SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original



Similar documents
Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Comparison of NEMA and IEC schematic diagrams

EET272 Worksheet Week 8

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

Electrical Symbols and Line Diagrams

D-Line Contactors, Overload Relays and Accessories

Sentron Series Circuit Breakers

Electronic overload relay EF65, EF96 and EF146

Programming A PLC. Standard Instructions

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Low Voltage Fuses For Motor Protection

Magnetic Starter - 30A, 120/240V Coils

Inverter / Charger Installation General Operations and AC and DC Connections

Electronic overload relay EF19 and EF45

Circuit Breakers. NRC Series. NRC Series

Cam switches. Page. Overview 4-2. ON-OFF switches, main switches, maintenance switches 4-3. Changeover switches, reversing switches 4-5

Manual motor starter MS116

Reversing starter circuit for single phase induction motors Updated 1 st September 2008

Catalog January. Heavy industrial power applications Motor contactors and starters

IEC style contactors - long electrical and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide

3BASIC RELAY INSTRUCTIONS

What is a multimeter?

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

FLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE

Figure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc.

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

mecotron Safety relay ESTOP-2 For emergency stop monitoring

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

Building an Auto-Start Rotary Three Phase Converter. by: Matt Isserstedt

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

SECTION VARIABLE FREQUENCY DRIVES

PSR The compact range Description

W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER A, SERIES BCF0 AND BCF6

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

AF / AF09Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

US Breaker Brand 3 Pole AC Contactors (Square D Telemecanique LC1 Replacements)

*.ppt 11/2/ :48 PM 1

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

HM-W536 Install Guide

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

ETZGAR CONVEYOR COMPANY Controls Section v12.05

Industrial Automation Commonly-Used Terms

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

CHECK LIST OF SITE INSPECTION ON LV ELECTRICAL INSTALLATION (Basic Information to be filled by Consultant)

VARIABLE FREQUENCY DRIVES Revised 4/30/ Mechanical Systems

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Micro Contactors. Micro Contactor Relays. Micro Contactors With Solder Pins. Coil voltages. Micro Reversing Contactor. Technical Data.

AC motor control circuits

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Wiring diagrams. Compact NSX. Contents

Number 1 in efficiency

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

Oil and Coolant Circulating Heating System. Model - OCSM

How To Protect A Motor From Overcurrent

POINTS POSITION INDICATOR PPI4

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

Guide to the China Compulsory Certification System December 2009 OMRON Corporation Industrial Automation Company

Solid State Timers Type F

Short-circuit current rating (SCCR) of. industrial control panels. NEC Article 409 and UL 508A

Molded Case Circuit Breakers, Motor Protection Circuit Breakers, and Motor Circuit Protectors. Technical Data

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,

Bimetallic Overload Relay Specifications

Glossary of Common Crane Ter ms:

Circuit Breakers Supplementary Protectors Manual Motor Controllers

Motor Protection Voltage Unbalance and Single-Phasing

How can a charging station for electric vehicles be set up simply and safely?

DC Motor control Reversing

3PH2 or 3PHE 3 Phase Control Board

Fundamentals of Power

THERMAL RELAYS, MOTORSTARTERS

PSR, PSRP and PSRPL Pump Start Relays

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Circuit Breakers. Next Generation of Protection Capabilities

Battery Chargers. Revised 8/00 Form Number FORM NO / BATTERY CHARGER SERVICE MANUAL / PARTS LIST - 45

MC1000 Series Installation and Operation Manual

AP/UP, AP/MIL Series. Magnetic Circuit Protectors

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

Safety technique. Emergency stop module BO 5988 safemaster

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

Contactor and Starter Ratings

Installation Manual Version 7.3 IMPORTANT:

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

Transcription:

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according to commands by an operator or a controller. Typically an induction motor will run by a voltage of 230 Volt or 460 Volt, 3 phase 60 Hz in USA and be controlled by a control voltage of 115 Volt AC or 24 Volt DC. Several other combinations are possible in USA or other countries and are easily derived from the methods shown in this document. The motor starter must have a contactor to open or close the flow of energy to the motor and an overload relay to protect the motor against thermal overload. Other devices for disconnecting and short-circuit protection are necessary, typically a circuit breaker or fuses. The short-circuit protection is not shown here. The contactor is a switch with 3 poles whose poles are closed by the application of a control voltage to the coil. When the coil is energized the 3 poles are closed and are kept closed as long as the coil is energized. The contactor is a special relay specifically designed for motor control, but can be used for resistive loads; in the case of resistive loads it is possible to handle the thermal current, which is more than the current of a motor. Since the motor has inductance, the breaking of the current is more difficult and the contactor has to be derated. The overload relay is a device that changes the status of a normally closed contact from ON to OFF when the current going thru any of the 3 phases increases above a set point. This device is designed to provide overcurrent protection to a motor. This document shows step by step the process of wiring the FUJI series of contactors that ADC sells. The main combinations are: a) Full voltage non reversible 3 phase motors. b) Full voltage reversing 3 phase motors c) Single phase motors d) Wye-delta open transition We will show the basic circuit and in some cases pictures on how to connect the wiring. The pictures are shown here to teach the methods and are not intended to show how a panel is professionally wired. The examples show only one size of contactor with a coil of but the concept is valid for all the available sizes. WARNING! Use the instructions of each specific device. Failure to do so may result in electric shock or damage. This set of pictures shows a set of elements you will need: Contactor Overload relay Auxiliary contact block Start/stop pushbutton Page 1

a) Full voltage non reversible 3 phase motors. The following diagram is shown for a 3-wire control with control voltage: The picture shows the same arrangement. We need a contactor, an auxiliary contact block, an overload relay, a normally open start pushbutton, a normally closed stop pushbutton and a power supply with a fuse (Not shown on the picture). Page 2

b) Full voltage reversible 3 phase motors. The diagram is shown on the following figure for a 3-wire reversing control with control voltage: The picture shows the same arrangement. We need here two contactors, two auxiliary contact blocks, an overload relay, a mechanical interlock, two normally open start pushbuttons, a normally closed stop pushbutton and a power supply with a fuse (Not shown on the picture) FORWARD MECHANICAL INTERLOCK M2 REVERSE Mechanical interlock shown mounted on the side of contactor Page 3

c) Full voltage single phase motors. The diagram is shown on the following figure for a 3-wire control: The picture shows the same arrangement.. We need here a contactor, an overload relay, one auxiliary contact block, a normally open start pushbutton, a normally closed stop pushbutton and a power supply with a fuse (Not shown on the picture) 1 PHASE Page 4

d) Wye-delta open transition 3-phase motors. The following diagram is shown for a 3-wire control of a delta-star connection:. We need here three contactors, an overload relay, one auxiliary contact block, a normally open start pushbutton, a normally closed stop pushbutton, a on delay timer of 0-20 second and a power supply with a fuse M2 M3 TR T6 T5 T4 Page 5