8 44.5 Made in Germany 22.0 x 44.5 = 979.0 1492-AME 1492-A2B8H Ser. A For use with 1492-FB: 80A/600V AC, 100kA RMS Sym.Amps SCCR w/175a J Fuse, 600V AC, max. For use with 1492-SP: 80A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 1009.0 +2-0 Figure 19 - Bulletin 1492-A3B8H 14.0 1492-AME 1492-A3B8H Ser. A For use with 1492-FB: 80A/600V AC, 100kA RMS Sym.Amps SCCR w/175a J Fuse, 600V AC, max. For use with 1492-SP: 80A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 1492-AME 1492-A3B8H Ser. A For use with 1492-FB: 80A/600V AC, 100kA RMS Sym.Amps SCCR w/175a J Fuse, 600V AC, max. For use with 1492-SP: 80A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 6.0 17.8 2.0 x 17.8 = 35.6 21.2 62.3 15.0 x 62.3 = 934.5 37.0 23.0 1.5 982.0 +2-0 Figure 20 - Bulletin 1492-A2B1H 36.5 23.0 21.2 2.0 14.0 6.0 17.8 44.0 1492-AME 1492-A2B1H Ser. A For use with 1492-FB: 100A/600V AC, 100kA RMS Sym.Amps SCCR w/200a J Fuse, 600V AC, max. For use with 1492-SP: 100A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 22.0 X 44.0 = 968.0 1492-AME 1492-A2B1H Ser. A For use with 1492-FB: 100A/600V AC, 100kA RMS Sym.Amps SCCR w/200a J Fuse, 600V AC, max. For use with 1492-SP: 100A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 1009.0 +2-0 Rockwell Automation Publication 1492-TD010D-EN-P April 2011 33

LISTED 3HXJ LISTED 3HXJ Figure 21 - Bulletin 1492-A3B1H 14.0 1492-AME 1492-A3B1H Ser. A For use with 1492-FB: 100A/600V AC, 100kA RMS Sym.Amps SCCR w/200a J Fuse, 600V AC, max. For use with 1492-SP: 100A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 1492-AME 1492-A3B1H Ser. A For use with 1492-FB: 100A/600V AC, 100kA RMS Sym.Amps SCCR w/200a J Fuse, 600V AC, max. For use with 1492-SP: 100A/480V AC, 10kA RMS Sym.Amps SCCR, 480V AC, max. Made in Germany 6.0 17.8 2.0 X 17.8 = 35.6 21.2 36.5 23.0 2.0 62.3 15.0 X 62.3 = 934.5 982.0 +2-0 Figure 22 - Auxiliary Contacts 1492-ASPHH3, ASPHS3, ASPH3, AS9HSC3P 80.0 45.0 44.0 8.8 5.5 60.0 Figure 23 - Undervoltage Release Module 1492-ASPU 80.0 45.0 17.5 5.5 44.0 60.0 Figure 24 - Shunt Trip Module 1492-ASPA 80.0 45.0 17.5 5.5 30.5 44.0 60.0 9.6 34 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

LISTED 1492-AAT1 Ser. A 3HXJ M4 Hex Screw Figure 25 - Bus Bar Accessories Bulletin 1492-A1E 1.0 14.0 8.5 1.7 2.1 5.0 1.1 Bulletin 1492-AME Bulletin 1492-AAT1 28.5 For use with 1492-FB and 1492-SP 100A/600V AC Wire Range: 10-1/0 AWG Torque: 50 lb-in. 3.0 Ø11.0 60.0 16.2 6.8 21.0 18.5 24.0 4.0 12.0 9.5 21.6 18.6 Bulletin 1492-AAP 11.5 17.8 4.0 x 17.8 = 71.2 24.0 13.0 84.2 Rockwell Automation Publication 1492-TD010D-EN-P April 2011 35

