The future electrical opening system for skylights, smoke hatches and windows
Actulux A/S Background and Visions Actulux develops, produces and distributes innovative electrical opening systems for skylights, windows and smoke hatches. Our visions are: that our products are technological market leaders with a very high performance. that our products can be produced at an attractive price level. that our company is a strategically partner for our customers to have a significant size on the European market.
Actulux Europe organization and sales markets Actulux representation with own organization: Denmark technique/development, production, service, sales Germany sales Estonia / Baltics / Russia sales Markets with continued sales (beyond the above): Belgium Finland Estonia Latvia Lithuania Switzerland Austria Norway Sweden UK Belarus Ukraine Serbia Slovenia Holland Portugal
Actulux Product Groups Electrical Opening Systems Traverse mounted: SA Power Mini 70-110cm SA Power Single 88-00 cm SA Power Double 160-300 cm SA Power Large 150 50 cm Side mounted: Chain motors 4V Chain motors 30V (incl. remote control) Rack & pinion motors EN 1101- tested Control Panels type SVM and SV Control Panel SVM 4V 5 Amp Control Panel SVM 4V 8 Amp Control Panel SV 4V 4 Amp Control Panel SV 4V 30 Amp Control Panel SV 4V 3 Amp Control Panel SV 48V 8 Amp Control Panel SV 48V 4 Amp Control Panel SV 48V 30 Amp Control Panel SV 48V 3 Amp Accessories Fire switch Comfort switch Wind and rain sensor Smoke / Heat detector One week & 4h watch Room thermostat Remote control Unit Etc. EN 1101-10 certified
Actulux opening systems can be supplied with either 4 Volt or 48 Volt Control Panels, 4V and 48V type SV(M) xx-xx-(ds) : Product Performance Notes Control Panels type SV(M) 4V 5 sizes: 5A, 8A, 4A, 30A, 3A Incl. battery back-up 1 or fire- and comfortgroups Intelligent BUS-communication Connection for fireswitches, detectors, wind-/rainsencor, comfortswitch Potential free failure and alarm output EN1101-10 Certified (class A= x supply) Control Panels type SV 48V 4 sizes: 8A, 4A, 30A, 3A Benefits of using 48V: The power consumption (amp.) to the opening systems are reduced by 50%. The thickness of the installation cables are reduced by 50% - 60%. The control units can supply twice as many opening systems, which reduces the total price for control units in medium and larger installations by 30-40%
Actulux Opening Systems SA Power Single Chain drives (Patent rights) Actulux Opening Systems in operation SA Power Mini SA Power Double Rack & Pinion drives SA Power Large
Actulux Control Panels EN 1101-10 certificate SVM Mini Control Panels SV Control Panels
Control Panels Volt / Ampere RWA / Comf, Groups SVM 4V-5A-ds 4V / 5A 1 Yes SVM 4V-8A-ds 4V / 8A 1 Yes SV 4V-4A 4V / 4A No SV 4V-3A 4V / 3A No SV 48V-4A 48V / 4A No SV 48V-3A 48V / 3A No SV 4V-4A-ds 4V / 4A Yes SV 4V-30A-ds 4V / 30A Yes SV 4V-3A-ds 4V / 3A Yes SV 48V-8A-ds 48V / 8A Yes SV 48V-4A-ds 48V / 4A Yes SV 48V-30A-ds 48V / 30A Yes SV 48V-3A-ds 48V / 3A Yes Type EN1101-10 Certified
Actulux Accessories
Actulux - Unique Selling Point 1. TECHNOLOGICAL LEADER Performance and strength characterized Actulux products Our partners/customers are seen as technological leaders (first movers) and can differentiate in their market with design and quality. Our customers and partners experience increased sales, both now and in the future.. ELECTRICAL OPENING SYSTEMS 100% focus on electrical solutions and developments Extremely low current consumption and low installation costs. Very low service and maintenance costs. Unique product design with the lowest build-in-height in the market. Silent operation with both smoke ventilation and natural ventilation, as standard, in the same product. Electrical opening systems are the future technology, also in traditional pneumatic markets 3. THE CUSTOMER- AND MARKET STRATEGY OF ACTULUX and development with our customers: Know-how on high level, partnership Technical know how on highest level and great experience with EN1101- tests - Actulux takes active part in the work of the certifying process of our customers. Constant product development and cost effectiveness in co-operation with our customers and partners with the purpose of creating further growth. Flexible with very short delivery time also for special solutions.
