Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems. History



Similar documents
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES


UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Introduction to Building Automation Systems (BAS)

Variable Air Volume - VAV

Comparing Energy Savings of Different VAV Systems

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2

HVAC Systems: Overview

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Topics for Today. Order of Magnitude Mechanical Estimating. Order of Magnitude Estimate Goal. Project Delivery Methods. Questions for Client

HVAC Processes. Lecture 7

Zoning Design and Application Guide. HVAC Zoning Systems

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

HVAC Simplified Approach Option

Dehumidification Design

Outline. CC objectives Site and building description Typical data floor overview CC measures Results Lessons learned

for Plans Examiners and Building Inspectors

HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN

Air Conditioning Contractors of America

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

HVAC Characteristics. Test Space HVAC Characteristics

Enclosed Football Stadium Design History and Lessons Learned

Preliminary Final Proposal

Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)

Design Options For HVAC Distribution System

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

CONTROL STRATEGIES FOR HVAC SYSTEMS

ENHANCED LABORATORY HVAC SYSTEM

HVAC Checklist - Long Form

MULTIZONE APPLICATION OF SOLUTION UNITS

Glossary of Heating, Ventilation and Air Conditioning Terms

Commissioning - Construction Documents (Page 1 of 6)

HVAC Systems in Schools & Commercial Buildings and Radon

Flexibility, Efficiency In San Antonio Arena

Design Options for HVAC Distribution Systems

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Using Time-of-Day Scheduling To Save Energy

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

Sample - Existing Building Commissioning Plan

ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations

Zoning Reference Guide

Integrating Kitchen Exhaust Systems with Building HVAC

USER S INFORMATION MANUAL

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Fundamentals of HVAC Control Systems

WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1

Glossary of HVAC Terms

Building Energy Systems. - HVAC: Heating, Distribution -

Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

Controller Operator Guide. VariTrac TM Central Control Panel VAV-SVU01A-EN

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

BSD Technical Standard Division 23: HVAC

Innovent LASER Packaged Fresh Air Conditioning Units

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA.

Challenges and Failures in Green Building Design Using Under-Floor Air Distribution. Ken Urbanek, PE, HBDP, LEED AP Director of Engineering

Lesson 36 Selection Of Air Conditioning Systems

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment

School HVAC. Design Manual. Application Guide AG Air Cooled Chiller. Chilled Water Pumps. Expansion Tank CHWR CHWS. Make up Water Line Boiler

Mechanical Systems Proposal revised

Product Data. Features/Benefits 37HC. Moduline VAV Air Terminals With Product Integrated Controls (PIC) Nominal 100 to 400 Cfm

SECTION TESTING, ADJUSTING, AND BALANCING

Kitchen Ventilation Systems: Part 2 Providing Adequate Makeup Air

Rev. No. 0 January 5, 2009

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone.

ECO-AIR AIR CONDITIONING

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes

Residential HVAC Load Sizing Training October 14, David Kaiser Green Code Plan Reviewer

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

APPENDIX C FORMS 2010 FLORIDA BUILDING CODE ENERGY CONSERVATION C.1

Pool Dehumidification Basics

Dual Maximum VAV Box Controls

APC APPLICATION NOTE #112

Energy Efficiency in Industrial HVAC Systems

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Bring the fresh in. Dedicated Outside Air Systems

SAM HOUSTON STATE UNIVERSITY

Aurora Mall. Aurora (Denver), Colorado

Element D Services Heating, Ventilating, and Air Conditioning

Noise in the Classroom

Xcel Business Customers: Program and Rebate Summary

PNEUMATIC CONTROLS Selection and Description

Dedicated Outdoor Air Systems (D.O.A.S.)