Internal Resistance The following table provides the internal resistance of a one-pole at room temperature. Table 18 - Internal Resistance of a One-Pole at Room Temperature R [mω]* I n [A] Type B Type C Type D 0.5 4670 4670 1 1102 1100 770 2 333 333 249 3 208 130 130 4 87.2 87.2 87.2 5 72.8 72.8 65.1 6 46.3 39.1 39.1 7 35 32 28 8 30.4 30.4 19.5 10 17.4 14.0 14.0 13 13.3 13.3 10.1 15 7.9 7.9 7.9 16 7.9 7.9 7.9 20 7.1 7.1 4.9 25 4.9 4.9 3.8 30 3.9 3.9 3.5 32 3.7 3.7 3.4 40 2.5 2.5 2.6 50 2.1 2.1 1.9 63 2.0 2.0 1.5 * 50 Hz 36 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Power Loss I n Entire Unit Table 19 - Entire Unit Power Loss I n Type B, C, & D Type B P* [W] Type C P* [W] Type D P* [W] I n [A] 1p 1pN 2p 3p 3pN 1p 1pN 2p 3p 3pN 1p 1pN 2p 3p 3pN 0.5 1.2 1.3 2.4 3.5 3.7 1.2 1.3 2.4 3.5 3.7 1 1.6 1.7 3.1 4.7 4.8 1.6 1.7 3.1 4.7 4.8 0.8 0.9 1.6 2.4 2.5 2 1.4 1.5 2.8 4.1 4.3 1.4 1.5 2.8 4.1 4.3 1.0 1.1 2.0 3.0 3.1 3 2.5 2.7 5.0 7.6 7.8 1.2 1.3 2.4 3.6 3.7 1.2 1.3 2.4 3.6 3.7 4 1.4 1.6 2.9 4.4 4.5 1.4 1.6 2.9 4.4 4.5 1.4 1.6 2.9 4.4 4.5 5 1.9 2.1 3.8 5.8 6.0 1.9 2.1 3.8 5.8 6.0 1.7 1.8 3.3 5.1 5.3 6 1.8 2.0 3.6 5.5 5.6 1.5 1.6 2.9 4.4 4.6 1.5 1.6 2.9 4.4 4.6 7 1.9 2.2 3.8 5.7 6.0 1.6 1.9 3.0 4.5 4.8 1.4 1.6 2.8 4.2 4.4 8 2.1 2.3 4.1 6.3 6.5 2.1 2.3 4.1 6.3 6.5 1.3 1.5 2.6 4.0 4.2 10 1.9 2.1 3.9 5.9 6.1 1.5 1.7 3.0 4.6 4.7 1.5 1.7 3.0 4.6 4.7 13 2.5 2.9 5.3 7.8 8.1 2.5 2.9 5.3 7.8 8.1 1.9 2.2 4.0 5.9 6.1 15 2.1 2.4 4.4 6.5 6.7 2.1 2.4 4.4 6.5 6.7 2.1 2.4 4.4 6.5 6.7 16 2.2 2.6 4.7 6.9 7.2 2.2 2.6 4.7 6.9 7.2 2.2 2.6 4.7 6.9 7.2 20 3.2 3.6 6.6 9.8 10.1 3.2 3.6 6.6 9.8 10.1 2.0 2.2 4.1 6.8 6.2 25 3.0 3.5 6.4 9.4 9.7 3.0 3.5 6.4 9.4 9.7 2.5 2.9 5.2 7.7 7.9 30 3.2 3.9 6.5 9.6 10.3 3.4 4.0 6.8 10.2 10.8 2.4 4.0 4.8 7.2 8.8 32 3.7 4.4 8.1 12.1 12.5 3.7 4.4 8.1 12.1 12.5 3.4 4.0 4.8 7.2 8.8 40 3.4 4.1 7.5 11.2 11.5 3.4 4.1 7.5 11.2 11.5 3.2 3.8 7.0 10.4 10.7 50 4.5 5.4 9.9 14.9 15.3 4.5 5.4 9.9 14.9 15.3 4.9 7.5 9.8 14.6 17.3 63 5.2 6.3 11.5 17.2 17.7 5.2 6.3 11.5 17.2 17.7 6.8 11.9 13.6 20.4 25.5 * 50 Hz Rockwell Automation Publication 1492-TD010D-EN-P April 2011 37