European norm EN 1101- regarding smoke ventilation (SHEV) Annex A (Test procedure): - Description of general test procedure, sequence, test reports, etc. Annex B (CV factor aerodynamic area): - Determination of CV factor, test method - Demands for opening angles (f.ex. 90 for double flap and 140 or 160 for single flap Annex C (Reliability and lifetime test): - 10.000 comfort openings (f.ex. 15 sec. opening time ~ 30 Openingangle) - Different classifications for full fire opening (f.ex. 50 or1000) within 60 sec. Annex D (Snow load): - 3 times full opening incl. snow load every opening within 60 sec. - Different classifications (f.ex. 50, 500, 800 or 1000N/m ) Annex E (Low temperature): - Define at which temperature snow load test has to be done - Different classifications (f.ex. 0, -5, or -15 C) Annex F (Wind load): - Define at which wind load (vacuum) the ventilator has to stay closed and afterwards be able to open in full fire opening - Different classifications (f.ex. 1500 N/m) Annex G (Heat): - Define at which heat temperature the ventilator has to operate as smoke ventilator - Different classifications (f.ex. 00, 300, or 600 C) Other relevant EN 1101 norm: - 1101-9 (Control panels and fire switches etc. preliminary) - 1101-10 (Power supply /energy source)
Electrical opening systems for smoke (EN1101-)- and comfort ventilation Product SA-Mini (Opening system for small single flap, 160 ) SA Power Single (Opening system for medium/large single flap, up to165 ) SA Power Double (Opening system for medium/large double flap, x90 ) SA Power Large (Opening system for very large single flap,165 ) Chainmotors + Rack & pinion (Opening systems for windows and domes) Performance Notes 4V (,5A) 48V (1,5A) For dome width: 70-110 cm Cover weight & snow: up to 140 kg Adjustable from 70-110 cm 4V (3A/4A) 48V (1,5A/A) For dome width: 88-00 cm Cover weight & snow: up to 300 kg European patent 4V (*3A/4A) 48V (*1,5A/A) For dome width: 160-300 cm Cover weight & snow: up to *300 kg 4V (6A/8A) 48V (3A/4A) For dome width: 150-50 cm Cover weight & snow: up to 400 kg 4VDC and 30VAC Stroke length: 300-1000mm Force: 300 1000N European patent
EN 1101- & EN 1101-10 certificates
HCV 4V HCVA 30V HCVM 4V HCMA 30V HCMAR 30V+radio Chainmotors
HTRW 4V HTRWA 30V Rack & Pinion motors
Installation cables - Example 1 of 3 (4V in Technic Room) Building 000m (7m x 8m x 7m) 4V system Actulux Control Panel SV 4V-4A mounted in Technic Room 000m warehouse area (or production) 4m Aa - aerodynamic vent area SHEV s / Domes 1 pcs.,4m x 1,m (geometric daylight size) - cv 0,7 Control panels: pcs. SV 4V-4A ( fire-comf. groups / control panel) Opening systems: 1 pcs. SA Power Single 1,m, 4V-4A / 48V-A Cable: 4 lines with 5x,5mm cable (= wire x 6,5mm) Total length of cable: 300m of 5x,5mm Voltage drop: 15% max. 3,6v calculated 3,04 (or 1m for production)
Installation cables - Example of 3 (4V decentral mounted) Building 000m (7m x 8m x 7m) 4V system Actulux Control Panel SV 4V-4A mounted decentralized 000m warehouse area (or production) 4m Aa - aerodynamic vent area SHEV s / Domes 1 pcs.,4m x 1,m (geometric daylight size) - cv 0,7 Control panels: pcs. SV 4V-4A ( fire-comf. groups / control panel) Opening systems: 1 pcs. SA Power Single 1,m, 4V-4A / 48V-A Cable: 4 lines with 5x1,5mm cable (= wire x 3,75mm) Total length of cable: 17m of 5x1,5mm Voltage drop: 15% max. 3,6v calculated 3,04 (or 1m for production)
Installation cables - Example 3 of 3 (48V in Technic Room) Building 000m (7m x 8m x 7m) 4V system Actulux Control Panel SV 48V-4A mounted in Technic Room 000m warehouse area (or production) 4m Aa - aerodynamic vent area SHEV s / Domes 1 pcs.,4m x 1,m (geometric daylight size) - cv 0,7 Control panels: 1 pcs. SV 48V-4A ( fire-comf. groups / control panel) Opening systems: 1 pcs. SA Power Single 1,m, 4V-4A / 48V-A Cable: lines with 5x1,5mm cable (= wire x 3,75mm) Total length of cable: 170m of 5x1,5mm Voltage drop: 15% max. 7,v calculated 6,5 (or 1m for production)