Contents Contents Introduction Equipment Zone-All Control Systems Inc 10/2010

Element D Services Heating, Ventilating, and Air Conditioning

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

Basics of HVAC Cleaning

Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

Transcription:

Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems Ryan R. Hoger, LEED AP 708.670.6383 ryan.hoger@tecmungo.com History VAV systems came into favor for mid and large size facilities in the 1960s and 1970s Save energy Improve comfort ake advantage of building diversity Cooling needed year round for true interior core zones Sequence Main AHU provides morning warm-up heat until RA setpoint is satisfied all zones at 100% design airflow AHU switches to 55 F discharge air controlled cooling zones modulate CFM to controls space temp No AHU heat remainder of day individual zone reheat or baseboard as needed 1

History (con t) What about the small buildings? IGVs and refrigerant capacity controls Not available on packaged RUs AHUs - too expensive Expensive zone level CFM/pressure measurement Lack of consistent cooling load for interior zones he Name Game Constant Volume Zoning Refers to primary air source (RU, AHU, etc.) Pressure Dependent Zoning Zone CFM is dependent upon system pressure Auto-changeover VAV Unlike standard VAV, RU/AHU switches from cooling to heating during the day Bypass VAV No IGV or VFD Shut-off VAV Variable Volume and emperature (VV) Parker 2

Variable Volume and emperature VV is called is called variable volume because it delivers a variable volume of air to each zone, as load dictates VV is called variable temperature because the temperature of the air supplied by the central unit varies with time General Application Several zones per system (RU/AHU) Small to medium zone 1/4-2 1/2 tons per zone 100-1000 CFM per zone ypically 3 to 15 zones per system (most manufacturers limit at 32) 3 to 25 tons per system Buildings up to 40,000 sq. ft. 3

Conceptual Layout ROOFOP HEAING AND COOLING UNI ROOF PS CEILING PLENUM REURN SUPPLEMENAL REHEA REURN HROUGH CEILING PLENUM ZONE 1 ZONE 2 ZONE 3 ZONE 4 VV System Design Steps Figure block cooling/heating loads Do preliminary equipment selection Determine control zones Figure zone cooling/heating loads and CFM requirements Select and position diffusers Some say oversize by 25% to reduce noise Some say size as normal to insure adequate throw Select and position dampers Size to handle zone peak CFM at 900-1200 FPM 4

VV System Design Steps (con t) Layout bypass system Position thermostats Size ductwork Main supply and return = unit CFM Branch = zone peak CFM Select supplementary heaters Final equipment selection Do not oversize equipment! Define control wiring requirements and routing Control riser wiring drawings ypical Layout DH-3 AC1 M W L 52/18 52/18 DG-3 4 3 20/14 20/14 10"Ø 16/14 YP. 8" YP. 10" YPICAL HO WAER SUPPLEMENARY HEAER YP. 10" AH-2 AC2 20/14 20/14 16/14 1 2 YP. 8" DG-3 DG-3 YP. 10" 7 16/14 5 DH-3 DH-3 YP. 10" 6 YP. 8" 5

Bypass - System Pressure Control Maintains system static pressure to insure adequate airflow into the zones and avoids over pressurization Size bypass adequately Bypass CFM = unit CFM - smallest zone CFM Minimum of 75% of unit CFM Select at 1500 FPM Avoid short-circuiting Facilitate mixing of bypass air with return air Plenum return preferred method VFD is acceptable if air source has hydronic heating and cooling ONLY Return Air Path and Bypass Plenum return design provides better mix of return air with supply air Ducted return provides better latent temperature control in humid environment Can cause nuisance equipment trips resulting in loss of comfort Static Pressure ubing RU Bypass Damper Do not place bypass directly beneath unit RU Bypass Damper Back Draft Damper Static Pressure ubing 6

Ceiling Plenum Return Layout SAIC PRESSURE SENSOR & BYPASS DAMPER ACUAOR ROOFOP UNI BYPASS DAMPER WIH SHOR DUC SUPPOR PROPERLY SAIC PRESSURE UBING AIM BYPASS DAMPER DISCHARGE AWAY FROM REURN INLE AVOID REURN GRILLES IN CLOSE PROXIMIY O BYPASS DISCHARGE AIR PAH SAIC PRESSURE PICKUP LOCAE PICKUP IN AREA OF LEAS URBULENCE, 5 DUC DIAMEERS DOWNSREAM OF BYPASS AKEOFF BU UPSREAM OF FIRS ZONE AKEOFF OR MAJOR JUNCION AVOID ELBOWS AND EES Ducted Return Layout REURN BACKDRAF DAMPER LOCAE REURN/BYPASS JUNCION A MINIMUM OF 15 F. FROM UNI INLE BYPASS DAMPER ROOFOP UNI AVOID HE EMPAION O INSALL A SHOR-CIRCUI BYPASS HERE. I WILL CAUSE NUISANCE RIPS WIH ZONE CAPACIY INERRUPION SAIC PRESSURE SENSOR & BYPASS DAMPER ACUAOR SAIC PRESSURE UBING SAIC PRESSURE PICKUP LOCAE PICKUP IN AREA OF LEAS URBULENCE, 5 DUC DIAMEERS DOWNSREAM OF BYPASS AKEOFF BU UPSREAM OF FIRS ZONE AKEOFF OR MAJOR JUNCION AVOID ELBOWS AND EES 7