Maximum Let-Through Energy IEC/EN 60898 Figure 26 - Type B Let-Through Current I 2 t [A 2 sec] 80000 70000 60000 50000 40000 30000 20000 15000 10000 9000 8000 7000 6000 5000 4000 3000 2000 1500 B8 B6, B7 B5 B4 B50, B63 B40 B30, B32 B20 B25 B15, B16 B10 B13 B3 B2 1000 900 800 700 600 500 400 300 B1 500 1000 1500 2000 3000 4000 Prospective Short-Circuit Current [A] 5000 6000 7000 8000 9000 10000 38 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Figure 27 - Type C 80000 70000 60000 50000 40000 30000 C63 C50 C40 C30, C32 C25 C20 C10 C13 C15, C16 Let-Through Current I 2 t [A 2 sec] 20000 15000 10000 9000 8000 7000 6000 5000 4000 3000 2000 1500 C7, C8 C6 C5 C4 C3 C2 1000 900 800 700 600 500 400 300 C1 C0.5 500 1000 1500 2000 3000 4000 5000 6000 7000 8000 9000 10000 Prospective Short-Circuit Current [A] Rockwell Automation Publication 1492-TD010D-EN-P April 2011 39

Figure 28 - Type D 80000 70000 60000 50000 40000 30000 D63 D50 D40 D30, D32 D20 D25 D13 D10 D7, D8 Let-Through Current I 2 t [A 2 sec] 20000 15000 10000 9000 8000 7000 6000 5000 4000 3000 2000 D6 D5 D4 D3 D2 D1 1500 1000 900 800 700 600 500 400 D0.5 300 500 1000 1500 2000 3000 4000 5000 6000 7000 8000 9000 10000 Prospective Short-Circuit Current [A] 40 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Maximum Let-Through Current IEC/EN 60898 Figure 29 - Type B 10000 9000 8000 7000 6000 5000 4000 B5 B63 B50 B40 B32 B16 B20 B25, B30 B13, B15 B10 B8 B6, B7 3000 B4 B3 Let-Through Current I [A] DL 2000 1500 1000 B2 500 B1 500 1000 1500 2000 3000 4000 5000 6000 7000 8000 9000 10000 Prospective Short-Circuit-Current I [A] CC Rockwell Automation Publication 1492-TD010D-EN-P April 2011 41

Figure 30 - Type C 10000 9000 8000 7000 6000 5000 4000 3000 C50, C63 C32, C40 C25,C30 C20 C15, C16 C10, C13 C8 C6, C7 C5 C4 C3 Let-Through Current I [A] DL 2000 1500 1000 C2 500 C1 C0.5 500 1000 1500 2000 3000 4000 Prospective Short-Circuit-Current I [A] 5000 6000 7000 8000 9000 10000 42 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Figure 31 - Type D Let-Through Current I [A] DL 10000 9000 8000 7000 6000 5000 4000 3000 2000 1500 D63 D50 D40 D30,D32 D20 D16 D25 D13 D10 D7,D8 D6 D5 D4 D3.5 D3 D2.5 D2 D1.5 D1 1000 500 D0.5 500 1000 1500 2000 3000 4000 5000 6000 Prospective Short-Circuit-Current I [A] 7000 8000 9000 10000 Rockwell Automation Publication 1492-TD010D-EN-P April 2011 43

44 Rockwell Automation Publication 1492-TD010D-EN-P April 2011

Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/. Installation Assistance If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running. United States or Canada 1.440.646.3434 Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative. New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States Outside United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process. Please contact your local Rockwell Automation representative for the return procedure. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 Publication 1492-TD010D-EN-P April 201116 Supersedes Publication 1492-TD010C-EN-P - March 2002 Copyright 2011 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.