Leaving Air emperature Protection As more air bypasses, the RU/AHU discharge temperature will continue to drop (cooling mode) or rise (heating mode) System should stage down mechanical equipment regardless of zone temperatures being satisfied Cool - 2 nd stage at 50ºF and 1 st stage at 45ºF Heat - 2 nd stage at 120-130ºF and 1 st stage at 130-140ºF System Mode Selection One (adj.) or more zones must be calling to start heating or cooling usually 25% of total # of zones All zones must satisfy to clear mode Allow auto changeover from heating/cooling if opposite mode has greater demand for 30 (adj.) minutes Bypass damper at 100% open/bypass until duct temp increases above 65ºF (heat) or decreases below 80ºF (cool) Allows supply air to be preconditioned before delivery to zones Minimum heat and cool run time 3 minutes acceptable for most HVAC equipment Heat pumps should be 5 minutes 8

Zone Ventilation Control Allows damper to modulate to provide ventilation airflow when: When system not in heat or cool mode Zone does not have demand Supply air temp is neutral (between 65 F and 80 F) Damper must be allowed to fully shut when RU/AHU is operating in an undesired mode Do not implement minimum zone damper positions CO2-based Demand Controlled Ventilation (DCV) Like a VAV, VV should be zone level DCV RA CO2 not acceptable for zoned systems A wall-mounted CO2 sensor can cover up to 5,000 ft 2 of open space Zone should first open zone damper to satisfy CO2 setpoint utilizing air already in the duct system OA damper should respond to the zone with the largest deviation from zone CO2 setpoint 9

Supplemental Heat Ducted and non-ducted heat types include: 2 position (open/closed) hot water heat 1 to 3 stages of electric heat Modulating hot water heat Modulating electric heat Solid State Relays (SSR) Combination 2 position baseboard w/ ducted staged heat Zone should call for supplemental heat before calling for RU/AHU heat Lockout based on OA Overhead heating - size reheat for 90ºF discharge Fan Powered Boxes Not common on VV type systems Can be used for perimeter or other zones with heating loads Sequence same as when used on VAV Series fans run continuously Downsize AHU supply fan selection Parallel fans run as the 1 st stage of zone heat and use warm plenum air 10

Internet Accessible View and modify data Perform system diagnostics Send alarm messages Dedicated PC for BAS not required around the world! Air Balancing Please see the supplemental document. Use in conjunction with industry standard balancing guidelines, as published by ABB or other reputable balancing organizations. Command the bypass damper closed and VV dampers open Adjust supply fan to achieve the desired system CFM Adjust the maximum damper position to provide the required design maximum airflow to each zone start with zones closest to RU/AHU Set the fan speed setting for each box (fan powered boxes only) Calibrate the duct static pressure transducer for the bypass Calibrate the building static pressure transducer for the exhaust fans (if applicable) 11

Air Balancing (con t) Set the OA minimum position for the RU/AHU Set the duct static pressure setpoint for the bypass controller Set the building static pressure setpoint for the exhaust fans (if applicable) Set the damper position for reheat (if applicable) for each box Route a courtesy copy of the balancing report to controls contractor so any setting changes can be preserved during future service calls. Do s and Don ts Don t apply to HVAC units over 20 tons Don t reduce the quantity of RU/AHUs as compared to single zone constant volume system Don t oversize RU/AHU Do install a XV Don t mix core interior zones on the same system as exterior zones Same rule for mixing exposures (east and west on the same unit, etc.) Exception: If you install and run supplemental heat in all of the perimeter zones Don t install the bypass damper too close to the HVAC unit Don t locate the bypass discharge near plenum return grills Do specify the complete scope of air balancing And the most common problem. Don t specify or implement minimum damper positions 12

Ryan R. Hoger, LEED AP 708.670.6383 ryan.hoger@tecmungo.com hanks to: 13